Professional Documents
Culture Documents
The software or hardware described in this document is furnished under a license and
may be used, copied, or disclosed only in accordance with the terms of such license.
Trademarks
ABB and Relion are registered trademarks of ABB Group. All other brand or product
names mentioned in this document may be trademarks or registered trademarks of their
respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
ABB Inc.
Distribution Automation
4300 Coral Ridge Drive
Coral Springs, FL 33065, USA
Toll-free: 1 (800) 523-2620
Phone: +1 954-752-6700
Fax: +1 954 345-5329
http://www.abb.com/substationautomation
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept or
product description and are not to be deemed as a statement of guaranteed properties.
All persons responsible for applying the equipment addressed in this manual must
satisfy themselves that each intended application is suitable and acceptable, including
that any applicable safety or other operational requirements are complied with. In
particular, any risks in applications where a system failure and/or product failure would
create a risk for harm to property or persons (including but not limited to personal
injuries or death) shall be the sole responsibility of the person or entity applying the
equipment, and those so responsible are hereby requested to ensure that all measures
are taken to exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested to
notify the manufacturer. Other than under explicit contractual commitments, in no
event shall ABB be responsible or liable for any loss or damage resulting from the use
of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European Communities
on the approximation of the laws of the Member States relating to electromagnetic
compatibility (EMC Directive 2004/108/EC) and concerning electrical equipment for
use within specified voltage limits (Low-voltage directive 2006/95/EC). This
conformity is the result of tests conducted by ABB in accordance with the product
standards EN 50263 and EN 60255-26 for the EMC directive, and with the product
standards EN 60255-6 and EN 60255-27 for the low voltage directive. The IED is
designed in accordance with the international standards of the IEC 60255 series and
ANSI C37.90.
Table of contents
Table of contents
Section 1 Introduction............................................................................5
This manual..............................................................................................5
Intended audience....................................................................................5
Product documentation.............................................................................6
Product documentation set..................................................................6
Document revision history...................................................................7
Related documentation........................................................................8
Symbols and conventions.........................................................................8
Safety indication symbols....................................................................8
Manual conventions.............................................................................9
Functions, codes and symbols............................................................9
REM615 ANSI 1
Application Manual
Table of contents
Functional diagrams..........................................................................31
Functional diagrams for protection...............................................31
Functional diagrams for digital fault recorder and trip circuit
monitoring.....................................................................................38
Functional diagrams for control and interlocking..........................43
Functional diagram for ARC flash detection and
autoreclosing................................................................................47
Standard Configuration MA02: Current and voltage inputs....................48
Applications.......................................................................................48
Functions...........................................................................................48
Default I/O connections................................................................50
Functional diagrams..........................................................................51
Functional diagrams for protection...............................................51
Functional diagrams for digital fault recorder and trip circuit
monitoring.....................................................................................60
Functional diagrams for control and interlocking..........................65
Functional diagram for ARC flash detection and
autoreclosing................................................................................69
2 REM615 ANSI
Application Manual
Table of contents
IRF.....................................................................................................80
Section 6 Glossary..............................................................................81
REM615 ANSI 3
Application Manual
4
1MAC259901-MB A Section 1
Introduction
Section 1 Introduction
The application manual contains application descriptions and setting guidelines sorted
per function. The manual can be used to find out when and for what purpose a typical
protection function can be used. The manual can also be used when calculating settings.
This manual addresses the protection and control engineer responsible for planning, pre-
engineering and engineering.
REM615 ANSI 5
Application Manual
Section 1 1MAC259901-MB A
Introduction
Decommissioning
Commissioning
Maintenance
Engineering
Operation
Installing
Engineering manual
Installation manual
Commissioning manual
Operation manual
Service manual
Application manual
Technical manual
Communication protocol
manual
en07000220.vsd
IEC07000220 V1 EN
The engineering manual contains instructions on how to engineer the IEDs using the
different tools in PCM600. The manual provides instructions on how to set up a
PCM600 project and insert IEDs to the project structure. The manual also recommends
a sequence for engineering of protection and control functions, LHMI functions as well
as communication engineering for IEC 61850 and DNP3.
The installation manual contains instructions on how to install the IED. The manual
provides procedures for mechanical and electrical installation. The chapters are
organized in chronological order in which the IED should be installed.
The commissioning manual contains instructions on how to commission the IED. The
manual can also be used by system engineers and maintenance personnel for assistance
6 REM615 ANSI
Application Manual
1MAC259901-MB A Section 1
Introduction
during the testing phase. The manual provides procedures for checking of external
circuitry and energizing the IED, parameter setting and configuration as well as
verifying settings by secondary injection. The manual describes the process of testing
an IED in a substation which is not in service. The chapters are organized in
chronological order in which the IED should be commissioned.
The operation manual contains instructions on how to operate the IED once it has been
commissioned. The manual provides instructions for monitoring, controlling and
setting the IED. The manual also describes how to identify disturbances and how to
view calculated and measured power grid data to determine the cause of a fault.
The service manual contains instructions on how to service and maintain the IED. The
manual also provides procedures for de-energizing, de-commissioning and disposal of
the IED.
The application manual contains application descriptions and setting guidelines sorted
per function. The manual can be used to find out when and for what purpose a typical
protection function can be used. The manual can also be used when calculating settings.
The technical manual contains application and functionality descriptions and lists
function blocks, logic diagrams, input and output signals, setting parameters and
technical data sorted per function. The manual can be used as a technical reference
during the engineering phase, installation and commissioning phase, and during normal
service.
The point list manual describes the outlook and properties of the data points specific to
the IED. The manual should be used in conjunction with the corresponding
communication protocol manual.
Download the latest documents from the ABB web site http://
www.abb.com/substationautomation.
REM615 ANSI 7
Application Manual
Section 1 1MAC259901-MB A
Introduction
The warning icon indicates the presence of a hazard which could result
in personal injury.
The information icon alerts the reader to important facts and conditions.
The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.
Although warning hazards are related to personal injury, it should be understood that
operation of damaged equipment could, under certain operational conditions, result in
8 REM615 ANSI
Application Manual
1MAC259901-MB A Section 1
Introduction
• Abbreviations and acronyms in this manual are spelled out in the glossary. The
glossary also contains definitions of important terms.
• Push button navigation in the LHMI menu structure is presented by using the push
button icons, for example:
To navigate between the options, use and .
• HMI menu paths are presented in bold, for example:
Select Main menu/Settings.
• LHMI messages are shown in Courier font, for example:
To save the changes in non-volatile memory, select Yes and press .
• Parameter names are shown in italics, for example:
The function can be enabled and disabled with the Operation setting.
• Parameter values are indicated with quotation marks, for example:
The corresponding parameter values are "Enabled" and "Disabled".
• IED input/output messages and monitored data names are shown in Courier font,
for example:
When the function picks up, the PICKUP output is set to TRUE.
• Dimensions are provided both in inches and mm. If it is not specifically mentioned
then the dimension is in mm.
REM615 ANSI 9
Application Manual
Section 1 1MAC259901-MB A
Introduction
10 REM615 ANSI
Application Manual
1MAC259901-MB A Section 1
Introduction
REM615 ANSI 11
Application Manual
12
1MAC259901-MB A Section 2
REM615 overview
2.1 Overview
REM615 is a dedicated motor protection and control IED (intelligent electronic device)
designed for the protection, control, measurement and supervision of induction motors
in manufacturing and process industry. REM615 is a member of ABB’s Relion®
product family and part of its 615 protection and control product series. The 615 series
IEDs are characterized by their compactness and withdrawable design.
Re-engineered from the ground up, the 615 series has been designed to unleash the full
potential of the IEC 61850 standard for communication and interoperability between
substation automation devices. Once the standard configuration IED has been given the
application-specific settings, it can directly be put into service.
The 615 series IEDs support a range of communication protocols including IEC 61850
with GOOSE messaging, Modbus® and DNP3.
REM615 ANSI 13
Application Manual
Section 2 1MAC259901-MB A
REM615 overview
• Label Printing
• IED User Management
• IED Users
The IED consists of two main parts: plug-in unit and case. The plug-in unit content
depends on the ordered functionality.
14 REM615 ANSI
Application Manual
1MAC259901-MB A Section 2
REM615 overview
1) The 0.2/1A input is normally used in applications requiring sensitive earth-fault protection and featuring
core-balance current transformers.
The rated input levels are selected in the IED software for phase current and ground
current. The binary input thresholds 18...176 V DC are selected by adjusting the IED's
parameter settings.
The optional BIO module can be added in the IED to all standard
configurations.
The connection diagrams of different hardware modules are presented in this manual.
See the installation manual for more information about the case and the
plug-in unit.
REM615 ANSI 15
Application Manual
Section 2 1MAC259901-MB A
REM615 overview
A070704-ANSI V1 EN
Figure 2: LHMI
16 REM615 ANSI
Application Manual
1MAC259901-MB A Section 2
REM615 overview
2.4.1 LCD
The LHMI includes a graphical LCD that supports two character sizes. The character
size depends on the selected language.
1 2
3 4
A070705-ANSI V2 EN
1 Header
2 Icon
3 Content
4 Scroll bar (displayed when needed)
2.4.2 LEDs
The LHMI includes three protection indicators above the display: Normal, Pickup and
Trip.
There are also 11 matrix programmable alarm LEDs on front of the LHMI. The LEDs
can be configured with PCM600 and the operation mode can be selected with the
LHMI, WHMI or PCM600.
REM615 ANSI 17
Application Manual
Section 2 1MAC259901-MB A
REM615 overview
There are two additional LEDs which are embedded into the control buttons and
. They represent the status of the circuit breaker.
2.4.3 Keypad
The LHMI keypad contains push-buttons which are used to navigate in different views
or menus. With the push-buttons you can give open or close commands to one primary
object, for example, a circuit breaker, disconnector or switch. The push-buttons are
also used to acknowledge alarms, reset indications, provide help and switch between
local and remote control mode.
A071176-ANSI V1 EN
Figure 4: LHMI keypad with object control, navigation and command push-
buttons and RJ-45 communication port
The WHMI enables the user to access the IED via a web browser. The supported web
browser version is Internet Explorer 7.0 or later.
18 REM615 ANSI
Application Manual
1MAC259901-MB A Section 2
REM615 overview
• Measurement display
• Oscillographic records
• Phasor diagram
The menu tree structure on the WHMI is almost identical to the one on the LHMI.
A070754-ANSI V2 EN
• Locally by connecting your laptop to the IED via the front communication port.
• Remotely over LAN/WAN.
2.6 Authorization
The user categories have been predefined for the LHMI and the WHMI, each with
different rights and default passwords.
REM615 ANSI 19
Application Manual
Section 2 1MAC259901-MB A
REM615 overview
2.7 Communication
The IED supports different communication protocols: IEC 61850, Modbus® and DNP
3.0 Level 2 - all using TCP/IP. DNP3 and Modbus also support serial communication.
Operational information and controls are available through these protocols.
The IEC 61850 communication implementation supports all monitoring and control
functions. Additionally, parameter setting and DFR records can be accessed using the
IEC 61850 protocol. Oscillographic files are available to any Ethernet-based
application in the standard COMTRADE format. Further, the IED can send and
receive binary signals from other IEDs (so called horizontal communication) using the
IEC61850-8-1 GOOSE profile, where the highest performance class with a total
transmission time of 3 ms is supported. The IED meets the GOOSE performance
requirements for tripping applications in distribution substations, as defined by the IEC
20 REM615 ANSI
Application Manual
1MAC259901-MB A Section 2
REM615 overview
61850 standard. The IED can simultaneously report events to five different clients on
the station bus.
All communication connectors, except for the front port connector, are placed on
integrated optional communication modules. The IED can be connected to Ethernet-
based communication systems via the RJ-45 connector (100BASE-TX) or the fiber-
optic LC connector (100BASE-FX).
REM615 ANSI 21
Application Manual
22
1MAC259901-MB A Section 3
REM615 variants
Functional diagrams
The functional diagrams describe the IED's functionality from the protection,
measuring, condition monitoring, recording, control and interlocking perspective.
Diagrams show the default functionality with simple symbol logics forming principle
diagrams. The external connections to primary devices are also shown, stating the
default connections to measuring transformers. The positive measuring direction is
towards the outgoing feeder, away from the bus bar.
The functional diagrams are divided into sections with each section constituting one
functional entity. The external connections are also divided into sections. Only the
relevant connections for a particular functional entity are presented in each section.
Protection function blocks are part of the functional diagram. They are identified based
on their ANSI function number/acronym, but the IEC based symbol and the IEC 61850
names are also included. Some function blocks are used several times in the
configuration. To separate the blocks from each other, the IEC 61850 name and ANSI
function number are appended with a running number, that is an instance number, from
one upwards. The IED’s internal functionality and the external connections are
separated with a dashed line presenting the IED’s physical casing.
Signal Matrix
With Signal Matrix in PCM600 the user can modify the standard configuration
according to the actual needs. The IED is delivered from the factory with default
connections described in the functional diagrams for BI's, BO's, function to function
connections and alarm LEDs. Signal Matrix has a number of different page views,
designated as follows:
• Binary input
• Binary output
• Functions
REM615 ANSI 23
Application Manual
Section 3 1MAC259901-MB A
REM615 variants
There are four IED variant-specific setting groups. Parameters can be set independently
for each setting group.
The active setting group (1...4) can be changed with a parameter. The active setting
group can also be changed via a binary input if the binary input is enabled for this. To
enable the change of the active setting group via a binary input, connect a free binary
input with PCM600 to the ActSG input of the SGCB-block.
The active setting group defined by a parameter is overridden when a binary input is
enabled for changing the active setting group.
24 REM615 ANSI
Application Manual
1MAC259901-MB A Section 3
REM615 variants
REM615 ANSI 25
Application Manual
Section 3 1MAC259901-MB A
REM615 variants
REM615
X120 X100
1 + 1
BI 1 Vaux
2 2
-
3 3
BI 2
IRF
IED FAILURE ALARM
4
4 5
P1
BI 3
PO1
5 BREAKER CLOSE
S1 BI 4
6 6
S2 7
7
IA
8 PO2
P2 9 BREAKER FAILURE
IB 8
52 10 9
11 10
IC SO1
A B C 12 COMMON PICKUP
13 11
IG 12
14 13
SO2 COMMON TRIP
X110 14
1 16
BI 1 PO3
2
17 MASTER TRIP 1
3 15
BI 2 19
4 TCM-1 18
5 20
BI 3 22
6
PO4
21 MASTER TRIP 2
BI 4 23
7
TCM-2 24
8
BI 5
9
X110
BI 6 14
10
SO1
11 16
BI 7 15
12
17
SO2
BI 8
13 19
18
20
SO3
X130
22
1 21
BI 1 1)
2 23
SO4
BI 2 24
3
4
BI 3 X130
5
10
1) SO1
BI 4
6 12
11
7 13
BI 5
8 SO2
15
BI 6 14
9 16
SO3
18
X1 17
1) 2)
LAN
X5
1)
1 GND
2 GNDC
3
4 IRIG-B-
5 IRIG-B+
6 AGND
7 B/- TX
8 A/+ TX
9 B/- RX
10 A/+ RX
X13
1)
Light sensor input 1
X14
1)
Light sensor input 2
X15
1)
Light sensor input 3
1) Optional
2) 100BaseFX / LC or 100BaseTX / RJ-45
GUID-4129EB43-568C-4D4A-8650-AC65D67D73A2 V1 EN
26 REM615 ANSI
Application Manual
1MAC259901-MB A Section 3
REM615 variants
A
B
C
N REM615
n
X120 X100
1 + 1
a BI 1 Vaux
2
da dn - 2
3 3
BI 2
IRF
IED FAILURE ALARM
4
4 5
P1
BI 3
PO1
5 BREAKER CLOSE
S1 BI 4
6 6
S2 7
7
IA
8 PO2
P2 9 BREAKER FAILURE
IB 8
52 10 9
11 10
IC SO1
A B C 12 COMMON PICKUP
13 11
IG 12
14 13
SO2 COMMON TRIP
X13 14
0
1 16
BI 1 PO3
2
17 MASTER TRIP 1
3 15
BI 2 19
4 TCM-1 18
5 20
BI 3 22
6
PO4
21 MASTER TRIP 2
7
BI 4 23
8
TCM-2 24
9
Not in use
10 X110
11
VA 14
12 SO1
13 16
VB 15
14 17
15
SO2
VC
16 19
17 18
VG 20
18 SO3
22
21
23
X110
SO4
1
BI 1 24
2
3
BI 2
4
5
BI 3
6
BI 4
7
8
BI 5
9
BI 6
10
11
BI 7
12
BI 8
13
X1
1) 2)
LAN
X5
1)
1 GND
2 GNDC
3
4 IRIG-B-
5 IRIG-B+
6 AGND
7 B/- TX
8 A/+ TX
9 B/- RX
10 A/+ RX
X13
1)
Light sensor input 1
X14
1)
Light sensor input 2
X15
1)
Light sensor input 3
1) Optional
2) 100BaseFX / LC or 100BaseTX / RJ-45
GUID-6773A86A-F538-42FB-8F3D-9F33B87DE356 V1 EN
Figure 7: Connection diagram for MA02 (induction motor) with current and
voltage inputs
REM615 ANSI 27
Application Manual
Section 3 1MAC259901-MB A
REM615 variants
3.3.1 Applications
The standard configuration is mainly intended for comprehensive protection and
control functionality of circuit breaker controlled induction motors. With minor
modifications this standard configuration can be applied also for contactor controlled
motors.
The IED with this standard configuration is delivered from the factory with default
settings and parameters. The end-user flexibility for incoming, outgoing and internal
signal designation within the IED enables this configuration to be further adapted to
different primary circuit layouts and the related functionality needs by modifying the
internal functionality using PCM600.
3.3.2 Functions
Table 9: Functions included in the REM615 standard configuration MA01
Function IEC 61850 IEC 60617 ANSI
Included functions
Three-phase current measurement CMMXU1 3I IA, IB, IC
Sequence current measurement CSMSQI1 I1,I2,I0 I1, I2, I0
28 REM615 ANSI
Application Manual
1MAC259901-MB A Section 3
REM615 variants
REM615 ANSI 29
Application Manual
Section 3 1MAC259901-MB A
REM615 variants
30 REM615 ANSI
Application Manual
1MAC259901-MB A Section 3
REM615 variants
The analog channels, measurements from CTs, have fixed connections to the different
function blocks inside the IED’s standard configuration.
The analog channels are assigned to different functions as shown in the functional
diagrams. The common signal marked with IA, IB, IC represents the three phase
currents. The signal IG represents the measured ground current.
The functional diagrams describe the IED’s protection functionality in detail and
according to the factory set default connections.
Three overcurrent stages are offered for overcurrent and short-circuit protection. The
motor jam protection function (51LR) is blocked by the motor startup protection
function. 51P can be used for overcurrent protection and 50P for the short-circuit
protection. The operation of 51P is not blocked as default by any functionality and it
should be set over the motor start current level to avoid unnecessary operation.
Trip1 LED2
LEDPTRC
INR
3I2f>
INRPHAR1 NOTE 1
50P OR 86/94 LED
IA, IB, IC BLK2H TRIP_PhA PHASE C TRIP
BLOCK
TRIP_PhB
TRIP_PhC TRIP_PhC
TRIP_PhC
3I>>>(1) Trip1 LED3
PHHPTOC1 LEDPTRC
IA, IB, IC PICKUP
BLOCK TRIP
AVAILABLE FOR MAPPING USING
SMT TOOL IN PCM TO ANY PROTECTION, ENA_MULT OVERCURRENT
DEPENDING ON APPLICATION. OR PROTECTION
LED5
GUID-B4F7FD46-8B4C-4C84-81F1-D21DEA7FA905 V1 EN
REM615 ANSI 31
Application Manual
Section 3 1MAC259901-MB A
REM615 variants
51LR
Ist>
JAMPTOC1
LOCKED ROTOR/JAM
IA,IB,IC PICKUP
66/51LRS Pickup BLOCK TRIP OR
LED7
GUID-45D4D872-D94F-490F-9AF8-E8E58E9A5007 V1 EN
51G
I0>(1)
EFLPTOC1 GROUND / NEUTRAL
IG
PROTECTION
X120 BI1 BLOCK TRIP
OR
LED4
OVERCURRENT
PROTECTION
OR
LED5
GUID-5B9283CE-C8C8-47E5-A219-6AFD9A22EE8A V1 EN
The ground-fault protection is blocked when the short circuit protection (51P) is
started. The operation of the ground-fault protection functions is connected to alarm
LED 2.
32 REM615 ANSI
Application Manual
1MAC259901-MB A Section 3
REM615 variants
62EST
ESTART
ESMGAPC1
IA,IB,IC ST_EMERG_EN ST_EMERG
BLOCK
X110 BI5 (Emergency start) ST_EMERG_RQ
49M
3Ith>M
MPTTR1 OVERLOAD ALARM/TRIP
IA,IB,IC Trip
OR
BLK_OPR ALARM LED10
ENA_MULT BLK_RESTART
ST_EMERG
TP-2
TP-2
TPGAPC2
RESTART_INHIBIT
OR
CB_OPENING IN1 OUT1
IN2 OUT2 86/94-1 TRIP
66/51LRS_LOCK_START
46M-1_BLK_RESTART
46M-2_BLK_RESTART
X110 BI6 (External restart inhibit)
GUID-3D99347A-FCAA-461C-94B2-272753711BDB V1 EN
The emergency start function (62EST) allows motor startups although the restart
inhibit is activated. The emergency start is enabled for ten minutes after the selected
binary input (X110:BI5) is energized. On the rising edge of the emergency start signal:
• Calculated thermal level is set slightly below the restart inhibit level to allow at
least one motor startup
• Value of the cumulative startup time counter 66/51LRS is set slightly below the
set restart inhibit value to allow at least one motor startup
• Set operate values of the temperature stages in 49M function is increased by 10
percent
• External restart inhibit signal (X100:PO1) is ignored
• Alarm LED is activated
The external restart inhibit signal is ignored for as long as the emergency start is
activated. A new emergency start cannot be made until the emergency start signal has
been reset and the emergency start time of 10 minutes has expired.
REM615 ANSI 33
Application Manual
Section 3 1MAC259901-MB A
REM615 variants
The thermal overload protection function (49M) detects short- and long term overloads
under varying load conditions. When the emergency start request is issued for the
emergency start function, it activates the corresponding input of the thermal overload
function. When the thermal overload function has issued a restart blocking, which
inhibits the closing of the breaker when the machine is overloaded, the emergency start
request removes this blocking and enables the user to start the motor again.
The restart inhibit is activated for a set period when a circuit breaker is opened. This is
called remanence voltage protection where the motor has damping remanence voltage
after circuit breaker opening and reclosing after a too short period of time. This can
lead to stress for the machine and other apparatuses. The remanence voltage protection
waiting time can be set to a timer function TP-2.
34 REM615 ANSI
Application Manual
1MAC259901-MB A Section 3
REM615 variants
66/51LRS
Is2t n<
STTPMSU1
X120 BI2 CB Closed BLOCK CPR_IIT
BLK_LK_ST OPR_STALL
CB_CLOSED MOT_START
OPTS
MDSOPT1
BLOCK ALARM
POS_ACTIVE WARNING
OPTM-2
OPTS
MDSOPT2
BLOCK ALARM
POS_ACTIVE WARNING
GUID-D458AEA2-9AE8-4C1E-A6B2-7FDB4D4357B8 V1 EN
With the motor startup supervision function (66/51LRS) the starting of the motor is
supervised by monitoring three-phase currents or the status of the energizing circuit
breaker of the motor. The motor speed switch indication can be used to determine the
locked rotor situation. If the motor is running, the speed switch activates the binary
input (X110:BI6).
When the emergency start request is activated by 62EST and 66/51LRS is in lockout
state, which inhibits motor starting, the lockout is deactivated and emergency starting
is available.
The upstream blocking from the motor startup is connected to the output SO1
(X110:14-15-16). The output is used for sending a blocking signal to the relevant
overcurrent protection stage of the IED at the infeeding bay.
REM615 ANSI 35
Application Manual
Section 3 1MAC259901-MB A
REM615 variants
The motor running time counter (OPTM-1) provides history data since last
commissioning. The counter counts the total number of motor running hours and is
incremented when the energizing circuit breaker is closed. The alarm of the runtime
counter is connected to alarm LED 7.
46M-1
I2>(1)
MNSPTOC1
I1, I2, I0 PICKUP
BLOCK TRIP
ENA_MULT
46M-2
46R
I2/I1>
PREVPTOC1
I1, I2, I0 PICKUP
BLOCK TRIP
ENA_MULT
GUID-CB28F952-7706-4FF3-9FE0-8BA28C76B812 V1 EN
Two negative-sequence overcurrent stages (46M-1 and 46M-2) are offered for phase
unbalance protection. These functions are used to protect the motor against phase
unbalance caused by, for example, a broken conductor. Phase unbalance in network
feeding of the motor causes overheating of the motor.
The phase reversal protection (46R) is based on the calculated negative phase-sequence
current. It detects too high NPS current values during motor start up, caused by
36 REM615 ANSI
Application Manual
1MAC259901-MB A Section 3
REM615 variants
incorrectly connected phases, which in turn causes the motor to rotate in the opposite
direction.
3I<1
LOFLPTUC1
IA, IB, IC PICKUP
BLOCK TRIP
LED6
GUID-7770F114-2193-40BD-802B-D88C6A6D4C4D V1 EN
The loss of load situation is detected by 37. The loss of load situation can happen, for
example, if there is damaged pump or a broken conveyor.
REM615 ANSI 37
Application Manual
Section 3 1MAC259901-MB A
REM615 variants
50BF
3I>/Io>BF(1)
CCBRBRF1
51P Trip
OR
50P Trip IA, IB, IC TRRET
46M-1 Trip IN TRBU
46M-2 Trip PICKUP CB_FAULT_AL
46R Trip POSCLOSE
49M Trip CB_FAULT
50BF Retrip BLOCK
1)
AFD-1 Trip
AFD-2 Trip
AFD-3 Trip PO2 X100
51G Trip
8
9
X120 BI2 (Breaker Closed)
Circuit Breaker failure
protection trip to
NOTES: 1) DASHED LINE INDICATES OPTIONAL associated breaker(s)
INPUT BASED ON CONFIGURATION.
GUID-1A8FBDD5-E0F7-4E5E-A85B-9AF88EA5E170 V1 EN
The circuit-breaker failure protection (50BF) is initiated via the start input by a number
of different protection stages in the IED. 50BF offers different operating modes
associated with the circuit-breaker position and the measured phase and residual currents.
50BF has two operating outputs: TRRET and TRBU. The TRRET operate output is
used for retripping its own circuit breaker through the Master Trip 1 again. The TRBU
output is used to give a backup trip to the circuit breaker feeding upstream. For this
purpose, the TRBU operate output signal is connected to the output PO2 (X100: 8-9).
LED 6 is used for backup (TRBU) operate indication.
3.3.3.2 Functional diagrams for digital fault recorder and trip circuit monitoring
The digital fault recorder has 64 digital inputs. All pickup and trip signals from the
protection stages are routed to trigger the digital fault recorder or alternatively only to
be recorded by the digital fault recorder depending on the parameter settings.
38 REM615 ANSI
Application Manual
1MAC259901-MB A Section 3
REM615 variants
DFR
DR
DREC
IA-A AI#1
IB-A AI#2
IC-A AI#3
IG-A AI#4
I1-A AI#5
I2-A AI#6
I0-A AI#7
Disabled AI#8
Disabled AI#9
Disabled AI#10
Disabled AI#11
Disabled AI#12
GUID-B05E3158-0F08-498D-9415-ED2E78D67C1B V1 EN
REM615 ANSI 39
Application Manual
Section 3 1MAC259901-MB A
REM615 variants
DFR
DR
DREC
51P Trip BI#1
Spare BI#3
Spare BI#4
51G Trip BI#5
Spare BI#6
Spare BI#7
Spare BI#8
Spare BI#9
46M-1 Trip BI#10
46M-2 Trip BI#11
46R Pickup BI#12
49M AlmThm BI#13
49M Trip BI#14
50BF Retrip BI#15
50BF Backup Trip BI#16
51LR Trip BI#17
AFD-11 FADet BI#18
AFD-21 FADet BI#19
AFD-31 FADet BI#20
AFD-11 Trip BI#21
AFD-21 Trip BI#22
AFD-31 Trip BI#23
66/51LRS Trip BI#24
66/51LRS Stall BI#25
66/51LRS StrInh BI#26
Spare BI#27
TCM-1 Alarm BI#28
TCM-2 Alarm BI#29
62EST Start BI#30
Spare BI#31
Spare BI#32
GUID-5938E2F6-F389-4348-BE7E-ABF5AE212B4F V1 EN
40 REM615 ANSI
Application Manual
1MAC259901-MB A Section 3
REM615 variants
DFR
DR
DREC
Spare BI#33
Spare BI#34
Spare BI#35
Spare BI#36
CCM Fail BI#37
CCM Alarm BI#38
Spare BI#39
37 Trip BI#40
Spare BI#41
Spare BI#42
52CM-1 TRV_T_OP_ALM BI#43
52CM-1 TRV_T_CL_ALM BI#44
52CM-1 CB_LIFE_ALM BI#45
52CM-1 Alarm BI#46
BI#47
BI#48
BI#49
BI#50
BI#51
BI#52
BI#53
BI#54
BI#55
BI#56
BI#57
BI#58
BI#59
BI#60
BI#61
BI#62
BI#63
BI#64
GUID-9CAE2413-38C1-47E8-A8BB-4F4DF8F1CC3B V1 EN
Two separate TCM functions have been included: TCM-1 for PO3 (X100:16-19) and
TCM-2 for PO4 (X100:20-23).
REM615 ANSI 41
Application Manual
Section 3 1MAC259901-MB A
REM615 variants
TCM-1
TCS(1)
X120 BI2 (CB Closed) TCSSCBR1
OR
86/94-1 Trip BLOCK ALARM
86/94-2 Trip
TCM-2
TCS(2)
TCSSCBR2
BLOCK ALARM
GUID-7076EC5C-8FB2-42D6-A589-57AEE9B6B712 V1 EN
The trip circuit monitoring 1 & 2 are blocked by the Master Trip (86/94-1 & 2) and the
circuit-breaker open position signal.
The motor runtime counter alarm is connected also to the alarm LED 9.
42 REM615 ANSI
Application Manual
1MAC259901-MB A Section 3
REM615 variants
GUID-F3EF647B-EDF2-48CF-B663-613AB8F4A176 V1 EN
X120 BI4
NOTES: 1) DASHED LINE INDICATES OPTIONAL
52 EXE_OP INPUT BASED ON CONFIGURATION.
2) NON-LATCHED MODE AS DEFAULT.
GUID-B5E4C044-8BDD-4591-BB2F-27E49E1FF35C V1 EN
The trip signals from the protections are connected to the trip output contact PO3
(X100:16-19) via the corresponding Master Trip (86/94-1). Open control commands to
the circuit breaker from the local or remote CBXCBR1-exe_op are connected directly
to the output PO3 (X100:16-19).
86/94-1 provides the lockout/latching function, event generation and the trip signal
duration setting. If the lockout operation mode is selected, one binary input can be
REM615 ANSI 43
Application Manual
Section 3 1MAC259901-MB A
REM615 variants
reassigned to the RST_LKOUT input of the Master Trip to enable external reset with a
push button. Similarly, 86/94-2 is used for Trip coil 2.
52CM
CBCM
BLOCK SSCBR1 TRV_T_OP_ALM
POSOPEN TRV_T_CL_ALM
POSCLOSE DIFTRVTOPALM
X110 BI3 (GAS pressure Alarm) PRES_ALM_IN DIFTRVTCLALM
PRES_LO_IN SPR_CHR_ALM
SPR_CHR_ST OPR_ALM
X110 BI4 (CB Spring Charged) SPR_CHR OPR_LO
RST_IPOW IPOW_ALM
RST_CB_WEAR IPOW_LO
CB_LIFE_ALM
MON_ALM
PRES_ALM
PRES_LO
OPENPOS
INTERMPOS
CLOSEPOS
GUID-3AA074FB-81C9-43FA-8AB0-C329C0737D9C V1 EN
The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The
input can be activated by the configuration logic, which is a combination of the
disconnector or breaker truck and earth switch position statuses and the statuses of the
Master Trip logics and gas pressure alarm and circuit-breaker spring charging.
When the motor restart is inhibited, the BLK_CLOSE input is activated and closing of
the breaker is not possible. When all conditions of the circuit breaker closing are
fulfilled, the CLOSE_ENAD output of the 52 is activated and PO1 output (X100:6-7)
is closed.
The ITL_BYPASS input can be used, for example, to always enable the closing of the
circuit breaker when the circuit breaker truck is in the test position, despite of the
interlocking conditions being active when the circuit breaker truck is closed in service
position.
44 REM615 ANSI
Application Manual
1MAC259901-MB A Section 3
REM615 variants
The circuit breaker condition monitoring function (52CM) supervises the circuit
breaker status based on the binary input information connected and measured current
levels. The function introduces various supervision methods.
1)
86/94 LED TP-1
Trip1 TP-1
LEDPTRC1 TPGAPC1
GUID-FCFBA73C-BF23-4F08-ADD6-6F293506FE5D V1 EN
REM615 ANSI 45
Application Manual
Section 3 1MAC259901-MB A
REM615 variants
Trip(1)
TRPPTRC1
PICKUP PICKUP
TRIP TRIP
Trip(2)
TRPPTRC2
PICKUP PICKUP
TRIP TRIP
SO#2 (X100:13-14-15)
Trip Signal
GUID-C0BFC2AD-2845-47B2-B884-6195D4F542EC V1 EN
The signal outputs from the IED are connected to give dedicated information on:
• Start of any protection function SO1 (X100:10-12)
• Operation (trip) of any protection function SO2 (X100:13-15)
• Motor startup indication to upstream level SO1 (X110:14-16)
• Motor thermal overload alarm indication SO2 (X110:17-19)
TP are timers and used for setting the minimum pulse length for the outputs. There are
four generic timers (TP1..4) available in the IED. The remaining ones not described in
the functional diagram are available in PCM600 for connection where applicable.
46 REM615 ANSI
Application Manual
1MAC259901-MB A Section 3
REM615 variants
ARC(1)
ARCSARC1
IG ARC_FLT_DET
BLOCK
REM_FLT_ARC LED11
OPR_MODE
ARC(2)
ARCSARC2
ARC(3)
ARCSARC3
GUID-B9CC4A91-7BC3-4DF0-921D-E95114B79280 V1 EN
The arc protection offers individual function blocks for three ARC sensors that can be
connected to the IED. Each arc protection function block has two different operation
modes, with or without the phase and residual current check. Operate signals from the
REM615 ANSI 47
Application Manual
Section 3 1MAC259901-MB A
REM615 variants
arc protection function blocks are connected to the Master Trip and also to the alarm
LED 10 as a common operate indication.
3.4.1 Applications
The standard configuration is mainly intended for comprehensive protection and
control functionality of circuit breaker controlled induction motors. With minor
modifications this standard configuration can be applied also for contactor controlled
motors.
The IED with this standard configuration is delivered from the factory with default
settings and parameters. The end-user flexibility for incoming, outgoing and internal
signal designation within the IED enables this configuration to be further adapted to
different primary circuit layouts and the related functionality needs by modifying the
internal functionality using PCM600.
3.4.2 Functions
Table 14: Functions included in the REM615 standard configuration MA02
Function IEC 61850 IEC 60617 ANSI
Included functions
Three-phase current measurement CMMXU1 3I IA, IB, IC
Three-phase voltage measurement VMMXU1 3U VA,VB,VC
Sequence current measurement CSMSQI1 I1,I2,I0 I1, I2, I0
48 REM615 ANSI
Application Manual
1MAC259901-MB A Section 3
REM615 variants
REM615 ANSI 49
Application Manual
Section 3 1MAC259901-MB A
REM615 variants
50 REM615 ANSI
Application Manual
1MAC259901-MB A Section 3
REM615 variants
The analog channels, measurements from CTs, have fixed connections to the different
function blocks inside the IED’s standard configuration.
The analog channels are assigned to different functions as shown in the functional
diagrams. The common signal marked with IA, IB, IC represents the three phase
currents. The signal IG represents the measured ground current.
The functional diagrams describe the IED’s protection functionality in detail and
according to the factory set default connections.
REM615 ANSI 51
Application Manual
Section 3 1MAC259901-MB A
REM615 variants
Three overcurrent stages are offered for overcurrent and short-circuit protection. The
motor jam protection function (51LR) is blocked by the motor startup protection
function. 51P can be used for overcurrent protection and 50P for the short-circuit
protection. The operation of 51P is not blocked as default by any functionality and it
should be set over the motor start current level to avoid unnecessary operation.
Trip1 LED2
LEDPTRC
INR
3I2f>
INRPHAR1 NOTE 1
50P OR 86/94 LED
IA, IB, IC BLK2H TRIP_PhA PHASE C TRIP
BLOCK
TRIP_PhB
TRIP_PhC TRIP_PhC
TRIP_PhC
3I>>>(1) Trip1 LED3
PHHPTOC1 LEDPTRC
IA, IB, IC PICKUP
BLOCK TRIP
AVAILABLE FOR MAPPING USING
SMT TOOL IN PCM TO ANY PROTECTION, ENA_MULT OVERCURRENT
DEPENDING ON APPLICATION. OR PROTECTION
LED5
GUID-B4F7FD46-8B4C-4C84-81F1-D21DEA7FA905 V1 EN
51LR
Ist>
JAMPTOC1
LOCKED ROTOR/JAM
IA,IB,IC PICKUP
66/51LRS Pickup BLOCK TRIP OR
LED7
GUID-45D4D872-D94F-490F-9AF8-E8E58E9A5007 V1 EN
52 REM615 ANSI
Application Manual
1MAC259901-MB A Section 3
REM615 variants
OVERCURRENT
51G PROTECTION
I0>(1) OR
EFLPTOC1 LED5
IG
X120 BI1 BLOCK TRIP
GUID-FE8C125E-1D82-4CE1-ABDA-540BE6D65B8D V1 EN
The ground-fault protection is blocked when the short circuit protection (51P) is
started. The operation of the earth-fault protection functions is connected to alarm LED
4.
REM615 ANSI 53
Application Manual
Section 3 1MAC259901-MB A
REM615 variants
59G
U0>(1)
ROVPTOV1
VG PICKUP
BLOCK TRIP
27
3U<(1)
PHPTUV1
VA,VB,VC
PICKUP OVER & UNDER
60 Pickup BLOCK
TRIP VOLTAGE PROTECTION
OR
LED8
27PS
U1<
PSPTOV1
VA,VB,VC
PICKUP
BLOCK
TRIP
47
U2>
NSPTOV1
VA,VB,VC
PICKUP
BLOCK
TRIP
GUID-643F3E06-EDB3-452A-BEE2-EE644DF34F2C V1 EN
54 REM615 ANSI
Application Manual
1MAC259901-MB A Section 3
REM615 variants
62EST
ESTART
ESMGAPC1
IA,IB,IC ST_EMERG_EN ST_EMERG
BLOCK
X110 BI5 (Emergency start) ST_EMERG_RQ
49M
3Ith>M
MPTTR1 OVERLOAD ALARM/TRIP
IA,IB,IC Trip
OR
BLK_OPR ALARM LED10
ENA_MULT BLK_RESTART
ST_EMERG
TP-2
TP-2
TPGAPC2
RESTART_INHIBIT
OR
CB_OPENING IN1 OUT1
IN2 OUT2 86/94-1 TRIP
66/51LRS_LOCK_START
46M-1_BLK_RESTART
46M-2_BLK_RESTART
X110 BI6 (External restart inhibit)
GUID-3D99347A-FCAA-461C-94B2-272753711BDB V1 EN
The emergency start function (62EST) allows motor startups although the restart
inhibit is activated. The emergency start is enabled for ten minutes after the selected
binary input (X110:BI5) is energized. On the rising edge of the emergency start signal:
• Calculated thermal level is set slightly below the restart inhibit level to allow at
least one motor startup
• Value of the cumulative startup time counter 66/51LRS is set slightly below the
set restart inhibit value to allow at least one motor startup
• Set operate values of the temperature stages in 49M function is increased by 10
percent
• External restart inhibit signal (X100:PO1) is ignored
• Alarm LED is activated
The external restart inhibit signal is ignored for as long as the emergency start is
activated. A new emergency start cannot be made until the emergency start signal has
been reset and the emergency start time of 10 minutes has expired.
REM615 ANSI 55
Application Manual
Section 3 1MAC259901-MB A
REM615 variants
The thermal overload protection function (49M) detects short- and long term overloads
under varying load conditions. When the emergency start request is issued for the
emergency start function, it activates the corresponding input of the thermal overload
function. When the thermal overload function has issued a restart blocking, which
inhibits the closing of the breaker when the machine is overloaded, the emergency start
request removes this blocking and enables the user to start the motor again.
The restart inhibit is activated for a set period when a circuit breaker is opened. This is
called remanence voltage protection where the motor has damping remanence voltage
after circuit breaker opening and reclosing after a too short period of time. This can
lead to stress for the machine and other apparatuses. The remanence voltage protection
waiting time can be set to a timer function TP-2.
56 REM615 ANSI
Application Manual
1MAC259901-MB A Section 3
REM615 variants
66/51LRS
Is2t n<
STTPMSU1
X120 BI2 CB Closed BLOCK CPR_IIT
BLK_LK_ST OPR_STALL
CB_CLOSED MOT_START
OPTS
MDSOPT1
BLOCK ALARM
POS_ACTIVE WARNING
OPTM-2
OPTS
MDSOPT2
BLOCK ALARM
POS_ACTIVE WARNING
GUID-D458AEA2-9AE8-4C1E-A6B2-7FDB4D4357B8 V1 EN
With the motor startup supervision function (66/51LRS) the starting of the motor is
supervised by monitoring three-phase currents or the status of the energizing circuit
breaker of the motor. The motor speed switch indication can be used to determine the
locked rotor situation. If the motor is running, the speed switch activates the binary
input (X110:BI6).
When the emergency start request is activated by 62EST and 66/51LRS is in lockout
state, which inhibits motor starting, the lockout is deactivated and emergency starting
is available.
The upstream blocking from the motor startup is connected to the output SO1
(X110:14-15-16). The output is used for sending a blocking signal to the relevant
overcurrent protection stage of the IED at the infeeding bay.
REM615 ANSI 57
Application Manual
Section 3 1MAC259901-MB A
REM615 variants
The motor running time counter (OPTM-1) provides history data since last
commissioning. The counter counts the total number of motor running hours and is
incremented when the energizing circuit breaker is closed. The alarm of the runtime
counter is connected to alarm LED 7.
46M-1
I2>(1)
MNSPTOC1
I1, I2, I0 PICKUP
BLOCK TRIP
ENA_MULT
46M-2
46R
I2/I1>
PREVPTOC1
I1, I2, I0 PICKUP
BLOCK TRIP
ENA_MULT
GUID-CB28F952-7706-4FF3-9FE0-8BA28C76B812 V1 EN
Two negative-sequence overcurrent stages (46M-1 and 46M-2) are offered for phase
unbalance protection. These functions are used to protect the motor against phase
unbalance caused by, for example, a broken conductor. Phase unbalance in network
feeding of the motor causes overheating of the motor.
The phase reversal protection (46R) is based on the calculated negative phase-sequence
current. It detects too high NPS current values during motor start up, caused by
58 REM615 ANSI
Application Manual
1MAC259901-MB A Section 3
REM615 variants
incorrectly connected phases, which in turn causes the motor to rotate in the opposite
direction.
3I<1
LOFLPTUC1
IA, IB, IC PICKUP
BLOCK TRIP
LED6
GUID-7770F114-2193-40BD-802B-D88C6A6D4C4D V1 EN
The loss of load situation is detected by 37. The loss of load situation can happen, for
example, if there is damaged pump or a broken conveyor.
REM615 ANSI 59
Application Manual
Section 3 1MAC259901-MB A
REM615 variants
50BF
3I>/Io>BF(1)
CCBRBRF1
51P Trip
OR
50P Trip IA, IB, IC TRRET
46M-1 Trip IN TRBU
46M-2 Trip PICKUP CB_FAULT_AL
46R Trip POSCLOSE
49M Trip CB_FAULT
50BF Retrip BLOCK
1)
AFD-1 Trip
AFD-2 Trip
AFD-3 Trip PO2 X100
51G Trip
67/51N Trip 8
9
X120 BI2 (Breaker Closed)
Circuit Breaker failure
protection trip to
NOTES: 1) DASHED LINE INDICATES OPTIONAL associated breaker(s)
INPUT BASED ON CONFIGURATION.
GUID-7BEF2E61-2E10-49B2-A660-1BAFA1E8ECCB V1 EN
The circuit-breaker failure protection (50BF) is initiated via the start input by a number
of different protection stages in the IED. 50BF offers different operating modes
associated with the circuit-breaker position and the measured phase and residual currents.
50BF has two operating outputs: TRRET and TRBU. The TRRET operate output is
used for retripping its own circuit breaker through the Master Trip 1 again. The TRBU
output is used to give a backup trip to the circuit breaker feeding upstream. For this
purpose, the TRBU operate output signal is connected to the output PO2 (X100: 8-9).
LED 6 is used for backup (TRBU) operate indication.
3.4.3.2 Functional diagrams for digital fault recorder and trip circuit monitoring
The digital fault recorder has 64 digital inputs. All pickup and trip signals from the
protection stages are routed to trigger the digital fault recorder or alternatively only to
be recorded by the digital fault recorder depending on the parameter settings.
60 REM615 ANSI
Application Manual
1MAC259901-MB A Section 3
REM615 variants
DFR
DR
DREC
IA-A AI#1
IB-A AI#2
IC-A AI#3
IG AI#4
I1-A AI#5
I2-A AI#6
I0-A AI#7
VA-kV AI#8
VB-kV AI#9
VC-kV AI#10
VG-kV AI#11
Disabled AI#12
GUID-CDD9A02C-C588-4274-B796-B44445322F53 V1 EN
REM615 ANSI 61
Application Manual
Section 3 1MAC259901-MB A
REM615 variants
DFR
DR
DREC
51P Trip BI#1
Spare BI#3
Spare BI#4
51G Trip BI#5
67/51N Trip BI#6
Spare BI#7
Spare BI#8
Spare BI#9
46M-1 Trip BI#10
46M-2 Trip BI#11
46R Pickup BI#12
49M AlmThm BI#13
49M Trip BI#14
50BF Retrip BI#15
50BF Backup Trip BI#16
51LR Trip BI#17
AFD-11 FADet BI#18
AFD-21 FADet BI#19
AFD-31 FADet BI#20
AFD-11 Trip BI#21
AFD-21 Trip BI#22
AFD-31 Trip BI#23
66/51LRS Trip BI#24
66/51LRS Stall BI#25
66/51LRS StrInh BI#26
Spare BI#27
TCM-1 Alarm BI#28
TCM-2 Alarm BI#29
62EST Start BI#30
Spare BI#31
Spare BI#32
GUID-2380BFE9-655C-49EF-B30D-4F6D6729F17E V1 EN
62 REM615 ANSI
Application Manual
1MAC259901-MB A Section 3
REM615 variants
DFR
DR
DREC
27PS Trip BI#33
27 Trip BI#34
59-G Trip BI#35
47 Trip BI#36
CCM Fail BI#37
CCM Alarm BI#38
60 Pickup BI#39
37 Trip BI#40
Spare BI#41
Spare BI#42
52CM TRV_T_OP_ALM BI#43
52CM TRV_T_CL_ALM BI#44
52CM CB_LIFE_ALM BI#45
52CM Alarm BI#46
BI#47
BI#48
BI#49
BI#50
BI#51
BI#52
BI#53
BI#54
BI#55
BI#56
BI#57
BI#58
BI#59
BI#60
BI#61
BI#62
Spare BI#63
Spare BI#64
GUID-4BE31BFD-1A74-402B-8960-46A235AD540F V1 EN
Two separate TCM functions have been included: TCM-1 for PO3 (X100:16-19) and
TCM-2 for PO4 (X100:20-23).
REM615 ANSI 63
Application Manual
Section 3 1MAC259901-MB A
REM615 variants
TCM-1
TCS(1)
X120 BI2 (CB Closed) TCSSCBR1
OR
86/94-1 Trip BLOCK ALARM
86/94-2 Trip
TCM-2
TCS(2)
TCSSCBR2
BLOCK ALARM
GUID-7076EC5C-8FB2-42D6-A589-57AEE9B6B712 V1 EN
The trip circuit monitoring 1 & 2 are blocked by the Master Trip (86/94-1 & 2) and the
circuit-breaker open position signal.
The motor runtime counter alarm is connected also to the alarm LED 9.
64 REM615 ANSI
Application Manual
1MAC259901-MB A Section 3
REM615 variants
GUID-7D6C5CB2-1099-4FF8-975F-57B787D242EF V1 EN
X120 BI4
NOTES: 1) DASHED LINE INDICATES OPTIONAL
52 EXE_OP INPUT BASED ON CONFIGURATION.
2) NON-LATCHED MODE AS DEFAULT.
GUID-61B274D3-3B7E-4C4D-9EA3-D23E01BA9809 V1 EN
The trip signals from the protections are connected to the trip output contact PO3
(X100:16-19) via the corresponding Master Trip (86/94-1). Open control commands to
the circuit breaker from the local or remote CBXCBR1-exe_op are connected directly
to the output PO3 (X100:16-19).
86/94-1 provides the lockout/latching function, event generation and the trip signal
duration setting. If the lockout operation mode is selected, one binary input can be
REM615 ANSI 65
Application Manual
Section 3 1MAC259901-MB A
REM615 variants
reassigned to the RST_LKOUT input of the Master Trip to enable external reset with a
push button. Similarly, 86/94-2 is used for Trip coil 2.
52CM
CBCM
BLOCK SSCBR1 TRV_T_OP_ALM
POSOPEN TRV_T_CL_ALM
POSCLOSE DIFTRVTOPALM
X110 BI3 (GAS pressure Alarm) PRES_ALM_IN DIFTRVTCLALM
PRES_LO_IN SPR_CHR_ALM
SPR_CHR_ST OPR_ALM
X110 BI4 (CB Spring Charged) SPR_CHR OPR_LO
RST_IPOW IPOW_ALM
RST_CB_WEAR IPOW_LO
CB_LIFE_ALM
MON_ALM
PRES_ALM
PRES_LO
OPENPOS
INTERMPOS
CLOSEPOS
GUID-3AA074FB-81C9-43FA-8AB0-C329C0737D9C V1 EN
The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The
input can be activated by the configuration logic, which is a combination of the
disconnector or breaker truck and earth switch position statuses and the statuses of the
Master Trip logics and gas pressure alarm and circuit-breaker spring charging.
When the motor restart is inhibited, the BLK_CLOSE input is activated and closing of
the breaker is not possible. When all conditions of the circuit breaker closing are
fulfilled, the CLOSE_ENAD output of the CBXCBR1 is activated and PO1 output
(X100:6-7) is closed.
The ITL_BYPASS input can be used, for example, to always enable the closing of the
circuit breaker when the circuit breaker truck is in the test position, despite of the
interlocking conditions being active when the circuit breaker truck is closed in service
position.
66 REM615 ANSI
Application Manual
1MAC259901-MB A Section 3
REM615 variants
The circuit breaker condition monitoring function (52CM) supervises the circuit
breaker status based on the binary input information connected and measured current
levels. The function introduces various supervision methods.
1)
86/94 LED TP-1
Trip1 TP-1
LEDPTRC1 TPGAPC1
GUID-FCFBA73C-BF23-4F08-ADD6-6F293506FE5D V1 EN
REM615 ANSI 67
Application Manual
Section 3 1MAC259901-MB A
REM615 variants
Trip(1)
TRPPTRC1
PICKUP PICKUP
TRIP TRIP
Trip(2)
TRPPTRC2
PICKUP PICKUP
TRIP TRIP
SO#2 (X100:13-14-15)
Trip Signal
GUID-C0BFC2AD-2845-47B2-B884-6195D4F542EC V1 EN
The signal outputs from the IED are connected to give dedicated information on:
• Start of any protection function SO1 (X100:10-12)
• Operation (trip) of any protection function SO2 (X100:13-15)
• Motor startup indication to upstream level SO1 (X110:14-16)
• Motor thermal overload alarm indication SO2 (X110:17-19)
TP are timers and used for setting the minimum pulse length for the outputs. There are
four generic timers (TP1..4) available in the IED. The remaining ones not described in
the functional diagram are available in PCM600 for connection where applicable.
68 REM615 ANSI
Application Manual
1MAC259901-MB A Section 3
REM615 variants
ARC(1)
ARCSARC1
IG ARC_FLT_DET
BLOCK
REM_FLT_ARC LED11
OPR_MODE
ARC(2)
ARCSARC2
ARC(3)
ARCSARC3
GUID-B9CC4A91-7BC3-4DF0-921D-E95114B79280 V1 EN
The arc protection offers individual function blocks for three ARC sensors that can be
connected to the IED. Each arc protection function block has two different operation
modes, with or without the phase and residual current check. Operate signals from the
REM615 ANSI 69
Application Manual
Section 3 1MAC259901-MB A
REM615 variants
arc protection function blocks are connected to the Master Trip and also to the alarm
LED 10 as a common operate indication.
70 REM615 ANSI
Application Manual
1MAC259901-MB A Section 4
Requirements for measurement transformers
The selection of a CT depends not only on the CT specifications but also on the
network fault current magnitude, desired protection objectives, and the actual CT
burden. The protection settings of the IED should be defined in accordance with the
CT performance as well as other factors.
Appropriate 'C' class CT should be used based on the total resistances of the CT
secondary circuit. If other accuracy class CTs are used then refer the following
discussions.
The rated accuracy limit factor (Fn) is the ratio of the rated accuracy limit primary
current to the rated primary current. For example, a protective current transformer of
type 5P10 has the accuracy class 5P and the accuracy limit factor 10. For protective
current transformers, the accuracy class is designed by the highest permissible
percentage composite error at the rated accuracy limit primary current prescribed for
the accuracy class concerned, followed by the letter "P" (meaning protection).
Table 19: Limits of errors according to IEC 60044-1 for protective current transformers
Accuracy class Current error at Phase displacement at rated primary Composite error at
rated primary current rated accuracy limit
current (%) minutes centiradians primary current (%)
5P ±1 ±60 ±1.8 5
10P ±3 - - 10
REM615 ANSI 71
Application Manual
Section 4 1MAC259901-MB A
Requirements for measurement transformers
The accuracy classes 5P and 10P are both suitable for non-directional overcurrent
protection. The 5P class provides a better accuracy. This should be noted also if there
are accuracy requirements for the metering functions (current metering, power
metering, and so on) of the IED.
The CT accuracy primary limit current describes the highest fault current magnitude at
which the CT fulfils the specified accuracy. Beyond this level, the secondary current of
the CT is distorted and it might have severe effects on the performance of the
protection IED.
In practise, the actual accuracy limit factor (Fa) differs from the rated accuracy limit
factor (Fn) and is proportional to the ratio of the rated CT burden and the actual CT burden.
Sin + Sn
Fa ≈ Fn ×
Sin + S
A071141 V1 EN
The nominal primary current I1n should be chosen in such a way that the thermal and
dynamic strength of the current measuring input of the IED is not exceeded. This is
always fulfilled when
The saturation of the CT protects the measuring circuit and the current input of the
IED. For that reason, in practice, even a few times smaller nominal primary current can
be used than given by the formula.
72 REM615 ANSI
Application Manual
1MAC259901-MB A Section 4
Requirements for measurement transformers
The factor 0.7 takes into account the protection IED inaccuracy, current transformer
errors, and imperfections of the short circuit calculations.
The adequate performance of the CT should be checked when the setting of the high
set stage overcurrent protection is defined. The trip time delay caused by the CT
saturation is typically small enough when the overcurrent setting is noticeably lower
than Fa.
When defining the setting values for the low set stages, the saturation of the CT does
not need to be taken into account and the pickup current setting is simply according to
the formula.
With definite time mode of operation, the saturation of CT may cause a delay that is as
long as the time the constant of the DC component of the fault current, when the
current is only slightly higher than the pickup current. This depends on the accuracy
limit factor of the CT, on the remanence flux of the core of the CT, and on the trip time
setting.
With inverse time mode of operation, the delay should always be considered as being
as long as the time constant of the DC component.
With inverse time mode of operation and when the high-set stages are not used, the AC
component of the fault current should not saturate the CT less than 20 times the pickup
current. Otherwise, the inverse operation time can be further prolonged. Therefore, the
accuracy limit factor Fa should be chosen using the formula:
The Current pickup value is the primary pickup current setting of the IED.
REM615 ANSI 73
Application Manual
Section 4 1MAC259901-MB A
Requirements for measurement transformers
The following figure describes a typical medium voltage feeder. The protection is
implemented as three-stage definite time non-directional overcurrent protection.
A071142-ANSI V2 EN
The maximum three-phase fault current is 41.7 kA and the minimum three-phase short
circuit current is 22.8 kA. The actual accuracy limit factor of the CT is calculated to be
59.
The pickup current setting for low-set stage (51P) is selected to be about twice the
nominal current of the cable. The trip time is selected so that it is selective with the
next IED (not visible in the figure above). The settings for the high-set stage and
instantaneous stage are defined also so that grading is ensured with the downstream
protection. In addition, the pickup current settings have to be defined so that the IED
operates with the minimum fault current and it does not trip with the maximum load
current. The settings for all three stages are as in the figure above.
For the application point of view, the suitable setting for instantaneous stage (50P-3) in
this example is 3 500 A (5.83 x I2n). For the CT characteristics point of view, the
criteria given by the current transformer selection formula is fulfilled and also the IED
setting is considerably below the Fa. In this application, the CT rated burden could
have been selected much lower than 10 VA for economical reasons.
74 REM615 ANSI
Application Manual
1MAC259901-MB A Section 5
IED physical connections
5.1 Inputs
REM615 ANSI 75
Application Manual
Section 5 1MAC259901-MB A
IED physical connections
76 REM615 ANSI
Application Manual
1MAC259901-MB A Section 5
IED physical connections
Terminal Description
X110-12 BI7, -
X110-12 BI8, -
X110-13 BI8, +
REM615 ANSI 77
Application Manual
Section 5 1MAC259901-MB A
IED physical connections
The IED is provided with connection sockets X13, X14 and X15 only if
the optional communication module with light sensor inputs has been
installed. If the arc flash detector option is selected when ordering an
IED, the light sensor inputs are included in the communication module.
5.2 Outputs
78 REM615 ANSI
Application Manual
1MAC259901-MB A Section 5
IED physical connections
Output contacts of slot X110 are optional. Output contacts of slot X130 are available in
the optional BIO module (BIOB02A).
REM615 ANSI 79
Application Manual
Section 5 1MAC259901-MB A
IED physical connections
Terminal Description
X130-14 SO2, NO
X130-15 SO2, NC
X130-16 SO3, common
X130-17 SO3, NO
X130-18 SO3, NC
5.2.3 IRF
The IRF contact functions as an output contact for the self-supervision system of the
protection IED. Under normal operating conditions, the IED is energized and the
contact is closed (X100/3-5). When a fault is detected by the self-supervision system or
the auxiliary voltage is disconnected, the output contact drops off and the contact
closes (X100/3-4).
80 REM615 ANSI
Application Manual
1MAC259901-MB A Section 6
Glossary
Section 6 Glossary
REM615 ANSI 81
Application Manual
Section 6 1MAC259901-MB A
Glossary
82 REM615 ANSI
Application Manual
83
Contact us
www.abb.com/substationautomation