Professional Documents
Culture Documents
PSV Scenario and Calculation PDF
PSV Scenario and Calculation PDF
1
Role of Pressure Safety Valve (PSV)
PSVs are installed to make sure that
Pressure Vessels
(ASME Sect VIII, API 520 & 521)
Unfired Boilers
(ASME Sect I)
Piping
(ASME B16.5 and 31.3)
2
Design Code & Standard (Pressure Vessel)
- ASME Section VIII
- API 520 Sizing, Selection and Installation of Pressure-Relieving
Devices in Refineries
3
Design Code & Standard (Unfired Boiler)
ASME Section I
106 106
103 106
Kerosene Pumparound
LP Steam Generator
4
PROCEDURES FOR PSV CALCULATION
LOCATE PSV and SPECIFY
RELIEF PRESSURE
DEVELOP SCENARIOS
(WHAT CAN GO WRONG?)
Required Information
CHOOSE WORST CASE
5
PSV SCENARIOS
(Refer API 521)
FOCUS ON COMMON CASES :
Effects
Pressure built-up in vessel
Outlet valve closed
Calculation
Pressure source (pump, compressor,
high pressure header)
For pump :
Is maximum pump shut-off
shut off pressure ≥ PSV set
Yes Relief rate =
pressure? maximum inlet flow
7
External Fire (1/4)
Cause
Effects
Calculation
8
External Fire - Liq. Vessel (2/4)
Relief rate (W) = Heat absorbed by liquid from external fire (Q)
Latent Heat of Vaporization of liquid (λ)
Case 1 :
If adequate drainage necessary to control the spread of major
spills
ill ffrom one area to
t another
th and d to
t control
t l surface
f drainage
d i
and refinery waste water.
Q = 43,200 x F x A0.82
76m
7.6 Case 2 :
C
If adequate drainage and firefighting equipment do not exist.
Q = 70,900 x F x A0.82
9
External Fire - Liq. Vessel (3/4)
Wetted Surface Area (A)
10
External Fire Environment Factor (F)
Liq. Vessel (4/4)
Latent Heat of Vaporization of liquid (λ)
for multi-component mixture
5 wt% flashed
Relief Pressure
Bubble point T
11
Source : API 521
Failure of Automatic Control (1/3)
Cause
- Failure of a single automatic control valve Consider this control valve fail
- Control valves are assumed to fail to non-favorable in full-open although it is
position (not necessarily to their specified fail specified as “fail-close”
position).
Effects SPLIT-RANGE
Calculation
12
Failure of Automatic Control (2/3)
CALCULATION OF MAX. FLOW THROUGH CONTROL VALVES
13
Failure of Automatic Control (1/3)
SPLIT-RANGE
EXAMPLE :
N2
Flare
Header PV01 PV02
1 FEED SURGE DRUM
1.
PIC
2. LPG VAPORIZER
Relief rate =
LPG Generated by max. steam flow
– normal LPG outlet flow
14
Hydraulic expansion (1/2)
Cause
Liquid is blocked-in
blocked in and later heated up (by hot fluid,
fluid steam
tracing / jacket or by solar radiation).
Effects
15
Hydraulic expansion (1/2)
Calculation
If applicable (e.g. in
cooling circuit)
circuit), consider
administrative control in
place of relief valve.
16
Heat Exchanger Tube Rupture (1/3)
Cause
Effects
Calculation
17
Heat Exchanger Tube Rupture (2/3)
18
ρ
Heat Exchanger Tube Rupture (3/3)
19
ρ
Total Power Failure (1/5)
Cause
Disruption
Di i in
i power supply,
l leading
l di to electrical
l i l power failure
f il off the
h
whole site.
Effects
Calculation
Note
20
Total Power Failure (2/5)
Enthalpy balance around Fractionator Column to find
excess heat (Q), which would cause vapor generation.
QC
HF HD
FEED DISTILLATE
F D
QR
HB
BOTTOMS
B
Excess Heat (Q) = HFF – HDD – HBB – QC + QR
21 Note : All values are taken from relieving condition
Total Power Failure (3/5)
Excess Heat (Q) = HFF – HDD – HBB – QC + QR
All pumps stop
t lloss off ffeed,
d di
distillate
till t and
d bottoms
b tt
22
Total Power Failure (4/5)
Reboiler Duty (QR) 2. Fired Heater
1. Thermosyphon using steam No flow to fired heater, but consider the
(QR = Normal Duty) possibility
p y that remainingg fluid inside tube is
heated up by heat from refractory surfaces
(QR = 30% of normal duty)
Steam
FUEL
23
Total Power Failure (5/5)
Relief load = V
24
Partial Power Failure (1/3)
Cause
Disruption in a single feeder, bus, circuit or line, leading to partial power
failure
Effects
- Varies, pending on power distribution system
- For Fractionating Column, worst case considered for Partial Power
Failure is simultaneous loss of reflux pump and air-cooled condenser,
while there is continuous heat input into column.
column
Calculation
For Fractionating
g Column : Enthalpy
py Balance Method
Internal Reflux Method (alternative)
Note
Usually controlling case for column PSV sizing
25
Partial Power Failure (2/3)
Worst case : simultaneous loss of reflux pump and air-
cooled condenser
QC
HF HD
FEED DISTILLATE
F D
QR
HB
BOTTOMS
B
Excess Heat (Q) = HFF – HDD – HBB – QC + QR
26
Partial Power Failure (3/3)
Temp (TH)
Latent Heat of Vaporization (λH)
Mass Flow ((mH)
Internal Reflux
Mass flow (mIR) Alternative : Internal reflux method
Relief load = mH + mIR
mRCp,R(TR-TH) + mIRλH = 0
mIR = mRCp,R(TH-TR)
λH
27
Cooling Water Failure (1/3)
Cause
Effects
Calculation
28
Cooling Water Failure (2/3)
QC
HF HD
FEED D DISTILLATE
F
QR
HB
B BOTTOMS
Excess Heat (Q) = HFF – HDD – HBB – QC + QR
Note : Need to recalculate D and HD
Alternative : Internal Reflux Method ((refer Partial Power Failure case
with re-calculated reflux temp, flowrate and specific heat)
29
Cooling Water Failure (3/3)
Temp (TH)
Latent Heat of Vaporization (λH)
Mass Flow ((mH)
Alternative : Internal reflux method
mRCp,R(TR-TH) + mIRλH = 0
mIR = mRCp,R p R((TH-TR)
λH
Specific heat (Cp,R)
Reflux
Mass flow (mR) , Temp (TR)
Effects
Calculation
31
Reflux Loss (2/2)
QC
HF HD
FEED DISTILLATE
F D
QR
HB
BOTTOMS
B
Excess Heat (Q) = HFF – HDD – HBB – QC + QR
32
Failure of air
air-cooled
cooled heat exchanger (1/2)
Cause
Failure
l off individual
d d l air-cooled
l d heat
h exchanger
h
Effects
Calculation
33
Failure of air
air-cooled
cooled heat exchanger (2/2)
QC
HF HD
FEED DISTILLATE
F D
QR
HB
BOTTOMS
B
Excess Heat (Q) = HFF – HDD – HBB – QC + QR
Note : Need to recalculate D and HD
February 3, 2014
35