Valid as of software version:
prosonic M
V 01.02.00 (amplifier)
V 1.0 (communication)
FMU 40/41/43
with Foundation Fieldbus
Ultrasonic Level Measurement
Operating Instructions
FMU 41
TM
FMU 40
FMU 43
TM
F
Prosonic M FMU 40/41/43 with Foundation Fieldbus
Short instructions
KA 183F/00/a2/02.02
52010993 Prosonic M - Quick Setup
000
measured value Contrast: + or +
008
- + E E dist./
Group E
meas value
- + E
selection
00 002 003 004 005 059 006 008 051 052 053
basic setup tank shape medium process empty blocking full dist./ check range of start
property cond. calibr. distance calibr. meas value distance mapping mapping
+
01 - dome - unknown - standard input E BD is input F D and L are - ok confirm
safety settings ceiling - liquid - calm (s. sketch) displayed (s. sketch) displayed - too small suggestion
- horizontal - > 4 mm surface (s. sketch) (s. sketch) - too big or specify
0E
temperature cyl. - < 4 mm - add. - unknown range
- bypass agitator - manual
04 … …
linearisation
05
extended calibr.
06
output (HART, FF)
profibus param.(PA) BD
100%
0E 0E1 0E2
Envelope curve plot settings recording D
curve
09 092 … … E
display language
F
-
0A 0A0 0A1 0A3 0A4
diagnostics present previous … … reset unlock … … L
error error parameter
0C 0C0 333 (HART) 100 (HART)
system tag no. … … 33333 (PA,FF) 2457 (PA,FF) 0%
parameter
BD: blocking distance
52010993
L00-FMU4xxx-05-00-00-en-001
You can find an overview of all the device functions in the Appendix.
You can find a detailed description of all the device functions in the operating
instructions BA 240F/00/en "Prosonic M - Description of Instrument Functions". This is
located on the supplied documentation CD-ROM.
2
Prosonic M FMU 40/41/43 with Foundation Fieldbus
Table of contents
1 Safety instructions . . . . . . . . . . . . . . 4 8.4 Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . 56
8.5 Spare parts (housing type F12) . . . . . . . . . . . 57
1.1 Designated use . . . . . . . . . . . . . . . . . . . . . . . . 4 8.6 Spare parts (housing type T12) . . . . . . . . . . . 58
1.2 Installation, commissioning, operation . . . . . . 4 8.7 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
1.3 Hazardous area . . . . . . . . . . . . . . . . . . . . . . . . 4 8.8 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
1.4 Notes on safety conventions and symbols . . . 5 8.9 Software history . . . . . . . . . . . . . . . . . . . . . . . 59
8.10 Contact addresses of Endress+Hauser . . . . . 59
2 Identification . . . . . . . . . . . . . . . . . . . 6
2.1 Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 9 Accessories . . . . . . . . . . . . . . . . . . . . 60
2.2 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . 6
9.1 Weather protection cover . . . . . . . . . . . . . . . . 60
2.3 Certificates and approvals . . . . . . . . . . . . . . . . 7
9.2 Installation bracket for FMU 40/41 . . . . . . . . . 60
2.4 Registered trademarks . . . . . . . . . . . . . . . . . . 7
9.3 Adapter flange for FMU 40 / FMU 41 . . . . . . . 61
9.4 Cantilever . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
3 Installation. . . . . . . . . . . . . . . . . . . . . 8 9.5 Mounting Frame for Cantilever . . . . . . . . . . . . 63
3.1 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 9.6 Wall Bracket for Cantilever . . . . . . . . . . . . . . . 63
3.2 Installation variants . . . . . . . . . . . . . . . . . . . . . 9 9.7 Mounting bracket for FMU 43 . . . . . . . . . . . . . 64
3.3 Installation conditions . . . . . . . . . . . . . . . . . . 10 9.8 Service Interface FXA 193 . . . . . . . . . . . . . . . 64
3.4 Measuring range . . . . . . . . . . . . . . . . . . . . . . 13 9.9 Remote display and operation FHX 40 . . . . . 65
3.5 Installation (FMU 40/41) . . . . . . . . . . . . . . . . . 14
3.6 Installation check . . . . . . . . . . . . . . . . . . . . . . 15 10 Technical Data . . . . . . . . . . . . . . . . . 66
10.1 Technical data at a glance . . . . . . . . . . . . . . . 66
4 Wiring . . . . . . . . . . . . . . . . . . . . . . . . 16
4.1 Electrical connection . . . . . . . . . . . . . . . . . . . 16 11 Appendix . . . . . . . . . . . . . . . . . . . . . . 70
4.2 Terminal assignment . . . . . . . . . . . . . . . . . . . 18 11.1 Operating menu . . . . . . . . . . . . . . . . . . . . . . . 70
4.3 Cable specifications Foundation Fieldbus . . 18 11.2 Measuring principle . . . . . . . . . . . . . . . . . . . . 72
4.4 Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . 18
4.5 Recommended connection . . . . . . . . . . . . . . 19
4.6 Checking the connection . . . . . . . . . . . . . . . . 19 Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
5 Operation . . . . . . . . . . . . . . . . . . . . . 20
5.1 Display and operating elements . . . . . . . . . . 20
5.2 Function codes . . . . . . . . . . . . . . . . . . . . . . . 22
5.3 Foundation Fieldbus interface . . . . . . . . . . . . 23
5.4 Operation using the on-site display VU 331 . 40
5.5 Lock/unlock configuration . . . . . . . . . . . . . . . 41
5.6 Resetting the customer parameters . . . . . . . 41
5.7 Resetting an interference echo suppression (tank
map) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
6 Commissioning . . . . . . . . . . . . . . . . 43
6.1 Power up instrument . . . . . . . . . . . . . . . . . . . 43
6.2 Basic calibration . . . . . . . . . . . . . . . . . . . . . . 44
6.3 Envelope curve . . . . . . . . . . . . . . . . . . . . . . . 49
7 Troubleshooting . . . . . . . . . . . . . . . 52
7.1 System error messages . . . . . . . . . . . . . . . . . 52
7.2 Application errors . . . . . . . . . . . . . . . . . . . . . 54
3
Safety instructions Prosonic M FMU 40/41/43 with Foundation Fieldbus
1 Safety instructions
4
Prosonic M FMU 40/41/43 with Foundation Fieldbus Safety instructions
Symbol Meaning
Warning!
# A warning highlights actions or procedures which, if not performed correctly,
will lead to personal injury, a safety hazard or destruction of the instrument
Caution!
" Caution highlights actions or procedures which, if not performed correctly,
may lead to personal injury or incorrect functioning of the instrument
Note!
. areas.
– Devices located in safe areas still require a certificate if their outputs run into
explosion hazardous areas
Direct voltage
% A terminal to which or from which a direct current or voltage may be applied or
supplied
Alternating voltage
& A terminal to which or from which an alternating (sine-wave) current or voltage
may be applied or supplied
Grounded terminal
) A grounded terminal, which as far as the operator is concerned, is already
grounded by means of an earth grounding system
5
Identification Prosonic M FMU 40/41/43 with Foundation Fieldbus
2 Identification
2.1 Nameplate
Order Code: 1
Ser.-No.: 2 IP68 / NEMA 6P
Profibus PA
Foundation Fieldbus
90 … 253 V AC 4VA 3
5
10,5 …32 V DC 1W
14 … 36 V DC 0,8W
4 … 20 mA HART 2-wire
4-wire 4
TA > 70°C : t >85°C
if modification Patents
X = see sep. label
Dat./Insp.: D01345-B
L00-FMU4xxxx-18-00-00-yy-001
1: Order Code; 2: erial number; 3: Designation according to Directive 94/9/EC and designation of the type of
protection (only for certified device variants); 4: Reference to additional safety-relevant documentation (only
for certified device variants); 5: Communication variant and supply voltage (the appropriate option is
highlighted)
6
Prosonic M FMU 40/41/43 with Foundation Fieldbus Identification
Safety instructions
Additional safety instructions (XA, ZE, ZD) are supplied with certified device versions.
Refer to the nameplate for the names of the safety instructions that apply to your device
variant.
7
Installation Prosonic M FMU 40/41/43 with Foundation Fieldbus
3 Installation
3.1 Dimensions
ca. 86 65 78 65 78
68 94
32
Ø 129
ENDRESS+HAUSER
Ø 129
Prosonic M ENDRESS+HAUSER
Prosonic M
162
150
85 85
FMU 40 FMU 41
60 AF
60 AF
G2”
~148
22
G1½”
~148
22
2 NPT
1½ NPT ~83
~87
Ø 39 Ø 50
~86 65 78
Ø 129
ENDRESS+HAUSER
89
Prosonic M
150
~248
2 x M8 119 25
85
~123
120
ANSI 4” Ø 230
DN 100
Alternatively, a separate
flange can be used.
2 25
40 40
11
L00-FMU4xxxx-06-00-00-en-003
8
Prosonic M FMU 40/41/43 with Foundation Fieldbus Installation
Sealing ring
(EPDM)
supplied
ENDRESS+HAUSER
Prosonic M
Sealing ring
(EPDM)
adapter flange supplied
sensor nozzle
L00-FMU4xxxx-17-00-00-en-002
ER
HAUS
ESS+
ENDR ic M
Proson
slip-on flange
nozzle
e.g.
Zone 20 sensor
.
Zone 20
L00-FMU43xxxx-17-00-00-en-001
9
Installation Prosonic M FMU 40/41/43 with Foundation Fieldbus
2 3 4
7
1
5
1/6D
D
6 L
α
L00-FMU4xxxx-17-00-00-de-005
• Do not install the sensor in the middle of the tank (3). We recommend leaving a
distance between the sensor and the tank wall (1) measuring 1/6 of the tank diameter.
• Use a protective cover, in order to protect the device from direct sun or rain (2).
• Avoid measurements through the filling curtain (4).
• Make sure that equipment (5) such as limit switches, temperature sensors, etc. are
not located within the emitting angle α. In particular, symmetrical equipment (6) such
as heating coils, baffles etc. can influence measurement.
• Align the sensor so that it is vertical to the product surface (7).
• Never install two ultrasonic measuring devices in a tank, as the two signals may affect
each other.
• To estimate the transmitted echo beam and its detection range, use the 3 dB emitting
angle α.
Sensor α L r
FMU 43 6° 15 m 0,79 m
L00-FMU4xxxx-17-00-00-en-010
10
Prosonic M FMU 40/41/43 with Foundation Fieldbus Installation
inflow outflow
empty calibr. BD
1 x b0
b0
L00-FMU4xxxx-17-00-00-en-003
11
Installation Prosonic M FMU 40/41/43 with Foundation Fieldbus
min. 2 Hmax
α
min. 2 Hmax
min. 3 H max
BD
empty calibr.
L00-FMU4xxxx-17-00-00-en-012
12
Prosonic M FMU 40/41/43 with Foundation Fieldbus Installation
FMU 43
FMU 40/41
BD FMU 40
SD D [mm] max. L [mm]
50 approx. 80
80 approx. 240
100 approx. 300
FMU 41
D [mm] max. L [mm]
E F
80 approx. 240
L 100 approx. 300
L
FMU 43
D D > approx. 100 mm
L < approx. 300 mm
D
FMU 40 0,25 m
FMU 41 0,4 m
FMU 43 0,6 m
" Caution!
If the blocking distance is undershot, it may cause device malfunction.
13
Installation Prosonic M FMU 40/41/43 with Foundation Fieldbus
3.4.3 Range
The sensor range is dependent on the measuring conditions. Refer to Technical
Information TI 365F/00/en for an estimation. The maximum range is shown in the above
diagram (valid for good conditions).
FMU 40 5m
FMU 41 8m
FMU 43 15 m
max torque
20 Nm
L00-FMU4xxxx-17-00-00-en-009
14
Prosonic M FMU 40/41/43 with Foundation Fieldbus Installation
15
Wiring Prosonic M FMU 40/41/43 with Foundation Fieldbus
4 Wiring
# Warning!
When you use the measuring system in hazardous areas, make sure to comply with
national standards and the specifications in the safety instructions (XA’s). Make sure
you use the specified cable gland.
1 2 3 4
L00-FMU4xxxx-04-00-00-yy-008
16
Prosonic M FMU 40/41/43 with Foundation Fieldbus Wiring
1 2 3 4
L00-FMU4xxxx-04-00-00-yy-009
L00-FMU4xxxx-04-00-00-yy-011
17
Wiring Prosonic M FMU 40/41/43 with Foundation Fieldbus
L00-FMR2xxxx-04-00-00-de-007
standard 9V 32 V
The current consumption is approx. 13 mA for the range of voltages given above.
18
Prosonic M FMU 40/41/43 with Foundation Fieldbus Wiring
1 1
L00-FMP4xxxx-17-00-00-yy-043
" Caution!
Applications, which are subject to the explosion prevention, permit only under special
conditions the repeated grounding of the protective screen , see to EN 60 079-14..
19
Operation Prosonic M FMU 40/41/43 with Foundation Fieldbus
5 Operation
END
Order MICR
RES
S+HA
OPIL
Ser.-NoCode:
.: OT USE
II R
Messbe
Measur reich
ing
range
U 16...36 max.
4...20 20
Maulburg
mAV DC
m
IP
65
T
Made in Germany
A >70°C
LCD
: t
>85°C
ENDRESS + HAUSER
– + E
Symbols 3 keys
L00-FMxxxxxx-07-00-00-en-001
position in menu
label
measured value
* display
group selection
selection list
position in menu
label
function with
free parameter
help texts
L00-FMxxxxxx-07-00-00-en-002
20
Prosonic M FMU 40/41/43 with Foundation Fieldbus Operation
Sybmol Meaning
ALARM_SYMBOL
This alarm symbol appears when the instrument is in an alarm state. If the symbol flashes, this
indicates a warning.
LOCK_SYMBOL
This lock symbol appears when the instrument is locked,i.e. if no input is possible.
COM_SYMBOL
This communication symbol appears when a data transmission via e.g. HART, PFOFIBUS-PA
or Foundation Fieldbus is in progress.
SIMULATION_SWITCH_ENABLE
This communication symbol appears when simulation in FF is enabled via the DIP switch.
Key(s) Meaning
O and F
or Contrast settings of the LCD
S and F
Hardware lock / unlock
After a hardware lock, an operation of the instrument via display or
O and S and F communication is not possible!
The hardware can only be unlocked via the display. An unlock parameter must
be entered to do so.
21
Operation Prosonic M FMU 40/41/43 with Foundation Fieldbus
005
Function
Function group
L00-FMU4xxxx-07-00-00-en-001
• basic setup 00
• safety settings 01
• linearisation 04
...
The third digit numbers the individual functions within the function group:
22
Prosonic M FMU 40/41/43 with Foundation Fieldbus Operation
5.3.1 Synopsis
There are two possibilities of connecting up a Foundation Fieldbus:
CO: Controller
H1: H1 interface
AI: Analog input
AO: Analog output
DI: Digital input
CO H1 AI AO DI CO H1 AI AO DI
FF/H1
CO: Controller
H1: H1 interface
AI: Analog input
CO CN AI AO DI
AO: Analog output
DI: Digital input
ControlNet or HSE
L00-FMR2xxxx-14-00-06-en-026
23
Operation Prosonic M FMU 40/41/43 with Foundation Fieldbus
END
Order MICR
RES
S+HA
OPIL
Ser.-NoCode:
.: OT USE
II R
Messbe
Measur reich
ing
range
U 16...36 max.
4...20 20
Maulburg
mAV DC
m
IP
65
T
Made in Germany
A >70°C
: t
>85°C
default settings:
write protection OFF
simulation ON (i.e. simulation is
allowed in the configuration tool)
on
off
SIM WP
write protection
on
off
SIM WP
simulation
L00-FMxxxxxx-19-00-00-en-002
Device identification
Foundation Fieldbus identifies the device by its identification code and automatically
allocates an appropriate field address. There is no separate hardware switch for this
purpose.
24
Prosonic M FMU 40/41/43 with Foundation Fieldbus Operation
E+H_PROSONIC_M_XXXXXXXX
NODE_ADDRESS the fieldbus node to which the device is connected (is automatically allocated by
the Configurator)
Device_ID = 452B48100F-XXXXXXXX
whereby:
A right-hand mouse click on the name opens up a menu from which the PD_TAG and
NODE_ADDRESS can be changed.
A click on the name expands the device tree to show the function blocks available for it:
E+H_PROSONIC_M_XXXXXXXX
RESOURCE_XXXXXX (RB2)
TRANSDUCER_XXXXXX (TBRL)
ANALOG_INPUT_1_XXXXXX (AI)
ANALOG_INPUT_2_XXXXXX (AI)
PID_XXXXXX(PID)
AR_XXXXXX (AR)
IS_XXXXXX (IS)
SC_XXXXXX (SC)
IT_XXXXXX (IT)
25
Operation Prosonic M FMU 40/41/43 with Foundation Fieldbus
Secondary value
(distance)
Analog Input Function Block 2
parameters that are important to OUT
Third value the process control system,
(temperature) e.g. scaling, status
L00-FMU4XXXX-02-00-00-en-003
26
Prosonic M FMU 40/41/43 with Foundation Fieldbus Operation
E+H_PROSONIC_M_XXXXXXXX
RESOURCE_XXXXXX (RB2)
TRANSDUCER_XXXXXX (TBUL)
ANALOG_INPUT_1_XXXXXX (AI)
Operation
The resource block contains the parameters used to describe physical resources of the
device. It has no linkable inputs or outputs.
The resource block is opened by a click on the resource line.
If the NI-FBUS Configurator is being used, a series of file tabs appears on the screen.
The files can be opened to view and/or edit the parameters in the following table. A short
description of the parameter function appears on the side of the screen. A change in
the parameter is stored by pressing the WRITE CHANGES button when the block is out
of service. Press the READ ALL button to check the values stored in the device.
Parameters
Parameter Description
MODE_BLK Lists the actual, target, permitted and normal operating modes of the block.
– Target: changes the operating mode of the block
– Actual: indicates the current operating mode of the block
– Permitted: states which operating modes are allowed
– Normal: indicates the normal operating mode of the block
The possible operating modes of the resources block are:
– AUTO: the block is operating as normal
– OOS: the block is out of service.
If the resource block is out of service, then all blocks within the device
(resource) are forced into the same status.
RS_STATE Indicates the state of the resource block application state machine
– On-line: block in AUTO mode
– Standby: block in OOS mode
BLOCK_ALM Shows any configuration, hardware, connection and system problems in the
block. The cause of the alert is to be seen in the subcode field.
The function of the resource block parameters not described here can can be taken
from the Foundation Fieldbus specification, see www.fieldbus.org.
27
Operation Prosonic M FMU 40/41/43 with Foundation Fieldbus
E+H_PROSONIC_M_XXXXXXXX
RESOURCE_XXXXXX (RB2)
TRANSDUCER_XXXXXX (TBUL)
ANALOG_INPUT_1_XXXXXX (AI)
Operation
The transducer block contains the parameters required to calibrate the device. These
parameters can also be addressed by using the VU 331 display module.
The transducer block is opened by clicking on the transducer line.
Parameter changes from the tool are made off-line while the device is operating. The
changes are downloaded by first setting MODE_BLK = OOS then pressing the WRITE
CHANGES button. Press the READ ALL button to check the values stored in the device.
Normally operation is resumed as soon as MODE-BLK is set to AUTO.
Parameter Description
MODE_BLK See description in Resource block. The possible operating modes of the
transducer block are:
– AUTO: the block is operating as normal.
– OOS: the block is out of service.
BLOCK_ERROR Shows the error status associated with the block components
– Out-of-Service: the block is in OOS mode.
Output values
Parameter Description
Configuration parameters
The transducer block also contains the configuration parameters, which are used to
commission and calibrate the instrument. They are identical to the functions of the
operating menu, except for the service parameters which are not accessible on the bus.
Thus, the calibration procedure via the display module (chapter "Commissioning") is
equally valid for a calibration via a network configuration tool.
A complete list of the configuration parameters can be found in the "Description of
Instrument Functions", BA 240F/00/en.
28
Prosonic M FMU 40/41/43 with Foundation Fieldbus Operation
Methods
The Foundation Fieldbus specification provides for the use of so-called methods to
simplify the operation of the device. A method is an interactive sequence of steps that
must be followed in order to obtain a particular function from the device.
The Prosonic M has got the following methods:
• Set to customer default
• Basic setup
• Safety settings
• Acknowledge alarm
• temperature
• Linearisation
• Extended calibration
• Output
• Display
• Diagnostics
• System parameters
• Lock TB Manufacturer parameters
Most of these methods are identical to the respective function group in the operating
menu. A detailed description of them can be found in the "Description of Instrument
functions", BA 240F.
29
Operation Prosonic M FMU 40/41/43 with Foundation Fieldbus
Parameter Position rel. Variable Name Size Type Read Write Storage
Indicator Index [bytes] Class
0 EH_USONICLEVEL_CAL_BASIC
Standard Parameter
E+H Parameter
30
Prosonic M FMU 40/41/43 with Foundation Fieldbus Operation
Parameter Position rel. Variable Name Size Type Read Write Storage
Indicator Index [bytes] Class
31
Operation Prosonic M FMU 40/41/43 with Foundation Fieldbus
E+H_MICROPILOT_M_XXXXXXXX
RESOURCE_XXXXXX (RB2)
TRANSDUCER_XXXXXX (TBRL)
ANALOG_INPUT_1_XXXXXX (AI)
The analog input block condito ns the signal output by the transducer block andoutputs
signal to the PCL or other function blocks.
L00-FMR2xxxx-05-00-00-en-008
Operation
The resource block is opened by a click on the resource line.
Parameter changes from the tool are made off-line while the device is operating. The
changes are downloaded by first setting MODE_BLK = OOS then pressing the WRITE
CHANGES button. Press the READ ALL button to check the values stored in the device.
Normally operation is resumed as soon as MODE-BLK is set to AUTO.
Parameter Description
MODE_BLK See description in Resource block. The possible operating modes of the
transducer block are:
– AUTO: the block is operating as normal
– MAN: the block is operated with a manually entered primary value.
– OOS: the block is out of service.
Output values
Parameter Description
32
Prosonic M FMU 40/41/43 with Foundation Fieldbus Operation
Parameter Description
OUT The primary value output as a result of executing the analog input block. Com-
prises value and status.
FIELD_VALUE Raw value of field device in % of PV range with a status reflecting the transdu-
cer condition before signal characterisation L_Type or filtering V_TIME. Com-
prises value and status.
Scaling parameters
Parameter Description
CHANNEL Selects the measured value to be input to the analogue input block
– 0 = no channel defined
– 1 = primary value: measured level/volume
– 2 = secondary value: measured distance
XD_SCALE Scales the transducer block value in the required engineering units (EU).
OUT_SCALE Scales the output value in the required engineering units (EU).
The relationship between the output values and scaling paramaters for the Micropilot M
is as follows:
PV = CHANNEL_VALUE
• Indirect:
33
Operation Prosonic M FMU 40/41/43 with Foundation Fieldbus
Parameter Description
Alarm parameters
Parameter Description
ACK_OPTION Sets the way in which alarms and warnings are to be acknowledged.
ALARM_HYS Sets the hysteresis (in output engineering units) for all configured alarms.
A hysteresis of e.g. 2% on a HI_HI_LIMIT of 95% would cause the alarm to
activate when the level reaches 95% and to deactivate when the level drops
below 93%.
A hysteresis of e.g. 2% on a LO_LO_LIMIT of 5% would cause the alarm to
activate when the level drops below 5% and to deactivate when the level rises
to 7%.
Alarm priorities
Parameter Description
0 Alarm is suppressed
Alarm status
Parameter Description
34
Prosonic M FMU 40/41/43 with Foundation Fieldbus Operation
Simulation
The SIMULATE parameter allows the transducer block output value to be simulated,
provided simulation has also been enabled at the device DIP switch. The simulation
must be enabled, a value and/or status entered and the block must be in AUTO mode.
During simulation the transducer output value is substituted by the simulated value.
A simulation is also possible by switching MODE_BLK to "MAN" and entering a value for
OUT.
Parameter Description
35
Operation Prosonic M FMU 40/41/43 with Foundation Fieldbus
36
Prosonic M FMU 40/41/43 with Foundation Fieldbus Operation
37
Operation Prosonic M FMU 40/41/43 with Foundation Fieldbus
! Note!
The parameters of the Analog-Input block are presently not accessible via ToF Tool.
! Note!
ToF-Tool operation of the Prosonic M is not possible via Foundation Fieldbus. Instead,
the PC or Laptop must be connected via the interface FXA 193 to the service adapter,
to which normally the display is connected.
Menu-guided commissioning
L00-FMU4xxxx-19-00-00-en-003
• You can find the function groups and functions of the device in the navigation bar.
• You can find the input fields for the parameters in the main window.
• If you click on a parameter name, the Help pages open with precise explanations of
the required input.
38
Prosonic M FMU 40/41/43 with Foundation Fieldbus Operation
L00-FMU4xxxx-19-00-00-en-004
Connection
• Service-Interface with adapter FXA 193
39
Operation Prosonic M FMU 40/41/43 with Foundation Fieldbus
ENDRESS + HAUSER
– + E
X
F 2x X
X X >3 s
O Group Selection
safety settings
O dome ceiling
horizontal cyl
O unknown
liquid
temperature bypass solid<4mm
stilling well solid>4mm
linearisation
...
S flat ceiling
sphere
S
no ceiling
S ...
L00-FMU4xxxx-19-00-00-en-018
Selection menus
a. Select the required Parameter in selected function with S oder O .
b. F confirms selection; ✓ appears in front of the selected parameter.
c. F confirms the edited value; system quits edit mode.
d. O and S (= Q) interrupts selection; system quits edit mode.
40
Prosonic M FMU 40/41/43 with Foundation Fieldbus Operation
If you try to change a parameter, the device jumps to the "unlock parameter" (0A4)
function. Enter "2457"
Now change the parameters.
L00-fmrxf0a4-20-00-00-de-001
! Note!
A hardware locking can only be unlocked again via the display by pressing the O, S
and F keys at the same time again. It is not possible to unlock the hardware by
communication.
In order to carry out the reset, enter the number "33333" in the "reset" (0A3) function in
the "diagnostics" (0A) function group.
" Caution!
A reset may lead to impairment of the measurement. As a rule, a basic calibration is
required after a reset.
! Note!
The default values of each parameter are shown in bold in the menu overview in the
appendix.
41
Operation Prosonic M FMU 40/41/43 with Foundation Fieldbus
Proceed as follows:
1. Switch to the "extended calibr." (05) function group and to the "selection" (050)
function.
2. Select "extended map."
3. Then proceed to the "cust. tank map" (055) function.
4. Select
– "reset", to delete (reset) the existing interference echo suppression.
– "inactive" to deactivate an existing interference echo suppression. The
suppression remains saved.
– "active" to reactivate an existing interference echo suppression.
42
Prosonic M FMU 40/41/43 with Foundation Fieldbus Commissioning
6 Commissioning
Commission the Prosonic M in the following stages:
• Installation check
• Power-up device
• Basic calibration
• Measuring signal check using the envelope curve
The chapter describes the commissioning process using the on-site display.
Commissioning using ToF Tool is identical. Access to the device functions using ToF
Tool is described on Page 21. You can find detailed information in the Tof Tool operating
instructions (BA 224F/00/en) on the supplied CD-ROM.
L00-fmp-fxxx-20-00-00-en-003
L00-fmrxf092-20-00-00-en-001
L00-fmrxf0c5-20-00-00-en-001
L00-fmrxf000-20-00-00-en-001
L00-fmrxfg00-20-00-00-en-001
43
Commissioning Prosonic M FMU 40/41/43 with Foundation Fieldbus
ENDRESS+HAUSER
Prosonic M
bypass stilling well
(ultrasonic guide pipe)
44
Prosonic M FMU 40/41/43 with Foundation Fieldbus Commissioning
For all fluid applications which do Storage tanks with immersion tube Storage / accumulation tanks with
not fit in any of the following or bottom filling uneven surface due to free filling,
groups. mixing nozzles or small bottom
stirrers
L00-FMU4xxxx-14-00-00-xx-001 L00-FMU4xxxx-14-00-00-xx-002
The filters and output damping are The averaging filters and output Special filters for stabilising the
set to average values. damping are set to large values. input signal are activated.
-> Stable measured value -> Stable measured value
-> Accurate measurement -> Medium reaction time
-> Slow reaction time
Moving surfaces (poss. with Rapid level change, particularly in For all bulk solids applications
vortex formation) due to agitators small tanks which do not fit in any of the
following groups.
Special filters for stabilising the The averaging filters are set to The filter and output damping are
input signal are set to large small values. set to average values.
values. -> Rapid reaction time
-> Stable measured value -> Possibly unstable measured
-> Medium reaction time value
45
Commissioning Prosonic M FMU 40/41/43 with Foundation Fieldbus
Dusty bulk solids Bulk solids with rapid level All the filters can be switched off
change for purposes of service and
diagnosis.
ENDRESS+HAUSER
Prosonic M
L00-FMU4xxxx-14-00-00-xx-007 L00-FMU4xxxx-14-00-00-xx-005
The filters are set to detect even The averaging filters are set to All filters off
relatively weak signals. small values.
-> Rapid reaction time
Possibly unstable measured value
46
Prosonic M FMU 40/41/43 with Foundation Fieldbus Commissioning
BD
20 mA
SD 100%
E F
4 mA
0%
L00-FMU4xxxx-19-00-00-yy-019
" Caution!
With dished boiler heads or conical outflows, the zero point should not be deeper than
the point at which the ultrasonic wave impinges on the tank bottom.
" Caution!
When entering the full calibration (span), please take into account, that the maximum
level may not project into the blocking distance (BD)
! Note!
After basic calibration, enter a safety distance (SD) in the "safety distance" (015)
function. If the level is within this safety distance, the Prosonic M signals a warning or
an alarm, depending on your selection in the "in safety distance" (016) function.
47
Commissioning Prosonic M FMU 40/41/43 with Foundation Fieldbus
L00-FMR2xxxx-14-00-06-en-010
Select
• "distance=ok" if the correct distance is displayed. Any echoes closer to the sensor
will be suppressed by the following interference echo suppression.
• "dist. too small" if the displayed distance is too small. In this case, the signal comes
from an interference echo which will be suppressed.
• "dist. too big" if the displayed distance is too large. This error cannot be cancelled
by suppressing the interference echo. This means that the following two functions are
skipped. Check the application parameters "tank shape" (002), "medium
proerty" (003) and "process cond." (004) and the "empty calibr."(005) in the
"basic setup" (00) function group.
• "dist. unknown" if you do not know the actual distance. This means that the following
two functions are skipped.
• "manual" if you want to specify the suppression area yourself in the following
function.
" Caution!
The suppression range must end 0.5 m in front of the echo of the actual level. With an
empty tank, do not enter E but E – 0.5 m.
48
Prosonic M FMU 40/41/43 with Foundation Fieldbus Commissioning
! Note!
If a mapping already exists, it will be overwritten up to the distance specified in the
"range of mapping" (052) function. Beyond this distance the existing mapping remains
unchanged.
! Note!
The FAC and the interference echo suppression (map) are explained in BA 240F
"Prosonic M - Description of Instrument Functions"
49
Commissioning Prosonic M FMU 40/41/43 with Foundation Fieldbus
L00-FMU4xxxx-07-00-00-en-003
! Note!
If the cyclical envelope curve display is still active on the display, the measured value
is updated at a slower cycle time. We therefore advise you to exit the envelope curve
display after optimising the measuring point. To do this, press F. (The instrument does
not leave the envelope curve display automatically.)
- horizontal zoom in
OE3
- horizontal zoom out
Move mode:
50
Prosonic M FMU 40/41/43 with Foundation Fieldbus Commissioning
S O
L00-FMxxxxxx-07-00-00-yy-007
Move mode
Then press F to switch to Move mode. Either or is displayed.
• O shifts the curve to the right.
• S shifts the curve to the left.
S O
L00-FMxxxxxx-07-00-00-yy-008
S O
L00-FMxxxxxx-07-00-00-yy-009
51
Troubleshooting Prosonic M FMU 40/41/43 with Foundation Fieldbus
7 Troubleshooting
The output signal assumes a value which can be set using the
"output on alarm" (010) function:
Alarm/Warning (E) You can define whether the error should behave as an alarm or as a warning.
W103 initialising If the message does not disappear after several seconds, replace
the electronics
52
Prosonic M FMU 40/41/43 with Foundation Fieldbus Troubleshooting
W153 initialising Wait a few seconds; if error is still displayed, switch the power off and
on again
W601 linearisation curve not Correct table (enter monotonously increasing table)
monotone
W621 simulation on Switch simulation mode off ["output" (06) function group,
"simulation" (065) function]]
E651 level in safety distance - Error disappears when the level leaves the safety distance. Possibly
risk of overspill reset the lock. ["safety settings" (01) function group, "ackn. alarm"
(017) function]]
53
Troubleshooting Prosonic M FMU 40/41/43 with Foundation Fieldbus
– level/ullage (040)
– max. scale(046)
expected
– diameter vessel(047)
– linearisation table
L00-FMR2xxxx-19-00-00-en-019
actual
expected
0% t→
L00-FMR2xxxx-19-00-00-en-014
0% t→
L00-FMR2xxxx-19-00-00-en-015
100%
0% t→
L00-FMR2xxxx-19-00-00-en-016
On filling/emptying the 1. Check tank shape (002), e.g. "dome ceiling" or "horizontal cyl."
measured value drops
2. If possible, do not select a central installation position
100%
3. Possible user stilling well/echo guide pipe
expected
actual
0% t→
L00-FMR2xxxx-19-00-00-en-017
54
Prosonic M FMU 40/41/43 with Foundation Fieldbus Troubleshooting
E 641 (echo loss) 1. Check application parameters (002), (003) and (004)
2. If necessary, select a different installation position and/or a larger
100%
sensor
3. Align the sensor parallel to the product surface (particularly for
bulk solids applications)
E 641
0% t→
L00-FMR2xxxx-19-00-00-en-018
55
Maintenance and repairs Prosonic M FMU 40/41/43 with Foundation Fieldbus
8.2 Repairs
The Endress+Hauser repair concept assumes that the measuring devices have a
modular design and that customers are able to undertake repairs themselves.
Spare parts are contained in suitable kits. They contain the related replacement
instructions.
All the spare parts kits which you can order from Endress+Hauser for repairs are listed
with their order numbers in the section "Spare parts".
For more information on service and spare parts, contact the Service Department at
Endress+Hauser.
8.4 Replacement
After a complete instrument or electronic module has been replaced, the parameters
can be downloaded into the instrument again via the communication interface.
Prerequisite to this is that the data were uploaded to the PC beforehand using the
ToF Tool / Commuwin II. Measurement can continue without having to carry out a new
setup. Only a linearisation and a tank map (interference echo suppression) have to be
recorded again.
56
Prosonic M FMU 40/41/43 with Foundation Fieldbus Maintenance and repairs
Housing F12
standard, complete pre-mounted, incl. nameplate,
cable gland and Teflon filter The spare parts listed are generally suitable
543 120 - 0022 G ½" cable gland for use in Ex-devices
543 120 - 0023 NPT ½" cable gland
543 120 - 0024 M20 x 1.5 cable gland
5200 1992 M12 PROFIBUS PA plug
5200 8556 7/8 UNC Fieldbus Foundation plug Power supply for 4wire electronics
5201 3348 4-wire, G ½" cable gland 10... 32 V DC 5201 3304
5201 3350 4-wire M20 x 1,5 cable gland 90...253 V AC 5201 3305
l
ina
rm
Te
Maulburg
Made in Germany
O-ring E
ER
US
HA
S+
O-ring D ENDR
ES
Gasket G
D
Gasket H
Nut G1.5"
5200 0599
Nut G2"
Gasket set 5201 0526 5200 0598 in preparation
consist of:
2 gaskets 25 x 20.5 x 2 FA; Pos. C Screw set 535 720 - 9020
1 O-ring 49.21 x 3.53 EPDM; Pos. D consist of:
1 O-ring 113.9 x 3.53 NBR; Pos. E 1 stop screw M5x10; Pos. A
1 O-ring 72.0 x 3.0 NBR; Pos. F 1 retaining screw M8x10; Pos. B FMU 43
1 gasket 58 x 47 x 2 EPDM; Pos. G Note the mounting
1 gasket 68 x 59 x 2.5 EPDM; Pos. H instructions!
L00-FMU4xxxx-09-00-00-en-001
57
Maintenance and repairs Prosonic M FMU 40/41/43 with Foundation Fieldbus
Housing T12
complete pre-mounted with lid for terminal compartment The spare parts listed are generally suitable
for use in Ex-devices
cable certificate
gland/ EEx d (ia) FM XP CSA XP
entry
G½ 5200 6204
NPT½ 543180-1023 543180-1023 543180-1023 F
M20 x 1.5 5200 6205
O-ring
D O-ring E
FMU 41
Sensor FMU 40 Sensor FMU 41
complete with O-ring complete with O-ring Screw set 535 720 - 9020
and nut 1.5" and nut 2" consist of:
G1/2" 5201 0509 G 2" 5201 0510 1 stop screw M5x10; Pos. A
NPT1/2" 5201 0507 NPT 2" 5201 0508 1 retaining screw M8x10; Pos. B
Note the mounting
Gasket G Gasket H instructions!
L00-FMU4xxxx-09-00-00-en-002
58
Prosonic M FMU 40/41/43 with Foundation Fieldbus Maintenance and repairs
8.7 Return
The following procedures must be carried out before a transmitter is sent to
Endress+Hauser e.g. for repair or calibration:
• Remove all residue which may be present. Pay special attention to the gasket grooves
and crevices where fluid may be present. This is especially important if the fluid is
dangerous to health, e.g. corrosive, poisonous, carcinogenic, radioactive, etc.
• Always enclose a duly completed "Declaration of contamination" form (a copy of the
“Declaration of contamination” is included at the end of this operating manual). Only
then can Endress +Hauser transport, examine and repair a returned device.
• Enclose special handling instructions if necessary, for example a safety data sheet as
per EN 91/155/EEC.
Additionally specify:
• An exact description of the application.
• The chemical and physical characteristics of the product.
• A short description of the error that occurred (specify error code if possible)
• Operating time of the device.
8.8 Disposal
In case of disposal please seperate the different components according to their material
consistence.
59
Accessories Prosonic M FMU 40/41/43 with Foundation Fieldbus
9 Accessories
EN
D
Orde M RE
ICR SS
r
Se Code OP +HA
r.-No
.:
: ILO US
T E II R
Me
Messbere
asur ich
ing
rang
U 16 e ma
4...20...36 x. 20
Maulburg
m
mAV DC
IP
65
T
Made in Germany
A >7
0°C
: t
>8 5°C
L00-FMR2xxxx-00-00-06-en-001
400
120
G
A ø16
250
120
3
30
L00-FMU4x-00-00-00-de-001
60
Prosonic M FMU 40/41/43 with Foundation Fieldbus Accessories
sealing ring
EPDM adapter flange
(supplied)
sensor nozzle
L00-FMUX3XXX-00-00-00-en-001
Thread
3 G 1½, ISO 228
4 G 2, ISO 228
Material
2 1.4435
7 PPs (Polypropylene)
Thread
5 NPT 1½ - 11,5
6 NPT 2 - 11,5
Material
2 1.4435
7 PPs (Polypropylene)
61
Accessories Prosonic M FMU 40/41/43 with Foundation Fieldbus
9.4 Cantilever
20
C
20
100
50
35
25
D M8
75 75 100 B 35
50/
62
22
C
105
6.5
15
L00-FMU4xxxx-06-00-00-yy-005
• The 50 mm or 62 mm orifices serve for the mounting of the FMU 40 or FMU 41 sensor,
respecitvely.
• The 22 mm orifice may be used for an additional sensor.
62
Prosonic M FMU 40/41/43 with Foundation Fieldbus Accessories
13
100
25
55
3.2
Ø 33.7
60
20 4
700/1400
6.5
45
76
200
100
100
130 150
L00-FMU4x-00-00-00-yy-005
3.2
5 ø 33.7
6.5
180
213
150
110
25
13
88 110
150
L00-FMU4x-00-00-00-yy-006
63
Accessories Prosonic M FMU 40/41/43 with Foundation Fieldbus
119 25
Material: 1.4301
~123
120
Order-Code.: 942666-0000
2 25
11
L00-FMU4x-00-00-00-en-003.eps
64
Prosonic M FMU 40/41/43 with Foundation Fieldbus Accessories
EN
DR
Orde ES
r S+
Se Code
r.-No HA
US
H
:
.: ER
Mes
Measber
surineich
g ra
nge
U 16 max
4...2 ...36 . 20
Maulburg
0 m V DC m
A
IP
65
T
Made in Germany
A >7
0°C
: t >8
5°C
D
Cable
L00-FMxxxxxx-00-00-06-en-002
Cable length
1 20 m cable
Additional option
A Additional option not selected
B Mounting bracket 1" or 2" pipe
! Note!
For the use of the remote display FHX 40, the instrument must be prepared accordingly.
Therefore, the product structure provides the option "prepared for remote display
FHX 40" under "display/on-site operation".
65
Technical Data Prosonic M FMU 40/41/43 with Foundation Fieldbus
10 Technical Data
10.1.1 Input
Measured variable The distance D between the sensor membrane and the product surface is measured.
Using the linearisation function, the device uses D to calculate:
• level L in any units
• volume V in any units
• flow Q across measuring weirs or open channels in any units
Maximum range/blocking Sensor Maximum range in liquids1 Maximum range in solids1 blocking distance
distance
FMU 40 5m 2m 0,25 m
FMU 43 15 m 7m 0,6 m
10.1.2 Output
Signal on alarm • Error symbol, error code and plain text description on the on-site display
• Status byte of the digital signal input
Cable entry • Cable gland M20x1.5 (recommended cable diameter 6 ... 10 mm)
• Cable entry G½ or ½ NPT
• 7/8" Foundation Fieldbus plug
66
Prosonic M FMU 40/41/43 with Foundation Fieldbus Technical Data
Reaction time The reaction time depends on the parameter settings (min. 2s).
FMU 40 1 mm
FMU 41 1 mm
FMU 43 2 mm
Measuring error Typical specifications for reference operating conditions (include linearity, repeatability,
and hysteresis):
1whichever
is greater
Vibration resistance DIN EN 60068-2-64 / IEC 68-2-64: 20…2000 Hz, 1 (m/s)/Hz; 3 x 100 min
67
Technical Data Prosonic M FMU 40/41/43 with Foundation Fieldbus
68
Prosonic M FMU 40/41/43 with Foundation Fieldbus Technical Data
69
Appendix Prosonic M FMU 40/41/43 with Foundation Fieldbus
11 Appendix
basic setup 00 tank shape 002 medium property 003 process cond. 004 empty calibr. 005 full calibr. 006
dome ceiling liquid standard liquid ditance membrane span
horizontal cyl. solid < 4mm calm surface to min. level max.: empty - BD
bypass solid > 4mm turb. surface Default: Default:
stilling well unknown add. agitator FMU 40: 5 m FMU 40: 4,75 m
flat ceiling fast change FMU 41: 8 m FMU 41: 7,6 m
sphere standard solid FMU 43: 15 m FMU 43: 14,4 m
no ceiling solid dusty
conveyor belt
test: no filter
safety settings 01 output on alarm 010 outp. echo loss 012 delay time 014
MAX 110% 22 mA hold in case of echo loss
hold alarm max. 4000 sec.
MIN - 10% 3,6 mA Default: 30 s
ramp %/min Rampe %span/min 013
specify value
temperature 03 measured temp. 030 max. temp. limit 031 max. meas. temp. 032 react. high temp 033 defect temp. sens. 034
is displayed is displayed is displayed warning alarm
alarm warning
extended calibr. 05 selction 050 dist./meas. value 008 check distance 051 range of mapping. 052 start mapping 053
mapping the following are manual accept proposed value off
displayed: distance = ok or on
- distance membrane distance too small specify range of
to level mapping
- measured value
dist. unknown
distance too big
common
extended map.
pres. map dist. 054 cust. tank map 055
is displayed inactive
active
reset
output 06
display 09 language 092 back to home 093 format display 094 no. of decimalas 095
specify time decimal x
Default: 100 s 1/16” x.x
x.xx
x.xxx
diagnostics 0A present error 0A0 previous error 0A1 clear last error 0A2 reset 0A3 unlock parameter 0A4
keep for reset code for unlock code
erase see manual see manual
system parameters 0C device tag 0C0 protocol + sw-no. 0C2 device id 0C4
Note! The Default values of the parameters are typed in bold face.
L00-FMU4xxxx-19-00-01-en-017
70
Prosonic M FMU 40/41/43 with Foundation Fieldbus Appendix
dist./meas. value 008 check distance 051 range of mapping. 052 start mapping 053 dist./meas. value 008
the following are manual accept proposed value off the following are
displayed: distance = ok or on displayed:
- distance membrane distance too small specify range of - distance membrane
to level mapping to level
- measured value - measured value
dist. unknown
distance too big
echo quality 056 offset 057 output damping 058 blocking dist. 059
is displayed will be added to the Default: 2 s is displayed
measured level
simulation 065
sim. off
sim. level simulation value 066
sim. volume
sim. current
L00-FMU4xxxx-19-00-02-en-017
71
Appendix Prosonic M FMU 40/41/43 with Foundation Fieldbus
BD
20 mA
100%
E F
4 mA
0%
L00-FMU4x-15-00-00-de-001
E: Empty distance; F: Span (full distance); D: Distance from sensor membrane - product surface; L: Level;
BD: Blocking distance
D = c ⋅ t/2
As the device knows the empty distance E from a user entry, it can calculate the level
as follows:
L=E-D
11.2.3 Calibration
Enter the empty distance E and the span F to calibrate the device.
72
Prosonic M FMU 40/41/43 with Foundation Fieldbus
Index
A repairs to Ex-approved devices. . . . . . . . . . . . . . . . . 56
adapter flange. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
application errors . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 S
service adapter FXA 193 . . . . . . . . . . . . . . . . . . . . . . 64
B shafts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
blocking distance . . . . . . . . . . . . . . . . . . . . . . . . 13, 47 software security locking . . . . . . . . . . . . . . . . . . . . . . 41
C W
cantilever. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
CE mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 weather protection cover . . . . . . . . . . . . . . . . . . . . . . 60
cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
D
declaration of conformity . . . . . . . . . . . . . . . . . . . . . . 7
declaration of contamination. . . . . . . . . . . . . . . . . . . 59
display appearance . . . . . . . . . . . . . . . . . . . . . . . . . 20
display symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
E
error codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
error messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
F
flow measurements . . . . . . . . . . . . . . . . . . . . . . . . . . 11
full calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
H
hardware security locking. . . . . . . . . . . . . . . . . . . . . 41
hazardous area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
I
installation bracket . . . . . . . . . . . . . . . . . . . . . . . . . . 60
interference echo suppression . . . . . . . . . . . . . . . . . 48
K
Khafagi-Venturi flume . . . . . . . . . . . . . . . . . . . . . . . . 11
L
level measurements . . . . . . . . . . . . . . . . . . . . . . . . . 10
M
measuring principle . . . . . . . . . . . . . . . . . . . . . . . . . 72
Measuring range. . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
N
nozzle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
O
on-site display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
operating menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
P
process conditions . . . . . . . . . . . . . . . . . . . . . . . . . . 45
R
range. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
73
Prosonic M FMU 40/41/43 with Foundation Fieldbus
74
IMPORTANT NOTICE
RETURN AUTHORIZATION POLICY
Endress+Hauser must pre-approve and assign a Return Authorization number to any instrument
you plan to return. Please identify the Return Authorization number clearly on all shipping
cartons and paperwork.
Please note that the issuance of a Return Authorization number does not automatically mean
that credit will be issued, or that the return is covered by our warranty. An Endress+Hauser
associate will contact you regarding the disposition of your returned equipment.
In order to serve you better, and to protect our employees from any potentially hazardous
contaminants, Endress+Hauser must return unopened, at the sender’s expense, all items that
do not have a Return Authorization number.
Please be sure to include the following information when requesting a Return Authorization
number. This information will help us speed up the repair and return process.
Customer name:
Customer address:
Customer phone number:
Customer contact:
Equipment type:
Original sales order or purchase order number:
Reason for return:
Failure description, if applicable:
Process material(s) to which the equipment has been exposed:
OSHA Hazard Communication Standard 29CFR 1910.1200 mandates that we take specific
steps to protect our employees from exposure to potentially hazardous materials. Therefore,
all equipment so exposed must be accompanied by a letter certifying that the equipment has
been decontaminated prior to its acceptance by Endress+Hauser.
Endress+Hauser Endress+Hauser
2350 Endress Place 1440 Graham’s Lane, #1, Burlington
Greenwood, IN 46143 Ont. Canada L7S 1W3
Return Authorization number: Return Authorization number:
Endress+Hauser
The Power of Know How