You are on page 1of 28

EASUN REYROLLE

SEL-311 Relay Family


EASUN REYROLLE

SEL-311 Relays

 Numerous Protection, Monitoring, and


Control Elements
 Six Setting Groups
 Enhanced SELOGIC® Control Equations
for Custom Schemes
EASUN REYROLLE

The SEL-311 Family of Relays

 SEL-311C
 SEL-311B
 SEL-311A
EASUN REYROLLE

SEL-311C Relay Functions

 Four Zones of Distance Protection


 Phase and ground mho
 Ground quadrilateral
 Two forward and two reversible zones

 Phase, Neg.-Seq., Ground Overcurrent


EASUN REYROLLE

SEL-311C Protection Functions


 Automatic Reclosing
 Synchronism Check
 Under / Over Voltage (+ VE, - VE, Zero
Sequence)
 Under / Over Frequency (6 Stage)
EASUN REYROLLE

SEL-311C Relay Functions

 Out of Step / Power Swing

 Support All Traditional Pilot Tripping


Scheme
EASUN REYROLLE

SEL-311B Protection Functions

 Three Zones of Distance Protection


 Phase and ground mho
 One reversible zone

 Zone 1 Extension
 Phase, Neg.-Seq., Ground Overcurrent
EASUN REYROLLE

SEL-311B Protection Functions

 Automatic Reclosing
 Synchronism Check
 Undervoltage / Overvoltage
 Direct Transfer Trip
EASUN REYROLLE

SEL-311A Protection Functions

 Two Zones of Distance Protection


 Phase and ground mho

 Phase and Ground Overcurrent


 Direct Transfer Trip
EASUN REYROLLE

Common SEL-311 Family Features


EASUN REYROLLE

SEL-311 Relay Functions

 Loss-of-Potential

 Switch-Onto-Fault
EASUN REYROLLE

SEL-311 Relay Functions

 Independent or Common Phase and


Ground Distance Timing
 CCVT Transient Overreach Security
 Load Encroachment
EASUN REYROLLE

SEL-311 Relays

 Advance Monitoring and Reporting


Functions
 Complete metering
 SER and improved event reports
EASUN REYROLLE

SEL-311 Monitoring and Metering


Functions
 Breaker Monitor

 Station DC Battery Monitor


 Demand / Energy Metering
 Maximum / Minimum Metering
 Fault Locator
EASUN REYROLLE
Instantaneous Metering
EASUN REYROLLE
Demand Metering
EASUN REYROLLE

Energy Metering
EASUN REYROLLE

Maximum / Minimum Metering


EASUN REYROLLE

SEL-311 Relay Custom Logic

 Use SELOGIC Control Equations to Set


 Trip Logic
 TR, TRSOTF, TRCOMM,
 Event Report Logic
 SER
EASUN REYROLLE

SEL-311 Relay Custom Logic

 Use SELOGIC Control Equations to Set


 SELOGIC Variables
 SV1 - SV16
 Output Contact Logic
 OUT101 – OUT107
EASUN REYROLLE

SEL-311 Relay
Enhanced SELOGIC Control Equations

 Combine Relay Logic Elements Using


 Parentheses “( )”
 AND “*”, OR “+”, and NOT “!”
 Rising edge “/” and falling edge “\”
 Examples
 TR = M1P + Z1G + M2PT + Z2GT + 51GT
 SV1 = (/M2P + /Z2G) * 52A + \3PO
 52A = IN101
EASUN REYROLLE

Sequential Events Recorder


 Create Custom SER Events Using Relay
Word Bits
 Create SER Reports to Date / Time
Stamp Selected Events
 Store up to 512 Sequential Events in
Nonvolatile Memory
EASUN REYROLLE

Event Reporting
 Long Event Report
 Four 180-cycles, Eleven 60-cycles, twenty-
three 30-cycles, or forty-four 15-cycles
reports
 Settable pre-fault length
 Includes Voltage, Current, I/O, Digital, and
Communication Elements
EASUN REYROLLE

Summary Event Report


 Automatic Summary Report
 Provides pre-fault and fault voltages
and currents
 Time of trip and time of close
 Breaker status
 Targets and recloser status
 Setting group and frequency
EASUN REYROLLE

Summary Event Report


SEL-311C POTT Date: 10/11/99 Time: 15:04:03.247
EXAMPLE: BUS B, BREAKER 3

Event: BC T Location: 9.82 Trip Time: 15:04:03.247


#: 01228 Shot: Freq: 60.02 Group: 6 Close Time: --:--:--.---
Targets: SOTF Breaker: Open

PreFault: IA IB IC IP IG 3I2 VA VB VC
MAG(A/kV) 994 994 992 0 0 2 131.050 131.140 131.160
ANG(DEG) -10.82-130.91 109.18 163.00-107.00 23.00 0.00 -120.12 119.94
Fault:
MAG(A/kV) 994 8015 7086 1 16 12644 131.020 84.970 89.840
ANG(DEG) -9.48-170.86 11.84 73.00 76.58 95.00 1.29 -136.00 141.22
EASUN REYROLLE
EASUN REYROLLE

SEL-311 Relay Communications

 Front-Panel EIA-232 Serial Port


 Two Rear-Panel EIA-232 Serial Ports,
One with IRIG
 Rear-Panel EIA-485 Multidrop Port with
IRIG
EASUN REYROLLE

SEL-311 Relay Communications


 Available Protocols
 SEL-ASCII (SEL)
 Distributed port switch (LMD)
 Distributed Network Protocol (DNP 3.00
Level 2 Slave)
 MIRRORED BITS (MBA, MBB, MB8A,
MB8B)
 Baud Rate: 300 to 38400