DW/172
DW/172 Specification for Kitchen Ventilation Systems
Specification ACKNOWLEDGEMENTS
The HVCA records its appreciation and thanks to the
many people and organisations who gave advice and
information during the preparation of this
specification, in particular to those members of the
ISBN 0-903783-29-0
©2005 HVCA
1
DW/172 Specification for Kitchen Ventilation Systems
FOREWORD
S
ince its publication in 1999, the HVCA’s Standard for Kitchen Ventilation
Systems (DW/171) has sold an impressive 2,300 copies. More importantly, it
has become widely acknowledged as the standard for kitchen ventilation design
throughout in the UK.
Like any other standard, however, it must be revised and updated from time to time, in
the light of new thinking, new procedures and new developments.
This review process has now been completed by the HVCA Ductwork Group. The
result is this new publication– designated DW/172 and re-badged as a specification
rather than simply a standard, in recognition of the authoritative status it has achieved
within the kitchen ventilation sector.
Among the many amendments and clarifications contained in the new document, three
are worthy of particular note.
Firstly, the previous publication made reference to the feasibility of establishing a test
procedure for grease filters. Since then, the Loss Prevention Council has published –
and the Association of British Insurers has endorsed – LPS1263, which sets out the
procedures, including the testing and grading of grease filters, required to reduce the
risk of fire in commercial kitchens.
Secondly, the section on appliances and their coefficients has been significantly
expanded, and now includes advice on the requirement for an interlock between the
ventilation system and the gas supply.
And, finally, for the purpose of this specification, stainless steel is the only suitable
material for the fabrication of canopies, and mesh filters can only be used as a
secondary method of grease extraction. For ventilated ceilings, however, some
manufacturers incorporate anodized aluminium into the supporting frame. This form of
construction should be agreed with the client or specifier.
All other sections have been revised and updated in the hope and expectation that the
HVCA’s Specification for Kitchen Ventilation Systems (DW/172) will be widely used
by all sectors of the catering industry.
3
DW/172 Specification for Kitchen Ventilation Systems
CONTENTS Page
Acknowledgements 1
Drafting Panel 1
Foreword 3
Specifications and Contents 5
Section 1 Introduction. 7
Section 2 Considerations prior to design 8
Section 3 Design Criteria 9
Section 4 Canopy Dimensions 11
Section 5 Extract Flow Rates 12
Section 6 Make-up Air 17
Section 7 Types of Canopy 20
Section 8 Ventilated Ceilings 22
Section 9 Spigot Connections 26
Section 10 Materials 27
Section 11 Construction 28
Section 12 Polishing 29
Section 13 Grease Filtration 29
Section 14 Canopy Lighting 34
Section 15 Ductwork 35
Section 16 Installation 38
Section 17 Fans 39
Section 18 Attenuation 42
Section 19 Dampers 42
Section 20 Fire Suppression 43
Section 21 Service Distribution Units 46
Section 22 Odour Control 47
Section 23 Heat Recovery 49
Section 24 Testing and Commissioning 50
Section 25 Cleaning and Maintenance 51
Appendix A Filter Classifications 53
Appendix B Conversion Factors 54
Appendix C IP Ratings 55
Appendix D Fire and Smoke Extract Ductwork 56
Appendix E Air Conditioned Kitchens 58
Appendix F Bibliography 60
5
DW/172 Specification for Kitchen Ventilation Systems
QUALITY ASSURANCE
This specification can be used as one criterion that will
assist customers and specifiers in performing their
important role of defining the standard of installation
they require.
The HVCA anticipates that this specification will be
complementary to quality assurance schemes and
quality assessment schedules. Where forming the basis
of an independent certification scheme, it defines good
practice in standards of installation.
SCOPE
This specification covers the type of kitchen ventilation
systems usually found in commercial premises.
The specification is not intended for residential
premises, although some of its provisions will apply.
This specification makes use of terms “should”,
“shall” and “must” when prescribing procedures:
- The term “must” identifies a requirement by law at
the time of publication.
- The term “shall” prescribes a procedure which it is
intended to be complied with, in full and without
deviation.
- The term “should” prescribes a procedure which it is
intended to be complied with unless, after prior
consideration, deviation is considered to be
equivalent or better.