Chapter 5 Parameters|VFD-B Series

5.1 Summary of Parameter Settings


a: The parameter can be set during operation.
Group 0 User Parameters
Parameter Explanation Settings
Identity Code of
00-00 Read-only
the AC motor drive
Rated Current
00-01 Display of the AC Read-only
motor drive
08: Keypad lock
09: All parameters are reset to factory settings
00-02 Parameter Reset (50Hz, 220V/380V/575V)
10: All parameters are reset to factory settings
(60Hz, 220V/440V/575V)
00: Display the frequency command value (LED
F)
01: Display the actual output frequency (LED H)
Start-up Display
a00-03 02: Display the content of user-defined unit
Selection
(LED U)
03: Multifunction display, see Pr.00-04
04: FWD/REV command

00: Display output current (A)


01: Display counter value (C)
02: Display process operation (1.tt)
03: Display DC-BUS voltage (u)
04: Display output voltage (E)
05: Output power factor angle (n)
06: Display output power (P)
Content of Multi 07: Display actual motor speed (HU)
a00-04
Function Display 08: Display the estimated value of torque as it
relates to current (t)
09: Display PG numbers/10ms (G)
10: Display analog feedback signal value (b)(%)
11: Display AVI (U1.) (%)
12: Display ACI (U2.) (%)
13: Display AUI (U3.) (%)
14: Display the temperature of heat sink (°C)

User-Defined
a00-05 0.01 to 160.00
Coefficient K
00-06 Software Version Read-only
00-07 Password Input 00 to 65535
00-08 Password Set 00 to 65535
00: V/f Control
01: V/f + PG Control
00-09 Control Method
02: Vector Control
03: Vector + PG Control
5-2 Revision July 2008, BE16, SW V4.08 & V5.00

Downloaded from www.Manualslib.com manuals search engine


Factory
Customer
Setting
## 23

#.# 45.0

0 00

0 00

0 00

1 1.00
#.## 4.24
0 00
0 00

0 00

6, SW V4.08 & V5.00


Chapter 5 Parameters|VFD-B Series
Factory
Parameter Explanation Settings
Setting
00-10 Reserved
Group 1 Basic Parameters
Factory
Parameter Explanation Settings
Setting
Maximum Output
01-00 50.00 to 400.00 Hz 60
Frequency (Fmax)
Maximum Voltage
01-01 0.10 to 400.00 Hz 60
Frequency (Fbase)
230V series: 0.1V to 255.0V 220.0
Maximum Output
01-02 460V series: 0.1V to 510.0V 440.0
Voltage (Vmax)
575V series: 0.1V to 637.0V 575.0
Mid-Point Frequency
01-03 0.10 to 400.00 Hz 0.50
(Fmid)
230V series: 0.1V to 255.0V 1.7
Mid-Point Voltage
01-04 460V series: 0.1V to 510.0V 3.4
(Vmid)
575V series: 0.1V to 637.0V 4.8
Minimum Output
01-05 0.10 to 400.00 Hz 0.50
Frequency (Fmin)
230V series: 0.1V to 255.0V 1.7
Minimum Output
01-06 460V series: 0.1V to 510.0V 3.4
Voltage (Vmin)
575V series: 0.1V to 637.0V 4.8
Output Frequency
01-07 1 to 120% 100
Upper Limit
Output Frequency
01-08 0 to100 % 0
Lower Limit
a01-09 Accel Time 1 0.01 to 3600.0 sec 10
a01-10 Decel Time 1 0.01 to 3600.0 sec 10
a01-11 Accel Time 2 0.01 to 3600.0 sec 10
a01-12 Decel Time 2 0.01 to 3600.0 sec 10
01-09 ~ 01-12: Factory setting for models of 30hp (22kW) and above is 60sec.
Jog Acceleration
a01-13 0.1 to 3600.0 sec 1
Time
a01-14 Jog Frequency 0.10 Hz to 400.00 Hz 6
00: Linear Accel/Decel
Auto acceleration / 01: Auto Accel, Linear Decel
deceleration (refer to 02: Linear Accel, Auto Decel
a01-15 0
Accel/Decel time 03: Auto Accel/Decel (Set by load)
setting) 04: Auto Accel/Decel (set by Accel/Decel
Time setting)
Acceleration S-
01-16 00 to 07 0
Curve
Deceleration S-
01-17 00 to 07 0
Curve
a01-18 Accel Time 3 0.01 to 3600.0 sec 10
a01-19 Decel Time 3 0.01 to 3600.0 sec 10
a01-20 Accel Time 4 0.01 to 3600.0 sec 10
Revision July 2008, BE16, SW V4.08 & V5.00 5-3

Downloaded from www.Manualslib.com manuals search engine


Customer
0

Customer

70.00

60.00

440.0

0.50

3.4

0.50

3.4

100

00
15.0
15.0
60.0
60.0

1.0
6.00

00

00

00
60.0
60.0
60.0
Chapter 5 Parameters|VFD-B Series
Factory
Parameter Explanation Settings
Setting
a01-21 Decel Time 4 0.01 to 3600.0 sec 10
01-18 ~ 01-21: Factory setting for models of 30hp (22kW) and above is 60sec.
Jog Deceleration
a01-22 0.1 to 3600.0 sec 1
Time
00: Unit: 1 sec
Accel/Decel Time
01-23 01: Unit: 0.1 sec 01
Unit
02: Unit: 0.01 sec
Group 2 Operation Method Parameters
Factory
Parameter Explanation Settings
Setting
00: Digital keypad (PU01) UP/DOWN keys or
Multi-function Inputs UP/DOWN. Last
used frequency saved.
01: 0 to +10V from AVI
02: 4 to 20mA from ACI
Source of First 03: -10 to +10Vdc from AUI
a02-00 Master Frequency 04: RS-485 serial communication (RJ-11). 0
Command Last used frequency saved.
05: RS-485 serial communication (RJ-11).
Last used frequency not saved.
06: Combined use of master and auxiliary
frequency command
(See Pr. 02-10 to 02-12)

00: Digital keypad (PU01)


01: External terminals. Keypad STOP/RESET
enabled.
02: External terminals. Keypad STOP/RESET
Source of First
a02-01 disabled. 0
Operation Command
03: RS-485 serial communication (RJ-11).
Keypad STOP/RESET enabled.
04: RS-485 serial communication (RJ-11).
Keypad STOP/RESET disabled.

00: STOP: ramp to stop; E.F.: coast to stop


01: STOP: coast to stop; E.F.: coast to stop
02-02 Stop Method 0
02: STOP: ramp to stop; E.F.: ramp to stop
03: STOP: coast to stop; E.F.: ramp to stop

230V&460V:1-5hp/0.75-3.7kW: 1-15kHz 15
7.5-25hp/5.5-18.5kW: 01-15kHz 09
PWM Carrier 30-60hp/22-45kW: 01-09kHz 06
02-03 Frequency 75-100hp/55-75kW: 01-06kHz 06
Selections 575V: 1-15hp/0.75-11kW: 01-10 kHz 06
20-60hp/15-45kW: 01-08 kHz 06
75-100hp/55-75kW: 01-06kHz 06

5-4 Revision July 2008, BE16, SW V4.08 & V5.00


Downloaded from www.Manualslib.com manuals search engine
Customer
60.0

1.0

01

Customer

00

02

01

06
Chapter 5 Parameters|VFD-B Series
Factory
Parameter Explanation Settings
Setting
00: Enable forward/reverse operation
Motor Direction
02-04 01: Disable reverse operation 0
Control
02: Disabled forward operation
2-wire/3-wire 00: 2-wire: FWD/STOP, REV/STOP
02-05 Operation Control 01: 2-wire: FWD/REV, RUN/STOP 0
Modes 02: 3-wire operation
00: Disable. Operation status is not changed
even if operation command source Pr.02-
01 and/or Pr.02-14 is changed.
01: Enable. Operation status is not changed
even if operation command source Pr.02-
01 and/or Pr.02-14 is changed.
02-06 Line Start Lockout 0
02: Disable. Operation status will change if
operation command source Pr.02-01
and/or Pr.02-14 is changed.
03: Enable. Operation status will change if
operation command source Pr.02-01
and/or Pr.02-14 is changed.
00: Decelerate to 0 Hz
Loss of ACI Signal 01: Coast to stop and display “EF”
02-07 0
(4-20mA) 02: Continue operation by last frequency
command
00: Based on accel/decel time
01: Constant speed
a02-08 Up/Down Mode 0
02: Based on accel/decel time, but frequency
command will be 0 when stopped.
Accel/Decel Rate of
Change of
a02-09 UP/DOWN 0.01~1.00 Hz/msec 0.01
Operation with
Constant Speed
00: Digital keypad (PU01) UP/DOWN keys or
Multi-function Inputs UP/DOWN. Last
used frequency saved.
Source of the Master
01: 0 to +10V from AVI
a02-10 Frequency 0
02: 4 to 20mA from ACI
Command
03: -10 to +10Vdc from AUI
04: RS-485 serial communication (RJ-11).
Last used frequency saved.
00: Digital keypad (PU01) UP/DOWN keys or
Multi-function Inputs UP/DOWN. Last
used frequency saved.
Source of the
01: 0 to +10V from AVI
a02-11 Auxiliary Frequency 0
02: 4 to 20mA from ACI
Command
03: -10 to +10Vdc from AUI
04: RS-485 serial communication (RJ-11).
Last used frequency saved.
Combination of the
Master and Auxiliary 01: Master frequency - auxiliary frequency
a02-12 0
Frequency 00: Master frequency + auxiliary frequency
Command
Combination of the
Master and Auxiliary 01: Master frequency - auxiliary frequency
a02-12 0
Frequency 00: Master frequency + auxiliary frequency
Command
Revision July 2008, BE16, SW V4.08 & V5.00 5-5

Downloaded from www.Manualslib.com manuals search engine


Customer

01

00

02

00

02

0.01

00

00

00
00
Chapter 5 Parameters|VFD-B Series

Parameter Explanation Settings

00: Digital keypad (PU01) UP/DOWN keys or


Multi-function Inputs UP/DOWN. Last
used frequency saved.
01: 0 to +10V from AVI
02: 4 to 20mA from ACI
Source of Second 03: -10 to +10Vdc from AUI
a02-13 Frequency 04: RS-485 serial communication (RJ-11).
Command Last used frequency saved
05: RS-485 serial communication (RJ-11).
Last used frequency not saved.
06: Combined use of master and auxiliary
frequency command (See Pr. 02-10 to 02-
12)
00: Digital keypad (PU01)
01: External terminals. Keypad STOP/RESET
enabled.
02: External terminals. Keypad STOP/RESET
Source of Second
a02-14 disabled.
Operation Command
03: RS-485 serial communication (RJ-11).
Keypad STOP/RESET enabled.
04: RS-485 serial communication (RJ-11).
Keypad STOP/RESET disabled.
Keypad Frequency
a02-15 0.00 ~ 400.00Hz
Command
Group 3 Output Function Parameters
Parameter Explanation Settings

Multi-Function
03-00 Output Relay (RA1, 00: No function
RB1, RC1) 01: AC drive operational
02: Master frequency attained
03: Zero speed
Multi-Function 04: Over torque detection
03-01 Output Terminal 05: Base-Block (B.B.) indication
MO1 06: Low-voltage indication
07: Operation mode indication
08: Fault indication
Multi-Function 09: Desired frequency attained 1
03-02 Output Terminal 10: PLC program running
MO2 11: PLC program step completed
12: PLC program completed
13: PLC program operation paused
14: Terminal count value attained
Multi-Function 15: Preliminary count value attained
03-03 Output Terminal 16: Auxiliary motor No.1
MO3 17: Auxiliary motor No.2

5-6 Revision July 2008, BE16, SW V4.08 & V5.00

Downloaded from www.Manualslib.com manuals search engine


Factory
Customer
Setting

0 00

0 00

60 0.00

Factory
Customer
Setting

08 20

01 01

02 02

20 20

6, SW V4.08 & V5.00


Chapter 5 Parameters|VFD-B Series
Factory
Parameter Explanation Settings
Setting
18: Auxiliary motor No.3
19: Heat sink overheat warning
20: AC motor drive ready
21: Emergency stop indication
22: Desired frequency attained 2
23: Software brake signal
24: Zero speed output signal
25: Under-current detection
26: Operation indication (H>=Fmin)
27: Feedback signal error
28: User-defined low-voltage detection
29: Brake control (Desired frequency attained
3)
Desired Frequency
03-04 0.00 to 400.00 Hz 0
Attained 1
00: Analog frequency meter
01: Analog current meter
Analog Output 02: Output voltage
03-05 0
Signal 03: Output frequency command
04: Output motor speed
05: Load power factor (cos90 to Cos0 )
o o

a03-06 Analog Output Gain 01 to 200% 100


Digital Output
a03-07 01 to 20 01
Multiplying Factor
Terminal Count
a03-08 00 to 65500 0
Value
Preliminary Count
a03-09 00 to 65500 0
Value
Desired Frequency
03-10 0.00 to 400.00 Hz 0
Attained 2
00: Preliminary count value attained, no EF
EF Active When
display
03-11 Preliminary Count 0
01: Preliminary count value attained, EF
Value Attained
active
00: Fan always ON
01: 1 minute after AC motor drive stops, fan
will be OFF
03-12 Fan Control 02: AC motor drive runs and fan ON, AC 0
motor drive stops and fan OFF
03: Fan ON to run when preliminary heatsink
temperature attained
Brake Release
03-13 0.00 to 400.00Hz 0
Frequency
Brake Engage
03-14 0.00 to 400.00Hz 0
Frequency
Revision July 2008, BE16, SW V4.08 & V5.00 5-7

Downloaded from www.Manualslib.com manuals search engine


Customer

0.00

00

100
01

00

00

0.00

00

00

0.00

0.00
Chapter 5 Parameters|VFD-B Series
Group 4 Input Function Parameters
Factory
Parameter Explanation Settings
Setting
AVI Analog Input
a04-00 0.00~200.00 % 0
Bias
00: Positive bias
04-01 AVI Bias Polarity 0
01: Negative bias
a04-02 AVI Input Gain 1 to 200 % 100
AVI Negative Bias, 00: No AVI negative bias command
04-03 Reverse Motion 01: Negative bias: REV motion enabled 0
Enable/Disable 02: Negative bias: REV motion disabled

Multi-Function Input
04-04 01
Terminal 1 (MI1)

00: No function
01: Multi-Step speed command 1
02: Multi-Step speed command 2
Multi-Function Input 03: Multi-Step speed command 3
04-05 02
Terminal 2 (MI2) 04: Multi-Step speed command 4
05: External reset (N.O.)
06: Accel/Decel inhibit
07: Accel/Decel time selection command 1
08: Accel/Decel time selection command 2
Multi-Function Input 09: External base block (N.O.)
04-06 03
Terminal 3 (MI3) 10: External base block (N.C.)
11: Up: Increment master frequency
12: Down: Decrement master frequency
13: Counter reset
Multi-Function Input 14: Run PLC program
04-07 04
Terminal 4 (MI4) 15: Pause PLC program
16: Auxiliary motor No.1 output disable
17: Auxiliary motor No.2 output disable
18: Auxiliary motor No.3 output disable
Multi-Function Input 19: Emergency stop (N.O.)
04-08 05
Terminal 5 (MI5) 20: Emergency stop (N.C.)
21: Master frequency selection AVI/ACI
22: Master frequency selection AVI/AUI
23: Operation command selection
(keypad/external terminals)
24: Auto accel/decel mode disable
25: Forced stop (N.C.)
26: Forced stop (N.O.)
Multi-Function Input 27: Parameter lock enable (N.O.)
04-09 28: PID function disabled 06
Terminal 6 (MI6)
29: Jog FWD/REV command
30: External reset (N.C.)
5-8 Revision July 2008, BE16, SW V4.08 & V5.00

Downloaded from www.Manualslib.com manuals search engine


Customer

0.00

00

100

00

11

12

03

04

05

06
Chapter 5 Parameters|VFD-B Series
Factory
Parameter Explanation Settings
Setting

31: Source of second frequency command


enabled
32: Source of second operation command
enabled
33: One shot PLC
34: Proximity sensor input for simple Index
function
35: Output shutoff stop (NO)
36: Output shutoff stop (NC)

Digital Terminal
04-10 Input Debouncing 1 to 20 (*2ms) 01
Time
ACI Analog Input
a04-11 0.00~200.00 % 0
Bias
00: Positive bias
04-12 ACI Bias Polarity 0
01: Negative bias
a04-13 ACI Input Gain 01 to 200 % 100

ACI Negative Bias, 00: No ACI negative bias command


04-14 Reverse Motion 01: Negative bias: REV motion enabled 0
Enable/Disable 02: Negative bias: REV motion disabled

AUI Analog Input


a04-15 0.00~200.00 % 0
Bias
00: Positive bias
04-16 AUI Bias Polarity 0
01: Negative bias
a04-17 AUI Input Gain 01 to 200 % 100
AUI Negative Bias 00: No AUI negative bias command
04-18 Reverse Motion 01: Negative bias: REV motion enabled 0
Enable/Disable 02: Negative bias: REV motion disabled
AVI Analog Input
04-19 0.00 to 10.00 sec 0.05
Delay
ACI Analog Input
04-20 0.00 to 10.00 sec 0.05
Delay
AUI Analog Input
04-21 0.00 to 10.00 sec 0.05
Delay
Analog Input
01: 0.1Hz
04-22 Frequency 01
00: 0.01Hz
Resolution
Gear Ratio for
04-23 Simple Index 4 ~ 1000 200
Function
Index Angle for
04-24 Simple Index 0.0 ~360.0 o
180
Function
Deceleration Time
a04-25 for Simple Index 0.00 ~100.00 sec 0
Function
Revision July 2008, BE16, SW V4.08 & V5.00 5-9

Downloaded from www.Manualslib.com manuals search engine


Customer

01

0.00

00

100

00

0.00

00

100

00

0.05

0.05

0.05

01

200

180.0
0.00
Chapter 5 Parameters|VFD-B Series
Group 5 Multi-Step Speed and PLC Parameters
Factory
Parameter Explanation Settings
Setting
1 Step Speed
st

a05-00 0.00 to 400.00 Hz 0


Frequency
2 Step Speed
nd

a05-01 0.00 to 400.00 Hz 0


Frequency
3 Step Speed
rd

a05-02 0.00 to 400.00 Hz 0


Frequency
4 Step Speed
th

a05-03 0.00 to 400.00 Hz 0


Frequency
5 Step Speed
th

a05-04 0.00 to 400.00 Hz 0


Frequency
6 Step Speed
th

a05-05 0.00 to 400.00 Hz 0


Frequency
7 Step Speed
th

a05-06 0.00 to 400.00 Hz 0


Frequency
8 Step Speed
th

a05-07 0.00 to 400.00 Hz 0


Frequency
9 Step Speed
th

a05-08 0.00 to 400.00 Hz 0


Frequency
10 Step Speed
th

a05-09 0.00 to 400.00 Hz 0


Frequency
11 Step Speed
th

a05-10 0.00 to 400.00 Hz 0


Frequency
12 Step Speed
th

a05-11 0.00 to 400.00 Hz 0


Frequency
13 Step Speed
th

a05-12 0.00 to 400.00 Hz 0


Frequency
14 Step Speed
th

a05-13 0.00 to 400.00 Hz 0


Frequency
15 Step Speed
th

a05-14 0.00 to 400.00 Hz 0


Frequency

00: Disable PLC operation


01: Execute one program cycle
02: Continuously execute program cycles
05-15 PLC Mode 0
03: Execute one program cycle step by step
04: Continuously execute program cycles
step by step

PLC Forward/
05-16 00 to 32767 (00: FWD, 01: REV) 0
Reverse Motion
Time Duration of 1st
05-17 00 to 65500 sec or 00 to 6550.0 sec 0
Step Speed
Time Duration of 2nd
05-18 00 to 65500 sec or 00 to 6550.0 sec 0
Step Speed
Time Duration of 3rd
05-19 00 to 65500 sec or 00 to 6550.0 sec 0
Step Speed
Time Duration of 4th
05-20 00 to 65500 sec or 00 to 6550.0 sec 0
Step Speed
Time Duration of 5th
05-21 00 to 65500 sec or 00 to 6550.0 sec 0
Step Speed
5-10 Revision July 2008, BE16, SW V4.08 & V5.00

Downloaded from www.Manualslib.com manuals search engine


Customer

0.00

0.00

0.00

0.00

0.00

0.00

0.00

0.00

0.00

0.00

0.00

0.00

0.00

0.00

0.00

00

00

00

00

00

00
00
Chapter 5 Parameters|VFD-B Series
Factory
Parameter Explanation Settings Customer
Setting
Time Duration of 6th 00
05-22 00 to 65500 sec or 00 to 6550.0 sec 0
Step Speed
Time Duration of 7th 00
05-23 00 to 65500 sec or 00 to 6550.0 sec 0
Step Speed
Time Duration of 8th 00
05-24 00 to 65500 sec or 00 to 6550.0 sec 0
Step Speed
Time Duration of 9th 00
05-25 00 to 65500 sec or 00 to 6550.0 sec 0
Step Speed
Time Duration of 00
05-26 00 to 65500 sec or 00 to 6550.0 sec 0
10th Step Speed
Time Duration of 00
05-27 00 to 65500 sec or 00 to 6550.0 sec 0
11th Step Speed
Time Duration of 00
05-28 00 to 65500 sec or 00 to 6550.0 sec 0
12th Step Speed
Time Duration of 00
05-29 00 to 65500 sec or 00 to 6550.0 sec 0
13th Step Speed
Time Duration of 00
05-30 00 to 65500 sec or 00 to 6550.0 sec 0
14th Step Speed
Time Duration of 00
05-31 00 to 65500 sec or 00 to 6550.0 sec 0
15th Step Speed
00: 1 sec 00
05-32 Time Unit Settings 0
01: 0.1 sec
The Amplitude of 0.00
05-33 0.00~400.00 Hz 0
Wobble Vibration
Wobble Skip 0.00
05-34 0.00~400.00 Hz 0
Frequency
Group 6 Protection Parameters
Factory
Parameter Explanation Settings Customer
Setting
230V series: 330.0V to 410.0V
390.0V
Over-Voltage Stall 460V series: 660.0V to 820.0V 780
06-00 780.0V
Prevention 575V series: 825.0V to1025.0V
975.0V
00: Disable over-voltage stall prevention
Over-Current Stall
06-01 Prevention during 20 to 250% 170 170
Accel
Over-Current Stall
06-02 Prevention during 20 to 250% 170 170
Operation
00: Disabled
01: Enabled during constant speed operation.
Over-Torque After the over-torque is detected, keep
06-03 Detection Mode running until OL1 or OL occurs. 0 00
(OL2) 02: Enabled during constant speed operation.
After the over-torque is detected, stop
running.

Revision July 2008, BE16, SW V4.08 & V5.00 5-11


Downloaded from www.Manualslib.com manuals search engine
Customer

00

00

00

00

00

00

00

00

00

00

00

0.00

0.00

Customer

780

170

170

00
Chapter 5 Parameters|VFD-B Series
Factory
Parameter Explanation Settings
Setting
03: Enabled during accel. After the over-
Over-Torque torque is detected, keep running until OL1 or
06-03 Detection Mode OL occurs.
(OL2) 04: Enabled during accel. After the over-
torque is detected, stop running.
Over-Torque
06-04 10 to 200% 150
Detection Level
Over-Torque
06-05 0.1 to 60.0 sec 0.1
Detection Time
Electronic Thermal 00: Standard motor (self cooled by fan)
06-06 Overload Relay 01: Special motor (forced external cooling) 02
Selection 02: Disabled
Electronic Thermal
06-07 30 to 600 sec 60
Characteristic

Present Fault
06-08
Record 00: No fault
01: Over current (oc)
02: Over voltage (ov)
03: Over heat (oH)
04: Over load (oL)
05: Over load (oL1)
06: External fault (EF)
07: IGBT protection (occ)
08: CPU failure (cF3)
Second Most Recent 09: Hardware protection failure (HPF)
06-09
Fault Record 10: Excess current during acceleration (ocA)
11: Excess current during deceleration (ocd)
12: Excess current during steady state (ocn)
13: Ground fault (GFF)
0
14: Reserved
15: CF1
16: CF2
17: Reserved
Third Most Recent 18: Motor over-load (oL2)
06-10 19: Auto Acel/Decel failure (CFA)
Fault Record
20: SW/Password protection (codE)
21: External Emergency Stop (EF1)
22: Phase-Loss (PHL)
23: Preliminary count value attained, EF
active (cEF)
24: Under-current (Lc)
25: Analog feedback signal error (AnLEr)
Fourth Most Recent 26: PG feedback signal error (PGErr)
06-11
Fault Record
Fourth Most Recent 26: PG feedback signal error (PGErr)
06-11
Fault Record

5-12 Revision July 2008, BE16, SW V4.08 & V5.00

Downloaded from www.Manualslib.com manuals search engine


Customer

00

150

0.1

02

60

04
Chapter 5 Parameters|VFD-B Series
Factory
Parameter Explanation Settings Customer
Setting
Under-Current 00
06-12 00~100% (00: Disabled) 0
Detection Level
Under-Current 10.0
06-13 0.1~ 3600.0 sec 10
Detection Time

00: Warn and keep operating


01: Warn and ramp to stop
Under-Current 00
06-14 02: Warn and coast to stop 0
Detection Mode
03: Warn, after coast to stop, restart (delay
06-15 setting time)

Under-Current
06-15 Detection Restart 1~600 Min. 10 10
Delay Time (Lv)

00: Disabled
User-Defined Low-
230V: 220 to 300VDC 00
06-16 Voltage Detection 0
460V: 440 to 600VDC
Level
575V: 520 to 780VDC

User-Defined Low-
06-17 Voltage Detection 0.1~ 3600.0 sec 0.5 0.5
Time
06-18 Reserved
Group 7 Motor Parameters
Factory
Parameter Explanation Settings
Setting
a07-00 Motor Rated Current 30 to 120% 100
Motor No-Load
a07-01 01 to 90% 40
Current
Torque
a07-02 0.0 to 10.0 0
Compensation
Slip Compensation
a07-03 0.00 to 3.00 0
(Used without PG)
Number of Motor
07-04 02 to 10 04
Poles
00: Disable
Motor Parameters
07-05 01: Auto tuning R1 0
Auto Tuning
02: Auto tuning R1 + no-load test
Motor Line-to-line
07-06 00~65535 mΩ 0
Resistance R1
07-07 Reserved
07-08 Motor Rated Slip 0.00 to 20.00 Hz 3
Slip Compensation
07-09 0 to 250% 200
Limit
07-10 Reserved
07-11 Reserved
Revision July 2008, BE16, SW V4.08 & V5.00 5-13
Downloaded from www.Manualslib.com manuals search engine
Customer

00

10.0

00

10

00

0.5

Customer
100
40

0.0

0.00

04

00

00
00
3.00
200
30.0
00
Chapter 5 Parameters|VFD-B Series
Factory
Parameter Explanation Settings
Setting
Torque
07-12 Compensation Time 0.01 ~10.00 Sec 0.05
Constant
Slip Compensation
07-13 0.05 ~10.00 sec 0.10
Time Constant
Accumulative Motor
07-14 Operation Time 00 to 1439 Min. 0
(Min.)
Accumulative Motor
07-15 Operation Time 00 to 65535 Day 0
(Day)
Group 8 Special Parameters
Factory
Parameter Explanation Settings
Setting
DC Brake Current
08-00 00 to 100% 0
Level
DC Brake Time
08-01 0.0 to 60.0 sec 0
during Start-Up
DC Brake Time
08-02 0.0 to 60.0 sec 0
during Stopping
Start-Point for DC
08-03 0.00 to 400.00Hz 0
Brake
00: Operation stops after momentary power
loss
01: Operation continues after momentary
Momentary Power
power loss, speed search starts with the
08-04 Loss Operation 0
Master Frequency reference value
Selection
02: Operation continues after momentary
power loss, speed search starts with the
minimum frequency
Maximum Allowable
08-05 0.1 to 5.0 sec 2
Power Loss Time
B.B. Time for Speed
08-06 0.1 to 5.0 sec 0.5
Search
Current Limit for
08-07 30 to 200% 150
Speed Search
Skip Frequency 1
08-08 0.00 to 400.00 Hz 0
Upper Limit
Skip Frequency 1
08-09 0.00 to 400.00 Hz 0
Lower Limit
Skip Frequency 2
08-10 0.00 to 400.00 Hz 0
Upper Limit
Skip Frequency 2
08-11 0.00 to 400.00 Hz 0
Lower Limit
Skip Frequency 3
08-12 0.00 to 400.00 Hz 0
Upper Limit
Skip Frequency 3
08-13 0.00 to 400.00 Hz 0
Lower Limit
5-14 Revision July 2008, BE16, SW V4.08 & V5.00
Downloaded from www.Manualslib.com manuals search engine
Customer

0.05

0.10

201

369

Customer

00

0.0

0.0

0.00

00

2.0

0.5

150

0.00

0.00

0.00

0.00

0.00

0.00
Chapter 5 Parameters|VFD-B Series
Factory
Parameter Explanation Settings
Setting
Auto Restart After
08-14 00 to 10 (00=disable) 0
Fault
00: Disable
08-15 Auto Energy Saving 0
01: Enable
00: AVR function enable
08-16 AVR Function 01: AVR function disable 0
02: AVR function disable for decel.
230V series: 370 to 430V 380
Software Brake
08-17 460V series: 740 to 860V 760
Level
575V series: 925 to1075V 950
00: Speed search starts with last frequency
Base-block Speed
08-18 command 0
Search
01: Starts with minimum output frequency
Speed Search 00: Speed search disable
08-19 0
during Start-up 01: Speed search enable
Speed Search
00: Setting frequency
a08-20 Frequency during 0
01: Maximum operation frequency (01-00)
Start-up
Auto Reset Time at
08-21 00 to 60000 sec 600
Restart after Fault
Compensation
a08-22 Coefficient for Motor 00~1000 0
Instability
Group 9 Communication Parameters
Factory
Parameter Explanation Settings
Setting
Communication
a09-00 01 to 254 01
Address
00: Baud rate 4800bps
01: Baud rate 9600bps
a09-01 Transmission Speed 01
02: Baud rate 19200bps
03: Baud rate 38400bps

00: Warn and keep operating


Transmission Fault 01: Warn and ramp to stop
a09-02 03
Treatment 02: Warn and coast to stop
03: No warning and keep operating
0.0 ~ 60.0 seconds
a09-03 Time-out Detection 0
0.0: Disable

00: 7,N,2 (Modbus, ASCII)


01: 7,E,1 (Modbus, ASCII)
Communication 02: 7,O,1 (Modbus, ASCII)
a09-04 0
Protocol 03: 8,N,2 (Modbus, RTU)
04: 8,E,1 (Modbus, RTU)
05: 8,O,1 (Modbus, RTU)
Revision July 2008, BE16, SW V4.08 & V5.00 5-15

Downloaded from www.Manualslib.com manuals search engine


Customer

00

00

00

760

00

00

00

600

00

Customer

01

01

03

0.0

00
Chapter 5 Parameters|VFD-B Series
Factory
Parameter Explanation Settings
Setting
09-05 Reserved
09-06 Reserved
Response Delay
a09-07 00 ~ 200 msec 0
Time
Group 10 PID Control Parameters
Factory
Parameter Explanation Settings
Setting
00: Inhibit PID operation
01: Negative PID feedback from external
terminal (AVI) 0 to +10V
02: Negative PID feedback from external
Input terminal for
10-00 terminal (ACI) 4 to 20mA 0
PID Feedback
03: Positive PID feedback from external
terminal (AVI) 0 to +10V
04: Positive PID feedback from external
terminal (ACI) 4 to 20mA
Gain over PID
10-01 0.00 to 10.00 1
Detection value
a10-02 Proportional Gain (P) 0.0 to 10.0 1

a10-03 Integral Gain (I) 0.00 to 100.00 sec (0.00=disable) 1


Derivative Control
a10-04 0.00 to 1.00 sec 0
(D)
Upper Bound for
10-05 00 to 100% 100
Integral Control
Primary Delay Filter
10-06 0.0 to 2.5 sec 0
Time
PID Output Freq
10-07 0 to 110% 100
Limit
Feedback Signal
10-08 0.0 to 3600.0 sec 60
Detection Time
Treatment of the 00: Warn and keep operation
a10-09 Erroneous Feedback 01: Warn and RAMP to stop 0
Signals 02: Warn and COAST to stop

10-10 PG Pulse Range 1 to 40000 600

00: Disable PG
01: Single phase
10-11 PG Input 0
02: Forward / Counterclockwise rotation
03: Reverse / Clockwise rotation
ASR (Auto Speed
a10-12 Regulation) control 0.0 to 10.0 1
(with PG only) (P)
5-16 Revision July 2008, BE16, SW V4.08 & V5.00

Downloaded from www.Manualslib.com manuals search engine


Customer

00
00

00

Customer

00

1.00

1.0

1.00

0.00

100

0.0

100

60.0

00

600

00

1.0
Chapter 5 Parameters|VFD-B Series
Factory
Parameter Explanation Settings
Setting
ASR (Auto Speed
a10-13 Regulation) control 0.00 to 100.00 (0.00 disable) 1
(with PG only) (I)
Speed Control
10-14 Output Frequency 0.00 to 100.00 Hz 10
Limit
Sample time for
refreshing the
10-15 0.01~1.00 seconds 0.10
content of 210DH
and 210EH
Deviation Range of
10-16 PID Feedback Signal 0.00~100.00% 100
Error
Group 11 Fan & Pump Control Parameters
Factory
Parameter Explanation Settings
Setting
00: V/f curve determined by Pr.01-00 to
Pr.01-06
01: 1.5 power curve
11-00 V/f Curve Selection 0
02: 1.7 power curve
03: Square curve
04: Cube curve
Start-Up Frequency
11-01 of the Auxiliary 0.00 to 400.00 Hz 0
Motor
Stop Frequency of
11-02 0.00 to 400.00 Hz 0
the Auxiliary Motor
Time Delay before
11-03 Starting the Auxiliary 0.0 to 3600.0 sec 0
Motor
Time Delay before
11-04 Stopping the 0.0 to 3600.0 sec 0
Auxiliary Motor
Sleep/Wake Up
11-05 0.0 ~6550.0 sec 0
Detection Time

11-06 Sleep Frequency 0.00~Fmax 0

11-07 Wakeup Frequency 0.00~Fmax 0

Revision July 2008, BE16, SW V4.08 & V5.00 5-17

Downloaded from www.Manualslib.com manuals search engine


Customer

1.00

10.00

0.10

100.00

Customer

00

0.00

0.00

0.0

0.0

0.0

0.00

0.00