Accessories

Barriers and Isolators

Description Automation, a replaceable fuse is used Galvanic isolators, unlike zener diode
to protect the barrier from miswiring and barriers, do not require grounding—
For applications involving sensor use in transients. therefore they may reduce ground loop
hazardous locations, Rockwell problems as well as installation and
Automation offers a line of Intrinsic The principle of a keyed fuse assembly maintenance costs. The slim ¾I wide
Safety Zener Diode Barriers and has been employed. In case of a fault housing on DC models also conserves
Galvanic Isolators. Both are economical due to overvoltage, polarity valuable mounting space. DIP switches
solutions for instrumentation and control misconnection or transients, only the provide convenient programming of
systems in hazardous locations as protective keyed fuse assembly needs output and diagnostic functions while
defined by NEC article 500 and CEC to be replaced. multiple LEDs provide visual indication
Part I, Section 18. of module and circuit status.
The replacement of the fuse assembly
Zener diode barriers are passive can be done by the user at the job site. Allen-Bradley’s zener diode barriers and
protective interface assemblies that limit The barriers do not have to be returned galvanic isolators are DIN-rail
the amount of energy (voltage and to the manufacturer for replacement. mountable and designed primarily for
current) that enters a hazardous area in use with intrinsically safe proximity
the event of a fault (i.e. overvoltage, Intrinsically Safe or Galvanic Isolators
are active protective interface sensors and photoelectrics. All of
shorted field wiring). The energy is Allen-Bradley’s barriers and isolators
limited to an amount that would not be assemblies that limit the amount of
energy allowed to enter a hazardous are FM and CENELEC approved, CSA
sufficient to ignite the potentially certified and CE marked for all
explosive atmosphere. Designed in a area under fault conditions. Sometimes
called Transformer Isolated Barriers, applicable directives.
slim ½in wide housing, each barrier
contains zener diodes that limit the they separate intrinsically safe wiring
voltage while a resistor prevents from non-intrinsically safe wiring
excessive current from being through the use of the same isolation
transferred to the hazardous area. In coils found in power transformers.
the barriers offered by Rockwell

R10–2
Accessories
Intrinsically Safe Zener Diode Barriers

Specifications
Leakage Current v1µA
Reverse Polarity Protection Protected by replaceable fuse
Over Voltage Protection Protected by replaceable fuse
Replaceable Fuse Rating 160mA
Short Circuit Protection Incorporated
Enclosure IP40 (IEC 529)
Housing Material Polyamide
Mounting Location Nonhazardous or Class 1, Division 2 location
Operating Temperature -20_C to +60_C (-4_F to +140_F)
® Shock and Vibration 20g, 55Hz (1.5mm amplitude)
Relative Humidity to 95%, no condensation
Operating Frequency v100kHz @ Isc u50mA; v50kHz @ Isc v0.50mA
Description
I.S. Connections for Class I, II, III; Div 1 and 2; Groups A-G
Intrinsic Safety Zener Diode Barriers
are passive protective interface Features Dimensions—mm (inches)
assemblies to isolate intrinsically safe
circuits from non-intrinsically safe • Replaceable fuse
1 2
circuits as defined in FM Class No. • Low internal resistance 2.75
160mA
3610 and CSA 22.2 No. 157 (70)
• Short circuited protected 160mA

The Intrinsic Safety Zener Diode 160mA


3.75
• Reverse polarity protection (93.5)
Barrier offer economical solutions for 4
160mA

instrumentation and control systems in • Slim 1/2in wide housing (102) Intrinsic
Safety
Barrier
hazardous locations defined by NEC • FM, CSA CENELEC (PTB)
3 4
Article 500 and CEC Part I, Section 18. approved, and CE marked for all 2.187
5 (56)
applicable directives DIN Rail Mounting Hole Spacing
0.5 4
Selection Guide (12.5) (102)

FM Entity Parameters
Rated Internal
Voltage Channel Resistance Groups Voc Isc Ca La Catalog Number
A, B 0.14uF 3.60mH
1 302 ohms C, E 100.0mA 0.43uF 13.9mH 897H-S120
897H S120
D, F, G 1.14uF 28.5mH
A, B 0.14uF
1 1V @22mA C, E 0.00mA 0.43uF 1000mH 897H-S140
897H S140
D, F, G 1.14uF
A, B 0.14uF 15.1mH
1 630 ohms C, E 47.5mA 0.43uF 57.0mH 897H-S150
897H S150
+24 to +26V D, F, G 1.14uF 125mH
28 0V
28.0V
DC A, B 0.14uF 2.9mH
1 280 ohms C, E 109.2mA 0.39uF 11.6mH
D, F, G 1.04uF 23.6mH
897H S214
897H-S214
A, B 0.14uF
2 1V @22mA C, E 0.00mA 0.39uF 1000mH
D, F, G 1.04uF
A, B 0.14uF 4.5mH
1, 2 340 ohms C, E 89mA 0.43uF 18.1mH 897H-S233
897H S233
D, F, G 1.1uF 37mH
Replacement Fuse Assembly 897H-F160

R10–3
Accessories
Intrinsically Safe or Galvanic Isolators

Specifications
Application NAMUR sensors
Number of Inputs 2
Switching Frequency 15Hz
Signal Range 8V @ 8.2mA
Switching Current On > 2.1mA, Off < 1.2mA
Input Resistance 1000ohms

Dimensions—mm (inches)
80mm 18mm 80mm 36.6mm
® (3 1/8I) (3/4I) (3 1/8I) (1 3/4I)

Description
114mm
Intrinsically Safe or Galvanic Isolators (4 3/8I)
are active protective interface
assemblies to isolate intrinsically safe
circuits from non-intrinsically safe
circuits as defined in FM Class No. 94mm 94mm
(3 7/8I) (3 7/8I)
3610 and CSA 22.2 No. 157. Galvanic 87mm 87mm
Isolators offer economical solutions for (3 7/16I) (3 7/16I)

instrumentation and control systems in


hazardous locations defined by NEC
Article 500 and CEC Part I, Section 18.
Unlike zener diode barriers, galvanic 897H-G211, 897H-G231 897H-G232
isolators do not require grounding. The
solid state output version isolators can Features
be located in a Division 2 area. • Reverse polarity protected
Allen-Bradley’s galvanic isolators • 1500V isolation between input and
provide 1500 volt isolation between output
hazardous area and nonhazardous • No separate Intrinsically Safe
area terminals and 500 volt isolation
grounding required
between input/output and external
power terminals. DIP switches provide • Slim 3/4in housing (DC models)
convenient programming for output or • FM, CSA, CENELEC (PTB)
diagnostic functions and multiple LEDs
approved, and CE marked for all
allow easy visual indication of module
applicable directives
and circuit status.

Selection Guide
FM Entity Parameters
External Catalog
Power Output Type Groups Voc Isc Ca La Number
100-140V
100 140V AC @ A, B 0.11µF 2.9mH
897H G232
897H-G232
2.5W SPDT Relayy C, E 0.33µF 11.6mH
10.5V 32mA
(250V AC @ 4A)
200-250V AC @
D, F, G 0.88µF 23.6mH 897H-G233
2.5W
A, B 2.5µF 40mH
SPST Relay
C, E 897H-G231
(250V AC @ 2A) 15µF 150mH
18-35V
18 35V DC @ D, F, G
10 6V
10.6V 29 7mA
29.7mA
32mA A, B 2.5µF 40mH
Transistor, open
Transistor
collector (35V DC C, E 897H-G211
@50mA) 15µF 150mH
D, F, G

R10–4