Electric Equipment
General Catalog
GIMAC-
MODBUS/RS-485
Protecting mis-wiring
R1
Rating
Model GIMAC-i
Self-diagnosis
R1-4
Measurement functions
Vavg ■ ■ ±0.3% -
Voltage Vab, Vbc, Vca ■ ■ ±0.3% -
Va, Vb, Vc ■ ■ ±0.3% -
lavg ■ ■ ±0.3% -
Current la, lb, lc ■ ■ ±0.3% -
Load factor la, lb, lc ■ ■ - -
∠VabVbc, ∠VabVca - ■ ±0.5。 3P3W
∠Vabla, ∠Vablb, ∠Vablc - ■ ±0.5。 3P3W
Phase
∠VaVb, ∠VaVc - ■ ±0.5。 3P4W
∠Vala, ∠Vblb, ∠Vclc - ■ ±0.5。 3P4W
P ■ ■ ±0.5% IEC 1036
Pa, Pb, Pc - ■ ±0.5% IEC 1036
Power
Q ■ ■ ±0.5% IEC 1036 R1
Qa, Qb, Qc - ■ ±0.5% IEC 1036
S ■ ■ ±0.5% IEC 1036
GIMAC-i
Sa, Sb, Sc - ■ ±0.5% IEC 1036
Wh ■ ■ ±0.5% IEC 1036
Varh ■ ■ ±0.5% IEC 1036
Energy rWh - ■ ±0.5% IEC 1036
rVarh - ■ ±0.5% IEC 1036
VAh ■ ■ ±0.5% IEC 1036
Frequency F(Hz) ■ ■ 0.05Hz -
PF ■ ■
+ : Lag
Power factor PFa, PFb, PFc - ■
- : Lead
DPFa, DPFb, DPFc - ■
THD(V) - ■ - Va(ab), Vb(bc), Vc(ca)
THD
THD(I) - ■ - Ia, Ib, Ic
1st ~ 15th Harmonics (V) - ■ - Va(ab), Vb(bc), Vc(ca)
Harmonics
1st ~ 15th Harmonics (I) - ■ - Ia, Ib, Ic
Demand W - ■ -
Demand
Demand la, lb, lc, lavg - ■ - -
max la, max lb, max Ic, max lavg
- ■ - -
max Va(ab) THD, max Vb(bc) THD
max Vc(ca) THD
- ■ - -
max la THD, max lb THD,
max lc THD - ■ - -
MAX
max W - ■ - -
max VAR - ■ - -
max VA - ■ - -
max Demand lavg, la, lb, lc - ■ - -
max Demand W - ■ - -
R1-5
Digital Power Meter
External
PHASE OPTION
(EX TYPE)
B PHASE
UP KEY
OPTION
(EX TYPE)
DOWN KEY
C PHASE
ENTER KEY
Minus (-)
×1000 unit
R1-6
Wirings
3P4W
LINE
LINE
R S T N
R S T N
Fuse, 2A
Fuse, 2A
CCT
R1
GIMAC-i
LOAD LOAD
3P3W
LINE
LINE
R S T
R S T
Fuse, 2A
Fuse, 2A
CCT CCT
LOAD LOAD
R1-7
Digital Power Meter
Wirings
LINE
R S T LINE
Fuse, 2A R S N
Fuse, 2A
CCT
CCT
LOAD LOAD
1P 2W
LINE
R N
Power Supply
CCT
LOAD
R1-8
Dimension & Ordering
Dimension
144
23.5 61.5 89 144
85
R1
GIMAC-i
86
92
86 92
Ordering
R1-9