Professional Documents
Culture Documents
MANUAL
BD2011052
MANUAL
Version: V1.00
WARNING
1) During operation of electrical equipment, certain parts of this equipment are
under high voltage. Severe personal injury or significant equipment damage
could result from improper behavior.
2) Only qualified personnel should work on this equipment or in vicinity of the
equipment. These persons must be familiar with warning & service procedure
described in this manual, as well as with safety regulations.
3) Prerequisites to proper & safety operation of the equipment are proper
storage, setup, installation, operation & maintenance of the equipment.
4) In particularly cases, the general rules & safety regulations according to
relating standards (e.g. IEC, National standards or other International
standards) for work with high voltage equipment must be observed.
COPYRIGHT
All rights reserved.
Registered trademark
® are registered trademark of Beijing Sifang Automation Co., Ltd.
CONTENTS
Part I Technical instruction of the equipment ...................................................................................... 1
1. Overview .............................................................................................................................................. 1
1.1 Application ................................................................................................................................. 1
1.2 Main features of CSC-326G protection equipment ............................................................. 1
1.3 Equipment model instruction and function configuration .................................................... 3
1.4 Execution standard................................................................................................................... 4
2. Technical conditions ........................................................................................................................... 4
2.1 Technical capbility ..................................................................................................................... 4
2.2 Main technical data .................................................................................................................. 6
3. Hardware.............................................................................................................................................. 8
3.1 Equipment structure ................................................................................................................. 8
3.2 Function module ....................................................................................................................... 8
3.3 AC module (AC) ........................................................................................................................ 9
3.4 Protection CPU module (CPU) ............................................................................................... 9
3.5 Digital input & output module (DIO) ....................................................................................... 9
3.6 Digital output module (DO)...................................................................................................... 9
3.7 Power module (POWER) ...................................................................................................... 10
3.8 Communication module (61850 COM)................................................................................ 10
3.9 4~20mA output module (AO) ................................................................................................ 10
Part II CSC-326GD Numerical Transformer Differential Protection Equipment .......................... 10
1 Introduction ......................................................................................................................................... 10
2 Equipment software ........................................................................................................................... 10
2.1 Software structure of the protection program ..................................................................... 10
2.2 Startup element....................................................................................................................... 10
2.3 Current differential protection ............................................................................................... 11
2.4 Non-electric event record ...................................................................................................... 14
2.5 Tap Control .............................................................................................................................. 14
3. Setting list........................................................................................................................................... 15
3.1 Connector list .......................................................................................................................... 15
3.2 Setting list ................................................................................................................................ 16
3.3 Instruction of differential protection control word ............................................................... 16
3.4 Instruction of transformer wiring control word .................................................................... 17
3.5 Setting calculation .................................................................................................................. 18
3.6 The related setting value of tap control ............................................................................... 19
4. Terminal diagram .............................................................................................................................. 21
Part IV CSC-326GL Numerical Transformer Protection Measuring and Control Equipment .... 22
1. Introduction ........................................................................................................................................ 22
2. Equipment software .......................................................................................................................... 22
2.1 Software structure of the protection program ..................................................................... 22
2.2 Multi-voltage blocking (directional) overcurrent protection ............................................... 23
2.3 One stage overcurrent protection......................................................................................... 25
2.4 Charging protection ................................................................................................................ 25
2.5 Zero sequence voltage protection........................................................................................ 26
2.6 Other protections .................................................................................................................... 26
2.7 TV failure detection................................................................................................................. 26
2.8 CT failure detection ................................................................................................................ 27
2.9 Tripping logic ........................................................................................................................... 27
3. Setting list........................................................................................................................................... 27
3.1 Soft connector ......................................................................................................................... 27
3.2 Setting list ................................................................................................................................ 28
3.3 Instruction of control word ..................................................................................................... 29
3.4 Setting of measuring and control ......................................................................................... 33
4 .Terminal diagram .............................................................................................................................. 35
Part V User instruction.......................................................................................................................... 36
1 .Current transformer polarity ............................................................................................................ 36
2 .Man-machine interface and manipulation ..................................................................................... 36
2.1 Menu structure ........................................................................................................................ 36
2.2 Display instruction .................................................................................................................. 36
2.3 Password ................................................................................................................................. 37
2.4 Setting instruction ................................................................................................................... 37
3. Common faults and treatment measures ...................................................................................... 40
Appendix A Transmitting reports ......................................................................................................... 43
Appendix B Differential protection setting calculation...................................................................... 43
B.1 Setting of the differential current threshold value ICD ...................................................... 43
B.2 Setting of restraint characteristic knee point current ........................................................ 43
B.3 Setting of slope of ratio restraint characteristics curve KID ............................................ 43
Appendix Calculation of back up protection setting ......................................................................... 45
C.1. Transformer Phase-phase fault back-up protection.......................................................... 45
C.1.1 Directional overcurrent protection with voltage blocking ............................................. 45
C.1.1.1 setting of current element ...................................................................................................... 45
C.1.1.2 Setting of under voltage startup element ............................................................................. 46
C.1.1.3 Setting of negative sequence voltage startup element...................................................... 47
C.2. Transformer ground fault backup protection ...................................................................... 47
C.2.1 Zero sequence overcurrent protection (directly earthed transformer) ...................... 47
C.2.2 Gap protection (neural point of the transformer earthed with gap) ............................ 48
C.2.2.1 Gap over voltage protection................................................................................................... 48
C.2.2.2 Gap overcurrent protection .................................................................................................... 48
C.2.3 Zero sequence current protection of auto-transformer neural point ......................... 49
C.3 Overload protection .................................................................................................................... 49
CSC-326G NumericalTransformer Protection Equipment Manual
1.1 Application
1
CSC-326G NumericalTransformer Protection Equipment Manual
2
CSC-326G NumericalTransformer Protection Equipment Manual
CSC-326 G □
C Differential protection
H Reserve protection of high voltge side
L Reserve protection of middle/low voltage side
3
CSC-326G NumericalTransformer Protection Equipment Manual
Number of
Function Stage Remark
time delay
Zero sequence Zero sequence voltage
2 3/Ⅰ,2/Ⅱ
overcurrent protection blocking
Gap overcurrent Parallel output with gap
1 2
protection overvoltage and
Gap overvoltage overcurrent protection
1 2
protection selected by control word
Zero sequence linkage
1 1
trip
Overload 1 1 Alarm
Start up aeration 1 1
Block voltage regulation 1 1
Voltage blocking can be
Multiple Voltage
enabled or disabled.
blocking (directional) 2 3
Directional can be enabled
overcurrent protection
Backup or disabled
protection Definite time current
1 2
on differential protection
medium/low Charging current automatic withdrawal mode
1 1
voltage side protection can be select
Zero sequence
1 1 Alarm
overvoltage protection
Overload 1 1 Alarm/trip
Note: it is the recommend configuration. With the modular program design, the
function can be configured according to the demand of the user (only used
protection function setting in the setting list). It is no need to modify the
program.
2. Technical conditions
DC voltage: 220V/110V
Rated inputs
phase voltage: 100V
4
CSC-326G NumericalTransformer Protection Equipment Manual
Open-delta voltage:300V
AC current: 1A/5A
Frequency: 60Hz
Current: ≤ 3%
Accuracy Voltage: ≤ 5%
Direction: ≤ ±2
DC circuit: ≤ 35W
Power
AC current: phase ≤ 1VA (In=5A) or ≤ 0.5VA (In=1A)
consumption
5
CSC-326G NumericalTransformer Protection Equipment Manual
6
CSC-326G NumericalTransformer Protection Equipment Manual
7
CSC-326G NumericalTransformer Protection Equipment Manual
3. Hardware
8
CSC-326G NumericalTransformer Protection Equipment Manual
7 6 5 4 3 2 1
POWER DO DO CPU DIO or AC2 AC1
61850 or
4~20MA
Power Digital Digital Protectio Extended Alternatin Alternating
output 2 output 1 n module g current current 1
2
Module 1 and 2 are AC modules, which include voltage convertor and current
convertor.Different type of the equipment have the different configuration
accordingly. Phase current transformer: rated current 5A, linearity range:
400mA~100A; rated current 1A, linearity range: 80mA~20A.
Module 4 and 5 are protection CPU modules used for differential protection;
Module 4 is the protection CPU module while equipment is used as back-up
protection. This module is the key module in the equipment. The two modules
are same which used for differential protection. CPU module is responsible
for all the protection function A/D conversion, software and hardware
self-monitoring and diagnostics.
Digital input & output module could be used selectively and it ‘s position is in
slot 3. It can input 7 external strong electricity (220V or110V) digital inputs at
most and output 9 idle contact. As for differential protection, this module is
applied to collection and control the position of transformer tap; for back-up
protection, this module is used for extended digital input and digital output.
Module 5 and 6 are digital output module used for back-up protection.
Module 6 is digital output module used for differential protection. This module
is protection tipping out module which could output 17 groups tripping
contacts and 3 groups alarm and protection action signal contact at most.
9
CSC-326G NumericalTransformer Protection Equipment Manual
The input of this module is DC 220V or DC 110V. The output of this module is
±24V、±12V、±5V. It can plug in 9 path external strong electricity (220V or
110V) digital inputs.
2 Equipment software
Phase current abrupt change element is the main startup component. Current
differential element is the auxiliary component.
10
CSC-326G NumericalTransformer Protection Equipment Manual
I d > I sd
protection setting
2.3.2 Ratio differential protection (Ratio DIFF)
2.3.2.1 Characteristic of ratio differential protection
Due to the differences of CT performance, transformation ratio and winding
connection type on each side, there is unbalanced current in differential
circuit. The regular three stage line characteristic is adopted to avoid
misoperation while the unbalanced current reaches the maximum due to
external faults. At the same time it could ensure the flexibility to eliminate
internal faults. The characteristic curve of the percentage ratio differential
protection is shown in Fig 2-1. The operating criterion is as follows:
11
CSC-326G NumericalTransformer Protection Equipment Manual
Isd
70
0.
3=
Kb
KID
Kb1=0.2
Icd
Ir
0.6Ie 4Ie
Fig 2-1 characteristic curve of the percentage ratio differential protection
It is distinguished by phase in program, if any phase could meet with the
above condition, ratio differential protection operates accordingly. If inrush
current discrimination and CT check are both meet, the ratio differential
protection would trip.
2.3.2.2 Inrush current discrimination principle
1) 2nd harmonics blocking principle
The ratio of 2nd harmonics magnitude to fundamental magnitude is used as
the criterion for inrush current discrimination.
I dφ 2 > K xb.2 I dφ
I dφ > 0.3I cd
13
CSC-326G NumericalTransformer Protection Equipment Manual
Fast DIFF
&
I d > I SD
1
Y 1
Fast DIFF trip
A 1 >=1 1
I d > I SD 1 H 1
1
B
I d > I SD
C
Ratio DIFF
2nd Har ON
1
1
I d .2 > K 2 I d .1 1 &
& 1
Ratio DIFF trip
A A 1 >=1 Y 1
Y
I d .2 > K 2 I d .1 1
1
H 1 1
B B
I d .2 > K 2 I d .1
C C
CT fail BLK Ratio 1 &
Y
DIFF 1
CT fail
CT fail Alarm
Id >IY
A X >=1
1
Id >IY 1 H 1
1
DIFF Ex-limit
B X
Id >IY
C X
Digital input which is non-electric contact from transformer will output a group
of idle contact to main differential protection equipment for event record. The
record would upload to SCADA. The equipment could access 9 digital inputs,
each of which can be configured to trigger fault signal and alarm signal or be
used as a common remote signal digital-in by control word.
The equipment could access the message of transformer tap (8421 code or
BCD code) which is converted and processed by tap transducer. 5 path tap
remote signal can support 32 taps position and upload the signal to computer;
the equipment outputs three groups contacts such as ascending, descending
and stopping tap contacts which can be controlled by monitoring system or by
external manual control. Emergency stopping tap can be settled on the site,
14
CSC-326G NumericalTransformer Protection Equipment Manual
Thd
0 &
Y
Succeed
0ms
To tap down Tfh Start
Tdn
0 &
JZ
Tapdown OP.
Thd
0 &
Y
Succeed
Expected value
Tstop
0
& &
Y JZ
Tapoff OP.
Grade error
3. Setting list
Name Function
Fast DIFF Fast differential protection can be enabled or
disabled.
Ratio restraint differential protection can be
Ratio DIFF
enabled or disabled.
Note: If any protection is enabled, external differential hard connector and the
corresponding soft connector should be enabled.
15
CSC-326G NumericalTransformer Protection Equipment Manual
Bit 0 1
16
CSC-326G NumericalTransformer Protection Equipment Manual
0 0 0 1 Y/△-11
0 0 1 0 Y/△-1
0 0 1 1 △/Y-11
0 1 0 0 △/Y-1
0 1 0 1 Y/Y-12
0 0 0 0 External convers
Instruction:
1. If connection control word is set as “0”, choose external Y/D conversion
(It is referring to CT phase correction outside the equipment). At this time,
special attention should be given to the amplification of CT secondary
current. For example, If CT primary current is connected as Y type,
secondary current is as △, CT secondary current is amplified 3 times. If
CT ration is 600/5, CT transformation ration is set as ( 600 / 3 )/5.
2. The software supports the above “6 kinds” transformer connection mode
to adjust phase automatically. It should be set according to the practical
transformer type. Setting error will result in protection misoperation. While
accessing secondary current, current on each side should be connected
with the current input terminal on the corresponding side according to
sequence listed in the above table. Misconnection will result in
misoperation.
For example:
If the transformer type is “Y/△-1”,the connection control word should be set
as 0002 and the software will adjust phase according to “Y/△-1”. Then the
secondary current on high voltage side(Y)is connected to I side of the
equipment, low voltage side(△-1)is connected to II side.
3. Note: I side is high voltage side fixedly, it is benchmark side.
17
CSC-326G NumericalTransformer Protection Equipment Manual
Sn
I 1e =
3U 1n
I 1e
I 2e =
nTA
18
CSC-326G NumericalTransformer Protection Equipment Manual
19
CSC-326G NumericalTransformer Protection Equipment Manual
20
CSC-326G NumericalTransformer Protection Equipment Manual
4. Terminal diagram
21
CSC-326G NumericalTransformer Protection Equipment Manual
2. Equipment software
22
CSC-326G NumericalTransformer Protection Equipment Manual
U
Where, U ab , U bc , U ca is three phase voltage., xjzd is low voltage setting; U 2
U fxzd
is negative sequence voltage, is the negative sequence voltage
setting(setted according to U 2 ).
The equipment may output operation contract in multi-voltage element on it’s
own side, Also there is a “MV DI” to access multi-voltage element contact
from other backup protection.
The equipment could set voltage blocking as “Own MV” or “Other MV” with
control word.
The phase angle difference of input current and voltage of the directional
element is 90 degrees. The maximum sensitive angle is -45 degrees; The
23
CSC-326G NumericalTransformer Protection Equipment Manual
⋅
Ia
850 ϕ lm = −⋅ 450 ⋅
U bc U bc
850
ϕ lm = 1350
⋅
Ia
Overcurrent element operate for each phase, the operation criterion is:
max( I a , I b , I c ) > I zd
There are two selections by control word: If the control word set as 1, it
means that directional and voltage blocking are satisfied after VT abnormity;
If the control word set as 0, it means that directional and voltage blocking are
not satisfied after VT abnormity
Whatever the control word is, after VT abnormity, complex voltage contact on
it’s own side would not output. Therefore, the consequence of VT abnormity
on each side will not affect action of voltage element in backup protection on
other side.
protection logic
24
CSC-326G NumericalTransformer Protection Equipment Manual
Mi
(U a , U bc , U ca ) < U z
n b d 1 >=1
H 1
1 1 &
Y 1
U2 > U2 z 0
d
1 >=1
H 1
MV component OP.
1
VT fail
MV componentt off
Own MV ON &
1
Y 1
1
Own MV OP.
1 >=1
Other MV ON 1 & H
1 1
Y 1
1
1
Other MV OP.
1 >=1
MV BLK OC ON 1
1 &
OC OP. 1 Y 1 Tzd MV directional OC OP.
1
1 &
OC Dir ON
Y 1
0 >=1 1
1 >=1 1
Dir OP. H 1 1
VT fail 1 &
Y 1
MV OC on
25
CSC-326G NumericalTransformer Protection Equipment Manual
within 2s after charging digital input and then charging protection will be
disabled after 2s automatically. Delay time setting of charging protection
should not be longer than 2s.
While control word is 1 and there are load on transformer, when charging
protection connector enables for more than 2 hours, “charging digital input
alarm” message will be sent.
When charging protection operates, The equipment will output the contacts of
“Trip own CB”and” BLK ABT ”.
Charge on
I>Idz
2s 1 &
0 Y Tzd1
1 & 1 1
Charging OP.
Y 1
1
Charging DI 1
1 &
Y 1
Charge on
1 &
Y Tzd1
I>Idz 1 1
Charging OP.
1
1 &
Y 1 2小时
Charge DI Alarm
Have current 1 0
There are other backup protections such as overload protection which could
alarm or trip by control word. When set to trip, the absolute contact would be
output.
26
CSC-326G NumericalTransformer Protection Equipment Manual
Criterion is as follows:
If 3I0 is larger than no current setting of CT abnormity detection, confirm CT
failure over 12s. CT faliure detection can be enabled or disabled by the
control word.
All protection elements can trip any output contacts by setting the trip control
word. The equipment have five groups trip output and one group blocking
backup power on it’s own side output for setting, the name of each output is
corresponding to the name in contact diagram. For example, the “Trip own
CB” is corresponding to the “X7-1~X7-6”.The defining of trip control word is
shown clearly in setting list.
Note: as for the limitation of the display screen, all export control words are
leaved out “control” word. For example, “CB Word”,“Bus joint Word”. Tripping
control word is defined according to digit number. As the above table, the
setting method is the same to the common control word. As for“CB Word”,If
bit0 is set as “1”, it means the own side break would be tripped by the element
of “MV OC Ⅱ T 1” ,If bit1 is set as “
1”, it m eans the CB would not be tripped by
the element of “MV OC Ⅱ T 1” .
3. Setting list
27
CSC-326G NumericalTransformer Protection Equipment Manual
Refer to the
1 Ctr Word 1 0000~FFFF None illustration of the
control word
Refer to the
2 Ctr Word 2 0000~FFFF None illustration of the
control word
0.04~20(In=1A)
3 MV OC Ⅰ I A
0.2~100(In=5A)
4 MV OC Ⅰ T 1 0.02~32.00 S
5 MV OC Ⅰ T 2 0.02~32.00 S
6 MV OC Ⅰ T 3 0.02~32.00 S
0.04~20(In=1A)
7 MV OC Ⅱ I A
0.2~100(In=5A)
8 MV OC Ⅱ T 1 0.02~32.00 S
9 MV OC Ⅱ T 2 0.02~32.00 S
10 MV OC Ⅱ T 3 0.02~32.00 S
0.04~20(In=1A)
11 OC I A
0.2~100(In=5A)
12 OC T1 0.02~32.00 S
13 OC T2 0.02~32.00 S
17 Charging T 0.02~32.00 S
28
CSC-326G NumericalTransformer Protection Equipment Manual
18 ZS OV V 10~100 V
19 ZS OV T 0.02~32.00 S
0.04~20(In=1A)
20 Overload I A
0.2~100(In=5A)
21 Overload T 0.2~8000.00 S
29
CSC-326G NumericalTransformer Protection Equipment Manual
Bit 0 1
D6 OC Ⅱ D ir O F F OC Ⅱ D ir O N
D5 MV OC Ⅰ T 3 O F F MV OC Ⅰ T 3 O N
D4 MV OC Ⅰ T 2 O F F MV OC Ⅰ T 2 O N
D3 MV OC Ⅰ T 1 O F F MV OC Ⅰ T 1 O N
D2 MV BLK OC Ⅰ O F F MV BLK OC Ⅰ O N
D1 OC Ⅰ D ir Tran. OC Ⅰ D ir B us
D0 OC Ⅰ D ir O F F OC Ⅰ D ir O n
D0 None MV OC Ⅰ T 1
D1 None MV OC Ⅰ T 2
D2 None MV OC Ⅰ T 3
D3 None MV OC Ⅱ T 1
D4 None MV OC Ⅱ T 2
D5 None MV OC Ⅱ T 3
D6 None OC T1
D7 None OC T2
30
CSC-326G NumericalTransformer Protection Equipment Manual
D0 None MV OC Ⅰ T 1
D1 None MV OC Ⅰ T 2
D2 None MV OC Ⅰ T 3
D3 None MV OC Ⅱ T 1
D4 None MV OC Ⅱ T 2
D5 None MV OC Ⅱ T 3
D6 None OC T1
D7 None OC T2
D0 None MV OC Ⅰ T 1
D1 None MV OC Ⅰ T 2
D2 None MV OC Ⅰ T 3
D3 None MV OC Ⅱ T 1
D4 None MV OC Ⅱ T2
D5 None MV OC Ⅱ T 3
D6 None OC T1
D7 None OC T2
D0 None MV OC Ⅰ T 1
D1 None MV OC Ⅰ T 2
D2 None MV OC Ⅰ T 3
D3 None MV OC Ⅱ T 1
D4 None MV OC Ⅱ T 2
D5 None MV OC Ⅱ T 3
D6 None OC T1
31
CSC-326G NumericalTransformer Protection Equipment Manual
Bit 0 1
D7 None OC T2
D0 None MV OC Ⅰ T 1
D1 None MV OC Ⅰ T 2
D2 None MV OC Ⅰ T 3
D3 None MV OC Ⅱ T 1
D4 None MV OC Ⅱ T 2
D5 None MV OC Ⅱ T 3
D6 None OC T1
D7 None OC T2
D0 None MV OC Ⅰ T 1
D1 None MV OC Ⅰ T 2
D2 None MV OC Ⅰ T 3
D3 None MV OC Ⅱ T 1
D4 None MV OC Ⅱ T 2
D5 None MV OC Ⅱ T 3
D6 None OC T1
D7 None OC T2
32
CSC-326G NumericalTransformer Protection Equipment Manual
1) Setting
NO. Name Scope Unit Remark
33
CSC-326G NumericalTransformer Protection Equipment Manual
34
CSC-326G NumericalTransformer Protection Equipment Manual
4 .Terminal diagram
35
CSC-326G NumericalTransformer Protection Equipment Manual
There are loop display, main menu, operation/ alarm report window for
display.
Eqipment loop display analog, connector which is enabled, current setting
zone; current time on the top of the screen; key QUIT could display
information of certain screen fixedly, press key QUIT again will go on with
loop display. In loop display, press key SET to enter device main menu.
36
CSC-326G NumericalTransformer Protection Equipment Manual
2.3 Password
The equipment provides 32 groups setting zone which may swithable, You
should select one setting zone first, after finish import setting, then select
object setting zone which need be fixed.
Table 2-1 Menu structure
Main Level 1 Level 2 Level 3
Comment
menu menu menu menu
Analog Examine device analog input
37
CSC-326G NumericalTransformer Protection Equipment Manual
Monitor and
Setting of monitor and control
control
fixed value
setting
ComConf
Serial port
Serial (RS232/RS485)functional
parameter
CSC2000 internal protocol
Label
address setting
DO Digital output trip
38
CSC-326G NumericalTransformer Protection Equipment Manual
39
CSC-326G NumericalTransformer Protection Equipment Manual
40
CSC-326G NumericalTransformer Protection Equipment Manual
41
CSC-326G NumericalTransformer Protection Equipment Manual
42
CSC-326G NumericalTransformer Protection Equipment Manual
Ie —rated secondary current of the base side. the same is as the follows
Ker ——ratio error of the CT, for 10P type ,this value is 0.03×2,for 5P type
and TP type, this value is 0.01×2;
43
CSC-326G NumericalTransformer Protection Equipment Manual
1
I zd =
2
∑ I
i
44
CSC-326G NumericalTransformer Protection Equipment Manual
Kres.max=Idz.max/Izd.max
The percentage restraint characteristic curve of the equipment is showing in
the following figure:
Id
Isd
70
0.
3=
Kb
KID
Kb1=0.2
Icd
Ir
0.6Ie 4Ie
KID=(Idz.max-ICD-0.12Ie)/(Izd.max-0.6Ie)
current
I dz in the restraint curve and the sensitivity coefficient:
I d ⋅min
K sen =
I dz (require K ≥ 2 )
sen
K rel
I op = Ie
Kr
45
CSC-326G NumericalTransformer Protection Equipment Manual
I k( .2min
)
K sen =
I op
( 2)
Where I k . min the minimum fault current at the boundary of backup protection
zone when phase-phase fault occurred. K sen ≥ 1.3 (local backup ) , K sen ≥ 1.2
(remote back-up )
C.1.1.2 Setting of under voltage startup element
The following condition should be take into consideration :
a) Avoid the minimum voltage under normal operation condition
K rel
U op = U min
Kr
U op =(0.5 ~ 0.6)U e
If the under voltage relay power supplies from VT of transformer on high
voltage side:
U op = 0.7U e
c) Sensitivity check:
U op
K sen =
U r . max
Where U r . max is the maximal residual voltage of relay location when metal
46
CSC-326G NumericalTransformer Protection Equipment Manual
U k .2. min
K sen =
U op.2
Where U k .2. min is the minimum negative sequence voltage at relay location at
the boundary of backup protection zone when metal attribute phase-phase
fault occurred K sen ≥ 2.0 (local backup) or K sen ≥ 1.5 (remote backup).
C.2. Transformer ground fault backup protection
C.2.1 Zero sequence overcurrent protection (directly earthed
transformer)
a) The setting of the zero sequence overcurrent stage I protection should
match with the zero sequence overcurrent stage I (stage II )protection or
instantaneous main protection from the adjacent line
I op.0. I = K rel K br . I I op.0.1I
I op.0. I
Where: -setting of the zero sequence overcurrent stage I;
47
CSC-326G NumericalTransformer Protection Equipment Manual
protection.
c) Sensitivity check:
3I k .0. min
K sen =
I op.0
where I k .0. min -the minimum current at relay location at stage I ( or stage II)
C.2.2 Gap protection (neural point of the transformer earthed with gap)
C.2.2.1 Gap over voltage protection
The setting of the over voltage is according to the following formula:
U 0. max < U op.0 < U sat
48
CSC-326G NumericalTransformer Protection Equipment Manual
two-winding transformer with high voltage side (or medium voltage side)
earthed directly .Take into account the zero sequence current protection of the
high voltage side or medium voltage side, it is a backup protection for the line
or bus ground fault. The function of the neural point overcurrent protection is
only the backup protection of the internal ground fault of the transformer.
I op.0 = K rel I unb..0
where : I k .0. min -the minimum zero sequence current pass through the neural
point of the transformer with the ground fault at the line in the
auto-transformer open circuit side.
K sen should satisfy K sen ≥ 1.5 .
49