AL-BEDHAN SEWER PIPE CALCULATIONS

Pipe No 1

Line Length = 60 m = 0.06 km Qinf = 0.0173611111 l/sec

Pop. = 67 capita Houses no = 3 House


House cap = 10 capita
Qrate = 460 l/cap/day Pop.now = 30 capita
Pop. 25 year = 67 capita
P.F. = 3.00
0.9xQrateXPop
24x60x60

Qaver = = 0.30 l/sec

Qmax = P.F.* Qaver +Qinf = 1.80 l/sec

Dproposed = 254 mm GRP Dinner = 254 mm

Sproposed = 0.20 ‰ n = 0.013

Vfull = )2/3* (S)1/2 = 0.17 m/sec

Qfull = 3.14* *Vfull = 8.77 l/sec

Qmax/Qfull = 0.21 OK<0.8


Vact/Vfull = 0.79

dmax/Dfull = 0.31 OK<0.75 from chart

Vacu = 0.14 m/sec CHANGE SLOOK<2.47 m/s

Dreq. = 254 mm Sreq. = 0.20 %


CHECK TANK
Qmax= 30000 m3/day
Qmax= 20.83333 m3/min c= 9 mwl= 0.6 m
pipeD = 0.7 6.6667
length= 2.9 width= 2.9
𝑇=60/6=
𝑇=60/� T= 6.6 𝑚𝑖�
6.6667
66
assume Nomber of pumps= 2 operat
66 1 as stand by TOTAL PU 3
Qmax of one pump= 10.42 m3/min 66
�=(𝑄∗𝑇)/4 67 m3
�= 17.36

area of cross secton= �=𝐿∗𝑊= 8.41 m3


actve volume= �=�/�= 2.06 m

HWL=minwater level+actve volume+inletpipe diam.= 0.6 + 2.06 + 0.7 = 3.36 m


the depth of inlet pipe invert from sum 1.75 m
Elevaton of INETPIPE =MANHOLE LVEL-SLOPOFPIPE*LENGTH= -0.22
SUMP ELEVATION=ELINLETPIPE-1.75= -1.97 m HWL= 1.39 m
pipe crown level= 0.48 < HWL= 1.39

max d/D in pipe = 0.525


ELV .of max d/D= 0.305 < HWL= 1.39 THEN THE WATER DEPTH IN MANHOLE= 1.61