Compact switchgear assemblies

HYpact

Volker JANICH
02/11/2010

GRID
Agenda

1st topic General layout Page 3

2nd topic Circuit breaker Page 6

3rd topic Disconnector / earth switch Page 11

4th topic Instrument transformers, cable sealing ends Page 18

5th topic Indicating devices, interlocking Page 23

6th topic Transportation, installation, maintenance Page 29

AGK-CSC [HYpact product] EN 06_2010- P 2


General layout

Compact switchgear assembly according to new standard IEC


62271-205: Mixed technology switchgear

1 Circuit breaker
2 Disconnector / Earth switch
3 Bushing current transformer
2
3
1
4 Drive mechanism
4 5 Central control cubicle
5
6 Steel stands
6

AGK-CSC [HYpact product] EN 06_2010- P 3


General layout

HYpact consist of three separate gas


compartments
− Each houses all switching
devices for one phase
• Circuit breaker
• Disconnector(s)
• Earth switch(es)
Bushing current transformer
− Placed around the disconnector
/ earth switch
Installed on two steel stands

AGK-CSC [HYpact product] EN 06_2010- P 4


General layout

Single cast design


− Avoid not always used openings
− Reduced number of sealings
and gaskets

Thus low leakage

AGK-CSC [HYpact product] EN 06_2010- P 5


Circuit breaker

Double motion principle ensures low stress, thus increased


reliability
Original design for dead tank circuit breakers
− Double motion breaking chamber is used with several thousend circuit
breakers for more than ten years
− Reduced energy requirement leads to increased reliability

E = ½ m v²

AGK-CSC [HYpact product] EN 06_2010- P 6


Circuit breaker

Circuit breaker dive mechanism from


ALSTOM’s FK3-1 range
− One hundred thousend units in
service
Helical compression springs for opening
and closing
− Most reliable spring design
Drive cubicle may double as central
termination box
− Centralized local operation

AGK-CSC [HYpact product] EN 06_2010- P 7


Circuit breaker

Interpole connection by short rotating


linkage
− Low energy dissipation
− Four rotationally stressed
sealings only
One drive coupling linkage
− Easy to connect

AGK-CSC [HYpact product] EN 06_2010- P 8


Circuit breaker

SF6 pipes with check valves located


above tanks
− Easy decoupling of gas
compartments
Central filling point with check
valves and DN8 coupling
− Allow access for topping up
gas and gas sampling
− Operator-friendly
− Safe access

AGK-CSC [HYpact product] EN 06_2010- P 9


Circuit breaker

Overpressure relief device at


rear end
− By means of
expansion springs
− Controlled blow-out
direction

AGK-CSC [HYpact product] EN 06_2010- P 10


Disconnector / Earth switch

Three position switch based on GIS technology

Connected Neutral Earthed


− Disconnector − Disconnector − Disconnector
closed open open
− Earth switch − Earth switch − Earth switch
open closed
open

AGK-CSC [HYpact product] EN 06_2010- P 11


Disconnector / Earth switch

Switching positions earthing through the breaker

CB open CB open CB closed CB open CB open CB closed


DS open DS closed DS closed DS closed DS open ES closed
ES closed Line
Earthing earthed
prepared

AGK-CSC [HYpact product] EN 06_2010- P 12


Disconnector / Earth switch

Three position switch based on GIS technology

Connected Neutral Earthed


− Disconnector − Disconnector − Disconnector
closed open open
− Earth switch − Earth switch − Earth switch
open open closed

AGK-CSC [HYpact product] EN 06_2010- P 13


Disconnector / Earth switch

Three position mechanism ME1-3

AGK-CSC [HYpact product] EN 06_2010- P 14


d1

Disconnector / Earth switch

Three position mechanism ME1-3R


Padlockable point of isolation
Motorized operation to „prepared
for earthing“- position
Position indicators
Optional 10A - auxiliary switch for
high impedance protection
schemes (Class 1 acc. IEC 62271-1 table 6)

AGK-CSC [HYpact product] EN 06_2010- P 15


Folie 15

d1 UK-specific, hidden in the standard presentation


dnotroff; 30.07.2010
Disconnector / earth switch

Disconnector / Earth switch


linkage
− Clearly separated from
other linkages

Position indicator directly


mounted on DS / ES input
shaft
− Allows for direct
detection of the
switching status

AGK-CSC [HYpact product] EN 06_2010- P 16


Disconnector / Earth switch

Drive mechanisms mounted on steel


stands
− No need for assembly at site
Drives already connected to central
control cubicle
− Connection made by weather-
proof Harting plugs
− Yet, not need to connect drive
wiring at site

AGK-CSC [HYpact product] EN 06_2010- P 17


Current transformer

Epoxy cast resin design


− Can be mounted on drive side
(standard), opposite side or both
sides of the circuit breaker
− Belated assembly possible (slip-over
design)
− Up to 5 multi-ratio cores per side
(depending on CT-specification)
− Integrated cable connection box 16
terminals (6mm²)
− Option: Cabling in separate pre-wired
CT-terminal box

AGK-CSC [HYpact product] EN 06_2010- P 18


Current transformer

Air insulated design


− Can be mounted on drive side
(standard), opposite side or both
sides of the circuit breaker
− Position above or below
disconnector/earth switch module
− Up to 5 multi-ratio cores per side
(depending on CT-specification)
− Aluminium covered
− Cabling in separate pre-wired CT-
terminal box

AGK-CSC [HYpact product] EN 06_2010- P 19


Voltage transformer (SF6 – type)

− With primary disconnector for


high voltage tests

− Without primary disconnector

AGK-CSC [HYpact product] EN 06_2010- P 20


Voltage transformer

Flexible design with multi-connection housing


SF6 to air interface

SF6 to cable interface

AGK-CSC [HYpact product] EN 06_2010- P 21


Cable sealing ends

Dry type and fluid type connectors available


1 Pluggable current contact
2 Stress-cone in silicone rubber
1
3 Insulator in cast resin
2
3 4 Inlet with inner spring assembly
4
5 Clip mounting
6 Screen connection
5
7 Cable clamp
6
8 XLPE cable
7

AGK-CSC [HYpact product] EN 06_2010- P 22


Cable sealing ends

Flexibility due to adaptable housing

Two different housings


− 470mm for dry type
connections
− 760mm for fluid type
connections
Female contacts of various suppliers
can be mounted

AGK-CSC [HYpact product] EN 06_2010- P 23


Indicating devices / Interlocking

SF6 density monitor


− Temperature compensated
reading on colour dial
− Electrical two-step alarm
• warning
• Lockout
Combined mimic diagram
− Circuit breaker on / off
− Disconnector open / close
− Earthing switch open / close

AGK-CSC [HYpact product] EN 06_2010- P 24


Indicating devices / Interlocking

spring condition indicator


− Symbol „charged“
− Symbol „discharged“

Mechanical circuit breaker operation


counter

AGK-CSC [HYpact product] EN 06_2010- P 25


d2

Indicating devices / Interlocking

UK-specific SF6 density monitor


− MPa/bar scale
− Temperature compensated
reading on colour dial
− Electrical two-step alarm
• warning
• Lockout
UK-specific circuit breaker position
indicator
− Coloured ON / OFF signs

AGK-CSC [HYpact product] EN 06_2010- P 26


Folie 26

d2 dnotroff30.07.2010
UK-specific, hidden in the standard presentation
dnotroff; 30.07.2010
d3

Indicating devices / Interlocking

UK-specific position indicator for


disconnector and earth switch
− Disconnector ON / OFF
− Earth switch ON / OFF

AGK-CSC [HYpact product] EN 06_2010- P 27


Folie 27

d3 dnotroff30.07.2010
UK-specific, hidden in the standard presentation
dnotroff; 30.07.2010
d4

Indicating devices / Interlocking

UK-specific spring condition


indicator
− Spring charged
− Spring discharged

Mechanical circuit breaker operation


counter

AGK-CSC [HYpact product] EN 06_2010- P 28


Folie 28

d4 dnotroff30.07.2010
UK-specific, hidden in the standard presentation
dnotroff; 30.07.2010
Indicating devices / Interlocking

Push buttons for local operation of circuit breaker and


disconnector / earth switch
padlockable Local / (Off) / Remote selector switch (option)
Position indicators (option)
− Green / red illumination (LED‘s)
− Mechanical Semafor indicators

AGK-CSC [HYpact product] EN 06_2010- P 29


Indicating devices / Interlocking

Intrinsic interlock between disconnector and Earth switch


Electrical interlocking between circuit breaker and disconnector /
earthing switch
− disconnector / earthing switch must not open or close when the
circuit breaker is closed
− disconnector / earthing switch can only operate when the circuit
breaker is open
− Cicuit breaker must not open or closed when the disconnector /
earthing switch is operating
− Circuit breaker shall automatically close when the earth switch‘s
function is completed

AGK-CSC [HYpact product] EN 06_2010- P 30


Transportation, installation, maintenance

Two packing units only

Sea transport Road transport

AGK-CSC [HYpact product] EN 06_2010- P 31


Transportation, installation, maintenance

Two packing units only

Support
− Steel stands
− Drive mechanisms
• Mounted on steel stands
− Central control cubicle (if
applicable)
• Mounted on steel stands
Three phase switchgear unit
− Completely assembled and
factory-tested
− SF6 piping completely mounted
− Interphase linkages installed and
adjusted
− CT connection box, pre-wired

AGK-CSC [HYpact product] EN 06_2010- P 32


Transportation, installation, maintenance

HYpact is designed for fast and easy site erection

To do at site
− Coupling of drive rods
− Mounting of current transformer
connection box
− SF6 density monitor wire
connection
− Top up gas to service pressure
− Commissioning test

No special tool required

AGK-CSC [HYpact product] EN 06_2010- P 33


Transportation, installation, maintenance

HYpact maintenance cycle based on GIS-, not on AIS-


disconnector cycle
Due to compactness, HYpact‘s circuit breaker cannot be isolated with disconnectors
Conventional AIS disconnectors also cannot be safely isolated without switching off HV
lines or busbars
Maintenance of conventional AIS disconnectors and earthing switched required after
several years, after every short circuit

With HYpact, conventional AIS disconnectors and earthing switches become obsolete,
thus no frequent DS/ES maintenance required anymore
HYpact disconnectors and earthing switches are based on GIS technology
Long maintenance cycles as of GIS reached

AGK-CSC [HYpact product] EN 06_2010- P 34


Transportation, installation, maintenance

Inspection
− Visual inspection on occasional base during station tours, latest after 6
years
• Corrosion
• SF6 gas pressure
• Ventilation ports and heating system
Maintenance
− Every 12 years
• Gas quality
• Cable joints and connecting linkages
• Function of electric control circuits
• Operation time
• Contact resistance
Reconditionning (normal service conditions)
− After 2.500-3000 operations at rated normal current or
− After a total current, i.e. 15 x rated breaking current

AGK-CSC [HYpact product] EN 06_2010- P 35


www.alstom.com
Circuit breaker

Presentation title - 01/01/2010 - P 37


Disconnector / Earth switch

Presentation title - 01/01/2010 - P 38