ETAP

Project: Page: 321


12.6.0H
Location: Date: 01-16-2019
Contract: SN:
Engineer: IZAAS IMAADURAFI / D400160052 Revision: Base
Study Case: LF
Filename: TUGAS ETAP 06 Config.: Normal

BusLoading
Loading
Branch
Branch SummaryReport
Losses Summary
Summary Report
Report

Directly Connected Load Total Bus Load


Vd
CKT / Branch From-To Bus Flow To-From Bus Flow Losses % Bus Voltage
Transformer % Drop
Bus CKT ID / Branch MW
Constant kVA
MvarCable &MW
Constant
Reactor Z
Mvar
Constant
kW
I
kvar
Generic
From To in Vmag Percent
ID kV Rated Amp MW Mvar
Ampacity MW
Loading Mvar MW
CapabilityMvar Loading
MW (input)Mvar Loading
MVA (output)
% PF Amp Loading
T1 245.118 129.111 -245.118 -112.993 0.2 16118.0 100.0 97.4 2.58
ID 500.000 Type (Amp) Amp (MVA)
Bus1 0 0 0 0% 0 0 MVA 0 % 0 MVA
554.084 %
88.5 639.8
T6 245.118 129.111 -245.118 -112.993 0.2 16118.0 100.0 97.4 2.58
Bus3 T1 150.000 Transformer 0 0 625.523 263.598 0500.000 0 277.042 0 55.4 0 269.908
678.796 54.0
92.2 2681.7
Cable1 -62.554 -17.973 63.099 20.665 545.2 2691.8 97.4 99.4 1.96
Bus7 T5 150.000 Transformer 0 0 0 0 0500.000 0 68.907 0 13.8 0 68.486
68.486 13.7
94.5 265.2
Cable2 -72.734 -19.638 73.347 22.661 612.5 3023.6 97.4 99.3 1.85
Bus8 T6 150.000 Transformer 0 0 9.855 4.435 0500.000 0 277.042 0 55.4 0 192.208
269.908 96.4
54.0 745.2
Cable3 1.637 1.685 -1.636 -1.681 0.6 3.2 99.4 99.3 0.12
Bus9 T7 150.000 Transformer 0 0 0 0 0500.000 0 0 0 0 0.0 0.0
T5 -64.736 -22.350 64.763 23.536 26.4 1186.8 99.4 100.0 0.61
Bus11 T8 150.000 Transformer 0 0 403.386 56.301 0500.000 0 0 0 597.595 98.3 2300.1
Cable4 -91.846 -24.643 92.086 26.384 240.1 1741.2 99.3 100.0 0.73
Bus12 T9 150.000 Transformer 0 0 0 0 0500.000 0 0 0 0 0.0 0.0
Cable5 -91.846 -24.643 92.086 26.384 240.1 1741.2 99.3 100.0 0.73
Bus13 150.000 0 0 0 0 0 0 0 0 0 0.0 0.0
T10 Transformer 500.000
Cable6 51.063 11.935 -50.820 -11.222 242.9 713.7 99.3 98.5 0.75
Bus14 150.000 0 0 50.477 50.477 0 0 0 0 123.678 82.2 483.2
T11 Transformer 500.000 48.742 9.7 48.053 9.6
Bus18 Cable7 150.000 51.063 0 11.935
0 -50.820
0 0-11.222 0 242.9 0 713.7 0 99.3 0 98.5
48.053 0.75
0.0 187.6
T12 Transformer 500.000
Bus20 T7 500.000 0.000 0 0.000
0 0.000
0 0 0.000 0 0 0 99.3 0 99.3
48.742 0.00
0.0 56.3
T14 Transformer 500.000 97.821 19.6 96.664 19.3
Bus21 T8 500.000 0.000 0 0.000
0 0.000
0 0 0.000 0 0 0 99.3 0 99.3 0 0.0 0.0
* Indicates a branch with operating load exceeding the branch capability.
Bus22 T9 150.000 0.000 0 0.000
0 0.000
55.624 23.2910.000 0 0 0 99.3 0 99.3
60.303 92.2 235.6
Bus23 Cable8 150.000 0.000 0 0
0.000 52.118
0.000 20.4500.000 0 0 0 98.5 0 61.391
98.5 92.2
0.00 239.4
Bus24 Cable9 150.000 0.024 0 0
-48.023 32.516
-0.014 13.477
48.053 0 10.1 0 30.2 0 98.5 0 96.664
98.6 92.2
0.06 376.5
Bus25 Cable10 500.000 51.124 0 0
19.982 0
-51.124 0-19.982 0 0.1 0 0.4 0 98.5 0 97.821
98.5 91.2
0.00 113.0
Bus26 Cable11 150.000 0.016 0 0
0.006 0
-0.016 0 -0.006 0 0.0 0 0.0 0 98.5 0 68.907
98.5 94.0
0.00 265.2
Bus27 150.000 0 0 0 0 0 0 0 0 0 0.0 0.0
T12 0.000 0.000 0.000 0.000 98.5 98.5
Bus28 150.000 0 0 0 0 0 0 0 0 0 0.0 0.0
T11 0.014 -48.053 0.000 48.742 13.8 688.8 98.6 100.0 1.41

Cable12 -2.242 -1.651 2.244 1.657 1.9 5.6 98.5 98.7 0.17
* Indicates operating load of a bus exceeds the bus critical limit ( 100.0% of the Continuous Ampere rating).
# Indicates operating Cable13 -2.242
load of a bus exceeds the bus marginal limit ( 95.0% of -1.651
the Continuous2.244 1.657
Ampere rating). 1.9 5.6 98.5 98.7 0.17

Cable14 -28.303 -11.882 28.313 11.955 10.0 72.4 98.7 98.8 0.12

Cable15 -28.303 -11.882 28.313 11.955 10.0 72.4 98.7 98.8 0.12

T14 -89.141 -37.386 89.197 40.160 55.5 2774.4 98.8 100.0 1.18

T10 0.000 0.000 0.000 0.000 98.5 98.5 0.00

2254.3 47700.9
ETAP
Project: Page: 54
12.6.0H
Location: Date: 01-16-2019
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: TUGAS ETAP 06 Config.: Normal

Marginal Report
Alert Summary Report
Device ID Type Condition Rating/Limit Unit Operating % Operating Phase Type

Bus3 Bus Under Voltage % AlertkVSettings 146.137


150.000 97.4 3-Phase

Critical Marginal
Loading
Bus 100.0 95.0
Cable 100.0 95.0
Reactor 100.0 95.0
Line 100.0 95.0
Transformer 100.0 95.0
Panel 100.0 95.0
Protective Device 100.0 95.0
Generator 100.0 95.0
Inverter/Charger 100.0 95.0

Bus Voltage
OverVoltage 105.0 102.0
UnderVoltage 95.0 98.0

Generator Excitation
OverExcited (Q Max.) 100.0 95.0
UnderExcited (Q Min.) 100.0

Critical Report

Device ID Type Condition Rating/Limit Unit Operating % Operating Phase Type

Cable16 Cable Overload 626.500 Amp 2428.563 387.6 3-Phase

Gen1 Generator Under Power 0.000 MW 0.000 0.0 3-Phase

Gen1 Generator Under Excited 0.000 Mvar 0.000 0.0 3-Phase

Gen2 Generator Under Power 0.000 MW 0.000 0.0 3-Phase

Gen2 Generator Under Excited 0.000 Mvar 0.000 0.0 3-Phase

Gen3 Generator Under Power 0.000 MW 0.000 0.0 3-Phase

Gen3 Generator Under Excited 0.000 Mvar 0.000 0.0 3-Phase

Gen4 Generator Under Power 0.000 MW 0.000 0.0 3-Phase

Gen4 Generator Under Excited 0.000 Mvar 0.000 0.0 3-Phase

Gen6 Generator Under Power 0.000 MW 0.000 0.0 3-Phase

Gen7 Generator Under Power 0.000 MW 0.000 0.0 3-Phase

Gen7 Generator Under Excited 0.000 Mvar 0.000 0.0 3-Phase

Marginal Report
ETAP
Project: Page: 6
12.6.0H
Location: Date: 01-16-2019
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: TUGAS ETAP 06 Config.: Normal

SUMMARY OF TOTAL GENERATION , LOADING & DEMAND

MW Mvar MVA % PF

Source (Swing Buses): 1231.752 430.988 1304.977 94.39 Lagging

Source (Non-Swing Buses): 0.000 48.742 48.742 0.00 Lagging

Total Demand: 1231.752 479.730 1321.876 93.18 Lagging

Total Motor Load: 0.000 0.000 0.000

Total Static Load: 1229.498 432.029 1303.194 94.34 Lagging

Total Constant I Load: 0.000 0.000 0.000

Total Generic Load: 0.000 0.000 0.000

Apparent Losses: 2.254 47.701

System Mismatch: 0.000 0.000

Number of Iterations: 3