You are on page 1of 36

Product AquaEdge™

23XRV
Data High-Efficiency Variable Speed Screw Chiller
with Greenspeed® Intelligence
50/60 Hz
HFC-134a

250 to 550 Nominal Tons (879 to 1934 Nominal kW)

Carrier’s AquaEdge™ 23XRV chiller


with Greenspeed® intelligence is the
world’s first integrated variable speed,
water-cooled, screw chiller.
It incorporates significant break-
throughs in water-cooled chiller tech-
nology to provide excellent reliability
and achieve superior efficiencies at
true operating conditions without com-
promising the environment.
The 23XRV chiller provides:
• Variable speed, positive
displacement screw compressor.
• Air Conditioning, Heating, and
Refrigerant Institute (AHRI) certified
efficiencies to 0.299 kW/ton (AHRI
IPLV).
• Chlorine-free HFC-134a refrigerant.
• IEEE-519 compliance for harmonic
distortion with units equipped with
the LF-2 variable frequency drive
(VFD).
• An ideal solution for constant and
variable flow pumping systems.

Features/Benefits
Quality design and con-
struction make the
AquaEdge 23XRV chillers the
best choice for modern,
efficient chilled water plants.
a23-211ef
23XRV Product reliability
(UNIT WITH R COMPRESSOR, LF-2 VFD SHOWN)
The 23XRV chiller uses proven tech-
nology from Carrier’s existing line of
AquaEdge chillers along with innova-

SEISMICOMPLIANT* tions that increase reliability. The


23XRV compressors are designed for
* Meets IBC 2006, ASCE-7-05, CBC 2007, and OSHPD seismic requirements. extremely high reliability. The ad-
vanced tri-rotor compressor features a
balanced rotor geometry and shorter
®
2008 AHR EXPO
screw lengths, resulting in vastly re-
INNOVATION duced compressor bearing loads and a
minimum L10 compressor bearing life
AWARD in excess of 500,000 hours when op-
erated at AHRI conditions.
WINNER – Green Building

 Carrier Corporation 2013 Form 23XRV-7PD


Features/Benefits (cont)
Variable speed capacity control elimi- input power to the chiller be lost, the 0.99 power factor — The Aqua-
nates slide valves, their associated loss- system design assures proper lubrica- Edge 23XRV chiller can operate at up
es, and their potential failure modes. tion of the bearings during coast down. to 0.99 displacement power factor
Component count (both rotating and Small footprint — The AquaEdge (with LF-2 VFD), which helps building
total) has been minimized, assuring 23XRV chiller’s positive pressure owners avoid power factor penalties
maximum reliability under a wide design reduces the chiller size by up and decreases electrical losses in cables
range of operating conditions. to 35% compared to negative-pressure and transformers. High power factor
designs. Extremely high compression may also reduce KVA requirements,
High efficiency saving electrical system costs on new
efficiencies allow for compact,
Per AHRI 550/590, chillers operate at high-efficiency chillers that require less projects or freeing up electrical re-
design conditions less than one percent mechanical room floor space. sources on existing systems operating
of the time. As a result, superior part near their maximum capacity.
load efficiency is required for today’s Constant or variable evaporator
flow — The 23XRV chiller combines Refrigerant-cooled VFD — Refrig-
chilled water applications. The Aqua- erant cooling of the VFD minimizes
Edge™ 23XRV screw chiller maximizes the advantages of positive displace-
ment compression with variable speed VFD size and ensures proper cooling
chiller efficiency by optimizing com- of the transistors for extended life.
pressor operation. Electric power con- capacity control. This process provides
a chiller that reacts substantially better Using R-134a refrigerant instead of
sumption drops dramatically when the
than chillers equipped with inlet guide water also eliminates costly mainte-
motor speed slows. The 23XRV screw nance associated with the water cool-
chiller delivers industry-leading inte- vanes or slide valves. This allows for
easier transition when bringing addi- ing pump, heat exchanger and rubber
grated part load values (IPLV) in an ex-
tional chillers on line in multiple chiller tubing used with water-cooled VFDs.
tremely broad range of applications
and climates. plants and eliminates any possibility of Optional seismic kit — A seismic
surge, regardless of the changes in the isolation package is available to meet
Respect for the environment system. International Building Code and ASCE
Carrier has long been committed to Low harmonic distortion option 7 seismic qualification requirements in
the environment and its sustainability. (with LF-2 VFD) — The AquaEdge concurrence with ICC ES AC156 Ac-
The AquaEdge 23XRV screw chillers 23XRV chiller will generate less than ceptance Criteria for Seismic Qualifica-
provide our customers with a high- 5% total harmonic distortion at the in- tion by Shake-Table Testing of Non-
efficiency, chlorine-free, long-term put to the VFD (variable frequency structural Components and Systems.
solution unaffected by refrigerant drive) without the use of any external Semi-hermetic motor — The Aqua-
phase outs. Carrier’s decision to utilize filters or line reactors. This assures the Edge 23XRV chiller utilizes motors
non-ozone depleting HFC-134a refrig- VFD alone cannot exceed IEEE-519 that are hermetically sealed from the
erant provides our customers with a standard for distortion at the point of machine room. Cooling is accom-
safe and environmentally balanced common coupling. Ultra-low harmon- plished by spraying liquid refrigerant
product without compromising effi- ics can eliminate need for complicated on the motor windings. This highly ef-
ciency. In addition, HFC-134a was harmonic system studies. ficient motor cooling method results in
given an A1 safety rating by ASHRAE Low starting current (inrush) — cooler-running motors than could be
(American Society of Heating, realized with air-cooled designs of the
The inrush current is limited to the
Refrigerating and Air-Conditioning chiller full load amps (rated load same type.
Engineers), meaning that it is the safest amperes). No other starting means can In addition, Carrier’s semi-hermetic
refrigerant available.
equal this level of starting current. The design eliminates:
Quality design combination of low current and ultra- • Compressor shaft seals that require
Positive displacement compres- low harmonics can reduce backup maintenance and increase the likeli-
sion — Positive displacement com- generator size requirements. hood of refrigerant leaks.
pression ensures stable operation
under all load conditions without the
possibility of compressor surge. Table of contents
Superior oil management/cold Page
condenser water operation — All Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
AquaEdge 23XRV chillers regulate oil Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
temperature, viscosity and pressure. A Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5, 6
patented process assures high quality Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
oil is delivered to the compressor bear- Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
ings by a positive displacement pump. Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Bearing lubrication is assured, allowing Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
continuous operation with cold Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-14
condenser water at all loads. Screw Typical Piping and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
chillers no longer need to rely on dif- Control Wiring Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
ferential system pressure to effectively Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17-23
lubricate the compressor. Should the Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24-33

2
• Machine room cooling requirements input power leads to the VFD provides refrigerant more evenly over the length
associated with air-cooled motors, all unit power. of the vessel for improved efficiency.
which dissipate heat to the mechan- Marine container shipment — The Closely spaced intermediate sup-
ical room. compact design allows for open-top port sheets — Support sheets pre-
• High noise levels common with air- container shipment to export destina- vent tube sagging and vibration, there-
cooled motors, which radiate noise tions, ensuring quality while reducing by increasing heat exchanger life.
to the machine room and adjacent shipping cost. Refrigerant filter isolation valves
areas.
Heat exchanger combinations — — These valves allow filter replace-
• Shaft alignment problems that occur
The AquaEdge 23XRV chillers are ment without pumping down the chill-
with open-drive designs during start-
available with a complete line of heat er, reducing service time and expense.
up and operation, when equipment
exchangers, ensuring the best combi- FLASC (flash subcooler) — The
temperature variations cause ther-
nation of chiller components to meet subcooler, located in the bottom of the
mal expansion.
project specific tonnage and efficiency condenser, increases the refrigeration
Positive pressure design — Posi- requirements. One, 2 and 3-pass effect by cooling the condensed liquid
tive pressure designs eliminate the arrangements are available to meet a refrigerant to a lower temperature,
need for costly low pressure contain- wide variety of flow conditions. Nozzle- thereby reducing compressor power
ment devices, reducing the initial cost in-head and marine waterboxes are consumption.
of the system. The AquaEdge™ available to meet 150 psig and
23XRV chiller’s positive pressure de- 300 psig piping requirements. AccuMeter™ system — The
sign ensures that air, moisture and oth- AccuMeter system regulates refrigerant
er performance degrading contami- Heat exchanger features flow according to load conditions,
nants are not sucked inside the chiller. ASME certified construction — An providing a liquid seal at all operating
Purge units and their associated main- independent agency certifies the conditions, eliminating unintentional
tenance are no longer necessary. design, manufacture, and testing of hot gas bypass.
Optional refrigerant isolation all heat exchangers to American Microprocessor controls
valves — The optional refrigerant Society of Mechanical Engineers features
isolation valves allow the refrigerant (ASME) standards, ensuring heat ex-
Direct Digital Product Integrated
to be stored inside the chiller during changer safety, reliability and long life.
The ASME U-stamp is applied to the control (PIC III) — Carrier’s PIC III
shipment from the factory, minimizing provides unmatched flexibility and
start-up time. During servicing, the refrigerant side of the evaporator and
condenser and is applied to the water functionality. Each unit integrates
“in-chiller” storage reduces refrigerant directly with the Carrier Comfort
loss and eliminates time-consuming side of heat exchangers when 300 psig
Network® (CCN) system, providing a
transfer procedures. As a self-contained marine water boxes are provided.
solution to controls applications.
unit, the AquaEdge 23XRV chiller does High performance tubing — Carrier’s
not require additional remote storage AquaEdge chillers utilize advances in heat International Chiller Visual Con-
systems. troller (ICVC) — The ICVC provides
transfer technology, providing compact,
high-efficiency heat exchangers. Tubing an unparalleled ease of operation and
Optional pumpdown unit — Com- can be configured to display English or
bined with the refrigerant isolation with advanced internally and externally
metric values.
valves listed above, the optional pump- enhanced geometry improves chiller per-
down unit eliminates complex connec- formance by reducing overall resistance For convenience, a single display lo-
tions to portable transfer systems, to heat transfer while reducing fouling. cated on the chiller VFD panel displays
thereby reducing service costs. The op- chiller and VFD data. The VGA 320 x
Cooler tube expansion — Cooler
tional pumpdown compressor meets tube expansion at center support 240 element LCD (liquid crystal dis-
Environmental Protection Agency’s sheets prevents unwanted tube move- play) features 4 menu specific soft-
(EPA) vacuum level requirements that keys. The default display offers an
ment and vibration, thereby reducing
mandate minimizing refrigerant emis- the possibility of premature tube fail- all-in-one glance review of key chiller
sions during service. ure. Tube wall thickness is greater at operation data, simplifying the interac-
tion between chiller and user.
Modular construction — The cool- the expansion location, support sheets,
er, condenser, and compressor assem- and end tube sheets in order to provide The display includes 4 standard
blies are bolted together, making Aqua- maximum strength and long tube life. languages:
Edge 23XRV chillers ideally suited for Double-grooved end tube sheet • English
replacement jobs where ease of disas- holes — This design provides a more • Chinese
sembly and reassembly at the jobsite robust seal than single rolled joints, re- • Japanese
are essential. ducing the possibility of leaks between • Korean
Single point power — The 23XRV the water and refrigerant sides of the Other languages are available.
chiller features internal control power chiller. Automatic capacity override —
transformers to provide low voltage Condenser baffle — The baffle de- This function unloads the compressor
power (115 v and 24 vdc) for machine flects hot discharge gas before it con- whenever key safety limits are
controls. Simply connecting the three tacts condenser tubes, reducing tube approached, increasing unit life. This
vibration and wear while distributing feature also allows the machine to

3
Features/Benefits (cont)
operate at reduced capacity, rather Ramp loading — Ramp loading en- can be prevented through password
than shut down, when key safety limits sures smooth pulldown of liquid loop protection. Built-in diagnostic capabili-
are approached. temperature and prevents a rapid ties assist in troubleshooting and rec-
Chilled liquid reset — Reset can be increase in compressor power con- ommend proper corrective action for
accomplished manually or automatical- sumption during the pulldown period. preset alarms, resulting in greater
ly from the building management sys- Automated controls test — The working time.
tem. For a given capacity, reset allows test can be executed prior to start-up Alarm file — This file maintains the
operation at slower compressor to verify that the entire control system last 25 time-and date-stamped alarm
speeds, saving energy when warmer is functioning properly. messages in memory. This function re-
chilled liquid can be used. 365-day real time clock — This duces troubleshooting time and cost.
Demand limiting — This feature lim- feature allows the operator to program Alert file — This file maintains the
its the power draw of the chiller during a yearly schedule for each week, week- last 25 alert messages in memory. This
peak loading conditions. When incor- ends, and holidays. function provides prognostic informa-
porated into the Carrier Comfort Occupancy schedules — Schedules tion and corrective actions that can
Network® building automation system, can be programmed into the controller avoid unit shutdown.
a red line command holds chillers at to ensure that the chiller operates Configuration data backup —
their present capacity and prevents any when cooling is required and remains Non-volatile memory provides
other chillers from starting. If a load off when not needed by the tenants or protection during power failures and
shed signal is received, the compres- process. eliminates time consuming control
sors are unloaded to avoid demand reconfiguration.
Extensive service menu — Unau-
charges whenever possible.
thorized access to the service menu

Model number nomenclature


23XRV 40 42 N R V AA 5 0 S

S – Special

23XRV – High Efficiency Compressor Option


Variable Speed Screw Chiller 0 – Full Load Optimized
1 – Part Load Optimized
Cooler Size*
30-32 Voltage Code
35-37 3 – 380-3-60
40-42 4 – 416-3-60
45-47 5 – 460-3-60
50-52 7 – 575-3-60
55-57 9 – 380/415-3-50
Condenser Size* Drive Code**
30-32 AA – LF-2, 440 Amps In, 442 Amps Out
35-37 BA – LF-2, 520 Amps In, 442 Amps Out
40-42 EC – Std Tier, 575-v, 389 Amps In, 389 Amps Out
45-47 EF – Std Tier, 575-v, 469 Amps In, 469 Amps Out
50-52 R2 – Std Tier, 230 Amps In, 230 Amps Out
55-57 R3 – Std Tier, 335 Amps In, 335 Amps Out
R4 – Std Tier, 445 Amps In, 445 Amps Out
Economizer Option
E – With Economizer
Motor Code
N – No Economizer
P T
Q U
Compressor Code R V
Q† S
R

* First number denotes frame size.


† Only type V motors are used with Q compressors.
**Maximum limits only. Additional application limits apply that may reduce these ampacities.
Quality Assurance
Certified to ISO 9001

ASME AHRI (Air Conditioning, Heating


‘U’ Stamp and Refrigeration Institute) a23-1677
Performance Certified

SEISMICOMPLIANT *
* Meets IBC 2006, ASCE-7-05, CBC 2007, and OSHPD seismic requirements.

4
Physical data
23XRV COMPRESSOR AND MOTOR WEIGHTS
ENGLISH SI
COMPRESSOR MOTOR Total Motor Total Motor
Compressor Stator Rotor Terminal Compressor Stator Rotor Terminal
TYPE SIZE Weight Weight Weight Weight
Weight (lb) (lb) Cover Weight (kg) (kg) Cover
(lb) (lb) (kg) (kg)
Q V 4090 370 193 39 1855 168 88 18
P,Q,R,S,
R 4866 441 229 46 2207 200 104 21
T,U,V

MAXIMUM COMPONENT WEIGHTS


FRAME 3 HEAT FRAME 4 HEAT FRAME 5 HEAT
COMPONENT EXCHANGER EXCHANGER EXCHANGER
lb kg lb kg lb kg
Isolation Valves 70 32 70 32 115 52
Q Compressor 159 72 187 85 184 83
Suction Elbow
R Compressor 179 81 237 108 232 105
Q Compressor 597 271 597 271 597 271
Discharge Elbow/Muffler
R Compressor 747 339 747 339 747 339
Control Center/VFD (LF-2) 1650 749 1650 749 1650 749
Control Center/VFD (Std Tier) 1029 467 1029 467 1029 467
Control Center/VFD (575-v Std Tier) 1650 749 1650 749 1650 749
Vaporizer and Oil Sump 700 318 700 318 700 318
Economizer 542 246 542 246 542 246
LEGEND
VFD — Variable Frequency Drive

23XRV HEAT EXCHANGER WEIGHTS


ENGLISH METRIC (SI)
Dry Rigging Dry Rigging
NUMBER Weight Machine Charge Weight Machine Charge
OF TUBES (lb)* (kg)*
CODE
Refrigerant Liquid Weight Refrigerant Liquid Weight
Cooler Cond. Weight (lb) (lb) Cooler Cond. Weight (kg) (kg)
Only Only With Without Only Only With Without
Cooler Cond. Economizer Economizer Cooler Cond. Economizer Economizer Cooler Cond.
30 200 218 4148 3617 800 650 464 464 1877 1676 363 295 210 210
31 240 266 4330 3818 800 650 531 542 1959 1769 363 295 241 246
32 282 315 4522 4023 800 650 601 621 2046 1860 363 295 273 282
35 200 218 4419 4529 910 760 511 513 2000 2089 413 345 232 233
36 240 266 4627 4758 910 760 587 602 2094 2195 413 345 266 274
37 282 315 4845 4992 910 760 667 692 2193 2299 413 345 303 314
40 324 366 5008 4962 900 825 863 915 2675 2746 408 375 391 415
41 364 415 5178 5155 900 825 930 995 2758 2839 408 375 422 451
42 400 464 5326 5347 900 825 990 1074 2832 2932 408 375 449 487
45 324 366 5463 5525 1015 960 938 998 2882 3001 460 436 425 453
46 364 415 5659 5747 1015 960 1014 1088 2976 3108 460 436 460 494
47 400 464 5830 5967 1015 960 1083 1179 3061 3214 460 436 491 535
50 431 507 5827 6013 1250 1100 1101 1225 3182 3304 567 499 499 556
51 485 556 6053 6206 1250 1100 1192 1304 3294 3397 567 499 541 591
52 519 602 6196 6387 1250 1100 1248 1379 3364 3485 567 499 566 626
55 431 507 6370 6708 1430 1280 1201 1339 3429 3620 649 581 545 607
56 485 556 6631 6930 1430 1280 1304 1429 3556 3726 649 581 591 648
57 519 602 6795 7138 1430 1280 1369 1514 3636 3238 649 581 621 687
LEGEND 3. For special tubes, refer to the 23XRV Computer Selection Program.
COND — Condenser 4. All weights for standard 2-pass NIH (nozzle-in-head) design with Vic-
taulic grooves.
*Rigging weights are for standard tubes of standard wall thickness (EDE and
Spikefin 3, 0.025-in. [0.635 mm] wall).
NOTES:
1. Cooler includes the suction elbow and 1/2 the distribution piping weight.
2. Condenser includes float valve and sump, discharge elbow, and 1/2 the
distribution piping weight.

5
Physical data (cont)
ADDITIONAL WEIGHTS FOR 23XRV MARINE WATERBOXES*
150 psig (1034 kPa) MARINE WATERBOXES

NUMBER ENGLISH (lb) SI (kg)


FRAME OF Cooler Condenser Cooler Condenser
PASSES Rigging Wgt Liquid Wgt Rigging Wgt Liquid Wgt Rigging Wgt Liquid Wgt Rigging Wgt Liquid Wgt
1 and 3 730 700 N/A N/A 331 318 N/A N/A
3
2 365 350 365 350 166 159 166 159
1 and 3 1888 908 N/A N/A 856 412 N/A N/A
4
2 944 452 989 452 428 205 449 205
1 and 3 2445 1019 N/A N/A 1109 462 N/A N/A
5
2 1223 510 1195 499 555 231 542 226

300 psig (2068 kPa) MARINE WATERBOXES

NUMBER ENGLISH (lb) SI (kg)


FRAME OF Cooler Condenser Cooler Condenser
PASSES Rigging Wgt Liquid Wgt Rigging Wgt Liquid Wgt Rigging Wgt Liquid Wgt Rigging Wgt Liquid Wgt
1 and 3 860 700 N/A N/A 390 318 N/A N/A
3
2 430 350 430 350 195 159 195 159
1 and 3 2162 908 N/A N/A 981 412 N/A N/A
4
2 1552 393 1641 393 704 178 744 178
1 and 3 2655 1019 N/A N/A 1204 462 N/A N/A
5
2 1965 439 1909 418 891 199 866 190
*Add to cooler and condenser weights for total weights. Cooler and condenser weights may be found in the 23XRV Heat Exchanger
Weights table on page 5. The first digit of the heat exchanger code (first column) is the heat exchanger frame size.

23XRV WATERBOX COVER WEIGHTS — ENGLISH (lb)


FRAMES 3, 4, AND 5

COOLER CONDENSER
WATERBOX Frame 3 Frame 4 Frame 5 Frame 3 Frame 4 Frame 5
DESCRIPTION Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic
Flanged Flanged Flanged Flanged Flanged Flanged
Nozzles Nozzles Nozzles Nozzles Nozzles Nozzles
NIH,1-Pass Cover 150 psig 282 318 148 185 168 229 282 318 148 185 168 229
NIH,2-Pass Cover 150 psig 287 340 202 256 222 275 287 340 191 245 224 298
NIH,3-Pass Cover 150 psig 294 310 472 488 617 634 294 310 503 519 628 655
NIH Plain End, 150 psig 243 243 138 138 154 154 225 225 138 138 154 154
MWB End Cover, 150 psig* 243/315 243/315 138/314 138/314 154/390 154/390 225/234 225/234 138/314 138/314 154/390 154/390
NIH,1-Pass Cover 300 psig 411 486 633 709 764 840 411 486 633 709 764 840
NIH,2-Pass Cover 300 psig 411 518 626 733 760 867 411 518 622 729 727 878
NIH,3-Pass Cover 300 psig 433 468 660 694 795 830 433 468 655 689 785 838
NIH Plain End, 300 psig 294 294 522 522 658 658 270 270 522 522 658 658
MWB End Cover, 300 psig* 445/619 445/619 522/522 522/522 658/658 658/658 359/474 359/474 658/658 658/658 658/658 658/658
LEGEND *Nozzle end weight/return end weight.
NIH — Nozzle-in-Head NOTE: Weight for NIH 2-pass cover, 150 psig (1034 kPa), is included in
MWB — Marine Waterbox the heat exchanger weights shown on page 5.

23XRV WATERBOX COVER WEIGHTS — SI (kg)


FRAMES 3, 4, AND 5

COOLER CONDENSER
WATERBOX Frame 3 Frame 4 Frame 5 Frame 3 Frame 4 Frame 5
DESCRIPTION Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic
Flanged Flanged Flanged Flanged Flanged Flanged
Nozzles Nozzles Nozzles Nozzles Nozzles Nozzles
NIH,1-Pass Cover 1034 kPa 128 144 67 84 76 104 128 144 67 84 76 104
NIH,2-Pass Cover 1034 kPa 130 154 92 116 101 125 130 154 87 111 102 135
NIH,3-Pass Cover 1034 kPa 133 141 214 221 280 288 133 141 228 235 285 297
NIH Plain End, 1034 kPa 110 110 63 63 70 70 102 102 63 63 70 70
MWB End Cover, 2068 kPa* 110/143 110/143 63/142 63/142 70/177 70/177 102/106 102/106 63/142 63/142 70/177 70/177
NIH,1-Pass Cover 2068 kPa 186 220 287 322 347 381 186 220 287 322 347 381
NIH,2-Pass Cover 2068 kPa 186 235 284 332 344 393 186 235 282 331 330 398
NIH,3-Pass Cover 2068 kPa 196 212 299 315 361 376 196 212 297 313 356 380
NIH Plain End, 2068 kPa 132 132 237 237 298 298 122 122 237 237 298 298
MWB End Cover, 2068 kPa* 202/281 202/281 237/237 237/237 298/298 298/298 163/215 163/215 298/298 298/298 298/298 298/298
LEGEND *Nozzle end weight/return end weight.
NIH — Nozzle-in-Head NOTE: Weight for NIH 2-pass cover, 150 psig (1034 kPa), is included in
MWB — Marine Waterbox the heat exchanger weights shown on page 5.

6
Options and accessories
ITEM OPTION* ACCESSORY†
Std Tier VFD X
Freestanding 5% Line Reactor (for use with Std Tier VFD only) X
.028 or .035 in. (0.711 or 0.889 mm) Internally/Externally Enhanced Copper Tubing — Cooler/Condenser X
.028 or .035 in. (0.711 or 0.889 mm) Internally/Externally Enhanced Cupronickel Tubing — Condenser X
.028 or .035 in. (0.711 or 0.889 mm) Smooth Bore/Externally Enhanced Copper Tubing — Cooler/Condenser X
.028 or .035 in. (0.711 or 0.889 mm) Smooth Bore/Externally Enhanced Cupronickel Tubing — Condenser X
Flanged Cooler and/or Condenser Waterbox Nozzles** X
Hinged Waterboxes X
Marine Waterboxes, 150 psig (1034 kPa)†† X
Marine Waterboxes, 300 psig (2068 kPa)†† X
Nozzle-in Head Waterbox, 300 psig (2068 kPa) X
One, 2, or 3 Pass Cooler or Condenser Waterside Construction X
Seismic Kit X
Zinc Anodes X
100K AIC (Amp Interrupt Capacity) High Interrupt Circuit Breaker (Not Available on 575-v Std Tier Drive) X
Analog Voltmeter and Ammeter with 3 Phase Selector Switch (LF-2 and 575-v Std Tier VFD Only) X
Digital Meter Kit (Std Tier Only) X
BACnet*** Communication X
LonWorks††† Carrier Translator X
Sensor Package X
Refrigerant Isolation Valves X
Separate Storage Tank and Pumpout Unit X
Shipped Factory Charged with Refrigerant X
Stand-Alone Pumpout Unit X
Unit-Mounted Pumpout Unit X
Hot Gas Bypass X
Soleplate Package X
Spring Isolator Kit X
Acoustical Sound Insulation Kit X
Full Cold Surface Thermal Insulation (Except Waterbox Covers) X
Customer Factory Performance Testing X
Export Crating X
Extended Warranty (North American Operations [NAO] only) X
Service Contract X
*Factory-installed. ††Optional marine waterboxes available for 23XRV heat exchangers.
†Field-installed. Standard waterboxes for 23XRV are nozzle-in-head type, 150 psig
**Standard waterbox nozzles are Victaulic type. Flanged nozzles are (1034 kPa).
available as an option with either nozzle-in-head type waterboxes or ***Sponsored by ASHRAE (American Society of Heating, Refrigerating,
marine waterboxes. and Air-Conditioning Engineers).
†††Registered trademark of Echelon Corporation.

7
Dimensions

23XRV DIMENSIONS
(UNIT WITH R COMPRESSOR SHOWN)
TUBE REMOVAL MOTOR SERVICE
SPACE FOR CLEARANCE
EITHER END 1’-10” (559 mm)
SIZES 30-32, 40-42
50-52
14’-3” (4343 mm) FRAME R COMPRESSOR 3’-0” (915mm)
SIZES 35-37, 45-47 RECOMMENDED OVERHEAD SERVICE CLEARANCE
55-57
14’-0” (4267 mm)

a23-1646
C

2’ MIN
(610 mm)
B
A (WIDEST POINT)

4’ MIN
(1219 mm)
SERVICE AREA 4’-10” MIN
(1475 mm)

23XRV DIMENSIONS (NOZZLE-IN-HEAD WATERBOX)


A (Length, with Nozzle-in-Head Waterbox)
HEAT EXCHANGER
SIZE 1-Pass 2-Pass* 3-Pass B (Width) C (Height)
ft-in. mm ft-in. mm ft-in. mm
30 to 32 14- 31/4 4350 13- 81/4 4172 14- 31/4 4350
35 to 37 15-113/4 4870 15- 43/4 4693 15-113/4 4870
40 to 42 14- 9 4496 14- 31/ 8 4347 14- 6 4420 See unit
certified
45 to 47 16- 51/2 5017 15-115/8 4867 16- 21/2 4940 drawings
50 to 52 14-10 4521 14- 41/2 4382 14- 61/2 4432
55 to 57 16- 61/2 5042 16- 1 4902 16- 3 4953

23XRV DIMENSIONS (MARINE WATERBOX)


A (Length, Marine Waterbox)
HEAT EXCHANGER
2-Pass* 1 or 3-Pass† B (Width) C (Height)
SIZE
ft-in. mm ft-in. mm
30 to 32 14- 9 4496 16- 43/4 4997
35 to 37 16- 51/2 5017 18- 11/4 5518
40 to 42 15- 23/4 4642 16- 31/4 5086 See unit
certified
45 to 47 16-113/4 5163 18- 43/4 5607 drawings
50 to 52 15- 31/2 4661 16- 81/2 5093
55 to 57 17- 0 5182 18- 5 5613
*Assumes both cooler and condenser nozzles on same end of chiller. 3. Certified drawings available upon request.
†1 or 3-pass length applies if cooler is a 1 or 3 pass design. 4. Marine waterboxes may add 6 in. (152 mm), to the width of the
NOTES: machine. See certified drawings for details.
1. Service access should be provided per American Society of Heat- 5. ‘A’ length and ‘B’ width dimensions shown are for standard
ing, Refrigerating, and Air-Conditioning Engineers (ASHRAE) 15, 150 psig (1034 kPa) design and Victaulic connections. The
latest edition, National Fire Protection Association (NFPA) 70, and 300 psig (2068 kPa) design and/or flanges will add length. See cer-
local safety code. tified drawings.
2. Allow at least 3 ft (915 mm) overhead clearance for service rigging 6. Dished head waterbox covers not available for the 3-pass design.
for the compressor.

8
Performance data
NOZZLE SIZE
NOZZLE SIZE (in.)
FRAME (Nominal Pipe Size)
SIZE Cooler Condenser
1-Pass 2-Pass 3-Pass 1-Pass 2-Pass 3-Pass
3 10 8 6 10 8 6
4 10 8 6 10 8 6
5 10 8 6 10 10 8

23XRV HEAT EXCHANGER MIN/MAX FLOW RATES*


ENGLISH (GPM)

COOLER 1-PASS 2-PASS 3-PASS CONDENSER 1-PASS 2-PASS 3-PASS


Frame Size Min Max Min Max Min Max Frame Size Min Max Min Max Min Max
30 611 2444 305 1222 204 815 30 646 2582 323 1291 215 861
31 733 2933 367 1466 244 978 31 791 3162 395 1581 263 1054
3 32 855 3422 428 1710 285 1141 3 32 932 3731 466 1865 311 1244
35 611 2444 305 1222 204 815 35 646 2582 323 1291 215 861
36 733 2933 367 1466 244 978 36 791 3162 395 1581 263 1051
37 855 3422 428 1710 285 1141 37 932 3731 466 1865 311 1244
40 989 3959 495 1979 330 1320 40 1096 4383 548 2192 365 1461
41 1112 4448 556 2224 371 1482 41 1235 4940 618 2470 412 1647
4 42 1222 4888 611 2444 407 1775 4 42 1371 5485 686 2743 457 1828
45 989 3959 495 1979 330 1320 45 1096 4383 548 2192 365 1461
46 1112 4448 556 2224 371 1482 46 1235 4940 618 2470 412 1647
47 1222 4888 611 2444 407 1775 47 1371 5485 686 2743 457 1828
50 1316 5267 658 2634 439 1756 50 1507 6029 754 3015 502 2010
51 1482 5927 741 2964 494 1976 51 1646 6586 823 3293 549 2195
5 52 1586 6343 793 3171 529 2114 5 52 1783 7131 891 3565 594 2377
55 1316 5267 658 2634 439 1756 55 1507 6029 754 3015 502 2010
56 1482 5927 741 2964 494 1976 56 1646 6586 823 3293 549 2195
57 1586 6343 793 3171 529 2114 57 1783 7131 891 3565 594 2377
*Flow rates based on standard tubes in the cooler and condenser. Minimum flow based on tube velocity of 3 ft/sec (0.91 m/sec);
maximum flow based on tube velocity of 12 ft/sec (3.66 m/sec). Consult the factory if variable primary flow.

SI (L/s)

COOLER 1-PASS 2-PASS 3-PASS CONDENSER 1-PASS 2-PASS 3-PASS


Frame Size Min Max Min Max Min Max Frame Size Min Max Min Max Min Max
30 38 154 19 77 13 51 30 41 163 20 81 14 54
31 46 185 23 92 15 62 31 50 199 25 100 17 67
3 32 54 215 27 108 18 72 3 32 59 235 29 118 20 79
35 38 154 19 77 13 51 35 41 163 20 81 14 54
36 46 185 23 92 15 62 36 50 199 25 100 17 67
37 54 215 27 108 18 72 37 59 235 29 118 20 79
40 62 249 31 125 21 83 40 69 277 35 138 23 92
41 70 281 35 140 23 93 41 78 312 39 156 26 104
4 42 77 307 38 154 26 112 4 42 86 346 43 173 29 115
45 62 249 31 125 21 93 45 69 277 35 138 23 92
46 70 281 35 140 23 93 46 78 312 39 156 26 104
47 77 307 38 154 26 112 47 86 346 43 173 29 115
50 83 332 42 166 28 111 50 95 380 48 190 32 127
51 93 374 47 187 31 125 51 104 416 52 208 35 138
5 52 100 400 50 200 33 133 5 52 112 450 56 225 37 150
55 83 332 42 166 28 111 55 95 380 48 190 32 127
56 93 374 47 187 31 125 56 104 416 52 208 35 138
57 100 400 50 200 33 133 57 112 450 56 225 37 150
*Flow rates based on standard tubes in the cooler and condenser. Minimum flow based on tube velocity of 3 ft/sec (0.91 m/sec);
maximum flow based on tube velocity of 12 ft/sec (3.66 m/sec). Consult the factory if variable primary flow.

9
Electrical data
VFD FRAME SIZES
FRAME SIZE MAX INPUT CURRENT* MAX OUTPUT CURRENT*
AA (LF-2) 440 442
BA (LF-2) 520 442
EC (575-v Std Tier) 389 389
EF (575-v Std Tier) 469 469
R2 (Std Tier) 230 230
R3 (Std Tier) 335 335
R4 (Std Tier) 445 445
*Maximum limits only. Additional application limits apply that will reduce these ampacities.

AUXILIARY RATINGS*
MAXIMUM
ITEM VOLTAGE PROTECTIVE DEVICE WATTS
SIZE (AMPS)
Controls, Oil Pump And Heater Circuit† 115 15 —
Oil Pump 115 1.48 130
Oil Sump Heater 115 4.35 500
Oil Vaporizer Heater Circuit† 115 15 —
Oil Vaporizer Heater 115 13 1500
*Factory wired to VFD.
†Minimum circuit ampacity of 15 amps.

10
Controls
Microprocessor controls Capacity control
Microprocessor controls provide the safety, interlock, ca- • Leaving chilled liquid control
pacity control, indications and accessibility necessary to • Entering chilled liquid control
operate the chiller in a safe and efficient manner. • Soft loading control by temperature or load ramping
• Hot gas bypass valve (optional)
Control system • Power (demand) limiter
The microprocessor control on each Carrier chiller is • Automatic chilled liquid reset (3 methods)
factory-mounted, factory-wired, and factory-tested to • Manual speed control
ensure machine protection and efficient capacity control.
Interlocks
In addition, the program logic ensures proper starting,
stopping, and recycling of the chiller and provides a com- • Manual/automatic remote start
munication link to the Carrier Comfort Network® (CCN) • Starting/stopping sequence
system. Pre-lube/post-lube
Pre-flow/post-flow
Features • Compressor run interlock
Control system • Pre-start check of safeties and alerts
• Component test and diagnostic check • Low chilled liquid (load) recycle
• Programmable recycle allows chiller to recycle at opti- • Monitor/number compressor starts and run hours
mum loads for decreased operating costs • Manual reset of safeties
• Menu-driven keypad interface for status display, set Indications
point control, and system configuration • Chiller operating status message
• CCN system compatible • Power-on
• Primary and secondary status messages • Pre-start diagnostic check
• Individual start/stop schedules for local and CCN opera- • Compressor motor amps
tion modes • Alert (pre-alarm)††
• Recall of up to 25 alarm messages and 25 alert mes- • Alarm
sages with diagnostic help • Contact for remote alarm
• Two chiller lead/lag with third chiller standby is stan- • Safety shutdown messages
dard in the PIC III software • Elapsed time (hours of operation)
• Optional soft stop unloading decreases compressor • Chiller input kW
speed to unload the motor to the configured amperage • Demand kW
level prior to stopping Drive control parameters
• Languages pre-programmed at factory for English, Chi-
nese, Japanese, Korean • Compressor 100% speed (Hz)
• ILT (International Language Translator) available for • Motor rated load kW
conversion of extended ASCII characters • Motor rated load amps
• Motor nameplate amps
Safety cutouts • Motor nameplate RPM
• Motor high temperature*† • Motor nameplate kW
• Refrigerant (condenser) high pressure*† • Inverter PWM (pulse width modulation) frequency
• Refrigerant (cooler) low temperature*†
• Lube oil low pressure*
• Compressor (refrigerant) high discharge temperature*
• Under voltage**
• Over voltage**
• Cooler and condenser liquid flow
• Motor overload†
• Motor acceleration time *Can be configured by the user to provide alert indication
• Intermittent power loss** at user-defined limit.
• Motor stall protection †Override protection: Causes compressor to first unload
• Low level ground fault and then, if necessary, shut down.
• Cooler and condenser freeze prevention* **Will not require manual reset or cause an alarm if auto-
• Low oil temperature restart after power failure is enabled.
• Motor current imbalance ††By display code only.
• Motor rotation reversal
• Excessive motor amps
• Motor starts limit
• VFD speed out of range
• High VFD inverter temperature*†
• DC bus voltage (Low/High)

11
Controls (cont)
CONTROL PANEL DISPLAY (Front View)
ICVC ENGLISH DISPLAY IN ENGLISH UNITS

51.5 44.0 43.7

75.0 81.7 82.1

24.1 145.2 51.5

a23-1655

ICVC CHINESE DISPLAY IN METRIC UNITS


a23-1656

10.8 6.7 6.5

23.9 27.6 27.8

166.2 62.9 51.5

12
CCN COMMUNICATION WIRING FOR MULTIPLE CHILLERS (TYPICAL)

DRAIN WIRE GROUND DRAIN WIRE DRAIN WIRE DRAIN WIRE


BLACK BLACK BLACK BLACK
WHITE WHITE WHITE WHITE
RED RED RED RED

LEGEND NOTE: Field-supplied terminal strip must be located in control panel.


CCM — Chiller Control Module
Factory Wiring

a23-1649
Field Wiring

13
Controls (cont)
Control sequence
CONTROL SEQUENCE
To start — Local start-up (manual start-up) is initiated by
0 0 pressing the LOCAL or CCN menu softkey, which is indi-
cated on the default international chiller visual control
MACHINE SAFETIES,
EVAPORATOR PUMP
(ICVC) screen. Time schedule 01 or 03, respectively, must
be in the Occupied mode and the internal 15-minute start-
CONDENSER WATER
to-start and the 1-minute stop-to-start inhibit timers must
PUMP have expired. All pre-start safeties are checked to verify
that all prestart alerts and safeties are within limits (if one is
WATER FLOWS not, an indication of the fault displays and the start will be
delayed or is aborted). The signal is sent to start the cooler
CHILLED WATER
liquid pump. Five seconds later, the condenser liquid pump
TEMP, TOWER FAN
CONTROL
is energized. If satisfied, it checks the chilled liquid temper-
ature against the control point. If the temperature is less
OIL PUMP
than or equal to the chilled liquid control point, the con-
denser liquid pump is deenergized and the chiller goes into
a recycle mode.
OIL PRESSURE
VERIFIED If the chilled liquid temperature is high enough, the start-
VFD FAULT TEST up sequence continues. The oil pump is started and waits a
COMPRESSOR, PHASE
REVERSAL, minimum of 45 sec to verify oil flow. Once oil flow is veri-
COMPRESSOR AND
SERVICE ONTIME COMPRESSOR
fied, the VFD is energized. The control will monitor for a
RUNNING phase reversal condition. At this time, the following occurs:
RAMP VFD TO
TARGET SPEED
• The “start-to-stop” timer is activated.
• The “compressor on-time” and “service on-time” timers
15-MINUTE
START-TO-START
are activated.
TIMER • The “starts in 12-hour counter” advances by one.
1-MINUTE
• The “total compressor starts counter” advances by one.
STOP-T O-START
TIMER (SOFTWARE Once started — If the VFD average current >5% within
VERSION 13)
15 seconds after VFD start, the machine enters run mode
a23-214ef and speed will be ramped up to meet VFD target speed.
A B C D E F G H I J L O/A
K
Once the target speed is met the controls, enter the capac-
TIME
ity control mode.
0 — Phase reversal monitored
A — START INITIATED: Pre-start checks are made; evaporator pump Shutdown sequence — The chiller shutdown is initiated
started
B — Condenser liquid pump started (5 seconds after A); tower fan control if any of the following occur:
enabled
C — Liquid flows verified (30 sec to 5 minutes maximum after B) • The Stop button is pressed for at least one second (the
D — Chilled liquid temperature checked against control point; oil pump alarm light blinks once to confirm the stop command).
on. • A recycle shutdown is initiated.
E — Oil pressure verified (oil pressure verified 45-300 sec after D).
F — VFD starts; phase reversal conditions monitored; compressor • The time schedule has gone into unoccupied mode.
ontime and service ontime start; 15-minute inhibit timer starts (VFD • The chiller protective limit has been reached and the
fault tests for 15 sec after F)
G — Verify average current >5% within 15 sec after VFD start, ramp to chiller is in alarm.
VFD target speed. • The start/stop status is overridden to stop from the
H — Compressor reaches target speed, chiller set to running status
I — Shutdown initiated: Target VFD speed to 0% (or J occurs) ICVC, CCN system, or building management system.
J — Ramp down until percent line current < soft stop amps threshold Once the controls shutdown sequence is initiated, the
(0-60 sec after I)
K — Oil pump relay off (1-20 sec after J) compressor is stopped and the VFD target speed is set to 0.
L — Evaporator pump deenergized (60 sec after K); condenser pump
and tower fan control may continue to operate if condenser pressure If optional soft stop unloading is activated when the Stop
is high; evaporator pump may continue if in RECYCLE mode button is pressed or the remote contacts open, motor
O/A — Restart permitted (both inhibit timers expired) (minimum of 15 min-
utes after F; minimum of 3 minutes after L) speed decreases to a configured amperage level, and the
compressor is stopped. The display indicates “Shutdown in
Progress” while the motor speed decreases. Compressor
ontime and service ontime timers stop once the current in
all phases is <5%, indicating a VFD Stop Complete. The oil
pump and cooler liquid pump are then deenergized. The
condenser liquid pump shuts down when the refrigerant
temperature or entering condenser liquid temperature is be-
low pre-established limits. The 3-minute start-to-stop timer
starts.
Restart — Restart is permitted after both inhibit timers
have expired. If shutdown was due to a safety shutdown,
the reset button must be depressed before restarting the
chiller.

14
Typical piping and wiring
23XRV CHILLER
(UNIT WITH R COMPRESSOR SHOWN)

MAIN COMPRESSOR
MOTOR POWER
1 1
1
1
8
7
6

TO CHILLED LIQUID PUMP


TO CONDENSER LIQUID PUMP 2
TO COOLING TOWER FAN

TO
COOLING
TOWER
9

3
3

FROM
COOLING TO
TOWER FROM LOAD
LOAD

DRAIN
5

a23-215ef
LEGEND NOTES:
1 — Disconnect 1. Wiring and piping (with flexible connections) shown are for general point-of-
2 — Unit-Mounted VFD/Control Center connection only and are not intended to show details for a specific installation.
3 — Pressure Gages Certified field wiring and dimensional diagrams are available on request.
4 — Chilled Liquid Pump 2. All wiring must comply with applicable codes.
5 — Condenser Liquid Pump 3. Refer to Carrier System Design Manual for details regarding piping techniques.
6 — Chilled Liquid Pump Starter 4. Wiring not shown for optional devices such as:
7 — Condenser Liquid Pump Starter • remote start/stop
8 — Cooling Tower Fan Starter • remote alarms
9 — Vents • optional safety device
• 4 to 20 mA resets
Piping • optional remote sensors
Control Wiring • kW output
Power Wiring • head pressure reference
5. Flow switches are NOT required.
6. Carrier suggests vibration spring isolation for chillers installed in upper floors.
Carrier suggests that a structural engineer be consulted if the transmission of
vibrations from mechanical equipment is of concern.

15
Control wiring schematic
23XRV COMPONENT ARRANGEMENT

LEGEND
CCM — Chiller Control Module
CCN — Carrier Comfort Network®
ICVC — International Chiller Visual Controller

16
Application data
23XRV MACHINE FOOTPRINT
A

D
C

CL
VESSELS

CL COND.

ACCESSORY
SOLEPLATE B
TYP.
0’-3” F
[76.2mm]
CL
COOLER

E
a23-1650

X X* G

0’-01/2”
[13mm] Y Y*
TYP.

*See detail on page 18.

23XRV DIMENSIONS (ft-in.) DIMENSIONS (mm)


HEAT EXCHANGER
SIZE A B C D E F G A B C D E F G
30-32 12-103/4 5-41/4 0 0-35/8 1-13/4 0-9 0-1/2 3931 1632 0 92 349 229 13
35-37 14- 71/4 5-41/4 0 0-35/8 1-13/4 0-9 0-1/2 4451 1632 0 92 349 229 13
40-42 12-103/4 6-0 0-11/2 0-35/8 1-13/4 0-9 0-1/2 3931 1829 38 92 349 229 13
45-47 14- 71/4 6-0 0-11/2 0-35/8 1-13/4 0-9 0-1/2 4451 1829 38 92 349 229 13
50-52 12-103/4 6-51/2 0- 1/2 0-35/8 1-13/4 0-9 0-1/2 3931 1969 13 92 349 229 13
55-57 14- 71/4 6-51/2 0- 1/2 0-35/8 1-13/4 0-9 0-1/2 4451 1969 13 92 349 229 13

17
Application data (cont)
23XRV ISOLATION WITH ACCESSORY SOLEPLATE PACKAGE

TYPICAL ISOLATION STANDARD ISOLATION

ELASTOMERIC PAD

VIEW Y-Y

ISOLATION WITH ISOLATION PACKAGE ONLY


(STANDARD)

NOTE: Isolation package includes 4 elastomeric pads.

a23-1647
a19-985

ACCESSORY SOLEPLATE DETAIL

a19-1110tf

VIEW X-X

NOTES:
1. Dimensions in ( ) are in millimeters.
2. Accessory soleplate package includes 4 soleplates, 16 jacking screws and leveling
pads. Requires isolation package.
3. Jacking screws to be removed after grout has set.
4. Thickness of grout will vary, depending on the amount necessary to level chiller. Use
only pre-mixed non-shrinking grout, Ceilcote 748 or Chemrex Embeco 636 Plus
Grout, 0-11/2 (38.1) to 0-21/4 (57) thick.
5. Service clearance under the chiller is enhanced if leveling pads are not extended
along the entire length of the heat exchangers.

18
23XRV NOZZLE ARRANGEMENTS
NOZZLE-IN-HEAD WATERBOXES

DISCHARGE END SUCTION END


a23-218tf
FRAME 3

12 3
6
9

5
11 8 2

10 4 1
7

DISCHARGE END SUCTION END


a23-219ef
FRAMES 4 AND 5

NOZZLE ARRANGEMENT CODES FOR ALL 23XRV NOZZLE-IN-HEAD WATERBOXES

COOLER WATERBOXES CONDENSER WATERBOXES


PASS Arrangement PASS Arrangement
In Out In Out
Code* Code*
8 5 A 11 2 P
1 1
5 8 B 2 11 Q
7 9 C 10 12 R
2 2
4 6 D 1 3 S
7 6 E 10 3 T
3 3
4 9 F 1 12 U
*Refer to certified drawings.

19
Application data (cont)
23XRV NOZZLE ARRANGEMENTS (cont)

MARINE WATERBOXES

a23-220tf

DISCHARGE END SUCTION END


FRAME 3
NOZZLE ARRANGEMENT CODES

COOLER WATERBOXES CONDENSER WATERBOXES


PASS Arrangement PASS Arrangement
In Out In Out
Code Code
8 5 A — — —
1 1
5 8 B — — —
7 9 C 10 12 R
2 2
4 6 D 1 3 S
7 6 E — — —
3 3
4 9 F — — —

DISCHARGE END SUCTION END

a23-221tf
FRAMES 4, AND 5
NOZZLE ARRANGEMENT CODES

COOLER WATERBOXES CONDENSER WATERBOXES


PASS Arrangement PASS Arrangement
In Out In Out
Code Code
9 6 A — — —
1 1
6 9 B — — —
7 9 C 10 12 R
2 2
4 6 D 1 3 S
7 6 E — — —
3 3
4 9 F — — —

20
23XRV WATERBOX NOZZLE SIZES (Nozzle-In-Head and Marine Waterboxes)
FRAME PRESSURE NOMINAL PIPE SIZE (in.) ACTUAL PIPE ID (in.)
PASS
SIZE psig (kPa) Cooler Condenser Cooler Condenser
1 10 10 10.020 10.020
150/300
3 (1034/2068) 2 8 8 7.981 7.981
3 6 6 6.065 6.065
1 10 10 10.020 10.020
150/300
4 (1034/2068) 2 8 8 7.981 7.981
3 6 6 6.065 6.065
1 10 10 10.020 10.020
150/300
5 (1034/2068) 2 8 10 7.981 10.020
3 6 8 6.065 7.981

RELIEF VALVE LOCATIONS

LOCATION FRAME RELIEF VALVE OUTLET SIZE QUANTITY WITHOUT QUANTITY WITH
SIZE ISOLATION VALVES ISOLATION VALVES
Discharge Pipe Assembly 3-5 11/4-in. NPT FEMALE CONNECTOR 1 1
Cooler 3-5 11/4-in. NPT FEMALE CONNECTOR 2 1
Condenser 3-5 11/4-in. NPT FEMALE CONNECTOR 2 2
Optional Storage Tank N/A 1-in. NPT FEMALE CONNECTOR 2 2

NOTE: All valves relieve at 185 psig (1275 kPa).

RELIEF VALVE ARRANGEMENTS


WITH OPTIONAL ISOLATION OF DISCHARGE AND COOLER
UNITS WITH Q COMPRESSOR

a23-1657

WITH OPTIONAL ISOLATION WITHOUT OPTIONAL ISOLATION

UNITS WITH R COMPRESSOR

a23-1657

WITH OPTIONAL ISOLATION WITHOUT OPTIONAL ISOLATION

21
Application data (cont)
Vent and drain connections Each heat exchanger and economizer (if equipped)
Nozzle-in-head waterboxes have vent and drain connec- is ASME ‘U’ stamped on the refrigerant side of each
tions on covers. Marine waterboxes have vent and drain vessel.
connections on waterbox shells. Relief valve discharge pipe sizing
Provide high points of the chiller piping system with vents See page 21 for number of relief valves.
and the low points with drains. If shutoff valves are provid-
ed in the main liquid pipes near the unit, a minimal amount Relief valve discharge piping size should be calculated
of system liquid is lost when the heat exchangers are per the current version of the ASHRAE 15, latest edition,
code using the tabulated C factors for each vessel shown in
drained. This reduces the time required for drainage and
saves on the cost of re-treating the system liquid. the table below.
23XRV RELIEF VALVE DISCHARGE PIPE SIZING
It is recommended that pressure gages be provided at
points of entering and leaving liquid to measure pressure VESSEL RELIEF
drop through the heat exchanger. Gages may be installed VALVE FIELD
HEAT FRAME REQUIRED RATED CONNECTION
as shown in Pressure Gage Location table. Pressure gages EXCHANGER SIZE C FACTOR
(lb air/Min) C FACTOR SIZE (FPT)
installed at the vent and drain connections do not include (lb air/Min)
nozzle pressure losses. 30 to 32 43.4 70.8 1 1 /4 
Use a reliable differential pressure gage to measure pres- 35 to 37 49.5 70.8 1 1 /4 
sure differential when determining liquid flow. Regular gag- 40 to 42 50.4 70.8 1 1 /4 
COOLER
es of the required pressure range do not have the accuracy 45 to 47 57.4 70.8 1 1 /4 
to provide accurate measurement of flow conditions. 50 to 52 53.7 70.8 1 1 /4 
55 to 57 61.1 70.8 1 1 /4 
PRESSURE GAGE LOCATION
30 to 32 41.4 70.8 1 1 /4 
NUMBER 35 to 37 47.1 70.8 1 1 /4 
GAGE LOCATION
OF
(Cooler or Condenser) 40 to 42 47.1 70.8 1 1 /4 
PASSES CONDENSER
45 to 47 53.7 70.8 1 1 /4 
1 or 3 One gage in each waterbox
50 to 52 51.2 70.8 1 1 /4 
2 Two gages in waterbox with nozzles
55 to 57 58.3 70.8 1 1 /4 

ASME stamping Carrier further recommends that an oxygen sensor be


All 23XRV heat exchangers are constructed in accordance installed to protect personnel. Sensor should be able to
with ASHRAE (American Society of Heating, Refrigerat- sense the depletion or displacement of oxygen in the ma-
ing, and Air-Conditioning Engineers) 15 Safety Code for chine room below 19.5% volume oxygen per ASHRAE
Mechanical Refrigeration (latest edition). This code, in 15, latest edition.
turn, requires conformance with ASME (American Society
of Mechanical Engineers) Code for Unfired Pressure Ves- Design pressures
sels wherever applicable. Design and test pressures for heat exchangers are listed
below.
DESIGN AND TEST PRESSURES (23XRV)
SHELL SIDE STANDARD TUBE SIDE OPTIONAL TUBE SIDE
PRESSURES (Refrigerant) (Liquid) (Liquid)
psig kPa psig kPa psig kPa
Leak Test at Design Pressure* 185 1276 150 1034 300 2068
Hydrostatic — — 195 1344 390 2689
Proof Test* 204 1407 — — — —
*Nitrogen/Helium.
HEAT EXCHANGER MATERIAL SPECIFICATIONS
ITEM MATERIAL SPECIFICATION
Shell HR Steel ASME SA516 GR 70
Tube Sheet HR Steel ASME SA516 GR 70
Condenser/Cooler Waterbox Cover HR Steel ASME SA516 GR 70, SA-36, or SA-285 GRC
ASME SA675 GR 60, SA-516 GR70, or SA-181 CL70,
Condenser/Cooler Waterbox Shell HR Steel SA-36, SA-675 GR70, SAE AME 7496
Tubes Finned Copper ASME SB359
Discharge/Suction
Pipe Steel ASME SA106 GRB
Flanges Steel ASME SA105
LEGEND
ASME — American Society of Mechanical Engineers
HR — Hot Rolled

22
Insulation conforms with Underwriters Laboratories (UL) Standard
94, Classification 94 HF-1. Both the 1/2-in. foam and the
23XRV MINIMUM FIELD-INSTALLED INSULATION 3/ -in. vinyl layer will pass flammability test method
16
REQUIREMENTS MVSS 302.
INSULATION Field insulation — As indicated in the Condensation vs
COMPONENT SIZE Relative Humidity table, the factory insulation provides
ft2 m2
30-32 96 8.9 excellent protection against condensation under most op-
35-37 108 10.0 erating conditions. If temperatures in the equipment area
40-42 109 10.1 exceed the maximum design conditions, extra insulation is
Cooler 45-47 122 11.3
50-52 115 10.7 recommended.
55-57 130 12.1 If the machine is to be field insulated, obtain the approx-
Misc. Liquid Lines All Sizes 21 2.0 imate areas from the 23XRV Minimum Field-Installed Insu-
Economizer All Sizes 20 1.9 lation Requirements table.
Compressor Motor All Sizes 17 1.6
Insulation of waterbox is made only in the field and this
area is not included in 23XRV Minimum Field-Installed In-
Factory insulation — Thermal insulation is factory- sulation Requirements table. When insulating the covers,
provided to the following areas: allow for service access and removal of covers. To estimate
• Cooler (not including waterbox) water-box cover areas, refer to certified drawings.
• Suction line High humidity jobsite locations may require field sup-
• Compressor and motor plied and installed insulation on the float chamber, suction
• Oil cooling line and oil return system line (oil and refrig- housing, and the lower half of the condenser.
erant lines at or near evaporator pressure are insulated)
• VFD cooling line (oil and refrigerant lines at or near CONDENSATION VS RELATIVE HUMIDITY*
evaporator pressure are insulated) ROOM DRY-BULB TEMPERATURE
• Motor cooling line AMOUNT OF 80 F (27 C) 90 F (32 C) 100 F (38 C)
CONDENSATION
• Vaporizer % Relative Humidity
• Liquid line and discharge line None 80 76 70
• Float chamber Slight 87 84 77
• Optional economizer (including vent line and econo- Extensive 94 91 84
mizer muffler) *These approximate figures are based on 35 F (1.7 C) saturated suction
temperature. A 2° F (1.1° C) change in saturated suction temperature
Factory insulation is not available for the waterboxes. changes the relative humidity values by 1% in the same direction.
Insulation applied at the factory is 1/2-in. (13 mm) thick Minimum fluid loop volume
closed cell and 1/2-in. (13 mm) open cell PVC-Nitrile foam.
Some parts of the chiller are also treated with an outer Minimum fluid volume must be in excess of 1.5 gal per ton
layer of 3/16-in. (5 mm) thick vinyl. The 1/2-in. (13 mm) (1.6 L per kW) for comfort cooling applications and apply
3 to 5 gal per ton (3.2 to 5.4 L per kW) fluid loop volume
closed cell foam has a thermal conductivity K value of
for process applications.
0.28 (BTU in.)/(hr sq ft °F) [0.0404 W/(m °C)] and

23
Guide specifications
Variable Speed Screw Chiller 1.02 QUALITY ASSURANCE
HVAC Guide Specifications A. Chiller performance shall be rated in accordance
with AHRI Standard 550/590, latest edition.
Size Range: 250 to 550 Tons (879 to 1934 kW)
Nominal B. Equipment and installation shall be in compliance
with ANSI/ASHRAE 15 (latest edition).
Carrier Model Number: 23XRV
C. Cooler and condenser refrigerant side shall include
Part 1 — General ASME “U” stamp and nameplate certifying compli-
1.01 SYSTEM DESCRIPTION ance with ASME Section VIII, Division 1 code for
A. Microprocessor-controlled liquid chiller shall use a unfired pressure vessels.
semi-hermetic screw compressor using refrigerant D. A manufacturer’s data report is required to verify
HFC-134a only. Chiller refrigerant shall not have a pressure vessel construction adherence to ASME
planned phase out date. vessel construction requirements. Form U-1 as
B. If a manufacturer proposes a liquid chiller using required per ASME code rules is to be furnished
HCFC-123 refrigerant, which has a planned phase to the owner. The U-1 Form must be signed by a
out date, then the manufacturer shall include in the qualified inspector, holding a National Board
chiller price: Commission, certifying that construction conforms
to the latest ASME Code Section VIII, Div. 1 for
1. A vapor activated alarm system consisting of all
pressure vessels. The ASME symbol “U” must also
alarms, sensors, safeties, and ventilation equip-
be stamped on the heat exchanger. Vessels specifi-
ment as required by ANSI/ASHRAE Standard
cally exempted from the scope of the code must
15 Safety Code for Mechanical Refrigeration
come with material, test, and construction methods
(latest edition) with the quotation. System shall
certification and detailed documents similar to
be capable of responding to HCFC-123 levels
ASME U-1; further, these must be signed by an offi-
of 10 ppm Allowable Exposure Limit (AEL).
cer of the company.
2. A free-standing refrigerant storage tank and
E. Chiller shall be designed and constructed to meet
pumpout unit shall be provided. The storage
UL and UL of Canada requirements and have labels
vessels shall be designed per ASME Section VIII
appropriately affixed.
Division 1 code with 300 psig (2068 kPa)
design pressure. Double relief valves per ANSI/ F. Unit shall be manufactured in a facility registered to
ASHRAE 15, latest edition, shall be provided. ISO 9001 Manufacturing Quality Standard.
The tank shall include a liquid level gage and G. Each compressor assembly shall undergo a mechan-
pressure gage. The pumpout unit shall use a ical run-in test to verify vibration levels, oil pressures,
semi-hermetic reciprocating compressor with and temperatures are within acceptable limits. Each
water-cooled condenser. Condenser water pip- compressor assembly shall be proof tested at a mini-
ing, 3-phase motor power, and 115-volt control mum 204 psig (1407 kPa) and leak tested at
power shall be installed at the jobsite by the 185 psig (1276 kPa) with a tracer gas mixture.
installing contractor. H. Entire chiller assembly shall be proof tested at
3. Zero emission purge unit capable of operating 204 psig (1407 kPa) and leak tested at 185 psig
even when the chiller is not operating. (1276 kPa) with a tracer gas mixture on the refriger-
4. Back-up relief valve to rupture disk. ant side. The leak test shall not allow any leaks
greater than 0.5 oz per year of refrigerant. The
5. Factory-installed chiller pressurizing system to
water side of each heat exchanger shall be hydro-
prevent leakage of noncondensables into the
statically tested at 1.3 times rated working pressure.
chiller during shutdown periods.
I. Prior to shipment, the chiller automated controls
6. Plant room ventilation.
test shall be executed to check for proper wiring and
7. Removal and disposal of refrigerant at the end ensure correct controls operation.
of the phase out period.
J. Chillers shall have factory-mounted, factory-wired
8. Chillers utilizing a purge unit shall include in the and factory-tested unit-mounted variable frequency
machine price the costs to perform the follow- drive (VFD). Proper VFD operation shall be con-
ing regular maintenance procedures: firmed prior to shipment.
a. Weekly: Check refrigerant charge. 1.03 DELIVERY, STORAGE AND HANDLING
b. Quarterly: Charge purge unit dehydrator at A. Unit shall be stored and handled in accordance with
least quarterly, more often if necessary. manufacturer’s instructions.
Clean foul gas strainer. Perform chemical
analysis of oil. B. Unit shall be shipped with all refrigerant piping and
control wiring factory-installed.
c. Annually: Clean and inspect all valves. Drain
C. Unit shall be shipped charged with oil and full
and flush purge shell. Clean orifices.
charge of refrigerant HFC-134a or a nitrogen hold-
ing charge as specified on the equipment schedule.

24
D. Unit shall be shipped with firmly attached labels that b. Oil pressure sensor with differential readout
indicate name of manufacturer, chiller model num- at main control center.
ber, chiller serial number, and refrigerant used. c. Oil pressure regulator.
E. If the unit is to be exported, the manufacturer shall d. Oil filter with isolation valves to allow filter
provide sufficient protection against sea water corro- change without removal of refrigerant
sion, making the unit suitable for shipment in a charge.
standard open top ocean shipping container.
e. Oil sump heater [115 v, 50 or 60 Hz] con-
F. Chiller and starter shall be stored indoors, protected trolled from unit microprocessor.
from construction dirt and moisture. Chiller shall be
f. Oil reservoir temperature sensor with main
inspected under shipping tarps, bags, or crates to be
control center digital readout.
sure water has not collected during transit. Protec-
tive shipping covers shall be kept in place until g. All wiring to oil pump, oil heater, and con-
machine is ready for installation. The inside of the trols shall be pre-wired in the factory and
protective cover shall meet the following criteria: power shall be applied to check proper
operation prior to shipment.
1. Temperature is between 40 F (4.4 C) and
120 F (48.9 C) 7. Compressor shall be fully field serviceable.
2. Relative humidity is between 10% and 80% Compressors that must be removed and
non-condensing. returned to the factory for service shall be
unacceptable.
1.04 WARRANTY
8. Acoustical attenuation shall be provided as
Warranty shall include parts and labor for one year
required, to achieve a maximum (full load
after start-up or 18 months from shipment, which- or part load) sound level, measured per AHRI
ever occurs first. A refrigerant warranty shall be Standard 575 (latest edition).
provided for a period of 5 years.
C. Motor:
Part 2 — Products
1. Compressor motor shall be of the semi-
2.01 EQUIPMENT hermetic, liquid refrigerant cooled, squirrel
A. General: cage, induction type suitable for voltage shown
Factory-assembled, single piece, liquid chiller shall on the equipment schedule.
consist of compressor, motor, VFD, lubrication sys- 2. If an open (air-cooled) motor is provided, a
tem, cooler, condenser, initial oil and refrigerant compressor shaft seal leakage containment
operating charges, microprocessor control system, system shall be provided:
and documentation required prior to start-up.
a. An oil reservoir shall collect oil and refriger-
B. Compressor: ant that leaks past the seal.
1. One variable speed, tri-rotor screw compressor b. A float device shall be provided to open
of the high performance type. when the reservoir is full, directing the
2. Compressor and motor shall be hermetically refrigerant/oil mixture back into the com-
sealed into a common assembly and arranged pressor housing.
for easy field servicing. c. A refrigerant sensor shall be located next to
3. The compressor motor shall be accessible for the open drive seal to detect leaks.
servicing without removing the compressor 3. Motors shall be suitable for operation in a
base from the chiller. Connections to the com- refrigerant atmosphere and shall be cooled by
pressor casing shall use O-rings and gaskets to atomized refrigerant in contact with the motor
reduce the occurrence of refrigerant leakage. windings.
Connections to the compressor shall be flanged
4. Motor stator shall be arranged for service or
or bolted for easy disassembly. removal with only minor compressor disassem-
4. Compressor bearings must have individual bly and without removing main refrigerant
design life of 500,000 hours or greater. piping connections.
5. Compressor shall provide capacity modulation 5. Full load operation of the motor shall not
from 100% to 15% capacity without the use of exceed nameplate rating.
hot gas bypass or mechanical unloaders.
6. One motor winding temperature sensor (and
6. Compressor shall be provided with a factory- one spare) shall be provided.
installed positive pressure lubrication system to
7. Should mechanical contractor choose to pro-
deliver oil under pressure to bearings and rotors
vide a chiller with an air-cooled motor instead of
at all operating conditions. Lubrication system
the specified semi-hermetic motor, the contrac-
shall include:
tor shall install additional cooling equipment to
a. Oil pump with factory-installed motor con- dissipate the motor heat.
tactor with overload protection.

25
Guide specifications (cont)
The following formula applies: 5. The vessel shall display an ASME nameplate
Btuh = (FLkW motor) (0.05) (3413) that shows the pressure and temperature data
and the “U” stamp for ASME Section VIII,
Btuh = (FLkW motor) (171) Division 1. A re-seating pressure relief valve(s)
and, alternately shall be installed on each heat exchanger. If a
Tons = Btuh/12,000 non-reseating type is used, a backup reseating
The additional piping, valves, air-handling type shall be installed in series.
equipment, insulation, wiring, switchgear 6. Waterboxes shall have vents, drains, and covers
changes, ductwork, and coordination with other to permit tube cleaning within the space shown
trades shall be the responsibility of the mechan- on the drawings. A thermistor type temperature
ical contractor. Shop drawings reflecting any sensor with quick connects shall be factory-
changes to the design shall be included in the installed in each water nozzle.
submittal, and incorporated into the final as- 7. Cooler shall be designed to prevent liquid refrig-
built drawings for the project. erant from entering the compressor. Devices
8. Also, if an open motor is provided, a mechani- that introduce pressure losses (such as mist
cal room thermostat shall be provided and set eliminators) shall not be acceptable because
at 104 F (40 C). If this temperature is they are subject to structural failures that can
exceeded, the chillers shall shut down and an result in extensive compressor damage.
alarm signal shall be generated to the central 8. Tubes shall be individually replaceable from
Energy Management System (EMS) display either end of the heat exchanger without affect-
module, prompting the service personnel to ing the strength and durability of the tube sheet
diagnose and repair the cause of the overtem- and without causing leakage in adjacent tubes.
perature condition. The mechanical contractor 9. The condenser shell shall include a FLASC
shall be responsible for all changes to the
(Flash Subcooler) which cools the condensed
design, including coordination with temperature liquid refrigerant to a reduced temperature,
control, electrical and other trades. In addition, thereby increasing the refrigeration cycle
the electrical power consumption of any auxil-
efficiency.
iary ventilation and/or mechanical cooling
required to maintain the mechanical room con- E. Refrigerant Flow Control:
ditions stated above shall be considered in the To improve part load efficiency, liquid refrigerant
determination of conformance to the scheduled shall be metered from the condenser to the cooler
chiller energy efficiency requirement. using a float-type metering valve to maintain the
D. Evaporator and Condenser: proper liquid level of refrigerant in the heat
exchangers under both full and part load operating
1. Evaporator and condenser shall be of shell and conditions. By maintaining a liquid seal at the float
tube type construction, each in separate shells. valve, bypassed hot gas from the condenser to the
Units shall be fabricated with high-performance
cooler is eliminated.
tubing, steel shell and tube sheets with fabri-
cated steel waterboxes. Waterboxes shall be F. Controls, Safeties, and Diagnostics:
nozzle-in-head type with stub out nozzles having 1. Controls:
Victaulic grooves to allow for use of Victaulic a. The chiller shall be provided with a factory-
couplings. installed and factory-wired microprocessor
2. Tubing shall be copper, high-efficiency type, control center. The control center shall include
with integral internal and external enhance- a 16-line by 40-character liquid crystal display,
ment unless otherwise noted. Tubes shall be 4 function keys, stop button, and alarm light.
nominal 3/4-in. OD with nominal wall thickness Other languages are available using the inter-
of 0.025 in. measured at the root of the fin national language translator software.
unless otherwise noted. Tubes shall be rolled b. All chiller and motor control monitoring shall
into tube sheets and shall be individually be displayed at the chiller control panel.
replaceable. Tube sheet holes shall be double
c. The controls shall make use of non-volatile
grooved for joint structural integrity. Intermedi-
memory.
ate support sheet spacing shall not exceed
36 in. (914 mm). d. The chiller control system shall have the ability
to interface and communicate directly to the
3. Waterboxes and nozzle connections shall be
building control system.
designed for 150 psig (1034 kPa) minimum
working pressure unless otherwise noted. e. The default standard display screen shall simul-
Nozzles should have grooves to allow use of taneously indicate the following minimum
Victaulic couplings. information:
4. The tube sheets of the cooler and condenser 1) Date and time of day
shall be bolted together to allow for field disas- 2) 24-character primary system status
sembly and reassembly. message

26
3) 24-character secondary status message i. Network Window Function:
4) Chiller operating hours Each chiller control panel shall be capable of
5) Entering chilled water temperature viewing multiple point values and statuses
6) Leaving chilled water temperature from other like controls connected on a
7) Evaporator refrigerant temperature common network, including controller main-
8) Entering condenser water temperature tenance data. The operator shall be able to
9) Leaving condenser water temperature alter the remote controller’s set points or
10) Condenser refrigerant temperature time schedule and to force point values or
11) Oil supply pressure statuses for those points that are operator
12) Oil sump temperature forcible. The control panel shall also have
13) Percent motor rated load amps (RLA) access to the alarm history file of all like con-
f. In addition to the default screen, status trollers connected on the network.
screens shall be accessible to view the status j. Pump Control:
of every point monitored by the control
Upon request to start the compressor, the
center including:
control system shall start the chilled and
1) Evaporator pressure condenser water pumps and shall verify that
2) Condenser pressure flows have been established.
3) Compressor speed
k. Ramp Loading:
4) Bearing oil supply temperature
5) Compressor discharge temperature A user-configurable ramp loading rate, effec-
6) Motor winding temperature tive during the chilled water temperature
7) Number of compressor starts pulldown period, shall prevent a rapid
8) Control point settings increase in compressor power consumption.
9) Discrete output status of various devices The controls shall allow configuration of the
10) Variable frequency drive status ramp loading rate in either degrees per min-
11) Optional spare input channels ute of chilled water temperature pulldown or
12) Line current and voltage for each phase percent motor amps per minute. During the
13) Frequency, kW, kWhr, demand kW ramp loading period, a message shall be
displayed informing the operator that the
g. Schedule Function:
chiller is operating in ramp loading mode.
The chiller controls shall be configurable for
l. Chilled Water Reset:
manual or automatic start-up and shutdown.
In automatic operation mode, the controls The control center shall allow reset of the
shall be capable of automatically starting and chilled water temperature set point based on
stopping the chiller according to a stored any one of the following criteria:
user programmable occupancy schedule. 1) Chilled water reset based on an external
The controls shall include built-in provisions 4 to 20 mA signal.
for accepting: 2) Chilled water reset based on a remote
1) A minimum of two 365-day occupancy temperature sensor (such as outdoor
schedules. air).
2) Minimum of 8 separate occupied/unoc- 3) Chilled water reset based on water tem-
cupied periods per day perature rise across the evaporator.
3) Daylight savings start/end m. Demand Limit:
4) 18 user-defined holidays The control center shall limit amp draw of
5) Means of configuring an occupancy the compressor to the rated load amps or to
timed override a lower value based on one of the following
6) Chiller start-up and shutdown via remote criteria:
contact closure
1) Demand limit based on a user input
h. Service Function: ranging from 40% to 100% of compres-
The controls shall provide a password sor rated load amps
protected service function which allows 2) Demand limit based on external 4 to
authorized individuals to view an alarm 20 mA signal.
history file which shall contain the last n. Controlled Compressor Shutdown:
25 alarm/alert messages with time and date
stamp. These messages shall be displayed in The controls shall be capable of being
text form, not codes. configured to soft stop the compressor. The
display shall indicate “shutdown in progress.”

27
Guide specifications (cont)
2. Safeties: b. Once the controls test has been initiated, all
a. Unit shall automatically shut down when any pressure and temperature sensors shall be
of the following conditions occur (each of checked to ensure they are within normal
these protective limits shall require manual operating range. A pump test shall automat-
reset and cause an alarm message to be dis- ically energize the chilled water pump, con-
played on the control panel screen, inform- denser water pump, and oil pump. The
ing the operator of the shutdown cause): control system shall confirm that water flow
and oil pressure have been established and
1) Motor overcurrent
require operator confirmation before pro-
2) Over voltage* ceeding to the next test.
3) Under voltage*
4) Single cycle dropout* (LF-2 VFDs only) c. In addition to the automated controls test,
5) Low oil sump temperature the controls shall provide a manual test
6) Low evaporator refrigerant temperature which permits selection and testing of indi-
7) High condenser pressure vidual control components and inputs. A
8) High motor temperature thermistor test and transducer test shall dis-
9) High compressor discharge temperature play on the ICVC screen the actual reading
10) Low oil pressure of each transducer and each thermistor
11) Prolonged stall installed on the chiller. All out-of-range sen-
12) Loss of cooler water flow sors shall be identified. Pressure transducers
13) Loss of condenser water flow shall be serviceable without the need for
14) Variable frequency drive fault refrigerant charge removal or isolation.
15) High variable frequency drive temperature 4. Multiple Chiller Control:
* Shall not require manual reset or cause an The chiller controls shall be supplied as stan-
alarm if auto-restart after power failure is dard with a two-chiller lead/lag and a third
enabled. chiller standby system. The control system shall
b. The control system shall detect conditions automatically start and stop a lag or second
that approach protective limits and take self- chiller on a two-chiller system. If one of the two
corrective action prior to an alarm occur- chillers on line goes into a fault mode, the third
ring. The system shall automatically reduce standby chiller shall be automatically started.
chiller capacity when any of the following The two-chiller lead/lag system shall allow
parameters are outside their normal operat- manual rotation of the lead chiller and a stag-
ing range: gered restart of the chillers after a power fail-
ure. The lead/lag system shall include load
1) High condenser pressure balancing if configured to do so.
2) High motor temperature
3) Low evaporator refrigerant temperature G. Electrical Requirements:
4) High motor amps 1. Electrical contractor shall supply and install
5) High VFD inverter temperature main electrical power line, disconnect switches,
c. During the capacity override period, a pre- circuit breakers, and electrical protection
alarm (alert) message shall be displayed devices per local code requirements and as indi-
informing the operator which condition is cated necessary by the chiller manufacturer.
causing the capacity override. Once the con- 2. Electrical contractor shall wire the chilled water
dition is again within acceptable limits, the pump and flow, condenser water pump and
override condition shall be terminated and flow, and tower fan control circuit to the chiller
the chiller shall revert to normal chilled control circuit.
water control. If during either condition the 3. Electrical contractor shall supply and install
protective limit is reached, the chiller shall electrical wiring and devices required to inter-
shut down and a message shall be displayed face the chiller controls with the building control
informing the operator which condition system if applicable.
caused the shutdown and alarm.
4. Electrical power shall be supplied to the unit at
d. Internal built-in safeties shall protect the the voltage, phase, and frequency listed in the
chiller from loss of water flow. Differential equipment schedule.
pressure switches shall not be allowed to be
H. Piping Requirements — Instrumentation and Safeties:
the only form of freeze protection.
1. Mechanical contractor shall supply and install
3. Diagnostics and Service:
pressure gages in readily accessible locations in
a. A self diagnostic controls test shall be an piping adjacent to the chiller such that they can
integral part of the control system to allow be easily read from a standing position on the
quick identification of malfunctioning floor. Scale range shall be such that design val-
components. ues shall be indicated at approximately mid-
scale.

28
2. Gages shall be installed in the entering and leav- piping and 3-phase motor power shall be
ing water lines of the cooler and condenser. installed at the jobsite by the installing contrac-
I. Vibration Isolation: tor.
Chiller manufacturer shall furnish neoprene isolator 7. Building Control System Interface (LON):
pads for mounting equipment on a level concrete The chiller control system shall have the ability
surface. to interface and communicate directly to the
J. Start-Up: building control using a LON based system. The
LonWorks Carrier Translator shall output data
1. The chiller manufacturer shall provide a factory-
in standard LON profiles.
trained representative, employed by the chiller
manufacturer, to perform the start-up proce- 8. Refrigerant Charge:
dures as outlined in the Start-Up, Operation The chiller shall ship from the factory fully
and Maintenance manual provided by the charged with R-134a refrigerant and oil.
chiller manufacturer. 9. Thermal Insulation:
2. Manufacturer shall supply the following Unit manufacturer shall insulate the cooler
literature: shell, economizer, suction elbow, motor shell
a. Start-up, operation and maintenance and motor cooling lines. Insulation shall be 1 in.
instructions. (25.4 mm) thick with a thermal conductivity not
b. Installation instructions. exceeding
c. Field wiring diagrams.
d. One complete set of certified drawings. 0.28
(Btu · in.)
hr. Ft2 F
( 0.0404 W
mC )
K. Special Features:
and shall conform to UL standard 94, classifica-
1. Soleplate Package: tion 94 HF-1.
Unit manufacturer shall furnish a soleplate 10. Automatic Hot Gas Bypass:
package consisting of soleplates, jacking
Hot gas bypass valve and piping shall be
screws, leveling pads, and neoprene pads.
factory-furnished to permit chiller operation for
2. Spring Isolators: extended periods of time.
Spring isolators shall be field furnished and 11. Cooler and Condenser Tubes:
selected for the desired degree of isolation.
Contact your local Carrier Representative for
3. Spare Sensors with Leads: other tube offerings.
Unit manufacturer shall furnish additional tem- 12. Cooler and Condenser Passes:
perature sensors and leads.
Unit manufacturer shall provide the cooler and/
4. Sound Insulation Kit: or condenser with 1, 2 or 3 pass configuration
Unit manufacturer shall furnish a sound insula- on the water side.
tion kit that covers the compressor housing, 13. Nozzle-In-Head, 300 psig (2068 kPa):
motor housing, compressor discharge pipe,
Unit manufacturer shall furnish nozzle-in-head
suction line, evaporator, and economizer (if
style waterboxes on the cooler and/or con-
equipped).
denser rated at 300 psig (2068 kPa).
5. Stand-Alone Pumpout Unit:
14. Marine Waterboxes, 150 psig (1034 kPa):
A free-standing pumpout unit shall be provided.
Unit manufacturer shall furnish marine style
The pumpout unit shall use a semi-hermetic
waterboxes on cooler and/or condenser rated
reciprocating compressor with liquid-cooled
at 150 psig (1034 kPa).
condenser. Condenser liquid piping and
3-phase motor power shall be installed at the 15. Marine Waterboxes, 300 psig (2068 kPa):
jobsite by the installing contractor. Unit manufacturer shall furnish marine style
6. Separate Storage Tank and Pumpout Unit: waterboxes on cooler and/or condenser rated
at 300 psig (2068 kPa).
A free-standing refrigerant storage tank and
pumpout unit shall be provided. The storage 16. Flanged Water Nozzles:
vessels shall be designed per ASME Section VIII Unit manufacturer shall furnish standard
Division 1 code with 150 psig (1034 kPa) flanged piping connections on the cooler and/
design pressure. Double relief valves per ANSI/ or condenser.
ASHRAE 15, latest edition, shall be provided. 17. Hinges:
The tank shall include a liquid level gage and
pressure gage. The pumpout shall use a Unit manufacturer shall furnish hinges on
hermetic reciprocating compressor with waterboxes to facilitate tube cleaning.
water-cooled condenser. Condenser water

29
Guide specifications (cont)
18. Optional Compressor Discharge Isolation Valve opening cabinet door with disconnect in
and Liquid Line Ball Valve: the “On” position or moving disconnect
These items shall be factory-installed to allow to the “On” position while the door is
isolation of the refrigerant charge in the con- open shall be provided.
denser for servicing the compressor. 4) Provisions shall be made for top entry of
incoming line power cables.
19. Pumpout Unit:
c. Heat Sink:
A refrigerant pumpout system shall be installed
on the chiller. Pumpout system shall include a 1) The heat sink shall be refrigerant
hermetic compressor and drive, internal piping, cooled. Heat sink and mating flanges
internal wiring, and motor. Field-supplied main shall be suitable for ASME design work-
power wiring and water piping shall be ing pressure of 185 psig (1276 kPa).
required. 2) Refrigerant cooling shall be metered to
maintain heat sink temperature within
20. BACnet Communication Option: acceptable limits for ambient tempera-
Shall provide factory-installed communication ture.
capability with a BACnet MS/TP network. d. VFD Rating:
Allows integration with i-Vu® Open control sys-
tem or a BACnet building automation system. 1) Drive shall be suitable for operation at
nameplate voltage ±10%.
21. Optional Seismic Isolation Package: 2) Drive shall be suitable for continuous
Package shall meet International Building Code operation at 100% of nameplate amps
and ASCE 7 seismic qualification requirements and 150% of nameplate amps for
in concurrence with ICC ES AC156 Accep- 5 seconds.
tance Criteria for Seismic Qualification by 3) Drive shall comply with applicable
Shake-Table Testing of Nonstructural Compo- ANSI, NEMA, UL and NEC standards.
nents and Systems. Manufacturer shall provide 4) Drive shall be suitable for operation in
seismic certificate from OSHPD (California ambient temperatures between 40 and
only). 122 F (4 and 50 C), 95% humidity (non-
22. Unit-Mounted Variable Frequency Drive (VFD) condensing) for altitudes up to 6000 ft
with Built-In Harmonic LiquiFlo™ II Filter: (1829 m) above sea level. Specific drive
a. Design: performance at jobsite ambient temper-
ature and elevation shall be provided by
1) The VFD shall be refrigerant cooled, the manufacturer in the bid.
microprocessor based, pulse width mod-
ulated design. Water-cooled designs are e. User Interface:
not acceptable. A single display shall provide interface for
2) Input and output power devices shall be programming and display of VFD and chiller
Insulated Gate Bipolar Transistors parameters. Viewable parameters include:
(IGBTs). 1) Operating, configuration, and fault
3) Rectifier shall convert incoming fixed messages
voltage/frequency to fixed DC voltage. 2) Frequency in hertz
4) Transistorized inverter and control regu- 3) Load and line side voltage and current
lator shall convert fixed DC voltage to a (at the VFD)
sinusoidal PWM waveform. 4) kW
5) Low voltage control sections and main 5) IGBT temperature
power sections shall be physically
f. VFD Performance:
isolated.
6) Integrated controls shall coordinate 1) The VFD Voltage Total Harmonic Dis-
motor speed to optimize chiller perfor- tortion (THD) and Harmonic Current
mance over a wide variety of operating Total Demand Distortion (TDD) shall not
conditions. exceed IEEE-519 requirements using
the VFD circuit breaker input terminals
b. Enclosure:
as the point of common coupling (PCC).
1) Pre-painted unit mounted, NEMA 1 cab- 2) The VFD full load efficiency shall meet
inet shall include hinged, lockable doors or exceed 97% at 100% VFD rated
and removable lifting lugs. ampacity.
2) The VFD shall have a short circuit inter- 3) Active rectifier shall regulate unity dis-
rupt and withstand rating of at least placement power factor to 0.99 or
65,000 amps. higher.
3) Provisions to padlock main disconnect 4) Voltage boost capability to provide full
handle in “Off” positions shall be pro- motor voltage at reduced line voltage
vided. Mechanical interlock to prevent conditions.

30
5) The VFD shall feature soft start, linear 23. Unit-Mounted Variable Frequency Drive (VFD)
acceleration, and coast to stop capabili- without Built-In Harmonic Filter:
ties. a. Design:
6) Base motor frequency shall permit
1) VFD shall be refrigerant cooled, micro-
motor to be utilized at nameplate volt-
processor based, pulse width modulated
age. Adjustable frequency range shall
design. Water-cooled designs are not
permit capacity control down to 15%.
acceptable.
7) The VFD shall have 150% instanta- 2) Output power devices shall be insulated
neous torque generation. gate bipolar transistors (IGBTs).
g. VFD Electrical Service (single point power): 3) Converter section with full-wave fixed
1) The VFD shall have input circuit breaker diode bridge rectifier shall convert
with minimum 65,000 amp interrupt incoming fixed voltage/frequency to
capacity. fixed DC voltage.
2) The VFD shall have standard branch oil 4) DC link shall filter and smooth the con-
pump circuit breaker to provide power verted DC voltage.
for chiller oil pump. 5) Transistorized inverter and control regu-
3) The VFD shall have standard 3 KVA lator shall convert fixed DC voltage to a
control power transformer with circuit sinusoidal PWM waveform.
breaker to provide power for oil heater, 6) Integrated controls shall coordinate the
VFD controls and chiller controls. motor speed to optimize chiller perfor-
4) The branch oil pump circuit breaker and mance over a wide variety of operating
control power transformer shall be fac- conditions.
tory-wired. b. Enclosure:
5) Input power shall be 380/460 vac, 1) Pre-painted unit mounted, NEMA 1 cab-
±10%, 3 Phase, 50/60 Hz, ±2% Hz. inet shall include hinged, lockable doors
h. Discrete Outputs: and removable lifting lugs.
115-v discrete contact outputs shall be pro- 2) VFD shall have a short circuit interrupt
vided for: and withstand rating of at least 100,000
amps.
1) Circuit breaker shunt trip 3) Provisions to padlock main disconnect
2) Chilled water pump handle in the “Off” positions shall be
3) Condenser water pump
provided. Mechanical interlock to pre-
4) Alarm status vent opening cabinet door with discon-
i. Analog Output: nect in the “On” position or moving
An analog (4 to 20 mA) output for head disconnect to the “ON” position while
pressure reference shall be provided. This the door is open shall be provided.
signal shall be suitable to control a 2-way or 4) Provisions shall be made for top entry of
3-way water regulating valve in the con- incoming line power cables.
denser piping. c. Heat Sink:
j. Protection (the following shall be supplied): 1) The heat sink shall be refrigerant
1) Under-voltage cooled. Heat sink and mating flanges
2) Over voltage shall be suitable for ASME design work-
3) Phase loss ing pressure of 185 psig (1276 kPa).
4) Phase reversal 2) Refrigerant cooling shall be metered by
5) Ground fault integrated standard controls to maintain
6) Phase unbalance protection heat sink temperature within acceptable
7) Single cycle voltage loss protection limits for ambient temperature.
(LF-2 VFD only) d. VFD Rating:
8) Programmable auto re-start after loss of 1) Drive shall be suitable for nameplate
power
voltage ±10%.
9) Motor overload protection (NEMA Class
2) Drive shall be suitable for continuous
10)
operation at 100% of nameplate amps
10) Motor over temperature protection
and 150% of nameplate amps for 3 sec-
k. VFD Testing: onds.
The VFD shall be factory-mounted, factory- 3) Drive shall comply with applicable UL,
wired and factory-tested on the chiller prior CE, and NEMA standards.
to shipment.

31
Guide specifications (cont)
4) Drive shall be suitable for operation in 5) Programmable auto re-start after loss of
ambient temperatures between 40 and power
104 F (4.4 and 40 C), 95% humidity 6) Motor overload protection (NEMA
(non-condensing) for altitudes up to Class 10)
3300 feet (1006 m) above sea level. 7) Motor over temperature protection
Specific drive performance at jobsite k. VFD Testing:
ambient temperature and elevation shall
The VFD shall be factory mounted, wire and
be provided by the manufacturer in the
tested on the chiller prior to shipment.
bid.
24. Unit-Mounted Variable Frequency Drive (575-v
e. User Interface:
VFD) without Built-In Harmonic Filter:
Displays shall provide interface for program-
a. Design:
ming and display of VFD and chiller parame-
ters. Viewable parameters include: 1) VFD shall be refrigerant cooled, micro-
processor based, pulse width modulated
1) Operating, configuration and fault
design. Water-cooled designs are not
messages
acceptable.
2) Frequency in hertz
2) Output power devices shall be insulated
3) Load side voltage and current (at the
gate bipolar transistors (IGBTs).
VFD)
3) Converter section with full-wave fixed-
4) kW (on the VFD interface)
diode bridge rectifier shall convert
f. VFD Performance: incoming fixed voltage/frequency to
1) VFD full load efficiency shall meet or fixed DC voltage.
exceed 97% at 100% VFD Rated 4) DC link shall filter and smooth the con-
Ampacity. verted DC voltage.
2) Base motor frequency shall be either 50 5) Transistorized inverter and control regu-
or 60 hertz. lator shall convert fixed DC voltage to a
g. VFD Electrical Service: (single point power): sinusoidal PWM waveform.
6) Integrated controls shall coordinate the
1) VFD shall have input circuit breaker with motor speed to optimize chiller perfor-
minimum 65,000 amp interrupt capac- mance over a wide variety of operating
ity.
conditions.
2) VFD shall have standard 15 amp branch
oil pump circuit breaker to provide b. Enclosure:
power for chiller oil pump. 1) Pre-painted unit mounted, NEMA 1 cab-
3) VFD shall have standard 3 kva control inet shall include hinged, lockable doors
power transformer with circuit breaker and removable lifting lugs.
provides power for oil heater, VFD con- 2) VFD shall have an Amp Interrupt
trols and chiller controls. Capacity (AIC) of 35,000 amps and a
4) The branch oil pump circuit breaker and withstand rating of 25,000 amps.
control power transformer shall be fac- 3) Provisions to padlock main disconnect
tory wired. handle in the “Off” positions shall be
5) Input power shall be 380/480 vac, ±10 provided. Mechanical interlock to pre-
percent, 3 phase, 50/60 Hz, ±3 Hz. vent opening cabinet door with discon-
h. Discrete Outputs: nect in the “On” position or moving
disconnect to the “On” position while
115-v discrete contact outputs shall be pro-
the door is open shall be provided.
vided for: 4) Provisions shall be made for top entry of
1) Chilled water pump incoming line power cables.
2) Condenser water pump
c. Heat Sink:
3) Alarm status.
1) The heat sink shall be refrigerant
i. Analog Output: cooled. Heat sink and mating flanges
An analog (4 to 20 mA) output for head shall be suitable for ASME design work-
pressure reference shall be provided. This ing pressure of 185 psig (1276 kPa).
signal shall be suitable to control a 2-way or 2) Refrigerant cooling shall be metered by
3-way water regulating valve in the con- integrated standard controls to maintain
denser piping. heat sink temperature within acceptable
j. Protection (the following shall be supplied): limits for ambient temperature.
1) Under-voltage
2) Over voltage
3) Phase loss
4) Phase unbalance protection

32
d. VFD Rating: 3) VFD shall have standard 3 kva control
1) Drive shall be suitable for nameplate power transformer with circuit breaker
voltage ±10%. provides power for oil heater, VFD con-
2) Drive shall be suitable for continuous trols and chiller controls.
operation at 100% of nameplate amps 4) The branch oil pump circuit breaker and
and 150% of nameplate amps for 3 sec- control power transformer shall be fac-
onds. tory wired.
3) Drive shall comply with applicable UL 5) Input power shall be 575 vac, ±10 per-
and NEMA standards. cent, 3 phase, 60 Hz, ±3 Hz.
4) Drive shall be suitable for operation in h. Discrete Outputs:
ambient temperatures between 40 and 115-v discrete contact outputs shall be pro-
104 F (4.4 and 40 C), 95% humidity vided for:
(non-condensing) for altitudes up to
1) Chilled water pump
3300 feet (1006 m) above sea level.
2) Condenser water pump
Specific drive performance at jobsite
3) Alarm status.
ambient temperature and elevation shall
be provided by the manufacturer in the i. Analog Output:
bid. An analog (4 to 20 mA) output for head
e. User Interface: pressure reference shall be provided. This
signal shall be suitable to control a 2-way or
Displays shall provide interface for program-
3-way water regulating valve in the con-
ming and display of VFD and chiller parame-
denser piping.
ters. Viewable parameters include:
j. Protection (the following shall be supplied):
1) Operating, configuration and fault
messages 1) Under-voltage
2) Frequency in hertz 2) Over voltage
3) Load side voltage and current (at the 3) Phase loss
VFD) 4) Phase unbalance protection
4) kW (on the VFD interface) 5) Programmable auto re-start after loss of
power
f. VFD Performance:
6) Motor overload protection (NEMA
1) VFD full load efficiency shall meet or Class 10)
exceed 97% at 100% VFD Rated 7) Motor over temperature protection
Ampacity.
k. VFD Testing:
2) Base motor frequency shall be 60 hertz.
The VFD shall be factory mounted, wire and
g. VFD Electrical Service: (single point power):
tested on the chiller prior to shipment.
1) VFD shall have input circuit breaker with
minimum 35,000 amp interrupt capac-
ity.
2) VFD shall have standard 15 amp branch
oil pump circuit breaker to provide
power for chiller oil pump.

33
Carrier Corporation • Syracuse, New York 13221 114 10-13
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Section 9 Pg 36 Catalog No. 04-52230006-01 Printed in U.S.A. Form 23XRV-7PD
Tab 9a Replaces: 23XRV-6PD

You might also like