Product Description

Issue 01

Date 2016-3-16

HUAWEI TECHNOLOGIES CO., LTD.


Copyright © Huawei Technologies Co., Ltd. 2016. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.

Trademarks and Permissions

and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.

Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.

Huawei Technologies Co., Ltd.


Address: Huawei Industrial Base
Bantian, Longgang
Shenzhen 518129
People's Republic of China

Website: http://www.huawei.com
Email: support@huawei.com

Huawei Proprietary and Confidential


Issue 01 (2016-3-16) i
Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description About This Document

About This Document

Overview
This document presents the exteriors and describes technical specifications, application
scenarios, components, and cable connections of the APM30H (Ver.E). It also describes the
configurations, functions, and specifications of the modules and boards, and details such as
cable types, cable connections, and connector specifications.

Product Version
APM30H is short for advanced power module with heat exchanger.

Product Name Solution Version Product Version


 BTS3900A  SRAN8.0 and later V100R008C00 and later
 DBS3900 versions versions
 GBSS15.0 and later
versions
 RAN15.0 and later
versions
 eRAN6.0 and later
versions

Intended Audience
 Base station installation personnel
 System engineers
 Site maintenance personnel

Issue 01 (2016-3-16) Huawei Proprietary and Confidential ii


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description Contents

Contents

About This Document .................................................................................................................... ii


1 Changes in APM30H (Ver.E) Product Description ................................................................. 1
2 Cabinet Exterior ............................................................................................................................. 2
3 APM30H Engineering Specifications........................................................................................ 3
4 Engineering Specifications of Customer Equipment in a Huawei cabinet ....................... 6
5 Application Scenario of an APM30H ...................................................................................... 11
6 Components in APM30H ........................................................................................................... 14
7 Components Description ........................................................................................................... 18
7.1 AC/DC Power System ................................................................................................................................................ 18
7.1.1 Components in an EPU05A ..................................................................................................................................... 18
7.1.2 EPU05A-06 and EPU05A-08 Subracks ................................................................................................................... 20
7.1.3 EPU05A-07 and EPU05A-09 Subracks ................................................................................................................... 26
7.1.4 PSU (R4850G2) ....................................................................................................................................................... 31
7.1.5 PDU01D-01 ............................................................................................................................................................. 33
7.1.6 PDU03D-02 ............................................................................................................................................................. 35
7.1.7 PMIU ....................................................................................................................................................................... 36
7.2 AC Junction Box ......................................................................................................................................................... 37
7.3 Fan Assembly ............................................................................................................................................................. 39
7.3.1 FAN 02E .................................................................................................................................................................. 39
7.3.2 CCUB ...................................................................................................................................................................... 41
7.4 ELU ............................................................................................................................................................................ 44
7.5 Door Status Sensor...................................................................................................................................................... 49
7.6 (Optional) AC Heater .................................................................................................................................................. 52
7.7 (Optional) SOU........................................................................................................................................................... 53

8 APM30H Cables .......................................................................................................................... 55


8.1 Cable List .................................................................................................................................................................... 55
8.2 Cable Connections ...................................................................................................................................................... 57
8.2.1 Power Cable Connections ........................................................................................................................................ 57
8.2.2 Monitoring Signal Cable Connections ..................................................................................................................... 59
8.3 PGND Cable ............................................................................................................................................................... 60

Issue 01 (2016-3-16) Huawei Proprietary and Confidential iii


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description Contents

8.4 Equipotential Cable .................................................................................................................................................... 61


8.5 Power Cables .............................................................................................................................................................. 63
8.5.1 EPU05A-06 or EPU05A-08 Power Cable ............................................................................................................... 63
8.5.2 EPU05A-07 or EPU05A-09 Power Cable ............................................................................................................... 65
8.5.3 SOU Power Cable .................................................................................................................................................... 67
8.5.4 Power Cable for an AC Heater................................................................................................................................. 68
8.5.5 FAN 02E Power Cable ............................................................................................................................................. 69
8.5.6 Power Cable for an AC Junction Box ...................................................................................................................... 70
8.6 Signal Cables .............................................................................................................................................................. 72
8.6.1 ELU Signal Cable .................................................................................................................................................... 72
8.6.2 Monitoring Signal Cables for Door Status Sensors ................................................................................................. 75
8.6.3 Monitoring Signal Transfer Cable for Fans in Front Doors ..................................................................................... 80
8.6.4 PMIU-CCUB Monitoring Signal Cable ................................................................................................................... 81

Issue 01 (2016-3-16) Huawei Proprietary and Confidential iv


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 1 Changes in APM30H (Ver.E) Product Description

1 Changes in APM30H (Ver.E) Product


Description

This chapter describes the changes in the APM30H (Ver.E) Product Description.

01 (2016-03-16)
This is the first commercial release.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 1


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 2 Cabinet Exterior

2 Cabinet Exterior

The APM30H is used for Huawei wireless products outdoors. It is small and easy to transport.
The following figure shows the exterior of the APM30H.

Figure 2-1 Exterior of the APM30H

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 2


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 3 APM30H Engineering Specifications

3 APM30H Engineering Specifications

This section describes the engineering specifications of APM30H, including input power
specifications, equipment specifications, environmental specifications, and surge protection
specifications of the ports.

Input Power Specifications


An APM30H can be supplied with different power. Power equipment in the APM30H
converts AC power into -48 V DC power for the base station.
The following table lists the AC input power specifications of an APM30H.

Table 3-1 AC input power specifications

Power Supply Rated Voltage Operating Voltage


220 V AC 200 V AC to 240 V AC 176 V AC to 290 V AC
single-phase
220 V AC  Line to neutral voltage: 200 V  Line to neutral voltage: 176 V
three-phase AC to 240 V AC AC to 290 V AC
 Phase-to-phase voltage: 346  Phase-to-phase voltage: 304
V AC to 415 V AC V AC to 500 V AC
110 V AC  Line to neutral voltage: 100 V  Line to neutral voltage: 90 V
dual-live-wire AC to 120 V AC AC to 135 V AC
 Phase-to-phase voltage: 200  Phase-to-phase voltage: 180
V AC to 240 V AC V AC to 270 V AC
120 V AC  Line to neutral voltage: 120 V  Line to neutral voltage: 105 V
dual-live-wire AC to 127 V AC AC to 150 V AC
 Phase-to-phase voltage: 208  Phase-to-phase voltage: 176
V AC to 220 V AC V AC to 260 V AC

Equipment Specifications
The following table lists the equipment specifications of an APM30H.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 3


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 3 APM30H Engineering Specifications

Table 3-2 Equipment specifications of an APM30H

Item Specifications Remarks


Dimension  Cabinet: 700 mm -
s (H x W x x 600 mm x 480
D) mm (27.56 in. x
23.62 in. x 18.90
in.)
 Base: 200 mm x
600 mm x 434 mm
(7.87 in. x 23.62
in. x 17.09 in.)
Weight ≤ 68 kg (149.91 lb) Total weight of the equipment
 Including the cabinet frame, outer air circulation
component (heat exchanger core and outer air
circulation fan), inner air circulation fan
assembly, and EPU
 Excluding the BBU, customer transmission
equipment, PMU, or PSU
≤ 87 kg (191.80 lb) Weight with the typical configurations
 Including the cabinet, two PSUs, and one BBU
 Excluding transmission equipment
Heat The maximum heat -
dissipation dissipation capability
capability is 1800 W when the
of a cabinet ambient temperature
is 50°C.

Environmental Specifications
The following table lists the environmental specifications of an APM30H.

Table 3-3 Environmental specifications

Item Specifications
Operating -40°C to +50°C (-40°F to 122°F) (1120 W/m2solar radiation). If
temperature the operating temperature is below -20°C (-4°F), a heater is
required.
Relative humidity 5% RH to 100% RH
Atmospheric pressure 70 kPa to 106 kPa
Noise power level  Meeting the ETS 300 753 4.1E standard (rural area) if the heat
consumption inside a cabinet is less than or equal to 700 W
− ≤ 6.1 bels@+25°C (77°F)
− ≤ 6.7 bels@+45°C (113°F)
 Meeting the ETS 300 753 4.1E standard (urban area) if the heat

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 4


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 3 APM30H Engineering Specifications

Item Specifications
consumption inside a cabinet is less than or equal to 1800 W or
between 700 W and 1800 W
− ≤ 6.6 bels@+25°C (77°F)
− ≤ 7.6 bels@+45°C (113°F)
Storage time The product must be installed and put into use within a year after
being delivered or it may malfunction.

Surge Protection Specifications of the Ports


The following table lists the surge protection specifications of the ports in an APM30H.

Table 3-4 Surge protection specifications of the ports

Port Specifications

Surge Surge Current


AC power  Differential mode: 2 kV (1.2/50  Differential mode: 30 kA (8/20
port us) us)
 Common mode: 4 kV (1.2/50 us)  Common mode: 30 kA (8/20 us)

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 5


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E) 4 Engineering Specifications of Customer Equipment in
Product Description a Huawei cabinet

4 Engineering Specifications of Customer


Equipment in a Huawei cabinet

The equipment in a Huawei cabinet must meet the requirements for engineering
specifications.
The following conditions must be met when the customer equipment is installed in the
following cabinets: APM30H (Ver.B)/APM30H (Ver.C)/APM30H (Ver.D)/APM30H
(Ver.E)/APM30H (Ver.D_B)/APM30H (Ver.D_A2)/APM30 (Ver.D_A1), TMC11H
(Ver.B)/TMC11H (Ver.C)/TMC11H (Ver.D)/TMC11H (Ver.E)/TMC11H (Ver.D_B)/TMC11H
(Ver.D_A2)/TMC (Ver.D_A1), BTS3012AE (Ver.D_Z), and BTS3900AL (Ver.A):
 Dimension requirements
Figure 4-1 shows the dimension requirements.
− The width is 19 inch.
− The depth of the customer equipment which uses natural ventilation or supports heat
dissipation from left to right is less than or equal to 280 mm (11.02 in.). The depth of
the customer equipment which supports heat dissipation from front to rear is less than
250 mm (9.84 in.).
− The cabling space in front of the front panel is less than or equal to 100 mm (3.94
in.).
 Heat dissipation requirements
− If the customer equipment has built-in fans, the fans must dissipate heat out from left
to right or from front to rear.
− If the customer equipment does not have built-in fans but uses natural ventilation, a
minimum of 1 U space must be reserved above and below the customer equipment to
ensure heat dissipation.
 Temperature requirements
Temperature requirements for customer equipment are different in common areas and
high-temperature areas. Figure 4-2 lists the detailed requirements.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 6


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E) 4 Engineering Specifications of Customer Equipment in
Product Description a Huawei cabinet

Figure 4-1 Dimension requirements and heat dissipation requirements

(1) Equipment using (2) Equipment dissipating heat (3) Equipment dissipating heat
natural ventilation out from left to right out from front to rear

Figure 4-2 Temperature requirements for the customer equipment

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 7


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E) 4 Engineering Specifications of Customer Equipment in
Product Description a Huawei cabinet

 Common areas and high-temperature areas are differentiated as follows:


 Common areas: The highest ambient temperature is equal to or less than 40oC.
 High-temperature areas: The highest ambient temperature exceeds 40oC.
 The following description illustrates the preceding figure using common areas as an example.
If the operating temperature of the customer equipment ranges from -15oC to 60oC, the customer
equipment meets requirements; if the operating temperature ranges from -5oC to 60oC, the customer
equipment does not meet requirements.

The customer equipment to be installed in the APM30, APM30H (Ver.A), TMC, or TMC11H
(Ver.A) must meet the following requirements:
 Dimension requirements
Figure 4-3 shows the dimension requirements.
− The width is 19 inch.
− The depth of the customer equipment which uses natural ventilation or supports heat
dissipation from left to right is less than or equal to 310 mm (12.20 in.). The depth of
the customer equipment which supports heat dissipation from front to rear is less than
280 mm (11.02 in.).
− The cabling space in front of the front panel is less than or equal to 70 mm (2.76 in.).
 Heat dissipation requirements
− If the customer equipment has built-in fans, the fans must dissipate heat out from left
to right or from front to rear.
− If the customer equipment does not have built-in fans but uses natural ventilation, a
minimum of 1 U space must be reserved above and below the customer equipment to
ensure heat dissipation.
 Temperature requirements
Temperature requirements for customer equipment are different in common areas and
high-temperature areas. Figure 4-4 lists the detailed requirements.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 8


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E) 4 Engineering Specifications of Customer Equipment in
Product Description a Huawei cabinet

Figure 4-3 Dimension requirements and heat dissipation requirements

(1) Equipment using (2) Equipment dissipating heat (3) Equipment dissipating heat
natural ventilation out from left to right out from front to rear

Figure 4-4 Temperature requirements for the customer equipment

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 9


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E) 4 Engineering Specifications of Customer Equipment in
Product Description a Huawei cabinet

 Common areas and high-temperature areas are differentiated as follows:


 Common areas: The highest ambient temperature is equal to or less than 40oC.
 High-temperature areas: The highest ambient temperature exceeds 40oC.
 The following description illustrates the preceding figure using common areas as an example.
If the operating temperature of the customer equipment ranges from -15oC to 60oC, the customer
equipment meets requirements; if the operating temperature ranges from -5oC to 60oC, the customer
equipment does not meet requirements.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 10


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 5 Application Scenario of an APM30H

5 Application Scenario of an APM30H

An APM30H can apply to a distributed base station or a separated macro base station.

APM30H Used in a Distributed Base Station


In a distributed base station, an APM30H is configured as follows:
 The APM30H provides 5 U space for transmission equipment and uses an embedded
power system to feed -48 V DC power into the distributed base station, transmission
equipment, and battery groups in the battery cabinet.
 When the mains are unavailable, battery groups feed -48 V DC power into the distributed
base station and transmission equipment.
Figure 5-1 shows the distributed base station where an APM30H is stacked on a battery
cabinet.

When an APM30H is configured in the distributed base station, an IBBS200D or IBBS200T can be
configured. Figure 5-1 shows the distributed base station configured with an IBBS200D.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 11


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 5 Application Scenario of an APM30H

Figure 5-1 APM30H stacked on a battery cabinet in a distributed base station

APM30H Used in a Separated Macro Base Station


In a separated macro base station, an APM30H is configured as follows:
 The APM30H provides 5 U space for transmission equipment and uses an embedded
power system to feed -48 V DC power into the BBU, RFU, transmission equipment, and
battery groups in the battery cabinet.
 When the mains are unavailable, battery groups feed -48 V DC power into the BBU,
RFU, and transmission equipment.
 The APM30H provides the function of reporting alarms from the fans of the RFC, door
status sensor, DCDU, and battery cabinet.
Figure 5-2 show the separated macro base station where an APM30H is configured.

When an APM30H is configured in the separated macro base station, an IBBS200D or IBBS200T can be
configured. Figure 5-2 show the separated macro base station configured with an IBBS200D.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 12


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 5 Application Scenario of an APM30H

Figure 5-2 APM30H in a separated macro base station

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 13


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 6 Components in APM30H

6 Components in APM30H

This section describes module and board configurations in APM30H.


An APM30H houses a BBU and also provides 5 U installation space for customer equipment
such as the EMUA or EMUB, AC heater, and service outlet unit (SOU), which are optional.

Components in an APM30H (Ver.E)


The following figure shows the components in an APM30H (Ver.E).

Figure 6-1 Components in an APM30H (Ver.E)

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 14


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 6 Components in APM30H

The following table lists the components in an APM30H (Ver.E).

Table 6-1 Components in an APM30H (Ver.E)

No. Module/B Optio Maximum Description


oard nal or Quantity
Mand in a
atory Single
Cabinet

1 Outer Air Mandat 1 An outer air circulation component includes


Circulation ory a heat exchanger core and fans.
Assembly  The heat exchanger core promotes the
inner and outer air circulation, and
accelerates internal and external air
exchanges. This lowers the operating
temperature of the cabinet and protects a
cabinet from dust.
 The fans dissipate heat from the cabinet.
2 AC Mandat 1 When a heater or a heating film is
Junction ory configured, an AC junction box provides
Box power for the heater or the heating film.
3 FAN 02E Mandat 1 A FAN 02E is configured with fans and a
ory cabinet control unit type B (CCUB). The fans
dissipate heat from the cabinet.
4 SLPU Mandat 2  To provide protection for trunk signals,
ory an SLPU is mandatory and installed in the
top 1 U space of the cabinet. It is
configured with the UELP or UFLP.
 To provide protection for monitoring
signals, an SLPU is optional and installed
in the 1 U space below the BBU. It is
configured with two USLP2 boards.
5 ELU Mandat 1 An ELU reports the cabinet type
ory automatically to facilitate troubleshooting.
6 Door Status Mandat 1 A door status sensor monitors whether the
Sensor ory cabinet door is open.
7 EPU05A-0 Mandat 1 An EPU05A subrack distributes AC and DC
6/08 ory power to other components in a cabinet.
Subrackor  The EPU05A-06 applies to a separated
EPU05A-0 macro base station supplied with 220 V
7/09 AC power.
Subrack
 The EPU05A-07 applies to a distributed
base station supplied with 220 V AC
power.
 The EPU05A-08 applies to a separated
macro base station supplied with 110 V
AC power.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 15


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 6 Components in APM30H

No. Module/B Optio Maximum Description


oard nal or Quantity
Mand in a
atory Single
Cabinet
 The EPU05A-09 applies to a distributed
base station supplied with 110 V AC
power.
8 BBU Mandat 2 A BBU processes baseband signals and
ory enables the base station to interact with the
base station controller.
The APM30H (Ver.E) supports the
BBU3900 and BBU3910.
9 GATM Option 2 A GATM supplies power to the TMA,
al reports alarms related to RET control signals,
and monitors the feeder current.
10 EMUA/EM Option 1 An EMUA or EMUB monitors the
UB al environment variables in a cabinet and
processes alarms. An EMUA or EMUB must
be configured in the 1 U space below the
BBU when more than 16 Boolean alarm
inputs are required. When a GATM is
configured, an EMUA or EMUB is installed
below the GATM.
11 Air baffle Mandat 5 An air baffle is configured in the reserved
ory space below the BBU to improve the
dissipation capability of a cabinet.
12 AC Heater Option 1 An AC heater ensures that components in a
al cabinet work within an acceptable
temperature range when the surrounding
temperature is low. It can be installed in the 1
U space at the bottom of the cabinet. If both
an AC heater and an SOU are configured, the
heater is installed in the 1 U space above the
SOU.
13 SOU Option 1 An SOU transfers AC power supply to
al customer equipment. It can be installed in the
1 U space at the bottom of the cabinet.
14 PDU03D-0 Option 3 A PDU03D-02 can supply power to three
2 al RRUs.
 In a BTS3900A (Ver.E) where RFUs and
RRUs are configured and the number of
RRUs is less than or equal to 9,
PDU03D-02s are configured to supply
power to the RRUs.
 In a DBS3900 where an APM30H
(Ver.E) is configured and the number of
RRUs ranges from 7 to 15, PDU03D-02s

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 16


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 6 Components in APM30H

No. Module/B Optio Maximum Description


oard nal or Quantity
Mand in a
atory Single
Cabinet
are configured to supply power to the
RRUs.
15 PDU01D-0 Option 1 A PDU01D-01 can be used together with an
1 al ODM to supply power to a maximum of 6
RRUs.
 In a BTS3900A (Ver.E) where RFUs and
RRUs are configured and the number of
RRUs ranges from 10 to 15,
PDU01D-01s are configured to supply
power to the RRUs.
 In a DBS3900 where an APM30H
(Ver.E) is configured and the number of
RRUs ranges from 16 to 21,
PDU01D-01s are configured to supply
power to the RRUs.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 17


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

7 Components Description

About This Chapter


An APM30H consists of the AC/DC power system, fan assembly, electronic label unit (ELU),
door status sensor, filler module, optional AC heater, and service outlet unit (SOU).

7.1 AC/DC Power System


The AC/DC system converts 110 V/220 V AC power to -48 V DC.

7.1.1 Components in an EPU05A


An EPU05A-06, EPU05A-07, EPU05A-08, or EPU05A-09 consists of an EPU05A subrack,
PSUs (R4850G2), a PDU03D-02, and a PDU01D-01.

Components of an EPU05A-06 or EPU05A-08


The following figure shows the components of an EPU05A-06 or EPU05A-08.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 18


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

Figure 7-1 Components of an EPU05A-06 or EPU05A-08

No. Component Description


(1) PSU (R4850G2) The number of PSUs ranges from 2
to 5. PSUs must be installed in
adjacent slots in the sequence from
slot 1 to slot 5.
(2) PDU01D-01 It is optional and can be installed in
slot 6.
(3) PDU03D-02 It is optional and can be installed in
slot 7, 8, or 9.
(4) EPU05A-06 and EPU05A-08 -
Subracks
- Filler panel Filler panels must be installed in any
of vacant slots 1 to 9.

Components of an EPU05A-07 or EPU05A-09


The following figure shows the components of an EPU05A-07 or EPU05A-09.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 19


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

Figure 7-2 Components of an EPU05A-07 or EPU05A-09

No. Component Description


(1) PSU (R4850G2) The number of PSUs ranges from 2
to 5. PSUs must be installed in
adjacent slots in the sequence from
slot 1 to slot 5.
(2) PDU01D-01 It is optional and can be installed in
slot 6.
(3) PDU03D-02 It is optional and can be installed in
slot 7, 8, or 9.
(4) EPU05A-07 and EPU05A-09 -
Subracks
- Filler panel Filler panels must be installed in any
of vacant slots 1 to 9.

7.1.2 EPU05A-06 and EPU05A-08 Subracks


An EPU05A-06 or EPU05A-08 subrack houses PSUs (R4850G2), a PDU03D-02, and a
PDU01D-01. It also distributes AC input power and DC output power. EPU05A-06 and
EPU05A-08 subracks can be used in separated macro base stations with different AC power
inputs.

Types and Applications of Subracks


The following table describes the applications of an EPU05A-06 subrack and an EPU05A-08
subrack.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 20


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

Table 7-1 Applications of an EPU05A-06 subrack and an EPU05A-08 subrack

Model Application Description


EPU05A-06 Separated macro base It is 5 U high and can house
station with external 220 V five PSUs (R4850G2) with
AC input 3000 W power of each PSU,
three PDU03D-02s, and one
EPU05A-08 Separated macro base PDU01D-01. It distributes
station with an external 110 large- and small-capacity
V AC power input DC power.

Exterior
Figure 7-3 and Figure 7-4 show the exteriors of EPU05A-06 and EPU05A-08 subracks,
respectively.

Figure 7-3 Exterior of an EPU05A-06 subrack

(1) AC surge (2) Circuit breakers for (3) AC OUTPUT (4) Output port and
protector PSUs 1, 2, 3, 4, and 5 circuit breaker circuit breaker for
RFC 1
(5) Output port and (6) Output terminals for (7) Indicator for the (8) Button switch
circuit breaker for storage batteries storage battery for the storage
RFC 2 circuit status battery circuit
(9) LOAD0 to (10) PMIU (11) Spare fuse box (12) AC OUTPUT
LOAD8 power port
output terminals

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 21


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

(13) AC INPUT (14) Short-circuiting - -


port bar

Figure 7-4 Exterior of an EPU05A-08 subrack

(1) AC surge (2) Circuit breakers (3) AC OUTPUT (4) Output port and
protector for PSUs 1, 2, 3, 4, circuit breaker circuit breaker for
and 5 RFC 1
(5) Output port and (6) Output terminals (7) Indicator for the (8) Button switch
circuit breaker for for storage batteries storage battery for the storage
RFC 2 circuit status battery circuit
(9) LOAD0 to (10) Power (11) Spare fuse box (12) AC OUTPUT
LOAD8 power monitoring interface port
output terminals unit (PMIU)
(13) AC INPUT - - -
port

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 22


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

 If a short-circuiting bar is installed on the AC INPUT wiring terminal to connect the L1, L2, and L3
terminals, an EPU subrack supplies 220 V AC single-phase power. If the EPU subrack supplies 220
V AC three-phase power, you must remove the short-circuiting bar.
 Circuit breakers in an EPU supplying 220 V AC power are gray. Circuit breakers in an EPU
supplying 110 V AC power are blue.
 The button switch for storage battery circuit controls the power supply of the storage batteries. If the
indicator for storage battery circuit status is steady off, the storage battery circuit is interrupted. If
the indicator is steady on, the storage battery circuit is normal.
 Before maintaining storage batteries, turn off the switch for storage battery circuit.

Function
An EPU05A-06 or EPU05A-08 distributes AC input power and DC output power.
 An EPU05A-06 or EPU05A-08 subrack performs the following AC power distribution
functions:
− Provides two AC power outputs (one for an SOU and one for the AC junction box on
the left of a cabinet). The AC junction box provides four AC power outputs for
heaters or heating films.
− Reports AC input surge protection alarms.
− Provides a circuit breaker for each of five PSUs.
 An EPU05A-06 or EPU05A-08 provides 12 DC power outputs by default and can be
configured with a PDU01D-01 and a PDU03D-02 to provide a maximum of 22 power
outputs to meet DC power distribution requirements in a separated macro base station.

Port
The following figure shows AC power input and output terminals as well as DC power output
ports on an EPU05A-06 or EPU05A-08 subrack. Table 7-2and Table 7-3list the specifications
of AC power input and output terminals as well as DC power output ports.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 23


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

Figure 7-5 AC power input and output terminals as well as DC power output ports on an
EPU05A-06 or EPU05A-08 subrack

Table 7-2 AC power input and output terminals on an EPU05A-06 or EPU05A-08 subrack
AC Input or Output Wiring Terminal Connector
Terminal
AC INPUT terminal L1, L2, L3, and N OT terminal (M6)
(EPU05A-06)
AC INPUT terminal L1, L2, N, and PE
(EPU05A-08)
AC OUTPUT terminal L1, N1, L2, and N2

Table 7-3 DC power output ports on an EPU05A-06 or EPU05A-08 subrack

DC Power DC Power Protector Specifications Connector


Output Port Supply Unit of the
Protector
LOAD0 and BBU Fusec 9x30 A EPC4
LOAD1
LOAD2 FAN
LOAD3 TM_0a
LOAD4 TM_1
LOAD5 TM_2, EMUA,
or EMUB

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 24


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

DC Power DC Power Protector Specifications Connector


Output Port Supply Unit of the
Protector

LOAD6 TM_3 or BBU


LOAD7 TMC
LOAD8 IBBSb
RFC 1 RFC 1 Breaker 2x100 A OT terminal
(M6)
RFC 2 RFC 2
BATd BAT - - -
a: TM is customer transmission equipment. LOAD3, LOAD4, LOAD5, and LOAD6 are
DC power output terminals for transmission equipment, supporting four DC power outputs.
b: If an IBBS200D is configured, LOAD8 is a DC power output terminal for the
IBBS200D fan power cable. If an IBBS200T is configured, LOAD8 is a DC power output
terminal for the IBBS200T TEC power cable.
c: A spare fuse box contains five 5 A fuses and three 30 A fuses for onsite replacement.
d: The BAT port in an EPU subrack does not have a protective component. The circuit
breaker BAT in a battery cabinet requires 250 A current.

Circuit Breaker
There are several circuit breakers on an EPU05A-06 or EPU05A-08 subrack to control DC
power outputs. The following figure shows the positions of circuit breakers and the following
table describes the specifications of circuit breakers.

Figure 7-6 Circuit breakers on an EPU05A-06 or EPU05A-08 subrack

Table 7-4 Circuit breakers on an EPU05A-06 or EPU05A-08 subrack

Circuit Breaker Silkscreen Requirements for the


Circuit Breaker

Circuit breakers for PSUs PSU1/2/3/4/5 5x32 A


AC power output circuit AC OUTPUT 1x16 A
breaker (EPU05A-06)

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 25


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

Circuit Breaker Silkscreen Requirements for the


Circuit Breaker
AC power output circuit AC OUTPUT 1x16 A
breaker (EPU05A-08)
Circuit breakers for RFCs RFC1 and RFC2 2x100 A

7.1.3 EPU05A-07 and EPU05A-09 Subracks


An EPU05A-07 or EPU05A-09 subrack houses PSUs (R4850G2), a PDU03D-02, and a
PDU01D-01. It also distributes AC input power and DC output power. EPU05A-07 and
EPU05A-09 subracks can be used in distributed base stations with different AC power inputs.

Types and Applications of Subracks


The following table describes the applications of an EPU05A-07 subrack and an EPU05A-09
subrack.

Table 7-5 Applications of an EPU05A-07 subrack and an EPU05A-09 subrack


Model Application Description

EPU05A-07 Distributed base station with It is 5 U high and can house


an external 220 V AC power five PSUs (R4850G2) with
input 3000 W power of each PSU,
three PDU03D-02s, and one
EPU05A-09 Distributed base station with PDU01D-01. It distributes
an external 110 V AC power large- and small-capacity
input DC power.

Exterior
Figure 7-7 and Figure 7-8 show the exteriors of an EPU05A-07 subrack and an EPU05A-09
subrack.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 26


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

Figure 7-7 Exterior of EPU05A-07 subrack

(1) AC surge protector (2) Circuit breakers (3) AC OUTPUT (4) LOAD9 to
for PSUs 1, 2, 3, 4, circuit breaker LOAD14 power
and 5 output terminals
(5) Power output (6) Indicator for (7) Button switch (8) LOAD0 to
terminals for storage the storage battery for the storage LOAD8 power
batteries circuit status battery circuit output terminals
(9) Power monitoring (10) Spare fuse box (11) AC OUTPUT (12) AC INPUT
interface unit (PMIU) terminal terminal
(13) Short-circuiting - - -
bar

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 27


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

Figure 7-8 Exterior of an EPU05A-09 subrack

(1) AC surge (2) Circuit breakers (3) AC OUTPUT (4) LOAD9 to


protector for PSUs 1, 2, 3, 4, circuit breaker LOAD14 power
and 5 output terminals
(5) Power output (6) Indicator for the (7) Button switch for (8) LOAD0 to
terminals for storage storage battery the storage battery LOAD8 power
batteries circuit status circuit output terminals
(9) PMIU (10) Spare fuse box (11) AC OUTPUT (12) AC INPUT
terminal terminal

 If a short-circuiting bar is installed on the AC INPUT wiring terminal to connect the L1, L2, and L3
terminals, an EPU subrack supplies 220 V AC single-phase power. If the EPU subrack supplies 220
V AC three-phase power, you must remove the short-circuiting bar.
 Circuit breakers in an EPU supplying 220 V AC power are gray. Circuit breakers in an EPU
supplying 110 V AC power are blue.
 The button switch for storage battery circuit controls the power supply of the storage batteries. If the
indicator for storage battery circuit status is steady off, the storage battery circuit is interrupted. If
the indicator is steady on, the storage battery circuit is normal.
 Before maintaining storage batteries, turn off the switch for storage battery circuit.

Function
An EPU05A-07 or EPU05A-09 distributes AC input power and DC output power.
 An EPU05A-07 or EPU05A-09 subrack performs the following AC power distribution
functions:
− Provides two AC power outputs (one for an SOU and one for the AC junction box on
the left of a cabinet). The AC junction box provides four AC power outputs for
heaters or heating films.
− Reports AC input surge protection alarms.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 28


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

− Provides a circuit breaker for each of five PSUs.


 An EPU05A-07 or EPU05A-09 provides 16 DC power outputs by default and can be
configured with a PDU01D-01 and a PDU03D-02 to provide a maximum of 26 DC
power outputs to meet DC power distribution requirements in a distributed base station.

Port
The following figure shows AC power input and output terminals as well as DC power output
ports on an EPU05A-07 or EPU05A-09 subrack. Table 7-6 and Table 7-7 list the
specifications of AC power input and output terminals as well as DC power output ports.

Figure 7-9 AC power input and output terminals as well as DC power output ports on an
EPU05A-07 or EPU05A-09 subrack

Table 7-6 AC power input and output terminals on an EPU05A-07 or EPU05A-09 subrack
AC Input or Output Wiring Terminal Connector
Terminal
AC INPUT terminal L1, L2, L3, and N OT terminal (M6)
(EPU05A-07)
AC INPUT terminal L1, L2, N, and PE
(EPU05A-09)
AC OUTPUT terminal L1, N1, L2, and N2

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 29


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

Table 7-7 DC power output ports on an EPU05A-07 or EPU05A-09 subrack

DC Power DC Power Protector Specifications Connector


Output Port Supply Unit of the
Protector
LOAD0 and BBU Fusec 9x30 A EPC4
LOAD1 ports
LOAD2 port FAN
LOAD3 port TM_0a
LOAD4 port TM_1
LOAD5 port TM_2, EMUA,
or EMUB
LOAD6 port TM_3 or BBU
LOAD7 TMC
LOAD8 port IBBSb
LOAD9 to RRUs Fuse 6x30 A EPC5
LOAD14 portsd
BATe BAT - - -
a: TM is customer transmission equipment. LOAD3, LOAD4, LOAD5, and LOAD6 are
DC power output terminals for transmission equipment, supporting four DC power outputs.
b: If an IBBS200D is configured, LOAD8 is a DC power output terminal for the
IBBS200D fan power cable. If an IBBS200T is configured, LOAD8 is a DC power output
terminal for the IBBS200T TEC power cable.
c: A spare fuse box contains five 5 A fuses and three 30 A fuses for onsite replacement.
d: LOAD9 to LOAD14 ports configured with EPC5 connectors supply power to RRUs.
e: The BAT port in an EPU subrack does not have a protective component. The circuit
breaker BAT in a battery cabinet requires 250 A current.

Circuit Breaker
There are several circuit breakers on an EPU05A-07 or EPU05A-09 subrack to control DC
power outputs. The following figure shows the positions of circuit breakers and the following
table describes the specifications of circuit breakers.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 30


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

Figure 7-10 Circuit breakers on an EPU05A-07 or EPU05A-09 subrack

Table 7-8 Circuit breakers on an EPU05A-07 or EPU05A-09 subrack

Circuit Breaker Silkscreen Requirements for the


Circuit Breaker

Circuit breakers for PSUs PSU1/2/3/4/5 5x32 A


AC power output circuit AC OUTPUT 1x16 A
breaker (EPU05A-07)
AC power output circuit AC OUTPUT 1x16 A
breaker (EPU05A-09)

7.1.4 PSU (R4850G2)


A power supply unit (PSU) (R4850G2) converts 110 V AC or 220 V AC power into -48 V DC
power. A PSU (R4850G2) can be used in any of the following cabinets: BTS3900 (Ver.D),
BTS3900L (Ver.D), BTS3900AL (Ver.A), OMB (Ver.C), BTS3900 (Ver.D_A), BTS3900
(Ver.D_B), APM30H (Ver.D), APM30H (Ver.E), APM30H (Ver.D_A1), APM30H (Ver.D_A2),
APM30H (Ver.E_A1), APM30H (Ver.E_A2), APM30H (Ver.D_B), BTS3012 (Ver.D_Z),
BTS3012AE (Ver.D_Z), and IMS06.

Exterior
The following figure shows the exterior of a PSU (R4850G2).

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 31


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

Figure 7-11 Exterior of a PSU (R4850G2)

Function
A PSU (R4850G2) performs the following functions:
 Converts 110 V AC or 220 V AC power into -48 V DC and adjusts the output voltage.
 Provides protection against overcurrent, overvoltage, and overtemperature for its DC
outputs.
 Dissipates heat using its built-in fans.

Indicator
The following figure shows the indicators on a PSU (R4850G2).

Figure 7-12 Indicators on a PSU (R4850G2)

The following table describes the indicators on a PSU (R4850G2).

Table 7-9 Indicators on a PSU (R4850G2)

Indicatora Color Status Description


(1) Power Green Steady on The board is functional.
indicator
Blinking (on for The PSU is loading software online.
0.125s and off for
0.125s)
Steady off The mains supply or the module is faulty.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 32


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

Indicatora Color Status Description


(2) Yello Steady off Yes
Protection w
indicator Steady on An alarm triggered by an external factorb
is generated.
Blinking (on for 1s The communication between the module
and off for 1s) and the PMU is interrupted.
(3) Fault Red Steady off Yes
indicator
Steady on The module is faulty or is shut down in an
emergency. Locate the fault and replace
the module.

a: If the red indicator and green indicator are steady on and the yellow indicator is blinking, PSUs not
securely installed in the slots.
b: An alarm can be triggered by the following external factors:
 The rectifier generates a prewarning for power limiting due to overtemperature.
 The rectifier generates an alarm for shutdown due to ambient overtemperature protection.
 The rectifier generates an alarm due to AC input overvoltage or undervoltage protection.
 The rectifier is hibernated.

7.1.5 PDU01D-01
A power distribution unit 01D-01 (PDU01D-01) can be used in an EPU05A-06, EPU05A-07,
EPU05A-08, or EPU05A-09 and be connected to an outdoor distribution module (ODM) to
provide power for RRUs.

Exterior
The following figure shows the exterior of a PDU01D-01.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 33


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

Figure 7-13 Exterior of a PDU01D-01

Function
A PDU01D-01 performs the following functions:
 Provides one -48 V DC power output.
 Provides power for a maximum of six RRUs if being used together with an ODM.

Port
The following figure shows the port on a PDU01D-01. The following table describes the port
on a PDU01D-01.

Figure 7-14 Port on a PDU01D-01

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 34


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

Table 7-10 Port on a PDU01D-01

DC Power Power-Consu Protector Specifications Connector


Output Port ming Device of the
Protector

LOAD port ODM Circuit breaker 1x100 A OT terminal


(M6)

7.1.6 PDU03D-02
A power distribution unit 03D-02 (PDU03D-02) can be used in an EPU05A-06, EPU05A-07,
EPU05A-08, or EPU05A-09 to provide power for RRUs.

Exterior
The following figure shows the exterior of a PDU03D-02.

Figure 7-15 Exterior of a PDU03D-02

Function
A PDU03D-02 performs the following functions:
 Provides three -48 V DC power outputs.
 Provides power for a maximum of three RRUs.

Port
The following figure shows the ports on a PDU03D-02. The following table describes the
ports on a PDU03D-02.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 35


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

Figure 7-16 Ports on a PDU03D-02

Table 7-11 Ports on a PDU03D-02

DC Power Power-Consu Protector Specifications Connector


Output Port ming Device of the
Protector
LOAD0, RRUs Fuse 3x30 A EPC5 connector
LOAD1, and
LOAD2 ports

7.1.7 PMIU
A power monitoring interface unit (PMIU) transfers monitoring signals from an EPU05A-06,
EPU05A-07, EPU05A-08, or EPU05A-09 to a CCUB. It can be used in APM30H (Ver.E) or
APM30H (Ver.E_A2).

Exterior
The following figure shows the exterior of a PMIU.

Figure 7-17 Exterior of a PMIU

(1) STATE indicator (2) RJ45 port

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 36


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

Function
A PMIU performs the following functions:
 Communicates with a CCUB, manages the power system, and charges and discharges
batteries
 Monitors power distribution analog signals, including DC voltage, battery current,
battery circuit status, and AC SPD status.
 Controls battery and load contactors.
 Identifies whether pluggable modules are in position.

Port
The following table describes the ports on a PMIU.

Table 7-12 Port on a PMIU

Silkscreen Connector Description


PMI RJ45 connector Connecting to the PMI port on the CCUB in a
cabinet and reporting monitoring information
about the power subrack to the CCUB.

Indicator
The following table describes the indicator on a PMIU.

Table 7-13 Indicator on a PMIU


Silkscr Color Status Description
een

STATE - Steady off There is no power supply, or the board is


faulty.
Green Steady on Communications are normal and no alarm is
reported.
Red Steady on An alarm is generated, and the module must be
replaced.

7.2 AC Junction Box


When a heater or a heating film is configured, the AC junction box provides power for the
heater or the heating film. An AC junction box can be used in a BTS3900AL, APM30H,
TMC11H, IBBS300D, IBBS700D, or IBBS700T.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 37


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

Exterior
The AC junction box in an APM30H, TMC11H, IBBS300D, IBBS700D, or IBBS700T is
located on the inner left wall of the cabinet. The AC junction box in a BTS3900AL cabinet is
located on the inner right wall of the cabinet. The following figure shows an APM30H as an
example.

Figure 7-18 Exterior of the AC junction box

Function
The AC junction box in a cabinet performs the following functions:
 The PDU05A-01 in a BTS3900AL cabinet feeds power into the AC junction box. The
power is divided into four AC power outputs, which are then provided for the heater in
the cabinet.
 An EPU subrack feeds power into the AC junction box in an APM30H. The power is
divided into four AC power outputs, which are then provided for the heater in the cabinet
or heating film in the IBBS200D.
 The AC junction box in the APM30H feeds power into the AC junction box in the
TMC11H. The power is divided into four AC power outputs, which are then provided for
the heater or service outlet unit (SOU) in the cabinet.
 The AC junction box in the basic cabinet (APM30H, BTS3900AL, or TP48600A-H17B1)
feeds power into the AC junction box in the IBBS300D, IBBS700D, or IBBS700T. The
power is divided into four AC power outputs, which are then provided for the heater in
the cabinet.

Interior
The following figure shows the interior of an AC junction box.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 38


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

Figure 7-19 Interior of an AC junction box

(1) Four AC output L (2) Four AC output N (3) Four AC output PE


wiring terminals wiring terminals wiring terminals
(4) Cable holes (5) AC input N wiring (6) AC input L wiring
terminal terminal

7.3 Fan Assembly


This section describes FAN 02E and CCUB.

7.3.1 FAN 02E


A FAN 02E dissipates heat from a cabinet and monitors temperature. A FAN 02E can be
installed in an APM30H (Ver.E) or TMC11H (Ver.E).

Exterior
A FAN 02E consists a fan, a fan subrack, and a CCUB. The following figure shows the
exterior of a FAN 02E.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 39


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

Figure 7-20 Exterior of a FAN 02E

(1) CCUB (2) Fan (3) Fan subrack

Port
The following figure shows the ports on a FAN 02E.

Figure 7-21 Ports on a FAN 02E

(1) ALM (2) ADDR (3) TEM (4) SMOKE (5) GATE
(6) (7) (8) D_COM3 (9) D_COM2 (10) COM_485
COM_OUT/U_ COM_IN/U_C
COM1 OM0
(11) FAN_EXT (12) PWR (13) (14) (15)
MON0-0/D_CO MON0-1/D_CO MON1-0/D_CO
M0-0 M0-1 M1-0
(16) (17) PMI (18) ELU (19) IN0, IN1, (20) TEM_BAT
MON1-1/D_CO and IN2
M1-1
(21) RUN - - - -

For details about the ports and indicators on a CCUB, see 7.3.2 CCUB.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 40


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

7.3.2 CCUB
A cabinet control unit type B (CCUB) monitors a fan module, a heater, cabinet temperature, a
power module, and lower-level devices. A CCUB can be installed in an APM30H (Ver.E) or
TMC11H (Ver.E).

Exterior
The following figure shows the exterior of a CCUB.

Figure 7-22 Exterior of a CCUB

Port
The following figure shows the ports on a CCUB.

Figure 7-23 Ports on a CCUB

The following table describes the ports on a CCUB.

Table 7-14 Ports on a CCUB

No Silkscr Description
. een

(1) PWR Power input port providing DC power inputs for boards
(2) EFAN1 Connecting an external circulation fan and receiving external circulation

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 41


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

No Silkscr Description
. een
fan alarm signals
(3) COM_4 Connecting a monitoring board in a battery cabinet and receiving alarm
85 signals from the battery cabinet
(4) MON0-  MON0-0: Connecting an environment monitoring unit in another
0/D_CO RFC, TMC11H, or APM30H
M0-0  D_COM0-0: Downlink communication port supporting RS485
communication and used for managing electromechanical devices
(5) MON0-  MON0-1: Connecting an environment monitoring unit in another
1/D_CO RFC, TMC11H, or APM30H
M0-1  D_COM0-1: Downlink communication port supporting RS485
communication and used for managing electromechanical devices
(6) MON1-  MON1-0: Connecting an environment unit in an RFC, TMC11H, or
0/D_CO APM30H
M1-0  D_COM1-0: Downlink communication port supporting RS485
communication and used for managing electromechanical devices
(7) MON1-  MON1-1: Connecting an environment unit in an RFC, TMC11H, or
1/D_CO APM30H
M1-1  D_COM1-1: Downlink communication port supporting RS485
communication and used for managing electromechanical devices
(8) D_COM Downlink communication port supporting RS485 communication and
2 used for managing electromechanical devices
Connecting a WIUA that is optional
(9) D_COM Downlink communication port supporting RS485 communication and
3 used for managing electromechanical devices
Connecting an electric lock that is optional
(10 COM_I  COM_IN: Connecting an upper-level CCUB or CMUH. If no BBU is
) N/U_CO installed in an APM30H (Ver.E) or TMC11H (Ver.E) or the BBU
M0 installed in an APM30H (Ver.E) or TMC11H (Ver.E) does not work
as a manager, this port communicates with an upper-level cascading
port for reporting monitoring information.
 U_COM0: If the BBU installed in an APM30H (Ver.E) or TMC11H
(Ver.E) works as a manager, this port connects to the MON1 port on
the BBU.
(11 COM_O  COM_OUT: If no BBU is installed in an APM30H (Ver.E) or
) UT/U_C TMC11H (Ver.E) or the BBU installed in an APM30H (Ver.E) or
OM1 TMC11H (Ver.E) does not work as a manager, this port
communicates with a lower-level cascading port for receiving
monitoring information and connecting a lower-level CMUH.
 U_COM1: If the BBU installed in an APM30H (Ver.E) or TMC11H
(Ver.E) works as a manager, this port connects to the MON1 port on
the BBU.
(12 PMI Connecting a power monitoring interface (PMI) board and receiving

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 42


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

No Silkscr Description
. een
) monitoring signals from the power system
(13 ELU Connecting an ELU to report the cabinet type
)
(14 IN0, Reserved Boolean signal port
) IN1, and
IN2
(15 GATE Boolean signal port for connecting a door status sensor that is configured
) by default
(16 SMOKE Boolean signal port
) Connecting a smoke sensor in an APM30H or TMC11H
(17 TEMP0 Reserved temperature monitoring port
)
(18 TEM_B Battery temperature sensor port for receiving temperature information
) AT about internal or external storage batteries of an APM30H
(19 ADDR Address monitored by the PMU function of a CCUB. The monitored
) address is 3 if the DIP switch is set to 1. The monitored address is 4 if the
DIP switch is set to 0.
(20 WATER Reserved port for connecting a water sensor
)
(21 TEMP2 Reserved port for connecting a temperature sensor
)
(22 IFAN0 Connecting an internal circulation fan and receiving internal circulation
) fan alarm signals

Indicator
The following table describes the two status indicators on a CCUB.

Table 7-15 Indicators on a CCUB

Label Color Status Meaning


RUN Green Blinking (on for 1s The board is functional and
and off for 1s) communicates with the upper-level
device properly.
Blinking (on for The board is functional but fails to
0.125s and off for communicate with the upper-level
0.125s) device or the board is not registered.
Steady on The board is in the power-on
self-check status.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 43


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

Label Color Status Meaning


Steady off There is no power supply, or the
board is faulty.
ALM Red Steady off No alarm is reported.
Steady on Alarms are generated, and the board
must be replaced.
Blinking (on for 1s An alarm is generated, and the alarm
and off for 1s) may be caused by an associated board
or port fault. Therefore, you need to
locate the fault before determining
whether to replace the board.

7.4 ELU
An electronic label unit (ELU) reports the cabinet type automatically to facilitate
troubleshooting. It applies to the following cabinets: BTS3900, BTS3900L, BTS3900AL,
OMB, OMB (Ver.C), IBC10,APM30H series cabinets, IBBS200D series cabinets, IBBS200T
series cabinets, IBBS300D, IBBS300T, IBBS20D, IBBS700D, and IBBS700T.

Exterior
The following figure shows the exterior of an ELU.

Figure 7-24 Exterior of an ELU

(1) Housing (2) RJ45 port

The ELU in a BTS3900 or BTS3900L cabinet does not have a housing.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 44


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

Installation Positions
The following figure shows the position of an ELU in a cabinet.

Figure 7-25 Position of the ELU in a BTS3900 cabinet

Figure 7-26 Position of the ELU in a BTS3900L cabinet

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 45


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

The ELU in an APM30H, TMC11H, or RFC is located on the inner right wall of the cabinet.
The ELU in an IBBS200D, IBBS200T, IBBS300D, or IBBS300T is located on the inner left
wall of the cabinet. The following figure shows an APM30H and an IBBS200D as examples.

Figure 7-27 Positions of the ELUs in an APM30H and an IBBS200D

Figure 7-28 Position of the ELU in an OMB

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 46


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

Figure 7-29 Position of the ELU in a BTS3900AL cabinet

Figure 7-30 Position of the ELU in the IBBS700D or IBBS700T cabinet

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 47


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

 In the IBBS700D, the ELU is located above a CCU when a CCU is installed in the cabinet or on the
right of the CMUEA when no CCU is installed in the cabinet.
 In the IBBS700T, the ELU is located above a CCU when a CCU is installed in the cabinet or on the
left of the CMUF when no CCU is installed in the cabinet.

Figure 7-31 Position of the ELU in an IBC10

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 48


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

Figure 7-32 Position of the ELU in an IBBS20D

7.5 Door Status Sensor


The door status sensor can monitor the status (open or closed) of a door. It can be used in any
of the following cabinets: BTS3900AL (Ver.A), OMB, OMB (Ver.C), APM30H, RFC,
TMC11H, IBBS200D, IBBS200T, IBBS300D, IBBS300T, IBBS20D, IBBS700D, and
IBBS700T.

Exterior
A door status sensor consists of a magnet and a switch. The following figures show the
exteriors of the magnet of a door status sensor.

Figure 7-33 Exterior of the magnet of a door status sensor

(1) Shell of the magnet (2) Magnet

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 49


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

The following figure shows the exterior of the switch of a door status sensor.

Figure 7-34 Exterior of the switch of a door status sensor

Installation Positions
The door status sensors in the BTS3900AL (Ver.A), IBBS700D, and IBBS700T are located in
the same positions. The following figure shows the BTS3900AL (Ver.A) as an example.

Figure 7-35 Position of the door status sensor in the BTS3900AL (Ver.A) cabinet

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 50


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

The door status sensors in the OMB and OMB (Ver.C) are located in the same positions. The
following figure shows the OMB (Ver.C) as an example.

Figure 7-36 Position of the door status sensor in the OMB (Ver.C) cabinet

The door status sensors in the APM30H, RFC, TMC11H, IBBS200D, IBBS200T, IBBS20D,
IBBS300D, and IBBS300T, are located in the same positions. The following figure shows the
APM30H (Ver.D) as an example.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 51


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

Figure 7-37 Position of the door status sensor in the APM30H (Ver.D) cabinet

7.6 (Optional) AC Heater


An AC heater ensures that the customer equipment in a cabinet works within the acceptable
temperature range. It is optionally installed in the customer space in an APM30H or
TMC11H.

Exterior
An AC heater is 1 U high. The following figure shows the exterior of an AC heater.

Figure 7-38 Exterior of an AC heater

Technical Specifications
The following table lists the technical specifications of an AC heater.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 52


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

Table 7-16 Technical specifications of an AC heater

Counter Specification
The temperature of the AC heater starts < 1oC (±6oC)
working
The temperature of the AC heater stops > 15oC (±3oC)
working
Rated heating power 330 W

7.7 (Optional) SOU


A service outlet unit (SOU) transfers AC power to the customer equipment. An SOU is
optionally installed in the customer space in an APM30H.

Exterior
An SOU is 1 U high. The following figure shows the exterior of an SOU.

Figure 7-39 Exterior of an SOU

(1) Input power port (2) Breaker (3) Socket (European standard)

An SOU applies to the four types of sockets meeting the following standards: North American
standard, European standard, Universal standard, and British standard. The following figure
shows the exteriors of the four types of sockets.

Figure 7-40 Exteriors of different types of sockets

(1) North American (2) European (3) Universal (4) British

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 53


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 7 Components Description

standard standard standard standard

Technical Specifications
The following table lists the technical specifications of an SOU.

Table 7-17 Technical specifications of an SOU

Counter Specification

Dimensions (H x W x D) 482.6 mm x 91 mm x 55 mm (7.87 in. x


23.62 in. x 17.09 in.)
Weight 1.5 kg (3.31 lb)
Input voltage range 200 V AC to 240 V AC
Maximum input current 10 A
Output voltage range 200 V AC to 240 V AC
Maximum output current 10 A
Frequency band 50 Hz or 60 Hz
Operating temperature -40oC to +55oC
Altitude ≤ 4000m
NOTE
Above the altitude of 3000 m (9842.52 ft), the
maximum operating temperature drops by 1oC
(33.8oF) as the altitude increases by 100 m
(328.08 ft).

Protection class IP20

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 54


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 8 APM30H Cables

8 APM30H Cables

About This Chapter


The APM30H cables consist of the power cables, equipotential cables, PGND cables, and
signal cables.

8.1 Cable List


APM30H cables mainly consist of the PGND cables, equipotential cables, power cables, and
signal cables.

Power Cables, PGND Cables, and Equipotential Cables


The following table lists the power cables, PGND cables, and equipotential cables.

Table 8-1 Power cables, PGND cables, and equipotential cables

Classif Cable One End The Other End


ication
Connector Installation Connector Installation
Position Position
Cables  8.5.1 OT terminal L and N Depending External
to be EPU05A-0 terminals on on external power
installe 6 or the AC power equipment
d onsite EPU05A-0 INPUT equipment
8 Power terminal
Cable block on the
 8.5.2 EPU
EPU05A-0
7 or
EPU05A-0
9 Power
Cable
8.3 PGND OT terminal Ground bar in OT terminal Ground
Cable the APM30H busbar outside
the cabinet

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 55


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 8 APM30H Cables

Classif Cable One End The Other End


ication
Connector Installation Connector Installation
Position Position
8.4 OT terminal Ground bar in OT terminal Ground bar in
Equipotential the APM30H the lower
Cable cabinet
Cables 8.5.5 FAN EPC4 LOAD5 port 3V3 PWR port on
installe 02E Power connector on the EPU connector the fan
d Cable in the assembly in
before APM30H the APM30H
deliver
y 8.5.4 Power OT terminal L0 and N0 C13 Input power
Cable for an terminals on connector port on the
AC Heater the AC AC heater
junction box
in the
APM30H and
the cabinet
ground bar
8.5.3 SOU OT terminal M4 ground C13 INPUT port
Power Cable screw, L2 connector on the SOU
terminal, and
N2 terminal
on the AC
OUTPUT
terminal
block on the
EPU
8.5.6 Power OT terminal M4 ground OT terminal L and N
Cable for an screw, L1 terminals on
AC Junction terminal, and the AC
Box N1 terminal junction box
on the AC in the
OUTPUT APM30H and
terminal the cabinet
block on the ground bar
EPU

The connection of power cables for optional components depends on the delivery mode. Table 8-1
describes the power cables in a macro base station.

Signal Cables
The following table describes the signal cables.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 56


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 8 APM30H Cables

Table 8-2 Signal cables

Classi Cable One End The Other End


ficati
on Connecto Installation Connect Installation
r Position or Position
Cables - - - - -
to be
install
ed
onsite
Cables 8.6.4 RJ45 PMI port on the RJ45 PMI port on the
install PMIU-CCU connector PMIU connector FAN 02E
ed B
before Monitoring
deliver Signal
y Cable
8.6.1 ELU RJ45 ELU RJ45 ELU port on the
Signal connector connector FAN 02E
Cable
8.6.2 Bare wire Door status sensor Bare wire GATE port on the
Monitoring FAN 02E
Signal
Cables for
Door Status
Sensors
8.6.3 Interconne Interconnection 4-pin FAN_EXT port on
Monitoring ction terminal on the connector the FAN 02E
Signal terminal front door of the
Transfer APM30H
Cable for
Fans in
Front Doors

8.2 Cable Connections


This section describes the principles for connecting power cables and signal cables in the
APM30H.

8.2.1 Power Cable Connections


This section describes the power cable connections in the APM30H.

Cable Connections in a Distributed Base Station


The following figure shows the APM30H power cable connections in a distributed base
station.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 57


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 8 APM30H Cables

Figure 8-1 Power cable connections in a distributed base station

(P1) 8.5.6 Power Cable for an (P2) 8.5.5 FAN 02E Power (P3) Storage Battery
AC Junction Box Cable Power Cable
(P4) 8.5.3 SOU Power Cable (P5) 8.5.4 Power Cable for -
an AC Heater

Cable Connections in a Separated Macro Base Station


The following figure shows the APM30H power cable connections in a separated macro base
station.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 58


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 8 APM30H Cables

Figure 8-2 Power cable connections in a separated macro base station

(1) 8.5.6 Power Cable for an (2) 8.5.5 FAN 02E (3) Storage Battery Power
AC Junction Box Power Cable Cable
(4) 8.5.3 SOU Power Cable (5) 8.5.4 Power Cable (6) Power Cable for the DC
for an AC Heater Junction Box in an RFC

8.2.2 Monitoring Signal Cable Connections


This section provides reference for onsite installation of monitoring signal cables.
The following figure shows the monitoring signal cable connections in the APM30H.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 59


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 8 APM30H Cables

Figure 8-3 Monitoring signal cable connections in the APM30H

(S1) 8.6.3 Monitoring Signal Transfer Cable for (S2) 8.6.4 PMIU-CCUB Monitoring
Fans in Front Doors Signal Cable
(S3) 8.6.2 Monitoring Signal Cables for Door (S4) 8.6.1 ELU Signal Cable
Status Sensors

8.3 PGND Cable


PGND cables include PGND cables for cabinets and PGND cables for modules, which ensure
grounding of cabinets and modules in the cabinets as well as safe operation of the base station
 PGND cables for cabinets are used for connecting the ground bars in the cabinets to the
ground bars at the site.
 PGND cables for modules are used for connecting the ground screws on the modules to
the ground bars in the cabinet.

Exterior
The following figure shows the exterior of a PGND cable.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 60


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 8 APM30H Cables

Figure 8-4 Exterior of a PGND cable

(1) OT terminal (2) Cord end terminal

In most cases, PGND cables are yellow and green. When 110 V dual-live-wire power is supplied for an
APM30H (Ver.C), APM30H (Ver.D), APM30H (Ver.E), RFC (Ver.C), RFC (Ver.D), or RFC (Ver.E),
PGND cables are green.

Description
Table 8-3 and Table 8-4 describe the PGND cables for cabinets and PGND cables for modules,
respectively.

Table 8-3 PGND cables for cabinets

Cabinet Type Connector Maximum Length Cable


Specifications

APM30H (Ver.E) or Both ends use OT 8 m (26.25 ft) 16 mm2 (0.025


TMC11H (Ver.E) terminals (M6). in.2)

Table 8-4 PGND cables for modules

Cabinet Type Connector Maximum Length Cable


Specifications
APM30H (Ver.E) or Both ends use OT 15 m (49.21 ft) 6 mm2 (0.009
TMC11H (Ver.E) terminals (M4). in.2)

8.4 Equipotential Cable


Equipotential cables connect the PGND terminals of two cabinets. They ensure equipotential
bonding between cabinets and safe operation of base stations.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 61


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 8 APM30H Cables

Exterior
The following figure shows the exterior of an equipotential cable.

Figure 8-5 Exterior of an equipotential cable

(1) OT terminal (M6)

In most cases, equipotential cables are yellow and green. When 110 V dual-live-wire power is supplied
for an APM30H (Ver.C), APM30H (Ver.D), APM30H (Ver.E), RFC (Ver.C), RFC (Ver.D), or RFC
(Ver.E), equipotential cables are green.

Description
The following table describes equipotential cables.

Table 8-5 Equipotential cables

Cabinet Type Cable Specifications


BTS3900 (Ver.B) cabinets stacked or 16 mm2 (0.025 in.2)
installed side by side
BTS3900 (Ver.C) cabinets stacked or
installed side by side
BTS3900 (Ver.D) cabinets stacked or
installed side by side
BTS3900 (Ver.D) cabinet stacked on
the IMS06
BTS3900L (Ver.D) cabinet stacked on 16 mm2 (0.025 in.2)
the IMS06
APM30H (Ver.B), RFC (Ver.B), 16 mm2 (0.025 in.2)
IBBS200D (Ver.B), IBBS200T
(Ver.B), and TMC11H (Ver.B)
stacked or installed side by side
APM30H (Ver.C), RFC (Ver.C), The cross-sectional areas of cables vary according
IBBS200D (Ver.C), IBBS200T to the installation scenarios of cabinets.
(Ver.C), and TMC11H (Ver.C)  16 mm2 (0.025 in.2) for stacked cabinets
stacked or installed side by side
 25 mm2 (0.039 in.2) for side-by-side cabinets
APM30H (Ver.D), RFC (Ver.D), 16 mm2
IBBS200D (Ver.D), IBBS200T
(Ver.D), IBBS700D, IBBS700T, and
TMC11H (Ver.D) stacked or installed

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 62


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 8 APM30H Cables

Cabinet Type Cable Specifications


side by side
APM30H (Ver.D), RFC (Ver.D), 16 mm2 (0.025 in.2)
IBBS300D (Ver.A), IBBS300T
(Ver.A), and TMC11H (Ver.D)
stacked or installed side by side
APM30H (Ver.E), RFC (Ver.E), 16 mm2
IBBS300D (Ver.A), IBBS300T
(Ver.A), and TMC11H (Ver.E)
stacked or installed side by side
IBBS20D, IBBS20L-E, or IBBS20L 16 mm2 (0.025 in.2)
installed side by side with RRU,
OPM50M, or BBU3910A3
BTS3900AL (Ver.A) AC cabinet and 35 mm2 (0.054 in.2)
BTS3900AL (Ver.A) DC cabinet
installed side by side
BTS3900AL (Ver.A) AC cabinet and
IBBS700D or IBBS700T cabinet
installed side by side
BTS3900AL (Ver.A) AC cabinet and
IBBS300D or IBBS300T installed
side by side
BTS3900AL (Ver.A) AC cabinet and 25 mm2 (0.039 in.2)
TMC11H (Ver.D) installed side by
side

8.5 Power Cables


This section describes the exteriors, functions, and pin assignments of the power cables in the
APM30H.

8.5.1 EPU05A-06 or EPU05A-08 Power Cable


An EPU05A-06 or EPU05A-08 power cable feeds AC power from external power equipment
into the power system of an APM30H (Ver.E) in a BTS3900A. The maximum length of an
EPU05A-06 or EPU05A-08 power cable is 15 m (49.21 ft).

Exterior
The colors and number of wires in an EPU05A-06 are different from those in an EPU05A-08
power cable. The following figure shows the exteriors of EPU05A-06 and EPU05A-08 power
cables.

The colors and structures of cables vary according to countries and regions. If cables are purchased
locally, the cables must comply with local rules and regulations.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 63


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 8 APM30H Cables

Figure 8-6 Exteriors of cables

(1) OT terminal (M6)

Description
The following table describes EPU05A-06 and EPU05A-08 power cables.

Table 8-6 Cable description

Cable Exterior Cable Wire Wire Color Cable


Specifications

Illustration 1 EPU05A-06 L1 Brown 6 mm2 (0.009


power cable in in.2)
a 220 V AC L2 Black
three-phase
L3 Gray
scenario
N wire Blue
PE Green and

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 64


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 8 APM30H Cables

Cable Exterior Cable Wire Wire Color Cable


Specifications
yellow
Illustration 2 EPU05A-06 L Brown 25 mm2 (0.039
power cable in in.2)
a 220 V AC N wire Blue
single-phase
PE wire Green and
scenario
yellow
Illustration 3 EPU05A-08 L1 Black 25 mm2 (0.039
power cable in.2)
L2 Red
N wire White
PE wire Green

8.5.2 EPU05A-07 or EPU05A-09 Power Cable


An EPU05A-07 or EPU05A-09 power cable feeds AC power from external power equipment
into the power system of an APM30H (Ver.E) in a DBS3900. The maximum length of an
EPU05A-07 or EPU05A-09 power cable is 15 m (49.21 ft).

Exterior
The colors and number of wires in an EPU05A-07 are different from those in an EPU05A-09
power cable. The following figure shows the exteriors of EPU05A-07 and EPU05A-09 power
cables.

The colors and structures of cables vary according to countries and regions. If cables are purchased
locally, the cables must comply with local rules and regulations.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 65


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 8 APM30H Cables

Figure 8-7 Exteriors of cables

(1) OT terminal (M6)

Description
The following table describes EPU05A-07 and EPU05A-09 power cables.

Table 8-7 Cable description

Cable Cable Wire Wire Color Cable


Exterior Specifications

Illustration 1 EPU05A-07 L1 wire Brown 6 mm2 (0.009 in.2)


power cable in
a 220 V AC L2 wire Black
three-phase
L3 wire Gray
scenario
N wire Blue
PE wire Green and

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 66


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 8 APM30H Cables

Cable Cable Wire Wire Color Cable


Exterior Specifications
yellow
Illustration 2 EPU05A-07 L wire Brown 25 mm2 (0.039 in.2)
power cable in
a 220 V AC N wire Blue
single-phase
PE wire Green and
scenario
yellow
Illustration 3 EPU05A-09 L1 wire Black 25 mm2 (0.039 in.2)
power cable
L2 wire Red
N wire White
PE wire Green

8.5.3 SOU Power Cable


The power cable for a service outlet unit (SOU) feeds AC power into the SOU from the AC
OUTPUT port on the EPU or EPS.

Exterior
The following figure shows the exterior of an SOU power cable.

The colors and structures of cables vary according to countries and regions. If cables are purchased
locally, the cables must comply with local rules and regulations.

Figure 8-8 Exterior of an SOU power cable

(1) C13 connector (2) OT terminal (M4)

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 67


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 8 APM30H Cables

Description
The following table describes an SOU power cable.

Table 8-8 Cable description

Wire Color Label Cable Specifications

W1 Brown L 2.5 mm2 (0.004 in.2)


W2 Green and yellow PE
W3 Blue N

8.5.4 Power Cable for an AC Heater


The power cable for an AC heater feeds AC power into the AC heater in an APM30H or
TMC11H from power equipment.

Power Cable for an AC Heater


Exterior
The following figure shows the exterior of a power cable for an AC heater.

The colors and structures of cables vary according to countries and regions. If cables are purchased
locally, the cables must comply with local rules and regulations.

Figure 8-9 Exterior of a power cable for an AC heater

(1) C13 connector (2) OT terminal (M4)

The L wire, PE wire, and N wire of a power cable for an AC heater are brown, green and yellow, and
blue, respectively, as shown in the preceding figure.

Description

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 68


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 8 APM30H Cables

The following table describes a power cable for an AC heater.

Table 8-9 Cable description

Cabinet Type Power Equipment Cable


Specif
ication
s
APM30H (Ver.B), APM30H (Ver.C), EPS or EPU in a cabinet 1.5
APM30H (Ver.D), or APM30H (Ver.E) mm2
(0.0023
in.2)
Transmission cabinet TMC11H (Ver.B), EPS or EPU in an APM30H 1.5
TMC11H (Ver.C), TMC11H (Ver.D), or (feeding power into the AC mm2
TMC11H (Ver.E) in an AC scenario junction box in a TMC11H) (0.0023
in.2)
Power cabinet TMC11H (Ver.B), TMC11H External power equipment 1.5
(Ver.C), TMC11H (Ver.D), or TMC11H mm2
(Ver.E) in a DC scenario (0.0023
in.2)

Power Transfer Cable for an AC Heater


The power transfer cable for an AC heater feeds AC power into the AC heater from the EPU
in an APM30 (Ver.D_A1) by connecting the AC power output terminal on the EPU to the
transfer terminal on the AC heater.
The following figure shows a power transfer cable for an AC heater in an APM30
(Ver.D_A1).

Figure 8-10 Exterior of a power transfer cable for an AC heater

(1) OT terminal (M4), 1 mm2 (0.0016 in.2) (2) Cord end terminal

8.5.5 FAN 02E Power Cable


A FAN 02E power cable feeds -48 V DC power into the FAN 02E in an APM30H (Ver.E) or
TMC11H (Ver.E).

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 69


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 8 APM30H Cables

Exterior
The RTN(+) and NEG(-) wires of a FAN 02E power cable are black, as shown in the
following figure.

Figure 8-11 Exteriors of cables

(1) 3V3 connector (2) EPC4 connector

Description
The following table describes a FAN 02E power cable.

Table 8-10 Cable description

Cable X1 End X2 End


W1 X1.A1 X2.B1
W2 X1.A3 X2.B2

8.5.6 Power Cable for an AC Junction Box


The power cable for an AC junction box feeds AC power into the AC junction box from
power equipment. The AC power is then converted by the AC junction box into four AC
outputs, which are provided for other components such as the heater or heating film. This
section also describes the specifications of power cables for AC junction boxes in different
cabinets.

Exterior
The following figure shows the exteriors of power cables for AC junction boxes.

The colors and structures of cables vary according to countries and regions. If cables are purchased
locally, the cables must comply with local rules and regulations.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 70


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 8 APM30H Cables

Figure 8-12 Exteriors of cables

(1) OT terminal (M4) (2) Cord end terminal

The L wire is brown and the N wire is blue, as shown in the preceding figure.

Description
The following table describes power cables for AC junction boxes.

Table 8-11 Cable description


Cable Cabinet Type Power Equipment Cable
Exterior Specifications
Illustration APM30H (Ver.B), EPS 01, EPU03A, or 1.5 mm2 (0.0023
1 APM30H (Ver.C), EPU05A in.2)
APM30H (Ver.D), or
APM30H (Ver.E)
TMC11H (Ver.B), EPS 01, EPU03A, or 1.5 mm2 (0.0023
TMC11H (Ver.C), EPU05A in an APM30H in.2)
TMC11H (Ver.D), or (feeding power into the AC
TMC11H (Ver.E) junction box in the APM30H)
IBBS700D or EPU05A in an APM30H 1.5 mm2 (0.0023
IBBS700T (Ver.D) (feeding power into in.2)

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 71


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 8 APM30H Cables

Cable Cabinet Type Power Equipment Cable


Exterior Specifications
the AC junction box in the
APM30H)
Illustration BTS3900AL AC PDU05A-01 2.5 mm2 (0.004
2 cabinet in.2)
Illustration BTS3900AL DC PDU05A-01 in a BTS3900AL 2.5 mm2 (0.004
3 cabinet AC cabinet (feeding power in.2)
into the AC junction box in
the BTS3900AL AC cabinet)
IBBS700D or PDU05A-01 in a BTS3900AL 2.5 mm2 (0.004
IBBS700T AC cabinet (feeding power in.2)
into the AC junction box in
the BTS3900AL AC cabinet)
IBBS300D EPU05A in an APM30H 2.5mm2
(Ver.D) or APM30H (Ver.E)
(feeding power into the AC
junction box in the APM30H)

8.6 Signal Cables


This section describes the exteriors, functions, and pin assignments of the signal cables in the
APM30H.

8.6.1 ELU Signal Cable


An electronic label unit (ELU) signal cable transmits the cabinet type to a monitoring board in
the cabinet.

Exterior
The following figure shows the exterior of an ELU signal cable.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 72


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 8 APM30H Cables

Figure 8-13 Exterior of an ELU signal cable

(1) RJ45 connector (2) 4-pin connector

Description
The following table describes the ELU signal cable shown by illustration 1 in the preceding
figure.

Table 8-12 Description of the ELU signal cable shown by illustration 1 in the preceding figure

X1 End X2 End Color Wire Type


X1.1 X2.1 White Twisted pair
X1.2 X2.2 Orange
X1.3 X2.3 White Twisted pair
X1.6 X2.6 Green
X1.5 X2.5 White Twisted pair
X1.4 X2.4 Blue
X1.7 X2.7 White Twisted pair
X1.8 X2.8 Brown

The following table describes the ELU signal cable shown by illustration 2 in the preceding
figure.

Table 8-13 Description of the ELU signal cable shown by illustration 2 in the preceding figure

X1 End X2 End Color Wire Type


X1.1 X2.1 Orange Twisted pair

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 73


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 8 APM30H Cables

X1 End X2 End Color Wire Type


X1.4 X2.2 White
X1.5 X2.3 Blue Twisted pair
X1.3 X2.4 White

In different cabinets, ELU signal cables are connected to different monitoring boards. The
following table lists monitoring boards to which ELUs reports information in different
cabinets.

Table 8-14 Monitoring boards to which ELUs reports information

Cable Exterior Cabinet Monitoring


Board

Illustration 1 BTS3900 (Ver.B) cabinet or BTS3900L (Ver.B) FMUC


cabinet
BTS3900 (Ver.C) cabinet or BTS3900L (Ver.C) FMUE
cabinet
BTS3900 (Ver.D) cabinet or BTS3900L (Ver.D) FMUEA
cabinet
APM30H (Ver.B), TMC11H (Ver.B), RFC CMUA
(Ver.B), IBBS200D (Ver.B), or IBBS200T
(Ver.B)
APM30H (Ver.C), TMC11H (Ver.C), RFC CMUE
(Ver.C), IBBS200D (Ver.C), or IBBS200T
(Ver.C)
APM30H (Ver.D), TMC11H (Ver.D), RFC CMUEA
(Ver.D), IBBS200D (Ver.D), IBBS200T (Ver.D),
or IBBS700D configured with an APM30H
(Ver.D) together
IBBS700T configured with an APM30H (Ver.D) CMUF
together
IBBS300D (Ver.A) or IBBS300T (Ver.A) CCU01D-03
OMB (Ver.C) HEUB
BTS3900AL (Ver.A) cabinet, or IBBS700D or CCU
IBBS700T configured with a BTS3900AL cabinet
together

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 74


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 8 APM30H Cables

Table 8-15 Monitoring boards to which ELUs reports information

Cable Exterior Cabinet Monitoring


Board

Illustration 1 BTS3900 (Ver.B) cabinet or BTS3900L (Ver.B) FMUC


cabinet
BTS3900 (Ver.C) cabinet or BTS3900L (Ver.C) FMUE
cabinet
BTS3900 (Ver.D) cabinet, BTS3900L (Ver.D) FMUEA
cabinet, or IBC10
APM30H (Ver.B), TMC11H (Ver.B), RFC CMUA
(Ver.B), IBBS200D (Ver.B), or IBBS200T
(Ver.B)
APM30H (Ver.C), TMC11H (Ver.C), RFC CMUE
(Ver.C), IBBS200D (Ver.C), or IBBS200T
(Ver.C)
APM30H (Ver.D), TMC11H (Ver.D), RFC CMUEA
(Ver.D), IBBS200D (Ver.D), IBBS200T (Ver.D),
or IBBS700D configured with an APM30H
(Ver.D) together
APM30H (Ver.E) or TMC11H (Ver.E) CCUB
RFC (Ver.E), IBBS200D (Ver.E), IBBS200T CMUH
(Ver.E), or IBBS700D configured with an
APM30H (Ver.E) together
IBBS700T configured with an APM30H (Ver.D) CMUF
or APM30H (Ver.E) together
OMB (Ver.C) HEUB
BTS3900AL (Ver.A) cabinet, or IBBS700D or CCU
IBBS700T configured with a BTS3900AL cabinet
together
Illustration 2 IBBS20D CMUG

8.6.2 Monitoring Signal Cables for Door Status Sensors


A monitoring signal cable for a door status sensor is used to inform the monitoring board of
the door status that is obtained from the door status sensor. Cabinets configured with door
status sensors are as follows: APM30H, TMC11H, RFC, IBBS200D, IBBS200T, IBBS300D,
IBBS300T, IBBS20D, IBBS20D, BTS3900AL cabinet, OMB, OMB (Ver.C), IBBS700D, and
IBBS700T.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 75


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 8 APM30H Cables

Exterior
There are four types of monitoring signal cables for door status sensors, which adapt to
different cabinets. Figure 8-14, Figure 8-15, Figure 8-16, Figure 8-17, and Figure 8-18 show
their exteriors.

Figure 8-14 Exterior of a monitoring signal cable for a door status sensor (1)

Figure 8-15 Exterior of a monitoring signal cable for a door status sensor (2)

 Cable 1 has a 2-pin connector at one end, which is connected to an HPMI. Cable 1 has a bare wire
and a cord end terminal at the other end, which are connected to a door status sensor and a cable
terminal block, respectively.
 Cable 2 has a cord end terminal at each end. The two cord end terminals are connected to the two
ports on one side of a cable terminal block.
 Cable 3 has a bare wire at one end, which is connected to a door status sensor. Cable 2 has a cord
end terminal at the other end, which is connected to a cable terminal block.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 76


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 8 APM30H Cables

Figure 8-16 Exterior of a monitoring signal cable for a door status sensor (3)

 Cable 1 has a 2-pin connector at one end, which is connected to the GATE port on a PMU. Cable 1
has a bare wire and a cord end terminal at the other end, which are connected to a door status sensor
and a cable terminal block, respectively.
 Cable 2 has a bare wire at one end, which is connected to a door status sensor. Cable 2 has a cord
end terminal at the other end, which is connected to a cable terminal block.
 Cable 3 has a cord end terminal at each end. The two cord end terminals are connected to the two
ports on one side of a cable terminal block.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 77


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 8 APM30H Cables

Figure 8-17 Exterior of a monitoring signal cable for a door status sensor (4)

 Cable 1 has a bare wire at one end, which is connected to the GATE port on a CCUB. Cable 1 has a
bare wire and a cord end terminal at the other end, which are connected to a door status sensor and a
cable terminal block, respectively.
 Cable 2 has a bare wire at one end, which is connected to a door status sensor. Cable 2 has a cord
end terminal at the other end, which is connected to a cable terminal block.
 Cable 3 has a cord end terminal at each end. The two cord end terminals are connected to the two
ports on one side of a cable terminal block.

Figure 8-18 Exterior of a monitoring signal cable for a door status sensor (5)

(1) Bare wire (2) 2-pin connector

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 78


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 8 APM30H Cables

Description
In different cabinets, monitoring signal cables for door status sensors are connected to
different monitoring boards. The following table lists monitoring boards that collect door
status information in different cabinets.

Table 8-16 Types of monitoring signal cables for door status sensors

Cable Cabinet Monitoring Board


Exterior

Figure 8-14  RFC (Ver.B) CMUA


 TMC11H (Ver.B)
 IBBS200D (Ver.B) or IBBS200T (Ver.B)
 RFC (Ver.C) CMUE
 TMC11H (Ver.C)
 IBBS200D (Ver.C) or IBBS200T (Ver.C)
 RFC (Ver.D) CMUEA
 TMC11H (Ver.D)
 IBBS200D (Ver.D) or IBBS200T (Ver.D)
 IBBS700D configured with an APM30H
(Ver.D) together
 RFC (Ver.E) CMUH
 IBBS200D (Ver.E) or IBBS200T (Ver.E)
TMC11H (Ver.E) CCUB
IBBS700T configured with an APM30H (Ver.D) CMUF
or APM30H (Ver.E) together
IBBS300D (Ver.A) or IBBS300T (Ver.A) CCU01D-03
OMB HEUA
OMB (Ver.C) HEUB
 BTS3900AL (Ver.A) CCU
 IBBS700D or IBBS700T configured with a
BTS3900AL cabinet together
Figure 8-15 APM30H (Ver.B) and APM30H (Ver.C) HPMI
Figure 8-16 APM30H (Ver.D) PMU 11A
Figure 8-17 APM30H (Ver.E) CCUB
Figure 8-18 IBBS20D CMUG

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 79


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 8 APM30H Cables

8.6.3 Monitoring Signal Transfer Cable for Fans in Front Doors


A monitoring signal cable for a fan in a front door feeds power into the fan in the front door of
an APM30H, TMC11H, BTS3900AL cabinet, or IBBS700T. It also reports fan monitoring
signals to the monitoring board in the cabinet.

Exterior
The following figure shows the exteriors of monitoring signal transfer cables for fans in front
doors.

Figure 8-19 Exteriors of monitoring signal transfer cables for fans in front doors

(1) 4-pin connector (2) Interconnection terminal (3) 4-pin male connector
(4) 4-pin female connector (5) 4-pin male connector (one row) -

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 80


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 8 APM30H Cables

Cable Type
The following table lists the types of monitoring boards to which monitoring signals are
reported. Monitoring cables vary according to boards.

Table 8-17 Cable type

Cable Exterior Cabinet Monitoring Board to


Which Monitoring
Signals Are Reported

Illustration 1 APM30H (Ver.B) or CMUA


TMC11H (Ver.B)
APM30H (Ver.C) or CMUE
TMC11H (Ver.C)
Illustration 2 APM30H (Ver.D) or CMUEA
TMC11H (Ver.D)
APM30H (Ver.E) or CCUB
TMC11H (Ver.E)
Illustration 3 BTS3900AL CMUF in a front door
Illustration 4 IBBS700T CMUF in a front door

Description
The following table describes monitoring signal transfer cables for fans in front doors.

Table 8-18 Monitoring signal transfer cables for fans in front doors

Cable X1 End X2 End Color


W1 X1.1 X2.1 Black
W2 X1.2 X2.2 Black
W3 X1.3 X2.3 Black
W4 X1.4 X2.4 Black

8.6.4 PMIU-CCUB Monitoring Signal Cable


A PMIU-CCUB monitoring signal cable connects a PMIU and a CCUB. It transmits the
RS485 signals collected by the PMIU to the CCUB, which then forwards the signals to the
BBU.

Exterior
PMIU-CCUB monitoring signal cables are black. The following figure shows the exterior of a
PMIU-CCUB monitoring signal cable.

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 81


Copyright © Huawei Technologies Co., Ltd.
APM30H (Ver.E)
Product Description 8 APM30H Cables

Figure 8-20 Exterior of a PMIU-CCUB monitoring signal cable

(1) RJ45 connector

Description
The following table describes a PMIU-CCUB monitoring signal cable.

Table 8-19 PMIU-CCUB monitoring signal cable

X1 End X2 End Color Wire Type


X1.1 X2.1 White Twisted pair
X1.2 X2.2 Orange
X1.3 X2.3 White Twisted pair
X1.4 X2.4 Green
X1.5 X2.5 White Twisted pair
X1.6 X2.6 Blue
X1.7 X2.7 White Twisted pair
X1.8 X2.8 Brown

Issue 01 (2016-3-16) Huawei Proprietary and Confidential 82


Copyright © Huawei Technologies Co., Ltd.