Date/Time Event Text Rec. SCHNEIDER


seconds
APERTURA Y CIERRE MANUAL Alimentador SUR

07/01/2019 15:27:21 564 Panel Close Request


07/01/2019 15:27:15 448 Operator control panel door opened
07/01/2019 15:07:33 340 Operator control panel door closed
07/01/2019 15:07:29 120 Load Supply Off
07/01/2019 15:07:27 245 Last Good Value Trapped is    61 A
07/01/2019 15:07:25 32 Lockout
07/01/2019 15:07:24 993 Panel Trip Request
07/01/2019 15:07:19 332 Operator control panel door opened
OPERACIÓN DE RECIERRE EXITOSO
07/01/2019 14:27:40 942 Protection Disk Reset
07/01/2019 14:27:40 844 All protection elements resetting
07/01/2019 14:27:40 805 Protection Group A Active
07/01/2019 14:27:40 782 Pickup
07/01/2019 14:27:40 746 Automatic Reclose
07/01/2019 14:27:39 870 Protection Disk Reset
07/01/2019 14:27:39 820 All protection elements resetting
07/01/2019 14:27:39 819 Measuring Frequency On Bushing Ci
07/01/2019 14:27:39 782 Phase C ‐ Maximum Current of 115 A during fault
07/01/2019 14:27:39 782 Phase B ‐ Maximum Current of 967 A during fault
07/01/2019 14:27:39 782 Phase A ‐ Maximum Current of 906 A during fault
07/01/2019 14:27:39 780 Current at trip C phase 87 A at the time of trip
07/01/2019 14:27:39 780 Current at trip B phase 914 A at the time of trip
07/01/2019 14:27:39 780 Current at trip A phase 867 A at the time of trip
07/01/2019 14:27:39 744 Protection Trip 1
07/01/2019 14:27:39 744 Phase Protection Trip
07/01/2019 14:27:39 744 Protection Group A Active
07/01/2019 14:27:39 744 Protection Trip Request
07/01/2019 14:27:39 693 Protection Group A Active
07/01/2019 14:27:39 669 Pickup