ACI 301-10
Specifications for Structural Concrete
1st printing
Reported by ACI Committee 301

1.3.2, Cited publications, page 9, update reference to:


CRSI MSP-2-01 Manual of Standard Practice, 28th edition

Table 4.2.3.3.a, page 24, Eq. (4-3) in Line 3, add prime symbol:
fcr′ = fc + 1.34kss fcr′ = fc′ + 1.34kss

6.2.1.6.a, page 31, renumber sections:


The section numbered 6.2.1.6.a must be changed to 6.2.1.5.b and subsequent sections in
6.2.1 need to be renumbered.

6.3.10, page 32:


Sections 6.3.11.1 through 6.3.11.4 Sections 6.3.10.1 through 6.3.10.3

9.2.2.3.b, page 38, point 1) subpoint (e):


Store the mixed grout at the temperature range listed in (a)

Store the mixed grout at the temperature range listed in (b)

9.3.9.1, page 42:


…Strand length protruding beyond wedges after cutting shall not be less than ½ in.