You are on page 1of 3

ETAP

Project: Page: 321


12.6.0H
Location: Date: 01-16-2019
Contract: SN:
Engineer: ADNAN IBRAHIM / D400160048 Revision: Base
Study Case: LF
Filename: TUGAS ETAP 06 Config.: Normal

BusLoading
Loading
Branch
Branch SummaryReport
Losses Summary
Summary Report
Report

Directly Connected Load Total Bus Load


Vd
CKT / Branch From-To Bus Flow To-From Bus Flow Losses % Bus Voltage
Transformer % Drop
Bus CKT ID / Branch MW
Constant kVA
MvarCable &MW
Constant
Reactor Z
Mvar
Constant
kW
I
kvar
Generic
From To in Vmag Percent
ID kV Rated Amp MW Mvar
Ampacity MW
Loading Mvar MW
CapabilityMvar Loading
MW (input)Mvar Loading
MVA (output)
% PF Amp Loading
T1 243.692 127.333 -243.692 -111.457 0.2 15875.9 100.0 97.5 2.54
ID 500.000 Type (Amp) Amp (MVA)
Bus1 0 0 0 0% 0 0 MVA 0 % 0 MVA
549.908 %
88.6 635.0
T6 243.692 127.333 -243.692 -111.457 0.2 15875.9 100.0 97.5 2.54
Bus3 T1 150.000 Transformer 0 0 622.183 259.991 0500.000 0 274.954 0 55.0 0 267.971
674.319 53.6
92.3 2663.1
Cable1 -62.221 -17.677 62.759 20.333 538.1 2656.6 97.5 99.4 1.94
Bus7 T5 150.000 Transformer 0 0 0 0 0500.000 0 68.226 0 13.6 0 67.817
67.817 13.6
94.6 262.6
Cable2 -72.578 -19.400 73.186 22.404 608.6 3004.3 97.5 99.3 1.83
Bus8 T6 150.000 Transformer 0 0 9.859 4.437 0500.000 0 274.954 0 55.0 0 188.803
267.971 96.6
53.6 731.9
Cable3 1.423 1.572 -1.423 -1.569 0.5 2.6 99.4 99.3 0.11
Bus9 T7 150.000 Transformer 0 0 0 0 0500.000 0 0 0 0 0.0 0.0
T5 -64.182 -21.905 64.208 23.068 25.9 1163.4 99.4 100.0 0.60
Bus11 T8 150.000 Transformer 0 0 403.386 56.301 0500.000 0 0 0 594.477 98.4 2288.1
Cable4 -90.439 -23.778 90.671 25.461 232.0 1683.0 99.3 100.0 0.71
Bus12 T9 150.000 Transformer 0 0 0 0 0500.000 0 0 0 0 0.0 0.0
Cable5 -90.439 -23.778 90.671 25.461 232.0 1683.0 99.3 100.0 0.71
Bus13 150.000 0 0 0 0 0 0 0 0 0 0.0 0.0
T10 Transformer 500.000
Cable6 49.627 11.142 -49.399 -10.471 228.4 671.1 99.3 98.6 0.72
Bus14 150.000 0 0 46.644 46.645 0 0 0 0 119.511 82.7 466.6
T11 Transformer 500.000 46.971 9.4 46.331 9.3
Bus18 Cable7 150.000 49.627 0 11.142
0 -49.399
0 0-10.471 0 228.4 0 671.1 0 99.3 0 98.6
46.331 0.72
0.0 180.8
T12 Transformer 500.000
Bus20 T7 500.000 0.000 0 0.000
0 0.000
0 0 0.000 0 0 0 99.3 0 99.3
46.971 0.00
0.0 54.2
T14 Transformer 500.000 96.737 19.3 95.611 19.1
Bus21 T8 500.000 0.000 0 0.000
0 0.000
0 0 0.000 0 0 0 99.3 0 99.3 0 0.0 0.0
* Indicates a branch with operating load exceeding the branch capability.
Bus22 T9 150.000 0.000 0 0.000
0 0.000
55.684 23.3170.000 0 0 0 99.3 0 99.3
60.369 92.2 235.7
Bus23 Cable8 150.000 0.000 0 0
0.000 52.140
0.000 20.4590.000 0 0 0 98.6 0 60.328
98.6 92.3
0.00 235.2
Bus24 Cable9 150.000 0.022 0 0
-46.303 32.528
-0.013 13.482
46.331 0 9.4 0 28.1 0 98.6 0 95.611
98.6 92.3
0.06 372.3
Bus25 Cable10 500.000 52.115 0 0
20.594 0
-52.115 0-20.593 0 0.1 0 0.4 0 98.6 0 96.737
98.6 91.3
0.00 111.7
Bus26 Cable11 150.000 0.016 0 0
0.006 0
-0.016 0 -0.006 0 0.0 0 0.0 0 98.6 0 68.226
98.6 94.1
0.00 262.6
Bus27 150.000 0 0 0 0 0 0 0 0 0 0.0 0.0
T12 0.000 0.000 0.000 0.000 98.6 98.6 0.00
Bus28 150.000 0 0 0 0 0 0 0 0 0 0.0 0.0
T11 0.013 -46.331 0.000 46.971 12.8 639.7 98.6 100.0 1.36

Cable12 -1.777 -1.359 1.778 1.362 1.2 3.6 98.6 98.7 0.14
* Indicates operating load of a bus exceeds the bus critical limit ( 100.0% of the Continuous Ampere rating).
# Indicates operating Cable13 -1.777
load of a bus exceeds the bus marginal limit ( 95.0% of -1.359
the Continuous1.778 1.362
Ampere rating). 1.2 3.6 98.6 98.7 0.14

Cable14 -27.848 -11.592 27.857 11.662 9.6 69.9 98.7 98.8 0.12

Cable15 -27.848 -11.592 27.857 11.662 9.6 69.9 98.7 98.8 0.12

T14 -88.243 -36.805 88.297 39.518 54.3 2713.3 98.8 100.0 1.16

T10 0.000 0.000 0.000 0.000 98.6 98.6 0.00

2192.7 46815.5
ETAP
Project: Page: 54
12.6.0H
Location: Date: 01-16-2019
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: TUGAS ETAP 06 Config.: Normal

Marginal Report
Alert Summary Report
Device ID Type Condition Rating/Limit Unit Operating % Operating Phase Type

Bus3 Bus Under Voltage % AlertkVSettings 146.191


150.000 97.5 3-Phase

Critical Marginal
Loading
Bus 100.0 95.0
Cable 100.0 95.0
Reactor 100.0 95.0
Line 100.0 95.0
Transformer 100.0 95.0
Panel 100.0 95.0
Protective Device 100.0 95.0
Generator 100.0 95.0
Inverter/Charger 100.0 95.0

Bus Voltage
OverVoltage 105.0 102.0
UnderVoltage 95.0 98.0

Generator Excitation
OverExcited (Q Max.) 100.0 95.0
UnderExcited (Q Min.) 100.0

Critical Report

Device ID Type Condition Rating/Limit Unit Operating % Operating Phase Type

Cable16 Cable Overload 626.500 Amp 2429.453 387.8 3-Phase

Gen1 Generator Under Power 0.000 MW 0.000 0.0 3-Phase

Gen1 Generator Under Excited 0.000 Mvar 0.000 0.0 3-Phase

Gen2 Generator Under Power 0.000 MW 0.000 0.0 3-Phase

Gen2 Generator Under Excited 0.000 Mvar 0.000 0.0 3-Phase

Gen3 Generator Under Power 0.000 MW 0.000 0.0 3-Phase

Gen3 Generator Under Excited 0.000 Mvar 0.000 0.0 3-Phase

Gen4 Generator Under Power 0.000 MW 0.000 0.0 3-Phase

Gen4 Generator Under Excited 0.000 Mvar 0.000 0.0 3-Phase

Gen6 Generator Under Power 0.000 MW 0.000 0.0 3-Phase

Gen7 Generator Under Power 0.000 MW 0.000 0.0 3-Phase

Gen7 Generator Under Excited 0.000 Mvar 0.000 0.0 3-Phase

Marginal Report
ETAP
Project: Page: 6
12.6.0H
Location: Date: 01-16-2019
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: TUGAS ETAP 06 Config.: Normal

SUMMARY OF TOTAL GENERATION , LOADING & DEMAND

MW Mvar MVA % PF

Source (Swing Buses): 1224.617 424.477 1296.097 94.48 Lagging

Source (Non-Swing Buses): 0.000 46.971 46.971 0.00 Lagging

Total Demand: 1224.617 471.447 1312.231 93.32 Lagging

Total Motor Load: 0.000 0.000 0.000

Total Static Load: 1222.424 424.632 1294.076 94.46 Lagging

Total Constant I Load: 0.000 0.000 0.000

Total Generic Load: 0.000 0.000 0.000

Apparent Losses: 2.193 46.816

System Mismatch: 0.000 0.000

Number of Iterations: 3