PROJECT Startegic water storage Tanks -TGSW Reference 0◦ to 90◦

CONSULTANT GROUPTypsa DATE 16/5/2017


CONTRACTOR Dngo Report no 1
PAINTING MATERIAL TANK GUARD 412 INSTRUMENT ELCOMETER AF456CFBS
MARINA 1 INSPECTION INTERMEDIATE DFT
Tank no 2 CALIBRATION DATE : 25/3/217,EXP 25/5/2018
INTERNAL TANK INTERMEDIATE DFT
SL NO ORIENTATION ACTIVITY PAINTING Material RESULT (REQ.265-375mic) REMARK
1 COURSE 2 INTERMEDIATE DFT TANK GUARD 412 325CC MIC 330,316,295,324,360
2 COURSE 3 INTERMEDIATE DFT TANK GUARD 412 313.8 MIC 285,296,310,336,342
3 COURSE 4 INTERMEDIATE DFT TANK GUARD 412 329 MIC 350,338,372,280,305
4 COURSE 5 INTERMEDIATE DFT TANK GUARD 412 350.8 MIC 415,318,330,341,350
5 COURSE 6 INTERMEDIATE DFT TANK GUARD 412 332.4 MIC 320,354,338,300,350
6 COURSE 7 INTERMEDIATE DFT TANK GUARD 412 297.4 MIC 260,300,304,315,308
7 COURSE 8 INTERMEDIATE DFT TANK GUARD 412 336.6 MIC 312,325,338,340,368

WEATHER TEMPERATIURE REPORT


TIME RELATIVE HUMIDITY SURFACE TEMPERATURE AIR TEMPERATURE DEW POINT TEMPERATURE REMARK
7:30AM 16.32 20.4◦C 28◦ 4.1◦C ACCEPTED
10:00AM 18.5 25◦C 34.9◦ 6.2◦C ACCEPTED
12:30PM 20.72 32.5◦C 37.7◦ 6.9◦C ACCEPTED
3:00PM 22.35 35◦C 36.8◦ 8.9◦C ACCEPTED
.
DNGO INSPECTION QUALITY ( THIRD PARTY ) GROUPTYPSA
NAME ISMAIL AZIZ MOHAMMED SAMIUDDIN MANOLITO ARANAS LAZARO
Designation QC ENGINEER QC PAINTING & COATING INSPECTOR MATERIAL ENGINEER
Signature/Date
PROJECT Startegic water stprage Tanks -TGSW Reference 0◦ to 90◦
CONSULTANT GROUPTypsa DATE 16/5/2017
CONTRACTOR Dngo Report no 1
PAINTING MATERIAL TANK GUARD 412 INSTRUMENT ELCOMETER AF456CFBS
MARINA 2 INSPECTION INTERMEDIATE DFT
Tank no 2 CALIBRATION DATE : 25/3/217,EXP 25/5/2018
INTERNAL TANK INTERMEDIATE DFT
SL NO ORIENTATION ACTIVITY PAINTING Material RESULT (REQ.265-375mic) REMARK
1 COURSE 2 INTERMEDIATE DFT TANK GUARD 412 345.2 MIC 368,380,335,328,315
2 COURSE 3 INTERMEDIATE DFT TANK GUARD 412 311 MIC 285,300,290,330,350
3 COURSE 4 INTERMEDIATE DFT TANK GUARD 412 323 MIC 320,298,362,275,360
4 COURSE 5 INTERMEDIATE DFT TANK GUARD 412 336 MIC 315,308,382,355,320
5 COURSE 6 INTERMEDIATE DFT TANK GUARD 412 352.6 MIC 370,365,338,322,368
6 COURSE 7 INTERMEDIATE DFT TANK GUARD 412 327 MIC 350,260,325,355,345
7 COURSE 8 INTERMEDIATE DFT TANK GUARD 412 341.2 MIC 339,365,340,337,325

WEATHER TEMPERATIURE REPORT


TIME RELATIVE HUMIDITY SURFACE TEMPERATURE AIR TEMPERATURE DEW POINT TEMPERATURE REMARK
7:30AM 16.32 20.4◦C 28◦ 4.1◦C ACCEPTED
10:00AM 18.5 25◦C 34.9◦ 6.2◦C ACCEPTED
12:30PM 20.72 32.5◦C 37.7◦ 6.9◦C ACCEPTED
3:00PM 22.35 35◦C 36.8◦ 8.9◦C ACCEPTED
.
DNGO INSPECTION QUALITY ( THIRD PARTY ) GROUPTYPSA
NAME ISMAIL AZIZ MOHAMMED SAMIUDDIN MANOLITO ARANAS LAZARO
Designation QC ENGINEER QC PAINTING & COATING INSPECTOR MATERIAL ENGINEER
Signature/Date
PROJECT Startegic water stprage Tanks -TGSW Reference 0◦ to 90◦
CONSULTANT GROUPTypsa DATE 16/5/2017
CONTRACTOR Dngo Report no 1
PAINTING MATERIAL TANK GUARD 412 INSTRUMENT ELCOMETER AF456CFBS
MARINA 3 INSPECTION INTERMEDIATE DFT
Tank no 2 CALIBRATION DATE : 25/3/217,EXP 25/5/2018
INTERNAL TANK INTERMEDIATE DFT
SL NO ORIENTATION ACTIVITY PAINTING Material RESULT (REQ.265-375mic) REMARK
1 COURSE 2 INTERMEDIATE DFT TANK GUARD 412 340 MIC 339,385,400,346,230
2 COURSE 3 INTERMEDIATE DFT TANK GUARD 412 356.4 MIC 285,345,377,385,380
3 COURSE 4 INTERMEDIATE DFT TANK GUARD 412 341 MIC 249,299,374,390,293
4 COURSE 5 INTERMEDIATE DFT TANK GUARD 412 339.6 MIC 324,370,276,280,348
5 COURSE 6 INTERMEDIATE DFT TANK GUARD 412 333.8 MIC 447,290,300,337,295
6 COURSE 7 INTERMEDIATE DFT TANK GUARD 412 273.4 MIC 366,215,,405,375,366
7 COURSE 8 INTERMEDIATE DFT TANK GUARD 412 347.2 MIC 328,397,340,323,348

WEATHER TEMPERATIURE REPORT


TIME RELATIVE HUMIDITY SURFACE TEMPERATURE AIR TEMPERATURE DEW POINT TEMPERATURE REMARK
7:30AM 16.32 20.4◦C 28◦ 4.1◦C ACCEPTED
10:00AM 18.5 25◦C 34.9◦ 6.2◦C ACCEPTED
12:30PM 20.72 32.5◦C 37.7◦ 6.9◦C ACCEPTED
3:00PM 22.35 35◦C 36.8◦ 8.9◦C ACCEPTED
.
DNGO INSPECTION QUALITY ( THIRD PARTY ) GROUPTYPSA
NAME ISMAIL AZIZ MOHAMMED SAMIUDDIN MANOLITO ARANAS LAZARO
Designation QC ENGINEER QC PAINTING & COATING INSPECTOR MATERIAL ENGINEER
Signature/Date
PROJECT Startegic water stprage Tanks -TGSW Reference 0◦ to 90◦
CONSULTANT GROUPTypsa DATE 16/5/2017
CONTRACTOR Dngo Report no 1
PAINTING MATERIAL TANK GUARD 412 INSTRUMENT ELCOMETER AF456CFBS
MARINA 4 INSPECTION INTERMEDIATE DFT
Tank no 2 CALIBRATION DATE : 25/3/217,EXP 25/5/2018
INTERNAL TANK INTERMEDIATE DFT
SL NO ORIENTATION ACTIVITY PAINTING Material RESULT (REQ.265-375mic) REMARK
1 COURSE 2 INTERMEDIATE DFT TANK GUARD 412 252.6 MIC 279,328,358,335,298
2 COURSE 3 INTERMEDIATE DFT TANK GUARD 412 335.4 MIC 335,320,308,324,390
3 COURSE 4 INTERMEDIATE DFT TANK GUARD 412 344.4 MIC 314,333,425,265,385,
4 COURSE 5 INTERMEDIATE DFT TANK GUARD 412 317.4 MIC 300,295,305,338,349
5 COURSE 6 INTERMEDIATE DFT TANK GUARD 412 339.8 MIC 311,293,333,458,304
6 COURSE 7 INTERMEDIATE DFT TANK GUARD 412 354.4 MIC 394,362,370,315,330
7 COURSE 8 INTERMEDIATE DFT TANK GUARD 412 296.8 MIC 314,282,295,289,304

WEATHER TEMPERATIURE REPORT


TIME RELATIVE HUMIDITY SURFACE TEMPERATURE AIR TEMPERATURE DEW POINT TEMPERATURE REMARK
7:30AM 16.32 20.4◦C 28◦ 4.1◦C ACCEPTED
10:00AM 18.5 25◦C 34.9◦ 6.2◦C ACCEPTED
12:30PM 20.72 32.5◦C 37.7◦ 6.9◦C ACCEPTED
3:00PM 22.35 35◦C 36.8◦ 8.9◦C ACCEPTED
.
DNGO INSPECTION QUALITY ( THIRD PARTY ) GROUPTYPSA
NAME ISMAIL AZIZ MOHAMMED SAMIUDDIN MANOLITO ARANAS LAZARO
Designation QC ENGINEER QC PAINTING & COATING INSPECTOR MATERIAL ENGINEER
Signature/Date
PROJECT Startegic water stprage Tanks -TGSW Reference 0◦ to 90◦
CONSULTANT GROUPTypsa DATE 16/5/2017
CONTRACTOR Dngo Report no 1
PAINTING MATERIAL TANK GUARD 412 INSTRUMENT ELCOMETER AF456CFBS
MARINA 5 INSPECTION INTERMEDIATE DFT
Tank no 2 CALIBRATION DATE : 25/3/217,EXP 25/5/2018
INTERNAL TANK INTERMEDIATE DFT
SL NO ORIENTATION ACTIVITY PAINTING Material RESULT (REQ.265-375mic) REMARK
1 COURSE 2 INTERMEDIATE DFT TANK GUARD 412 347.4 MIC 282,375,330,382,365
2 COURSE 3 INTERMEDIATE DFT TANK GUARD 412 326 MIC 310,335,365,295,325
3 COURSE 4 INTERMEDIATE DFT TANK GUARD 412 342 MIC 351,345,324,333,357
4 COURSE 5 INTERMEDIATE DFT TANK GUARD 412 310.6 MIC 323,279,299,314,338
5 COURSE 6 INTERMEDIATE DFT TANK GUARD 412 333.8 MIC 293,357,335,345,339
6 COURSE 7 INTERMEDIATE DFT TANK GUARD 412 347 MIC 390,394,296,330,325
7 COURSE 8 INTERMEDIATE DFT TANK GUARD 412 366.2 MIC 385,338,425,368,315

WEATHER TEMPERATIURE REPORT


TIME RELATIVE HUMIDITY SURFACE TEMPERATURE AIR TEMPERATURE DEW POINT TEMPERATURE REMARK
7:30AM 16.32 20.4◦C 28◦ 4.1◦C ACCEPTED
10:00AM 18.5 25◦C 34.9◦ 6.2◦C ACCEPTED
12:30PM 20.72 32.5◦C 37.7◦ 6.9◦C ACCEPTED
3:00PM 22.35 35◦C 36.8◦ 8.9◦C ACCEPTED
.
DNGO INSPECTION QUALITY ( THIRD PARTY ) GROUPTYPSA
NAME ISMAIL AZIZ MOHAMMED SAMIUDDIN MANOLITO ARANAS LAZARO
Designation QC ENGINEER QC PAINTING & COATING INSPECTOR MATERIAL ENGINEER
Signature/Date
PROJECT Startegic water stprage Tanks -TGSW Reference 0◦ to 90◦
CONSULTANT GROUPTypsa DATE 16/5/2017
CONTRACTOR Dngo Report no 1
PAINTING MATERIAL TANK GUARD 412 INSTRUMENT ELCOMETER AF456CFBS
MARINA 6 INSPECTION INTERMEDIATE DFT
Tank no 2 CALIBRATION DATE : 25/3/217,EXP 25/5/2018
INTERNAL TANK INTERMEDIATE DFT
SL NO ORIENTATION ACTIVITY PAINTING Material RESULT (REQ.265-375mic) REMARK
1 COURSE 2 INTERMEDIATE DFT TANK GUARD 412 367.6 MIC 348,395,368,352,375,
2 COURSE 3 INTERMEDIATE DFT TANK GUARD 412 372.2 MIC 339,345,385,420,372
3 COURSE 4 INTERMEDIATE DFT TANK GUARD 412 299.4 MIC 298,320,345,369,372
4 COURSE 5 INTERMEDIATE DFT TANK GUARD 412 300.4 MIC 348,315,305,265,269
5 COURSE 6 INTERMEDIATE DFT TANK GUARD 412 341.6 MIC 394,332,331,285,366
6 COURSE 7 INTERMEDIATE DFT TANK GUARD 412 334.4 MIC 383,323,303,313,350
7 COURSE 8 INTERMEDIATE DFT TANK GUARD 412 338.8 MIC 349,359,348,318,320

WEATHER TEMPERATIURE REPORT


TIME RELATIVE HUMIDITY SURFACE TEMPERATURE AIR TEMPERATURE DEW POINT TEMPERATURE REMARK
7:30AM 16.32 20.4◦C 28◦ 4.1◦C ACCEPTED
10:00AM 18.5 25◦C 34.9◦ 6.2◦C ACCEPTED
12:30PM 20.72 32.5◦C 37.7◦ 6.9◦C ACCEPTED
3:00PM 22.35 35◦C 36.8◦ 8.9◦C ACCEPTED
.
DNGO INSPECTION QUALITY ( THIRD PARTY ) GROUPTYPSA
NAME ISMAIL AZIZ MOHAMMED SAMIUDDIN MANOLITO ARANAS LAZARO
Designation QC ENGINEER QC PAINTING & COATING INSPECTOR MATERIAL ENGINEER
Signature/Date
PROJECT Startegic water stprage Tanks -TGSW Reference 0◦ to 90◦
CONSULTANT GROUPTypsa DATE 16/5/2017
CONTRACTOR Dngo Report no 1
PAINTING MATERIAL TANK GUARD 412 INSTRUMENT ELCOMETER AF456CFBS
MARINA 7 INSPECTION INTERMEDIATE DFT
Tank no 2 CALIBRATION DATE : 25/3/217,EXP 25/5/2018
INTERNAL TANK INTERMEDIATE DFT
SL NO ORIENTATION ACTIVITY PAINTING Material RESULT (REQ.265-375mic) REMARK
1 COURSE 2 INTERMEDIATE DFT TANK GUARD 412 362.6 MIC 370,324,349,376,394
2 COURSE 3 INTERMEDIATE DFT TANK GUARD 412 309.2 MIC 306,334,284,296,326
3 COURSE 4 INTERMEDIATE DFT TANK GUARD 412 333.2 MIC 325,358,366,311,306
4 COURSE 5 INTERMEDIATE DFT TANK GUARD 412 321.2 MIC 340,305,314,317,330
5 COURSE 6 INTERMEDIATE DFT TANK GUARD 412 368.4 MIC 390,353,389,345,365
6 COURSE 7 INTERMEDIATE DFT TANK GUARD 412 355 MIC 333,362,345,385,350
7 COURSE 8 INTERMEDIATE DFT TANK GUARD 412 328.8 MIC 315,340,354,270,365

WEATHER TEMPERATIURE REPORT


TIME RELATIVE HUMIDITY SURFACE TEMPERATURE AIR TEMPERATURE DEW POINT TEMPERATURE REMARK
7:30AM 16.32 20.4◦C 28◦ 4.1◦C ACCEPTED
10:00AM 18.5 25◦C 34.9◦ 6.2◦C ACCEPTED
12:30PM 20.72 32.5◦C 37.7◦ 6.9◦C ACCEPTED
3:00PM 22.35 35◦C 36.8◦ 8.9◦C ACCEPTED
.
DNGO INSPECTION QUALITY ( THIRD PARTY ) GROUPTYPSA
NAME ISMAIL AZIZ MOHAMMED SAMIUDDIN MANOLITO ARANAS LAZARO
Designation QC ENGINEER QC PAINTING & COATING INSPECTOR MATERIAL ENGINEER
Signature/Date
PROJECT Startegic water stprage Tanks -TGSW Reference 0◦ to 90◦
CONSULTANT GROUPTypsa DATE 16/5/2017
CONTRACTOR Dngo Report no 1
PAINTING MATERIAL TANK GUARD 412 INSTRUMENT ELCOMETER AF456CFBS
MARINA 8 INSPECTION INTERMEDIATE DFT
Tank no 2 CALIBRATION DATE : 25/3/217,EXP 25/5/2018
INTERNAL TANK INTERMEDIATE DFT
SL NO ORIENTATION ACTIVITY PAINTING Material RESULT (REQ.265-375mic) REMARK
1 COURSE 2 INTERMEDIATE DFT TANK GUARD 412 373.6 MIC 366,395,370,392,345
2 COURSE 3 INTERMEDIATE DFT TANK GUARD 412 308.4 MIC 345,297,278,302,320
3 COURSE 4 INTERMEDIATE DFT TANK GUARD 412 324.8 MIC 309,323,342,380,270
4 COURSE 5 INTERMEDIATE DFT TANK GUARD 412 267.8 MIC 294,271,337,357,340
5 COURSE 6 INTERMEDIATE DFT TANK GUARD 412 360.8 MIC 333,353,393,375,350
6 COURSE 7 INTERMEDIATE DFT TANK GUARD 412 347.6 MIC 365,380,355,308,330
7 COURSE 8 INTERMEDIATE DFT TANK GUARD 412 366.2 MIC 392,360,375,344,360

WEATHER TEMPERATIURE REPORT


TIME RELATIVE HUMIDITY SURFACE TEMPERATURE AIR TEMPERATURE DEW POINT TEMPERATURE REMARK
7:30AM 16.32 20.4◦C 28◦ 4.1◦C ACCEPTED
10:00AM 18.5 25◦C 34.9◦ 6.2◦C ACCEPTED
12:30PM 20.72 32.5◦C 37.7◦ 6.9◦C ACCEPTED
3:00PM 22.35 35◦C 36.8◦ 8.9◦C ACCEPTED
.
DNGO INSPECTION QUALITY ( THIRD PARTY ) GROUPTYPSA
NAME ISMAIL AZIZ MOHAMMED SAMIUDDIN MANOLITO ARANAS LAZARO
Designation QC ENGINEER QC PAINTING & COATING INSPECTOR MATERIAL ENGINEER
Signature/Date
PROJECT Startegic water stprage Tanks -TGSW Reference 0◦ to 90◦
CONSULTANT GROUPTypsa DATE 16/5/2017
CONTRACTOR Dngo Report no 1
PAINTING MATERIAL TANK GUARD 412 INSTRUMENT ELCOMETER AF456CFBS
MARINA 9 INSPECTION INTERMEDIATE DFT
Tank no 2 CALIBRATION DATE : 25/3/217,EXP 25/5/2018
INTERNAL TANK INTERMEDIATE DFT
SL NO ORIENTATION ACTIVITY PAINTING Material RESULT (REQ.265-375mic) REMARK
1 COURSE 2 INTERMEDIATE DFT TANK GUARD 412 323.2 MIC 266,285,305,320,340
2 COURSE 3 INTERMEDIATE DFT TANK GUARD 412 342 MIC 392,345,382,375,370
3 COURSE 4 INTERMEDIATE DFT TANK GUARD 412 341.2 MIC 365,345,338,321,337
4 COURSE 5 INTERMEDIATE DFT TANK GUARD 412 300.6 MIC 334,274,285,295,315
5 COURSE 6 INTERMEDIATE DFT TANK GUARD 412 358.2 MIC 332,345,365,369,380
6 COURSE 7 INTERMEDIATE DFT TANK GUARD 412 354.6 MIC 334,365,348,398,328
7 COURSE 8 INTERMEDIATE DFT TANK GUARD 412 306.4 MIC 333,289,265,300,345
400,354,367,348,357
WEATHER TEMPERATIURE REPORT
TIME RELATIVE HUMIDITY SURFACE TEMPERATURE AIR TEMPERATURE DEW POINT TEMPERATURE REMARK
7:30AM 16.32 20.4◦C 28◦ 4.1◦C ACCEPTED
10:00AM 18.5 25◦C 34.9◦ 6.2◦C ACCEPTED
12:30PM 20.72 32.5◦C 37.7◦ 6.9◦C ACCEPTED
3:00PM 22.35 35◦C 36.8◦ 8.9◦C ACCEPTED
.
DNGO INSPECTION QUALITY ( THIRD PARTY ) GROUPTYPSA
NAME ISMAIL AZIZ MOHAMMED SAMIUDDIN MANOLITO ARANAS LAZARO
Designation QC ENGINEER QC PAINTING & COATING INSPECTOR MATERIAL ENGINEER
Signature/Date
PROJECT Startegic water stprage Tanks -TGSW Reference 0◦ to 90◦
CONSULTANT GROUPTypsa DATE 16/5/2017
CONTRACTOR Dngo Report no 1
PAINTING MATERIAL TANK GUARD 412 INSTRUMENT ELCOMETER AF456CFBS
MARINA 10 INSPECTION INTERMEDIATE DFT
Tank no 2 CALIBRATION DATE : 25/3/217,EXP 25/5/2018
INTERNAL TANK INTERMEDIATE DFT
SL NO ORIENTATION ACTIVITY PAINTING Material RESULT (REQ.265-375mic) REMARK
1 COURSE 2 INTERMEDIATE DFT TANK GUARD 412 301.1 MIC 392,360,375,344,360
2 COURSE 3 INTERMEDIATE DFT TANK GUARD 412 360.8 MIC 333,353,393,375,350
3 COURSE 4 INTERMEDIATE DFT TANK GUARD 412 339.8 MIC 311,293,333,458,304
4 COURSE 5 INTERMEDIATE DFT TANK GUARD 412 299.4 MIC 334,274,285,289,315
5 COURSE 6 INTERMEDIATE DFT TANK GUARD 412 321.2 MIC 383,283,303,313,350
6 COURSE 7 INTERMEDIATE DFT TANK GUARD 412 328.8 MIC 340,305,314,317,330
7 COURSE 8 INTERMEDIATE DFT TANK GUARD 412 315,340,354,270,365

WEATHER TEMPERATIURE REPORT


TIME RELATIVE HUMIDITY SURFACE TEMPERATURE AIR TEMPERATURE DEW POINT TEMPERATURE REMARK
7:30AM 16.32 20.4◦C 28◦ 4.1◦C ACCEPTED
10:00AM 18.5 25◦C 34.9◦ 6.2◦C ACCEPTED
12:30PM 20.72 32.5◦C 37.7◦ 6.9◦C ACCEPTED
3:00PM 22.35 35◦C 36.8◦ 8.9◦C ACCEPTED
.
DNGO INSPECTION QUALITY ( THIRD PARTY ) GROUPTYPSA
NAME ISMAIL AZIZ MOHAMMED SAMIUDDIN MANOLITO ARANAS LAZARO
Designation QC ENGINEER QC PAINTING & COATING INSPECTOR MATERIAL ENGINEER
Signature/Date
PROJECT Startegic water stprage Tanks -TGSW Reference 0◦ to 90◦
CONSULTANT GROUPTypsa DATE 16/5/2017
CONTRACTOR Dngo Report no 1
PAINTING MATERIAL TANK GUARD 412 INSTRUMENT ELCOMETER AF456CFBS
MARINA 11 INSPECTION INTERMEDIATE DFT
Tank no 2 CALIBRATION DATE : 25/3/217,EXP 25/5/2018
INTERNAL TANK INTERMEDIATE DFT
SL NO ORIENTATION ACTIVITY PAINTING Material RESULT (REQ.265-375mic) REMARK
1 COURSE 2 INTERMEDIATE DFT TANK GUARD 412 280.8 MIC 300,394,306,280,376
2 COURSE 3 INTERMEDIATE DFT TANK GUARD 412 333.2 MIC 325,358,366,311,306
3 COURSE 4 INTERMEDIATE DFT TANK GUARD 412 344 MIC 351,345,334,333,357
4 COURSE 5 INTERMEDIATE DFT TANK GUARD 412 365.2 MIC 400,354,367,348,357
5 COURSE 6 INTERMEDIATE DFT TANK GUARD 412 257 MIC 285,300,290,330,350
6 COURSE 7 INTERMEDIATE DFT TANK GUARD 412 349.6 MIC 385,338,425,368,315
7 COURSE 8 INTERMEDIATE DFT TANK GUARD 412 369 MIC 393,335,357,370,390

WEATHER TEMPERATIURE REPORT


TIME RELATIVE HUMIDITY SURFACE TEMPERATURE AIR TEMPERATURE DEW POINT TEMPERATURE REMARK
7:30AM 16.32 20.4◦C 28◦ 4.1◦C ACCEPTED
10:00AM 18.5 25◦C 34.9◦ 6.2◦C ACCEPTED
12:30PM 20.72 32.5◦C 37.7◦ 6.9◦C ACCEPTED
3:00PM 22.35 35◦C 36.8◦ 8.9◦C ACCEPTED
.
DNGO INSPECTION QUALITY ( THIRD PARTY ) GROUPTYPSA
NAME ISMAIL AZIZ MOHAMMED SAMIUDDIN MANOLITO ARANAS LAZARO
Designation QC ENGINEER QC PAINTING & COATING INSPECTOR MATERIAL ENGINEER
Signature/Date
PROJECT Startegic water stprage Tanks -TGSW
CONSULTANT GROUPTypsa
CONTRACTOR Dngo
PAINTING MATERIAL TANK GUARD 412
MARINA 1
Tank no 2
INTERNAL TANK INTERMEDIATE DFT
SL NO ORIENTATION ACTIVITY PAINTING Material
1 COURSE 2 INTERMEDIATE DFT TANK GUARD 412
2 COURSE 3 INTERMEDIATE DFT TANK GUARD 412
3 COURSE 4 INTERMEDIATE DFT TANK GUARD 412
4 COURSE 5 INTERMEDIATE DFT TANK GUARD 412
5 COURSE 6 INTERMEDIATE DFT TANK GUARD 412
6 COURSE 7 INTERMEDIATE DFT TANK GUARD 412
7 COURSE 8 INTERMEDIATE DFT TANK GUARD 412

WEATHER TEMPERATIURE REPORT


TIME RELATIVE HUMIDITY SURFACE TEMPERATURE AIR TEMPERATURE
7:30AM 16.32 20.4◦C 28◦
10:00AM 18.5 25◦C 34.9◦
12:30PM 20.72 32.5◦C 37.7◦
3:00PM 22.35 35◦C 36.8◦
.
DNGO INSPECTION QUALITY ( THIRD PARTY )
NAME ISMAIL AZIZ MOHAMMED SAMIUDDIN
Designation QC ENGINEER QC PAINTING & COATING INSPECTOR
Signature/Date
e Tanks -TGSW Reference 90◦ to 180◦
sa DATE 17/5/2017
Report no 1
D 412 INSTRUMENT ELCOMETER AF456CFBS
INSPECTION INTERMEDIATE DFT
CALIBRATION DATE : 25/3/217,EXP 25/5/2018
NK INTERMEDIATE DFT
RESULT (REQ.265-375mic) REMARK
280.8 MIC 318,364,355,288,380
333.2 MIC 365,370,343,328,360
344 MIC 360,364,337,300,278
365.2 MIC 315,343,273,383,260
257 MIC 270,353,282,333,310
349.6 MIC 295,340,345,268,365
369 MIC 373,312,257,385,342

MPERATIURE REPORT
DEW POINT TEMPERATURE REMARK
4.1◦C ACCEPTED
6.2◦C ACCEPTED
6.9◦C ACCEPTED
8.9◦C ACCEPTED

TION QUALITY ( THIRD PARTY ) GROUPTYPSA


MOHAMMED SAMIUDDIN MANOLITO ARANAS LAZARO
INTING & COATING INSPECTOR MATERIAL ENGINEER
PROJECT Startegic water stprage Tanks -TGSW Reference 90◦ to 180◦
CONSULTANT GROUPTypsa DATE 17/5/2017
CONTRACTOR Dngo Report no 1
PAINTING MATERIAL TANK GUARD 412 INSTRUMENT ELCOMETER AF456CFBS
MARINA 2 INSPECTION INTERMEDIATE DFT
Tank no 2 CALIBRATION DATE : 25/3/217,EXP 25/5/2018
INTERNAL TANK INTERMEDIATE DFT
SL NO ORIENTATION ACTIVITY PAINTING Material RESULT (REQ.265-375mic) REMARK
1 COURSE 2 INTERMEDIATE DFT TANK GUARD 412 280.8 MIC 340,393,306,248,365
2 COURSE 3 INTERMEDIATE DFT TANK GUARD 412 333.2 MIC 318,340,270,300,315
3 COURSE 4 INTERMEDIATE DFT TANK GUARD 412 344 MIC 295,378,320,358,280
4 COURSE 5 INTERMEDIATE DFT TANK GUARD 412 365.2 MIC 268,370,362,379,330
5 COURSE 6 INTERMEDIATE DFT TANK GUARD 412 257 MIC 298,270,348,340,328
6 COURSE 7 INTERMEDIATE DFT TANK GUARD 412 349.6 MIC 307,320,268,335,325
7 COURSE 8 INTERMEDIATE DFT TANK GUARD 412 369 MIC 36,343,305,334,370

WEATHER TEMPERATIURE REPORT


TIME RELATIVE HUMIDITYSURFACE TEMPERATURE AIR TEMPERATURE DEW POINT TEMPERATURE REMARK
7:30AM 16.32 20.4◦C 28◦ 4.1◦C ACCEPTED
10:00AM 18.5 25◦C 34.9◦ 6.2◦C ACCEPTED
12:30PM 20.72 32.5◦C 37.7◦ 6.9◦C ACCEPTED
3:00PM 22.35 35◦C 36.8◦ 8.9◦C ACCEPTED
.
DNGO INSPECTION QUALITY ( THIRD PARTY ) GROUPTYPSA
NAME ISMAIL AZIZ MOHAMMED SAMIUDDIN MANOLITO ARANAS LAZARO
Designation QC ENGINEER QC PAINTING & COATING INSPECTOR MATERIAL ENGINEER
Signature/Date
PROJECT Startegic water stprage Tanks -TGSW Reference 90◦ to 180◦
CONSULTANT GROUPTypsa DATE 17/5/2017
CONTRACTOR Dngo Report no 1
PAINTING MATERIAL TANK GUARD 412 INSTRUMENT ELCOMETER AF456CFBS
MARINA 3 INSPECTION INTERMEDIATE DFT
Tank no 2 CALIBRATION DATE : 25/3/217,EXP 25/5/2018
INTERNAL TANK INTERMEDIATE DFT
SL NO ORIENTATION ACTIVITY PAINTING Material RESULT (REQ.265-375mic) REMARK
1 COURSE 2 INTERMEDIATE DFT TANK GUARD 412 313.6 MIC 370,302,306,260,330
2 COURSE 3 INTERMEDIATE DFT TANK GUARD 412 329.6 MIC 376,329,348,325,270
3 COURSE 4 INTERMEDIATE DFT TANK GUARD 412 348.2 MIC 369,345,337,403,287
4 COURSE 5 INTERMEDIATE DFT TANK GUARD 412 314.6 MIC 335,234,317,348,339
5 COURSE 6 INTERMEDIATE DFT TANK GUARD 412 312.4 MIC 328,310,324,335,265
6 COURSE 7 INTERMEDIATE DFT TANK GUARD 412 344 MIC 373,350,355,342,300
7 COURSE 8 INTERMEDIATE DFT TANK GUARD 412 344.6 MIC 333,347,298,345,400

WEATHER TEMPERATIURE REPORT


TIME RELATIVE HUMIDITY SURFACE TEMPERATURE AIR TEMPERATURE DEW POINT TEMPERATURE REMARK
7:30AM 16.32 20.4◦C 28◦ 4.1◦C ACCEPTED
10:00AM 18.5 25◦C 34.9◦ 6.2◦C ACCEPTED
12:30PM 20.72 32.5◦C 37.7◦ 6.9◦C ACCEPTED
3:00PM 22.35 35◦C 36.8◦ 8.9◦C ACCEPTED
.
DNGO INSPECTION QUALITY ( THIRD PARTY ) GROUPTYPSA
NAME ISMAIL AZIZ MOHAMMED SAMIUDDIN MANOLITO ARANAS LAZARO
Designation QC ENGINEER QC PAINTING & COATING INSPECTOR MATERIAL ENGINEER
Signature/Date
PROJECT Startegic water stprage Tanks -TGSW Reference 90◦ to 180◦
CONSULTANT GROUPTypsa DATE 17/5/2017
CONTRACTOR Dngo Report no 1
PAINTING MATERIAL TANK GUARD 412 INSTRUMENT ELCOMETER AF456CFBS
MARINA 4 INSPECTION INTERMEDIATE DFT
Tank no 2 CALIBRATION DATE : 25/3/217,EXP 25/5/2018
INTERNAL TANK INTERMEDIATE DFT
SL NO ORIENTATION ACTIVITY PAINTING Material RESULT (REQ.265-375mic) REMARK
1 COURSE 2 INTERMEDIATE DFT TANK GUARD 412 329.4 MIC 371,326,320,290,342
2 COURSE 3 INTERMEDIATE DFT TANK GUARD 412 332 MIC 373,336,351,318,282
3 COURSE 4 INTERMEDIATE DFT TANK GUARD 412 340.4 MIC 332,330,323,369,348
4 COURSE 5 INTERMEDIATE DFT TANK GUARD 412 313 MIC 299,237,358,342,329
5 COURSE 6 INTERMEDIATE DFT TANK GUARD 412 322.6 MIC 316,252,322,328,395
6 COURSE 7 INTERMEDIATE DFT TANK GUARD 412 350.6 MIC 358,338,332,355,370
7 COURSE 8 INTERMEDIATE DFT TANK GUARD 412 319.4 MIC 310,374,347,302,264

WEATHER TEMPERATIURE REPORT


TIME RELATIVE HUMIDITY SURFACE TEMPERATURE AIR TEMPERATURE DEW POINT TEMPERATURE REMARK
7:30AM 16.32 20.4◦C 28◦ 4.1◦C ACCEPTED
10:00AM 18.5 25◦C 34.9◦ 6.2◦C ACCEPTED
12:30PM 20.72 32.5◦C 37.7◦ 6.9◦C ACCEPTED
3:00PM 22.35 35◦C 36.8◦ 8.9◦C ACCEPTED
.
DNGO INSPECTION QUALITY ( THIRD PARTY ) GROUPTYPSA
NAME ISMAIL AZIZ MOHAMMED SAMIUDDIN MANOLITO ARANAS LAZARO
Designation QC ENGINEER QC PAINTING & COATING INSPECTOR MATERIAL ENGINEER
Signature/Date
PROJECT Startegic water stprage Tanks -TGSW Reference 90◦ to 180◦
CONSULTANT GROUPTypsa DATE 17/5/2017
CONTRACTOR Dngo Report no 1
PAINTING MATERIAL TANK GUARD 412 INSTRUMENT ELCOMETER AF456CFBS
MARINA 5 INSPECTION INTERMEDIATE DFT
Tank no 2 CALIBRATION DATE : 25/3/217,EXP 25/5/2018
INTERNAL TANK INTERMEDIATE DFT
SL NO ORIENTATION ACTIVITY PAINTING Material RESULT (REQ.265-375mic) REMARK
1 COURSE 2 INTERMEDIATE DFT TANK GUARD 412 336.6 MIC 363,344,325,356,295
2 COURSE 3 INTERMEDIATE DFT TANK GUARD 412 342 MIC 305,358,346,370,331
3 COURSE 4 INTERMEDIATE DFT TANK GUARD 412 339 MIC 331,347,338,333,346
4 COURSE 5 INTERMEDIATE DFT TANK GUARD 412 331.2 MIC 330,335,355,348,288
5 COURSE 6 INTERMEDIATE DFT TANK GUARD 412 328 MIC 334,320,270,342,374
6 COURSE 7 INTERMEDIATE DFT TANK GUARD 412 355.6 MIC 365,380,355,308,370
7 COURSE 8 INTERMEDIATE DFT TANK GUARD 412 359.2 MIC 392,360,375,344,325

WEATHER TEMPERATIURE REPORT


TIME RELATIVE HUMIDITY SURFACE TEMPERATURE AIR TEMPERATURE DEW POINT TEMPERATURE REMARK
7:30AM 16.32 20.4◦C 28◦ 4.1◦C ACCEPTED
10:00AM 18.5 25◦C 34.9◦ 6.2◦C ACCEPTED
12:30PM 20.72 32.5◦C 37.7◦ 6.9◦C ACCEPTED
3:00PM 22.35 35◦C 36.8◦ 8.9◦C ACCEPTED
.
DNGO INSPECTION QUALITY ( THIRD PARTY ) GROUPTYPSA
NAME ISMAIL AZIZ MOHAMMED SAMIUDDIN MANOLITO ARANAS LAZARO
Designation QC ENGINEER QC PAINTING & COATING INSPECTOR MATERIAL ENGINEER
Signature/Date
PROJECT Startegic water stprage Tanks -TGSW
CONSULTANT GROUPTypsa
CONTRACTOR Dngo
PAINTING MATERIAL TANK GUARD 412
MARINA 6
Tank no 2
INTERNAL TANK INTERMEDIATE DFT
SL NO ORIENTATION ACTIVITY PAINTING Material
1 COURSE 2 INTERMEDIATE DFT TANK GUARD 412
2 COURSE 3 INTERMEDIATE DFT TANK GUARD 412
3 COURSE 4 INTERMEDIATE DFT TANK GUARD 412
4 COURSE 5 INTERMEDIATE DFT TANK GUARD 412
5 COURSE 6 INTERMEDIATE DFT TANK GUARD 412
6 COURSE 7 INTERMEDIATE DFT TANK GUARD 412
7 COURSE 8 INTERMEDIATE DFT TANK GUARD 412

WEATHER TEMPERATIURE REPORT


TIME RELATIVE HUMIDITY SURFACE TEMPERATURE AIR TEMPERATURE
7:30AM 16.32 20.4◦C 28◦
10:00AM 18.5 25◦C 34.9◦
12:30PM 20.72 32.5◦C 37.7◦
3:00PM 22.35 35◦C 36.8◦
.
DNGO INSPECTION QUALITY ( THIRD PARTY )
NAME ISMAIL AZIZ MOHAMMED SAMIUDDIN
Designation QC ENGINEER QC PAINTING & COATING INSPECTOR
Signature/Date
ge Tanks -TGSW Reference 90◦ to 180◦
ypsa DATE 17/5/2017
Report no 1
RD 412 INSTRUMENT ELCOMETER AF456CFBS
INSPECTION INTERMEDIATE DFT
CALIBRATION DATE : 25/3/217,EXP 25/5/2018
NK INTERMEDIATE DFT
RESULT (REQ.265-375mic) REMARK
356.8 MIC 342,375,330,382,355
321.6 MIC 310,283,333,358,324
333 MIC 300,365,333,322,345
330.2 MIC 360,305,341,317,328
340.2 MIC 330,343,323,345,360
361.2 MIC 373,362,345,385,341
327 MIC 345,340,354,270,326

MPERATIURE REPORT
DEW POINT TEMPERATURE REMARK
4.1◦C ACCEPTED
6.2◦C ACCEPTED
6.9◦C ACCEPTED
8.9◦C ACCEPTED

CTION QUALITY ( THIRD PARTY ) GROUPTYPSA


MOHAMMED SAMIUDDIN MANOLITO ARANAS LAZARO
INTING & COATING INSPECTOR MATERIAL ENGINEER
PROJECT Startegic water stprage Tanks -TGSW Reference 90◦ to 180◦
CONSULTANT GROUPTypsa DATE 17/5/2017
CONTRACTOR Dngo Report no 1
PAINTING MATERIAL TANK GUARD 412 INSTRUMENT ELCOMETER AF456CFBS
MARINA 7 INSPECTION INTERMEDIATE DFT
Tank no 2 CALIBRATION DATE : 25/3/217,EXP 25/5/2018
INTERNAL TANK INTERMEDIATE DFT
SL NO ORIENTATION ACTIVITY PAINTING Material RESULT (REQ.265-375mic) REMARK
1 COURSE 2 INTERMEDIATE DFT TANK GUARD 412 307.2 MIC 336,302,306,250,342
2 COURSE 3 INTERMEDIATE DFT TANK GUARD 412 325.6 MIC 320,329,348,339,292
3 COURSE 4 INTERMEDIATE DFT TANK GUARD 412 326.6 MIC 369,345,337,303,279
4 COURSE 5 INTERMEDIATE DFT TANK GUARD 412 323.6 MIC 378,315,305,265,355
5 COURSE 6 INTERMEDIATE DFT TANK GUARD 412 319.6 MIC 304,333,331,285,345
6 COURSE 7 INTERMEDIATE DFT TANK GUARD 412 320.8 MIC 303,306,312,313,370
7 COURSE 8 INTERMEDIATE DFT TANK GUARD 412 337.4 MIC 309,369,348,318,343

WEATHER TEMPERATIURE REPORT


TIME RELATIVE HUMIDITY SURFACE TEMPERATURE AIR TEMPERATURE DEW POINT TEMPERATURE REMARK
7:30AM 16.32 20.4◦C 28◦ 4.1◦C ACCEPTED
10:00AM 18.5 25◦C 34.9◦ 6.2◦C ACCEPTED
12:30PM 20.72 32.5◦C 37.7◦ 6.9◦C ACCEPTED
3:00PM 22.35 35◦C 36.8◦ 8.9◦C ACCEPTED
.
DNGO INSPECTION QUALITY ( THIRD PARTY ) GROUPTYPSA
NAME ISMAIL AZIZ MOHAMMED SAMIUDDIN MANOLITO ARANAS LAZARO
Designation QC ENGINEER QC PAINTING & COATING INSPECTOR MATERIAL ENGINEER
Signature/Date
PROJECT Startegic water stprage Tanks -TGSW Reference 90◦ to 180◦
CONSULTANT GROUPTypsa DATE 17/5/2017
CONTRACTOR Dngo Report no 1
PAINTING MATERIAL TANK GUARD 412 INSTRUMENT ELCOMETER AF456CFBS
MARINA 8 INSPECTION INTERMEDIATE DFT
Tank no 2 CALIBRATION DATE : 25/3/217,EXP 25/5/2018
INTERNAL TANK INTERMEDIATE DFT
SL NO ORIENTATION ACTIVITY PAINTING Material RESULT (REQ.265-375mic) REMARK
1 COURSE 2 INTERMEDIATE DFT TANK GUARD 412 344.6 MIC 331,339,430,328,295
2 COURSE 3 INTERMEDIATE DFT TANK GUARD 412 339.8 MIC 305,365,325,337,367
3 COURSE 4 INTERMEDIATE DFT TANK GUARD 412 328.8 MIC 314,340,310,335,345
4 COURSE 5 INTERMEDIATE DFT TANK GUARD 412 356.8 MIC 370,332,352,331,399
5 COURSE 6 INTERMEDIATE DFT TANK GUARD 412 339.2 MIC 322,375,336,321,342
6 COURSE 7 INTERMEDIATE DFT TANK GUARD 412 332.8 MIC 345,362,312,330,315
7 COURSE 8 INTERMEDIATE DFT TANK GUARD 412 350.8 MIC 385,370,345,320,334

WEATHER TEMPERATIURE REPORT


TIME RELATIVE HUMIDITY SURFACE TEMPERATURE AIR TEMPERATURE DEW POINT TEMPERATURE REMARK
7:30AM 16.32 20.4◦C 28◦ 4.1◦C ACCEPTED
10:00AM 18.5 25◦C 34.9◦ 6.2◦C ACCEPTED
12:30PM 20.72 32.5◦C 37.7◦ 6.9◦C ACCEPTED
3:00PM 22.35 35◦C 36.8◦ 8.9◦C ACCEPTED
.
DNGO INSPECTION QUALITY ( THIRD PARTY ) GROUPTYPSA
NAME ISMAIL AZIZ MOHAMMED SAMIUDDIN MANOLITO ARANAS LAZARO
Designation QC ENGINEER QC PAINTING & COATING INSPECTOR MATERIAL ENGINEER
Signature/Date
PROJECT Startegic water stprage Tanks -TGSW Reference 90◦ to 180◦
CONSULTANT GROUPTypsa DATE 17/5/2017
CONTRACTOR Dngo Report no 1
PAINTING MATERIAL TANK GUARD 412 INSTRUMENT ELCOMETER AF456CFBS
MARINA 9 INSPECTION INTERMEDIATE DFT
Tank no 2 CALIBRATION DATE : 25/3/217,EXP 25/5/2018
INTERNAL TANK INTERMEDIATE DFT
SL NO ORIENTATION ACTIVITY PAINTING Material RESULT (REQ.265-375mic) REMARK
1 COURSE 2 INTERMEDIATE DFT TANK GUARD 412 346.2 MIC 364,336,325,336,370
2 COURSE 3 INTERMEDIATE DFT TANK GUARD 412 328.4 MIC 320,308,330,346,338
3 COURSE 4 INTERMEDIATE DFT TANK GUARD 412 335 MIC 331,315,328,343,358
4 COURSE 5 INTERMEDIATE DFT TANK GUARD 412 312.8 MIC 355,298,265,305,341
5 COURSE 6 INTERMEDIATE DFT TANK GUARD 412 321.2 MIC 308,336,315,337,310
6 COURSE 7 INTERMEDIATE DFT TANK GUARD 412 300.8 MIC 290,318,,306,270,320
7 COURSE 8 INTERMEDIATE DFT TANK GUARD 412 326 MIC 355,364,333,300,278

WEATHER TEMPERATIURE REPORT


TIME RELATIVE HUMIDITY SURFACE TEMPERATURE AIR TEMPERATURE DEW POINT TEMPERATURE REMARK
7:30AM 16.32 20.4◦C 28◦ 4.1◦C ACCEPTED
10:00AM 18.5 25◦C 34.9◦ 6.2◦C ACCEPTED
12:30PM 20.72 32.5◦C 37.7◦ 6.9◦C ACCEPTED
3:00PM 22.35 35◦C 36.8◦ 8.9◦C ACCEPTED
.
DNGO INSPECTION QUALITY ( THIRD PARTY ) GROUPTYPSA
NAME ISMAIL AZIZ MOHAMMED SAMIUDDIN MANOLITO ARANAS LAZARO
Designation QC ENGINEER QC PAINTING & COATING INSPECTOR MATERIAL ENGINEER
Signature/Date
PROJECT Startegic water stprage Tanks -TGSW Reference 90◦ to 180◦
CONSULTANT GROUPTypsa DATE 17/5/2017
CONTRACTOR Dngo Report no 1
PAINTING MATERIAL TANK GUARD 412 INSTRUMENT ELCOMETER AF456CFBS
MARINA 10 INSPECTION INTERMEDIATE DFT
Tank no 2 CALIBRATION DATE : 25/3/217,EXP 25/5/2018
INTERNAL TANK INTERMEDIATE DFT
SL NO ORIENTATION ACTIVITY PAINTING Material RESULT (REQ.265-375mic) REMARK
1 COURSE 2 INTERMEDIATE DFT TANK GUARD 412 324.2 MIC 360,375,300,298,288
2 COURSE 3 INTERMEDIATE DFT TANK GUARD 412 338.6 MIC 341,355,306,371,320
3 COURSE 4 INTERMEDIATE DFT TANK GUARD 412 323.2 MIC 327,372,345,307,265
4 COURSE 5 INTERMEDIATE DFT TANK GUARD 412 328.4 MIC 310,322,315,330,365
5 COURSE 6 INTERMEDIATE DFT TANK GUARD 412 327.4 MIC 285,375,390,300,287
6 COURSE 7 INTERMEDIATE DFT TANK GUARD 412 339.8 MIC 305,298,384,340,372
7 COURSE 8 INTERMEDIATE DFT TANK GUARD 412 348 MIC 378,336,355,367,304

WEATHER TEMPERATIURE REPORT


TIME RELATIVE HUMIDITY SURFACE TEMPERATURE AIR TEMPERATURE DEW POINT TEMPERATURE REMARK
7:30AM 16.32 20.4◦C 28◦ 4.1◦C ACCEPTED
10:00AM 18.5 25◦C 34.9◦ 6.2◦C ACCEPTED
12:30PM 20.72 32.5◦C 37.7◦ 6.9◦C ACCEPTED
3:00PM 22.35 35◦C 36.8◦ 8.9◦C ACCEPTED
.
DNGO INSPECTION QUALITY ( THIRD PARTY ) GROUPTYPSA
NAME ISMAIL AZIZ MOHAMMED SAMIUDDIN MANOLITO ARANAS LAZARO
Designation QC ENGINEER QC PAINTING & COATING INSPECTOR MATERIAL ENGINEER
Signature/Date
PROJECT Startegic water stprage Tanks -TGSW
CONSULTANT GROUPTypsa
CONTRACTOR Dngo
PAINTING MATERIAL TANK GUARD 412
MARINA 11
Tank no 2
INTERNAL TANK INTERMEDIATE DFT
SL NO ORIENTATION ACTIVITY PAINTING Material
1 COURSE 2 INTERMEDIATE DFT TANK GUARD 412
2 COURSE 3 INTERMEDIATE DFT TANK GUARD 412
3 COURSE 4 INTERMEDIATE DFT TANK GUARD 412
4 COURSE 5 INTERMEDIATE DFT TANK GUARD 412
5 COURSE 6 INTERMEDIATE DFT TANK GUARD 412
6 COURSE 7 INTERMEDIATE DFT TANK GUARD 412
7 COURSE 8 INTERMEDIATE DFT TANK GUARD 412

WEATHER TEMPERATIURE REPORT


TIME RELATIVE HUMIDITY SURFACE TEMPERATURE AIR TEMPERATURE
7:30AM 16.32 20.4◦C 28◦
10:00AM 18.5 25◦C 34.9◦
12:30PM 20.72 32.5◦C 37.7◦
3:00PM 22.35 35◦C 36.8◦
.
DNGO INSPECTION QUALITY ( THIRD PARTY )
NAME ISMAIL AZIZ MOHAMMED SAMIUDDIN
Designation QC ENGINEER QC PAINTING & COATING INSPECTOR
Signature/Date
ge Tanks -TGSW Reference 90◦ to 180◦
ypsa DATE 17/5/2017
Report no 1
RD 412 INSTRUMENT ELCOMETER AF456CFBS
INSPECTION INTERMEDIATE DFT
CALIBRATION DATE : 25/3/217,EXP 25/5/2018
TANK INTERMEDIATE DFT
RESULT (REQ.265-375mic) REMARK
350 MIC 316,394,350,325,365
333.2 MIC 325,358,366,311,306
353.6 MIC 351,345,334,333,357
365.2 MIC 400,354,367,348,357
311 MIC 285,300,290,330,350
366.2 MIC 385,338,425,368,315
369 MIC 393,335,357,370,390

R TEMPERATIURE REPORT
DEW POINT TEMPERATURE REMARK
4.1◦C ACCEPTED
6.2◦C ACCEPTED
6.9◦C ACCEPTED
8.9◦C ACCEPTED

ON QUALITY ( THIRD PARTY ) GROUPTYPSA


OHAMMED SAMIUDDIN MANOLITO ARANAS LAZARO
TING & COATING INSPECTOR MATERIAL ENGINEER