DEMAND LOAD TABULATION

CIRCUIT PHASE CURRENT CIRCUIT BREAKER CONDUCTOR CONDUIT


LOAD DESCRIPTION VA LOAD VOLTAGE
NUMBER AN CN BN POLE AT AF SIZE TYPE DIAMETER TYPE
1 PANEL 1 23538 230 30.99 34.25 37.12 3P 90 100 3-22mm^2 & 1-8mm^2 THW 32mm PVC
2 PANEL 2 25306 230 37.98 33.23 38.81 3P 90 100 3-22mm^2 & 1-8mm^2 THW 32mm PVC
3 PANEL 3 27900 230 41.49 39.94 39.94 3P 100 100 3-22mm^2 & 1-8mm^2 THW 32mm PVC
4 PANEL 4 41580 230 61.83 59.22 59.74 3P 150 225 3-38mm^2 & 1-14mm^2 THW 50mm PVC
TOTAL= 118324 172.29 166.64 175.61

VA LOAD230v = (√3 )(EL)(ILBIGGEST) Use: 2 SETS OF 3- 200 KVA,1-ø, 69KV-400/230, double-


= (√3 )(230𝑥√3)(175.61) bushing transformer

= 121.170 KVA

VA LOAD400v = (√3 )(EL)(ILBIGGEST)

= (√3 )(400𝑥√3)(796)

= 955.2 KVA

TOTAL KVA LOAD = 955.2 KVA + 121.17 KVA

TOTAL KVA LOAD = 1076.37 KVA

KVA RATING/PHASE= KVA LOAD/3

= 1076.37 KVA/3

= 358.79 KVA/2

=179.295 KVA
 SIZE OF THE FEEDER OF MDP OF 230V

𝟑𝒙𝟒𝟎𝟎𝑲𝑽𝑨
𝑰𝑭𝑳 = = 3012A
𝟐𝟑𝟎√𝟑

USE: 10 SETS OF 3- 200𝑚𝑚2,THW CU. WIRE/330A


1- 250𝑚𝑚2 ,THW CU. WIRE/4000A

 SIZE OF THE MAIN PROTECTIVE DEVICE,P169

𝑰𝑭𝑳 = 3012 A

USE: 3-POLE,USE 3000A FUSE