52014981 prosonic T
FMU 230/231
Ultrasonic Level Measurement

Operating Instructions
Short Instructions Prosonic T FMU 230/231

Short Instructions
Quick and easy
without display
1. Unlock device:
– H

2. Reset: BD
– V

or
3. Adjust level to 0%,
wait 35 s, confirm
(s. upper figure):
– +
0%

4. Adjust level to 100%,


wait 35 s, confirm
(s. lower figure):
V H

5. Lock device: BD

+ V 100%

or

More functions with


plugged-in display
Operation matrix Basic calibration (Chap. 6.1)

Matrix 1. Reset instrument V9H5 5. Application V0H3


Parameter – Input:
Position – Input: 333
VH 0: Liquid
1.660 02 2. Length unit V8H2
– Input: 0: m
1: ft
1: Rapid level
3. Empty calibration V0H1 change
– Input: E (m/ft)
Selection of matrix position:
4. Full calibration V0H2
H – Input: F (m/ft) 2: Dome cover
H0 H1 H2 H3 H4
V V0
V1
V2
V3 3: Bulk solids
V4
BD

100% 4: Conveyor belt


+ : Increases the parameter value E
F
– : Decreases the parameter value
After Basic calibration:
V or H : Confirms the entry •Linearization (Chap. 6.2)
0% •Set current output (Chap. 6.3)

2 Endress+Hauser
Prosonic T FMU 230/231 Table of Contents

Table of Contents

Short Instructions . . . . . . . . . . . . . . . . . . . . . . . 2 7 Trouble shooting . . . . . . . . . . . . . . . . . 16

1 Safety instructions . . . . . . . . . . . . . . . . . 4 8 Accessories . . . . . . . . . . . . . . . . . . . . . . . 18

2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . 5 9 Technical Data . . . . . . . . . . . . . . . . . . . 20

3 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

4 Display and operating elements . . . 7 Operating Matrix FMU 230/231 . . . . . . . . 22

5 Commissioning without
display module . . . . . . . . . . . . . . . . . . . . 8

6 Commissioning with
display module . . . . . . . . . . . . . . . . . . . . 9
6.1 Basic calibration . . . . . . . . . . . . . . . . . . . . . . 10
6.2 Linearization . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6.3 Current output . . . . . . . . . . . . . . . . . . . . . . . . 13
6.4 Additional parameters . . . . . . . . . . . . . . . . . . 14
6.5 Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.6 Locking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Endress+Hauser 3
1 Safety instructions Prosonic T FMU 230/231

1 Safety instructions
The compact transmitters Prosonic T FMU have been designed to operate safely in
accordance with current technical and safety standards and must be installed by
qualified personnel according to the instructions in this manual. The manufacturer
accepts no responsibility for any damage arising from incorrect use, insatallation or
operation of the equipment. Changes or modifications to the equipment not expressly
approved in the operating instructions or by the bodies responsible for compliance may
make the user‘s authority to use the equipment null and void. Damaged instruments
which may be a safety hazard must not be operated and are to be marked as defective.

Use in hazardous areas When used in explosion hazardous areas, the equipment must be installed in
accordance with local regulations as well as with technical and safety requirements on
the measuring point as specified in the accompanying certificates.

Installation and Installation, electrical connection, commissioning, operation and maintenance may only
Commissioning be carried out by trained and authorized personnel. The personnel must read and
understand these operating instructions before carrying them out.

Operation The instruments may only be operated by trained personnel authorized by the plant
operator. The instructions given in this manual are to be followed exactly.

Safety conventions and In this operating instructions, safety-relevant information is indicated by the following
symbols symbols:

Symbol Meaning

!
Note!
"Note" indicates activities which - if improperly executed - could have an indirect impact
on operation or trigger unexpected device actions.

" Caution!
"Caution" indicates activities or processes which - if improperly executed - could lead to
personal injury or to incorrect functioning of the device.

# Warning!
"Warning" indicates activities or processes which - if improperly executed - could lead to
serious injury to persons, to a safety risk or to destruction of the device.

% DC voltage
A terminal at which DC voltage is applied or through which DC flows.

& Alternating current


A terminal at which (sinusoidal) alternating voltage is applied or through which AC flows.

) Ground connection
A grounded terminal, which, from the user's point of view, is already grounded by a
grounding system.

* Protective earth connection


A terminal which must be grounded before other connections may be made.

Equipotential terminal
+ A connection which must be connected to the grounding system of the equipment: this
can, for example, be a potential matching line of a star-shaped grounding system,
depending on national or company code of practice.

4 Endress+Hauser
Prosonic T FMU 230/231 2 Installation

2 Installation
Installation variants
Installation with counter nut Installation with sleeve

counter nut (PA)


supplied for G 1 ½"
and G 2" instruments

Installation with adapter flange Installation with installation bracket

seal

adapter flange

Blocking distance
FMU 230 with Display
D [mm] max.L [mm]
50 80
BD 80 240
100 300
max. seal

FMU 231 with Display


adapter flange D [mm] max.L [mm]
80 240
100 300

L
D
FMU 230/231
without Display:
Dmin = 100 mm
Lmax = 150 mm

Sensor Blocking distance


FMU 230 0,25m
FMU 231 0,4m

Level echos from the blocking distance (BD) cannot be evaluated due to the transient
characteristics of the sensor. Install the Prosonic T at a height so that the blocking
distance BD is not undershot, even at maximum fill level. Use a pipe nozzle if you cannot
maintain the blocking distance in any other way. The interior of the nozzle must be
smooth and may not contain any edges or welded joints. In particular, there should be
no burr on the inside of the tank side nozzle end. Note the specified limits for nozzle
diameter and length.

" Caution!
If the blocking distance is undershot, it may cause device malfunction.

Endress+Hauser 5
2 Installation Prosonic T FMU 230/231

Installation position
2 3 4

1
5

1/3 R
Sensor L r
FMU 230 5m 0,38 m
α
6 FMU 231 7m 0,67m

α/2 = 5,5°

• Do not install the sensor in the middle of the tank (3). We recommend leaving a
distance between the sensor and the tank wall (1) measuring 1/3 of the tank radius.
• Use a protective cover (page 18), in order to protect the device from direct sun or rain
(2).
• Avoid measurements through the filling curtain (4).
• Make sure that equipment (5) such as limit switches, temperature sensors, etc. are not
located within the emitting angle α. In particular, symmetrical equipment (6) such as
heating coils, baffles etc. can influence measurement.
• Align the sensor so that it is vertical to the product surface.
• Never install two ultrasonic measuring devices in a tank.

! Note!
Make use of the echo quality display (page 14) to find the best installation position.

Installation Screw the Prosonic T at the screw-in piece using an 60 AF spanner. In order to facilitate
the wiring the housing is rotatable after installation.

housing
turnable after
installation

#
Caution!
Use only the hexagonal
nut to screw in the
Prosonic T AF 60
60

max torque
20 Nm

6 Endress+Hauser
Prosonic T FMU 230/231 3 Wiring

3 Wiring
1. Open the housing cover.
2. Insert cable through gland, make
connection according to the figure.
3. Tighten cable gland.

Note!
Use screened two-core instrumentation
cable.
For optimal protection against
electromagnetic interference, the
screen should be grounded in the
control room or the nearest earthing
point.
A good connection to ground is
Supply voltage:
12 ... 36 VDC essential to good screening.

4 Display and operating elements


Operating elements
matrix position

VH
parameters

+ -
!
4 5

segmented bar diagram

green LED:
confirm entry
+ V H
plug-in display

operating keys

The operating elements are located under the cover of the housing.

LED Pressing of a key is confirmed by a flash of the green LED.

Display module When the display module is used, the Prosonic T is operated via an operating matrix.
(optional) The current matrix position and the associated parameter (e.g. measured value) are
displayed on the module. The bargraph represents the measured value or the echo
quality, depending on the matrix position.
The basic functions for simple applications (empty and full calibration, locking and
unlocking) are accesible without the display module.

Endress+Hauser 7
5 Commissioning without display module Prosonic T FMU 230/231

5 Commissioning without display module


When operated without the display module, the empty- and full-distance are detected
by the instrument itself and have to be confirmed by a key combination.

Methods of calibration • after installation: The vessel is emptied to 0% and filled to 100% afterwards.
• before installation: The respective levels are simulated by directing the Prosonic T at
the appropriate distance to a plain wall.

The procedure
1. Unlock device:
– H

2. Reset: BD
– V

or
3. Adjust level to 0%,
wait 35 s, confirm
(s. upper figure):
– +
0%

4. Adjust level to 100%,


wait 35 s, confirm
(s. lower figure):
V H

5. Lock device: BD

+ V 100%

or

Reset A reset causes most of the instrument settings to return to the factory settings. The
following parameters are not affected by a reset:
• all linearisation parameters
• the m/ft selection (V8H2)
The factory settings are included in the operating matrix on page 22.

Locking Locking protects the entries against unwanted and unauthorized changes.

Current output After calibration the Prosonic T outputs a current according to the measured value. The
complete measuring range (0% ... 100%) is mapped to the current interval 4 ... 20 mA.

8 Endress+Hauser
Prosonic T FMU 230/231 6 Commissioning with display module

6 Commissioning with display module


Operating matrix

When the display module is used, the Prosonic T is operated via an operating matrix.
Each matrix field represents an operating parameter. The matrix can be accessed via
the keys. The meaning of the matrix fields is summarised on page 22.

Key operation with


Selecting the matrix field
plugged-in display
V Increases the vertical matrix position by 1.
H Increases the horizontal matrix position by 1.
V and H Resets the display to V0H0 (measured value).
Entering parameters
+ or - Activates the selected matrix position. The smallest digit flashes.
Increases or decreases the flashing digit.
To enter large parameter changes hold the key pressed.
+ or - When the decimal is exceeded (for the first or second time), the digit retains
the value 0 and the next digit begins to change. If you release the key, the
smallest digit can be edited again.
+ and - Resets the parameter to its original value, if it has not yet been confirmed.
Confirming the entry

V Confirms the entry and selects the next matrix position (vertically).

H Confirms the entry and selects the next matrix position (horizontally).

V and H Confirms the entry and resets the display to V0H0.


Locking/unlocking the matrix

+ and V Locks the matrix.


- and H Unlocks the matrix.

Endress+Hauser 9
6 Commissioning with display module Prosonic T FMU 230/231

6.1 Basic calibration


Reset 1. Enter "333" into the matrix position V9H5.
(V9H5) This sets all matrix positions back to the factory settings. Only the linearisation para-
meters (V2H0 ... V2H3) and the length unit (V8H2) retain their current values.

Length unit 2. In V8H2, select the length unit for all subsequent inputs:
(V8H2)
V8H2 Unit
0 (Default) m
1 ft

" Caution!
Change the unit only immediately after a reset. If you change the length unit at a later
point, all subsequent entries have to be repeated in the new unit.

Empty distance (V0H1) 3. Enter the empty distance E into V0H1 and the span F into V0H2. Use the units, which
Span (V0H2) have been selected in V8H2.
• The Empty distance E is the
distance from the sensor diaphragm
to the 0% level.
BD
E: Empty distance
• The Span F is the distance from the
100% F: Measuring range 0% to the 100% level.
(span)
E
F

0%

Application parameter 4. In V0H3 enter the application parameter according to the following table:
(V0H3)
V0H3 Application
0 Liquid
1 Liquid with rapid level change
2 Liquid in vessels with dome ceiling
3 Coarse bulk solids
4 Conveyor belt

Measured value display 5. Now the instrument is measuring. You can read out the following values:
Matrixfeld Display
V0H0 Level in %
V0H8 Distance D from sensor diaphragm to product
surface (m or ft)
V0H9 Level in m or ft

Check, if the displayed values match the actual level.


– If the displayed distance D (V0H8) is too small: Perform an interference echo sup-
pression (page 14).
– If al false level is displayed: Adjust empty distance and span.

Current output 6. After the basic calibration the Prosonic T outputs the level in the form of a current sig-
(V9H8) nal. The complete measuring range (0% ... 100%) is mapped to the current interval
4 ... 20 mA. The current value (mA) is displayed in matrix position V9H8.

10 Endress+Hauser
Prosonic T FMU 230/231 6 Commissioning with display module

6.2 Linearization
After the basic calibration, the measured value is displayed in V0H0 as a percentage of
the span. The value can be converted into any other unit by the linearization function.
Four different modes of linearization can be selcted in V2H0.

Linearization mode Use this mode, if you want to display the level in the length unit, which has been
"Level" (V2H0=0) selected in V8H2 (m or ft).

Linearization mode Use this mode, if you want to measure:


"linear"(V2H0=5, Default) • the level in any unit other than m, ft or
%.
• the volume or weight, if the volume-to-
level relationship of your vessel is
linear.

Step Matrix Entry / Meaning


position
1 V2H0 "4": Deletes a linearization table that might be present
2 V2H0 "5": Linearization mode "linear"
3 V2H5 Maximum level F (or appropriate volume or weight, respectively) in the desired unit.

! Note!
The factory setting is V2H5=100. That means, the level is expressed in % by default.

Linearization mode Use this mode, if you want to measure


"manual" (V2H0=2) the volume or weight, and if a sufficient
number of value pairs level/volume or
level/weight are known.
You can enter up to 11 value pairs into
the linearization table. The table must be
monotonically increasing.

Step Matrix Entry / Meaning


position
1 V2H0 "4": Deletes a linearization table that might be present
2 V2H0 "2": Linearization mode "manual"
3 V2H1 number of the value pair (1 ... 11)
4 V2H2 Level of the value pair (unit according to V8H2, m or ft)
5 V2H3 Volume or weight of the value pair (in the desired unit)
Repeat steps 3 to 5 for all value pairs
6 V2H0 "1": Activates the table

Endress+Hauser 11
6 Commissioning with display module Prosonic T FMU 230/231

Linearization mode Use this linearization mode, if you want to measure the volume or weight, while the value
"semi-automatic" pairs level/volume or level weight are not yet known.
(V2H0=3) The vessel is emptied in steps. At each step, the Prosonic T automatically registers the
level. The associated volume or weight must be entered manually.
Step Matrix Entry / Meaning
position
Fill the vessel to a level of 100%
1 V2H0 "4": Deletes a linearization table that might be present
2 V2H0 "3": Linearisation mode "semi-automatic"
3 V2H1 number of the value pair (1 ... 11)
4 V2H2 Check the displayed level and confirm by pressing H .
5 V2H3 Enter the associated volume or weight (in the desired unit)
Empty the vessel stepwise and repeat steps 3 ... 5 for each point
6 V2H0 "1": Activates the table

Exception: cylincrical The linearization for a cylindrical horizontal


horizontal tank tank is performed in the following way:
1. Determine the diameter D and the total
volume Vtot of the tank.
2. Multiply this value by the factors given
in the table below.
3. Enter these values into the instrument
as described above (Linearization
mode "manual").

V2H1 V2H2 (m or ft) V2H3 (desired unit)


1 0 0
2 D x 0,1 = Vtot x 0,052 =
3 D x 0,2 = Vtot x 0,1424 =
4 D x 0,3 = Vtot x 0,2523 =
5 D x 0,4 = Vtot x 0,3735 =
6 D x 0,5 = Vtot x 0,5 =
7 D x 0,6 = Vtot x 0,6164 =
8 D x 0,7 = Vtot x 0,7477 =
9 D x 0,8 = Vtot x 0,8576 =
10 D x 0,9 = Vtot x 0,9479 =
11 D= Vtot =

Error message As long as a linearization table is being entered, the current output indicates an error
message. The error disappears as soon as the table is complete and activated.

Measured value display When the table has been activated, the following measured values can be read out:
Matrix posi- Display
tion
V0H0 Volume or weight in the unit of the linearization
V0H8 Distance D from sensor diaphragm to product surface (m or ft)
V0H9 Level in m or ft

Current output The current output always follows the measured value V0H0. Therefore, the
4 mA value (V0H5) and the 20 mA value (V0H6) must be adapted to the new units (see
chapter 6.3).

12 Endress+Hauser
Prosonic T FMU 230/231 6 Commissioning with display module

6.3 Current output


In V8H1 you can define the mode of the current output. You have got the following
options:

Continuous output • In the continuous mode, the output


(V8H1=0, Default) directly follows the measured value
V0H0.
• V0H5 and V0H6 define the interval of the
Measured measuring range which is mapped to
value
the current interval 4 ... 20 mA. The
100% V0H6 factory settings (V0H5=0, V0H6=100)
can only be used if no linearization is
F
V0H0 present. In any other case these values
must be specified in the unit of the
V0H5
0%
Current
linerization.
4 mA 20 mA • If V0H5 is larger than V0H6, then the
current output is inverted. That means
the current decreases if the level
increases and vice versa.

Continuous output with In addition to the linear scaling the 4 mA threshold becomes effective in this option. It
4 mA threshold makes sure, that the current output does not fall below 4 mA even if the measured value
(V8H1=1) is less than V0H5. Use this option, if your control system can not handle currents below
4 mA.

Binary output If binary output is selected, the current


Measured
4/20mA (V8H1=2) or value only assumes two possible values:
8/16mA (V8H1=3) 100% V0H6
• It jumps to 20mA (or 16mA), as soon as
the measured value exceeds V0H6.
F • It jumps to 4mA (or 8mA), as soon as the
measured value falls below V0H5.
V0H5
0%
Current
4 mA 20 mA
8 mA 16 mA

Current on Fault In V0H7 specify the behaviour of the current output for the case of an error.
(V0H7)
V0H7 Output on error
0 3,8mA
1 22 mA (Default)
2 hold last value

Display of the current The current output (mA) is displayed in matrix positon V9H8.
output (V9H8)

Endress+Hauser 13
6 Commissioning with display module Prosonic T FMU 230/231

6.4 Additional parameters


Echo Quality The echo quality of the ultrasonic signal is displayed in V3H3 in steps from 1 to 10.
(V3H2) Additionally it is indicated by the bargraph in the matrix positions V0H8 and V0H9. Use
this display in order to find the best installation position. For a sound measurement, the
echo quality should be at least 5.

Interference echo The interference echo suppression is used


suppression (V3H0) when the level echo is not detected
because a fitting is generating a stronger
interference echo. Up to three interfernece
echos can be suppressed. The
suppression should be activated with the
tank as empty as possible.

Step Matrix Entry / Meaning


position
1 V0H8 Check the displayed distance between sensor diaphragm and product surface. An
interference echo suppression is necessary, if the displayed value is too low.
2 V3H0 Enter the actual distance between sensor diaphragm and product surface. Confirm
by pressing H. Wait approx. 40 s. The interference echo is suppressed.
3 V0H8 Check the displayed distance between sensor diaphragm and product surface. If
the displayed value is still to low, a furhter interference echo must be suppressed.
Therefore, repeat Step 2.

Temperature The actual temperature at the sensor is shown in V3H5. If the limit of 80°C has been
(V3H5) exceeded once, the highest value ever reached remains stored (drag indicator).

Lost echo delay time The lost echo delay time makes sure that no alarm will be output if the echo becomes
(V8H3) lost for a short period of time (for example due to foam). Values between 0 and 255 s
can be entered. The dafault setting is 60 s. For standard applications the lost echo delay
time should be not less than 30 s.

Actual level Falsifications in height in V0H9 (e.g. by temperature effects) can be corrected by
(V3H1) entering the correct height - the actual height - in V3H1. Entering the actual height then
automatically corrects the empty calibration.

First Echo Factor Vessels with tightly rounded roofs (dome covers) can cause double echos giving rise to
(V3H4) a display showing a level which is too low. Double echos can be excluded by increasing
the first echo factor to "maximum".
V3H4 First Echo Factor
0 off
1 medium
2 maximum

Output damping The effect of the output damping is to attenuate the analogue output and the measurand
(V0H4) indication on the display of the Prosonic T. When the liquid surface is not steady, a
steady reading can be obtained with the aid of the output damping. Values from 0 to
255 s can be entered. The default setting is 3 s. Please note, that the Prosonic T can not
resolve level changes faster than the output damping.

14 Endress+Hauser
Prosonic T FMU 230/231 6 Commissioning with display module

6.5 Simulation

V0H9 V0H0: main value V9H8 external


Level (level, volume, weight) Current output instruments

Linearization

scaling
Output
The measured value is processed by the Prosonic T in two steps and subsequently
output to external instruments. With the simulation function the correct operation of each
of these steps can be checked.

Level simulation Use the level simulation to check the linearisation:


(V9H6=1) 1. Set V9H6=1
2. In V9H7, enter a level. Use the unit, which has been selected in V8H2 (m or ft).
3. Check if V0H0 assumes the correct value.
4. Set V9H6=0 to return to the ordinary operation mode.

Volume simulation Use the volume simulation, to check the scaling of the output value:
(V9H6=2) 1. Set V9H6=2
2. In V9H7, enter a main value (level, volume or weight).
3. Check if the output current (V9H8) assumes the correct value.
4. Set V9H6=0 to return to the ordinary operation mode.

Current simulation Use the current simulation to check correct operation of the external instruments:
(V9H6=3) 1. Set V9H6=3
2. In V9H7, enter a current (in mA).
3. Now, the specified current is present at the output. Check, if the external instruments
respond correctly to this current.
4. Set V9H6=0 to return to the ordinary operation mode.

6.6 Locking
Locking via the keyboard
Key combination Meaning

+ and V Locking of the instrument against parameter


changes
- and H Unlocking of the instrument

Locking via the matrix V9H9 Meaning


(V9H9)
≠ 333 Locking of the instrument against parameter
changes
333 Unlocking of the instrument

! Note!
If the instrument has been locked via the keyboard, it can only be unlocked again via
the keyboard. Unlocking via the matrix is not possible in this case.

Endress+Hauser 15
7 Trouble shooting Prosonic T FMU 230/231

7 Trouble shooting
Types of error messages The self monitoring system of the Prosonic T distinguishes beween alarms and
warnings.

Alarm
• The bargraph flashes (if the display is plugged in)
• The current output adopts a preselected value (page 13)
• An error code is output in V9H0.

Warning
• The instrument continues to measure.
• An error code is output in V9H0.

Error codes V9H0 Type Cause Removal

E101 ... Alarm/ Initialisation Appears after switching on. If error remains,
E103 Warning contact Endress-Hauser service.

E106 Alarm Download in progress Wait until completed.

E110 ... Alarm Electronics error Reset instrument (V9H5 = 333). If error
E121 remains, contact Endress+Hauser service.

E125 Alarm Defective sensor Check sensor connection, contact End-


ress+Hauser service if error remains

E261 Alarm Error in temperature sensor Contact Endress+Hauser service

E501 Alarm Sensor electronics not recog- Contact Endress+Hauser service


nised

E602 Warning Linearisation curve is not rising Check manual linearisation curve. Does the
continuously volume increase with height?

E604 Warning Linearisation curve has less than Enter more points
2 points

E605 Alarm Linearisation table not available Activate the linearisation curve after entering
all points.

E613 Warning Simulation activated Switch to normal operation after simulation is


completed (V9H6=0).

E620 Warning Current outside range Check calibration and setting of the current
output.

E641 Alarm No usable echo Check, if a better position of the sensor is pos-
sible.

E661 Warning High temperature (greater than Check measuring conditions.


80°C/176°F)

16 Endress+Hauser
Prosonic T FMU 230/231 7 Trouble shooting

Fault analysis
Output current Check V0H0: yes Adjust output
too large or Is the displayed measured scaling
too small value correct? (s. chap. 6.3)

no

V0H0 to large or
V0H0 to small, see below.

Main value V0H0 Check V0H8 : yes yes Contact


Gas layering?
too small or Is the displayed distance service
jumps occasion- between sensor diaphragm
ally to small and product surface no
values too large?

no Multiple echos
- V0H3: Select "2" (dome cover)
- V3H4: increase first echo factor
Adjust linearisation
(s. chap. 6.2)

Main value V0H0 Check V0H8: yes Interference echos


too large Is the displayed distance - fittings in vessel removable?
between sensor diaphragm - nozzle too long?
and product surface - V0H3: Select "0" (liquid) or "2" (dome
too small? cover)
- Perform Interference echo suppression
no

Adjust linearisation
(s. chap. 6.2)

Main value V0H0 Turbulent surface? yes - Agitator blades in measuring range?
vacillates - Increase output damping
- V0H3: Select "0" (liquid) or "2" (dome
cover)

Matrix can not Unlock matrix


be edited (s. chap. 6.6)

Endress+Hauser 17
8 Accessories Prosonic T FMU 230/231

8 Accessories
Protective cover

Order Code: 942665-0000

Adapter flange
sealing ring
EPDM adapter flange
(supplied)

sensor nozzle

FAU70E Process connection FAU70A Process connection


12 DN50 PN 16 22 ANSI 2" 150 psi
14 DN80 PN16 44 ANSI 3" 150 psi
15 DN100 PN16 25 ANSI 4" 150 psi
Sensor connection Sensor connection
3 G 1 1/2" ISO 228 5 NPT 1 1/2 - 11,5
4 G 2" ISO 228 6 NPT 2 - 11,5
Material Material
2 1.4435 2 1.4435
7 Polypropylene, 7 Polypropylene,
PPS PPS

FAU70E- Order Code FAU70A- Order Code

Mounting bracket

– for FMU 230:


G 1 1/2, A=55 mm
Order code: 942669-0000
– for FMU 231
G2, A=66 mm
Order code: 942669-0001
– Material: 14301 (SS 304)
– suited for NPT 1 1/2" and
2" as well

18 Endress+Hauser
Prosonic T FMU 230/231 8 Accessories

Cantilever
A

20
C

20

100
50
35

25
D M8

75 75 100 B 35

50/
62

22

C
105

6.5

15
A B C D for Sensor Material Order Code
585 250 2 200 FMU 40 1.4301 (AISI 304) 52014132
galv. steel 52014131
FMU 41 1.4301 (AISI 304) 52014136
galv. steel 52014135
1085 750 3 300 FMU 40 1.4301 (AISI 304) 52014134
galv. steel 52014133
FMU 41 1.4301 (AISI 304) 52014138
galv. steel 52014137

• The 50 mm or 62 mm orifices serve for the mounting of the FMU 40 or FMU 41 sensor,
respecitvely.
• The 22 mm orifice may be used for an additional sensor.

Mounting Frame or
Wall Bracket
13

for Cantilever
100
25

55 3.2
5 ø 33.7
6.5
180

3.2

213
Ø 33.7
60
150
110

20 4 25
700/1400

13
6.5
45

76

88 110
200

150
100

100
130 150

Height Material Order Code Material Order Code


700 mm galv. steel 919791-0000 galv. steel 919792-0000
700 mm 1.4301 (AISI 919791-0001 1.4301 (AISI 919792-0001
304) 304)
1400 mm galv. steel 919791-0002
1400 mm 1.4301 (AISI 919791-0003
304)

Endress+Hauser 19
9 Technical Data Prosonic T FMU 230/231

9 Technical Data
Input variables Measuring range Type in liquids in solids
FMU 230 0,25 ... 4 m 0,25 ... 2 m
FMU 231 0,4 ... 7 m 0,4 ... 3,5 m
Blocking distance FMU 230: 0,25m; FMU 231: 0,4m
Operating frequency FMU 230: approx. 70 kHz; FMU 231: approx. 55 kHz
Pulse frequency 0,5 ... 1 Hz depending on sensor and electronic version

Output variables Current output 4 ... 20 mA


Output damping 0 ... 255 s
Load max. 600 Ω

Measuring accuracy Reference conditions Ideal reflection from a calm surface at 20 °C


Measuring uncertainty 0,25 % for max. measuring span
(includes linearity, reproducibility and hysteresis)
Resolution 3 mm

Application conditions Process temperature –40…+80 °C (built-in temperature sensor)


Operating temperature –20…+60 °C
Storage temperature –40…+80 °C
Operating pressure pabs 3 bar
Climatic class IEC 68 T2-30Db
Type of protection IP 67 (NEMA 6), with housing cover open: IP 20
Vibration resistance IEC 68 T2-6 Tab. 2.C (10...55 Hz)
Electromagnetic compati- Interference emmission according to EN 61326 ; apparatus of class B;
bility Interference immunity according to EN 61326 ; Appendix A (industrial are) and
NAMUR recommendation EMV (NE 21)
Use screened cable for wiring. Installation hints for screened cables and gene-
ral notes on EMC test conditions: see TI 241F

Mechanical construction Material Housing: PBT (glass reinforced, flame-retended)


Threaded boss and sensor: PVDF
Seals between threaded boss and sensor, internal: EPDM seal
on threaded boss, external: EPDM seal
Process connection FMU 230: G 1 ½ or NPT 1 ½, FMU 231: G 2 or NPT 2
Dimensions
(The housing dimensions
are the same for both vari-
ants)

Display and operating Display LCD (optional) 4 character display with segment display of current
elements LED for entry acknowledgement
Operation via four keys: –, +, V, H

Power supply Supply voltage 12 ... 36 VDC


Power consumption < 2,5 W

20 Endress+Hauser
Prosonic T FMU 230/231 Index

Index

A L
Actual level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Adapter flange . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Length unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Application parameter . . . . . . . . . . . . . . . . . . . . . . . 10 Level simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Linearization mode. . . . . . . . . . . . . . . . . . . . . . . . . . . 11
B Locking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Binary output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Lost echo delay time . . . . . . . . . . . . . . . . . . . . . . . . . 14
Blocking distance . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
M
C Measured value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Cantilever . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Measured value display. . . . . . . . . . . . . . . . . . . . . . . 12
Continuous output. . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Methods of calibration . . . . . . . . . . . . . . . . . . . . . . . . . 8
Current on Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Mounting bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Current output . . . . . . . . . . . . . . . . . . . . . . . . . 8, 10, 12 Mounting Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Current simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
cylincrical horizontal tank . . . . . . . . . . . . . . . . . . . . . 12 O
Operating elements . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
D Operating matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Display module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Output damping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

E P
Echo Quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Protective cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Empty distance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Error codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 R
Error message. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8, 10

F S
Fault analysis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Span. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
First Echo Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
T
I Temperature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Threshold . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Installation position . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Installation variants . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 V
Interference echo suppression . . . . . . . . . . . . . . . . . 14 Volume simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

K W
Key operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Wall Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Endress+Hauser 21
Operating Matrix FMU 230/231 Prosonic T FMU 230/231

Operating Matrix FMU 230/231

H0 H1 H2 H3 H4 H5 H6 H7 H8 H9
V0 Measured Empty Full Application Output 4mA value 20mA value Output on Measured Level
Basic value calibration calibration 0: liquid. damping Default: 0% Default: Alarm diestance (Bargraph:
1: fast Default: 3 s switch point 100% 0: 3,8mA (Bargraph: Echo Quality)
Calibration 2: dome cov.. for switch point 1: 22mA Echo Quality
3: solids 4 mA (8mA) for 2: hold
4: conveyor 20mA(16mA)

User unit m/ft m/ft seconds User unit unser unit m/ft m/ft

V2 Linearisation Table Table Table: Volume max.


Linearisa- 0: height Line-No. Level Volume/ Default: 100
1. activate Weight
tion 2: manual
3: automatic.
4. cancel
5: linear
V3 Range auto- Actual level Echo Quality First echo Temperature
Ext. para- matic sup- Default: 0,0 0 ... 10 factor
pression 0: none
meter Default: 0,0 1: medium
2: max. °C
V8 Current outp. Select unit Lost echo
Operating 0: 4 ... 20mA 0: m delay time
1: 4 ... 20mA 1: ft 0 ... 255 s
parameter +threshold Default: 60 s
2: 4/20mA
3: 8/16mA
V9 diagnostic last diag- Type of sen- Instrument & Reset Simulation Simualtion Current Locking
Service/ code nostic code sor/electro- Software No. 333 0: off value output 333:
nics 1: level unlocked
Simulat. 2: volume ≠ 333:
3: current locked

bold: factory settings


Entry field
italic: units

Display field

22 Endress+Hauser
(UNOlUXQJ]XU.RQWDPLQDWLRQ

Lieber Kunde,
Aufgrund der gesetzlichen Bestimmungen und zum Schutz unserer Mitarbeiter und Betriebseinrichtungen
benötigen wir die unterschriebene »Erklärung zur Kontamination«, bevor Ihr Auftrag bearbeitet werden kann.
Legen Sie diese vollständig ausgefüllte Erklärung unbedingt den Versandpapieren bei. Dies gilt auch für
zusätzliche Sicherheitsdatenblätter und/oder spezielle Handhabungsvorschriften.

Geräte- / Sensortyp: __________________________________ Seriennummer: _____________________________

Medium / Konzentr.: __________________________________ Temperatur: ________ Druck: _______

Gereinigt mit: __________________________________ Leitfähigkeit: ________ Viskosität: _______

:DUQKLQZHLVH]XP0HGLXP

SAFE

o o o o o o o o
radioaktiv explosiv ätzend giftig gesundheits- bio- brand- unbedenklich
schädlich gefährlich fördernd
Kreuzen Sie bitte zutreffende Warnhinweise an.

*UXQGGHU(LQVHQGXQJ
________________________________________________________________________

________________________________________________________________________

$QJDEHQ]XU)LUPD

Firma: _________________________ Ansprechpartner: _______________________


_________________________ _______________________
_________________________ Abteilung: _______________________
Adresse: _________________________ Telefon-Nummer: _______________________
_________________________ Fax / E-Mail: _______________________
_________________________ Ihre Auftrags-Nr.: _______________________

Hiermit bestätigen wir, dass die zurückgesandten Teile gereinigt wurden und frei sind von jeglichen Gefahr- oder
Giftstoffen entsprechend den Gefahren-Schutzvorschriften.

BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB
(Ort, Datum) (Firmenstempel und rechtsverbindliche Unterschrift)

Allgemeine Informationen zu Service und Reparaturen:


www.services.endress.com
Netherland Bolivia Pakistan
Europe ❑ Endress+Hauser B.V. Tritec S.R.L. Speedy Automation
Naarden Cochabamba Karachi
Austria Tel. (035) 6958611, Fax (035) 6958825 Tel. (042) 56993, Fax (042) 50981 Tel. (021) 7722953, Fax (021) 7736884
❑ Endress+Hauser Ges.m.b.H. Brazil Papua-Neuguinea
Norway
Wien ❑ Samson Endress+Hauser Ltda. SBS Electrical Pty Limited
Tel. (01) 88056-0, Fax (01) 88056-35 ❑ Endress+Hauser A/S
Tranby Sao Paulo Port Moresby
Belarus Tel. (032) 859850, Fax (032) 859851 Tel. (011) 50313455, Fax (011) 50313067 Tel. 3251188, Fax 3259556
❑ Belorgsintez Canada Philippines
Poland
Minsk ❑ Endress+Hauser Ltd. ❑ Endress+Hauser Philippines Inc.
Tel. (0172) 263166, Fax (0172) 263111 ❑ Endress+Hauser Polska Sp. z o.o.
Burlington, Ontario Metro Manila
Warszawy
Belgium / Luxembourg Tel. (905) 6819292, Fax (905) 6819444 Tel. (2) 3723601-05, Fax (2) 4121944
Tel. (022) 7201090, Fax (022) 7201085
❑ Endress+Hauser N.V. Chile
Portugal Singapore
Brussels ❑ Endress+Hauser Chile Ltd.
Tecnisis - Tecnica de Sistemas Industriais ❑ Endress+Hauser (S.E.A.) Pte., Ltd.
Tel. (02) 2480600, Fax (02) 2480553 Santiago
Linda-a-Velha Singapore
Bulgaria Tel. (21) 4267290, Fax (21) 4267299 Tel. (02) 3213009, Fax (02) 3213025 Tel. 5668222, Fax 5666848
INTERTECH-AUTOMATION Colombia
Sofia Romania South Korea
Colsein Ltda.
Tel. (02) 664869, Fax (02) 9631389 Romconseng S.R.L. ❑ Endress+Hauser (Korea) Co., Ltd.
Bogota D.C.
Bucharest Tel. (01) 2367659, Fax (01) 6104186 Seoul
Croatia Tel. (01) 4101634, Fax (01) 4101634 Tel. (02) 6587200, Fax (02) 6592838
❑ Endress+Hauser GmbH+Co. Costa Rica
Zagreb Russia Taiwan
EURO-TEC S.A.
Tel. (01) 6637785, Fax (01) 6637823 ❑ Endress+Hauser Moscow Office San Jose Kingjarl Corporation
Moscow Tel. (02) 961542, Fax (02) 961542 Taipei R.O.C.
Cyprus Tel. (095) 1587564, Fax (095) 1589871 Tel. (02) 27183938, Fax (02) 27134190
I+G Electrical Services Co. Ltd. Ecuador
Nicosia Slovakia Insetec Cia. Ltda. Thailand
Tel. (02) 484788, Fax (02) 484690 Transcom Technik s.r.o. Quito ❑ Endress+Hauser Ltd.
Bratislava Tel. (02) 269148, Fax (02) 461833 Bangkok
Czech Republic Tel. (7) 44888684, Fax (7) 44887112 Tel. (2) 9967811-20, Fax (2) 9967810
❑ Endress+Hauser GmbH+Co. Guatemala
Praha Slovenia ACISAAutomatizacionYControlIndustrial S.A. Vietnam
Tel. (026) 6784200, Fax (026) 6784179 ❑ Endress+Hauser D.O.O. Ciudad de Guatemala, C.A. Tan Viet Bao Co. Ltd.
Ljubljana Tel. (03) 345985, Fax (03) 327431 Ho Chi Minh City
Denmark
Tel. (061) 1592217, Fax (061) 1592298 Tel. (08) 8335225, Fax (08) 8335227
❑ Endress+Hauser A/S Mexico
Søborg Spain ❑ Endress+Hauser S.A. de C.V. Iran
Tel. (70) 131132, Fax (70) 132133 ❑ Endress+Hauser S.A. Mexico City PATSA Co.
Sant Just Desvern Tel. (5) 5682405, Fax (5) 5687459 Tehran
Estonia
Tel. (93) 4803366, Fax (93) 4733839 Paraguay Tel. (021) 8754748, Fax(021) 8747761
ELVI-Aqua
Tartu Sweden Incoel S.R.L Israel
Tel. (7) 441638, Fax (7) 441582 .Asuncion
❑ Endress+Hauser AB Instrumetrics Industrial Control Ltd.
Tel. (021) 213989, Fax (021) 226583
Finland Sollentuna Tel-Aviv
Tel. (08) 55511600, Fax (08) 55511655 Uruguay Tel. (03) 6480205, Fax (03) 6471992
❑ Endress+Hauser Oy
Espoo Circular S.A. Jordan
Switzerland
Tel. (09) 8676740, Fax (09) 86767440 Montevideo
❑ Endress+Hauser AG Tel. (02) 925785, Fax (02) 929151 A.P. Parpas Engineering S.A.
France Reinach/BL 1 Amman
Tel. (061) 7157575, Fax (061) 7111650 USA Tel. (06) 4643246, Fax (06) 4645707
❑ Endress+Hauser S.A.
Huningue ❑ Endress+Hauser Inc.
Turkey Kingdom of Saudi Arabia
Tel. (389) 696768, Fax (389) 694802 Greenwood, Indiana
Intek Endüstriyel Ölcü ve Kontrol SistemleriIs- Anasia Ind. Agencies
Tel. (317) 535-7138, Fax (317) 535-8498
Germany tanbul Jeddah
Tel. (0212) 2751355, Fax (0212) 2662775 Venezuela Tel. (02) 6710014, Fax (02) 6725929
❑ Endress+HauserMesstechnik GmbH+Co.
Controval C.A. Lebanon
Weil am Rhein Ukraine Caracas
Tel. (07621) 975-01, Fax (07621) 975-555 Network Engineering
Photonika GmbH Tel. (02) 9440966, Fax (02) 9444554
Kiev Jbeil
Great Britain
Tel. (44) 26881, Fax (44) 26908 Tel. (3) 944080, Fax (9) 548038
❑ Endress+Hauser Ltd.
Manchester
Asia Sultanate of Oman
Yugoslavia Rep.
Tel. (0161) 2865000, Fax (0161) 9981841 Meris d.o.o. Mustafa & Jawad Sience & Industry Co. L.L.C.
China
Beograd Ruwi
Greece ❑ Endress+Hauser Shanghai
Tel.(11) 4441966, Fax (11) 4441966 Tel. 602009, Fax 607066
I & G Building Services Automation S.A. Instrumentation Co. Ltd.
Athens Shanghai United Arab Emirates
Tel. (01) 9241500, Fax (01) 9221714 Tel. (021) 54902300, Fax (021) 54902303 Descon Trading EST.
Africa Dubai
Hungary
Egypt ❑ Endress+Hauser Beijing Office Tel. (04) 2653651, Fax (04) 2653264
Mile Ipari-Elektro
Budapest Anasia Beijing
Yemen
Tel. (01) 2615535, Fax (01) 2615535 Heliopolis/Cairo Tel. (010) 68344058, Fax: (010) 68344068
YemenCompany for Ghee andSoapIndustry
Tel. (02) 4179007, Fax (02) 4179008 Hong Kong Taiz
Iceland
BIL ehf Morocco ❑ Endress+Hauser HK Ltd. Tel. (04) 230664, Fax (04) 212338
Reykjavik Oussama S.A. Hong Kong
Tel. (05) 619616, Fax (05) 619617 Casablanca Tel. 25283120, Fax 28654171
Tel. (02) 241338, Fax (02) 402657 Australia + New Zealand
Ireland India
Flomeaco Company Ltd. South Africa ❑ Endress+Hauser (India) Pvt Ltd. Australia
Kildare ❑ Endress+Hauser Pty. Ltd. Mumbai ALSTOM Australia Limited
Tel. (045) 868615, Fax (045) 868182 Tel. (022) 8521458, Fax (022) 8521927 Milperra
Sandton
Tel. (011) 4441386, Fax (011) 4441977 Tel. (02) 97747444, Fax (02) 97744667
Italy Indonesia
❑ Endress+Hauser S.p.A. Tunisia PT Grama Bazita New Zealand
Cernusco s/N Milano Jakarta EMC Industrial Group Limited
Controle, Maintenance et Regulation
Tel. (02) 921921, Fax (02) 92107153 Tel. (21) 7975083, Fax (21) 7975089 Auckland
Tunis
Tel. (01) 793077, Fax (01) 788595 Tel. (09) 4155110, Fax (09) 4155115
Latvia Japan
Rino TK ❑ Sakura Endress Co. Ltd.
Riga Tokyo All other countries
Tel. (07) 312897, Fax (07) 312894
America Tel. (0422) 540613, Fax (0422) 550275
❑ Endress+Hauser GmbH+Co.
Lithuania Argentina Malaysia Instruments International
UAB "Agava" ❑ Endress+Hauser Argentina S.A. ❑ Endress+Hauser (M) Sdn. Bhd. D-Weil am Rhein
Kaunas Buenos Aires Petaling Jaya, Selangor Darul Ehsan Germany
Tel. (07) 202410, Fax (07) 207414 Tel. (01) 145227970, Fax (01) 145227909 Tel. (03) 7334848, Fax (03) 7338800 Tel. (07621) 975-02, Fax (07621) 975345

❑ Unternehmen der Endress+Hauser-Gruppe

BA 259F/00/de/07.02
52014980
FM+SGML 6.0

You might also like