Tianshui Changcheng Switchgear Factory

KYN28A-12 (GZS1)

A.C METALCLAD REMOVABLE SWITCHGEAR

FOR INDOOR USE

CHINATCS
2001.09
Tianshui Changcheng Switchgear Factory

KYN28A-12 (GZS1)

A.C Metalclad Removable Switchgear for Indoor Use

--------The Leader in Switchgear Up to 12kV

1. The cabinet is set up with the parts made of by aluminum-coated zinc plates.

2. Complete metalclad and isolated.

3. All operations can be carried out with the cubicle door closed.

4. The degree of protection of the enclosure is IP4X, which can prevent sundries and reptiles

from entering.

5. Simple and reliable interlocking system can avoid misoperations.

6. Can be equipped with type ZN63A (VS1) and imported type VD4 vacuum circuit breaker.

7. Few maintenance for the vacuum circuit breaker and its operation device in the H.V

compartment.

8. It is easy to replace circuit breaker, and the truck is provided with perfect

interchangeability.

9. The cabinet can be mounted against the wall and maintenance can be carried out in front

of the cubicles, thus less room required.

10. Easy connections for secondary circuit in the wiring channel with rich space.

11. Rich area for connection enough cables in cable compartment.

12. The cable compartment can be inspected easily through the front inspection window.

13. Quick earthing switch for earthling and short-circuit case.

14. Conforming to the standards of GB3906, DL404, and IEC298.

KYN28A-12 (GZS1) 1
Tianshui Changcheng Switchgear Factory

1 General

1.1 Summary

Type KYN28A-12 (GZS1) A.C Metalclad Removable Switchgear manufactured by Tianshui


Changcheng Switchgear Factory (called the switchgear or the switchgear in the following)
which is indoor power distributing equipment of 3-phase, A.C 50Hz system, is suitable to be
used to receive and distribute the electric power of 3.6 ~ 12 kV power system, as well as to
control, protect and monitor the circuit. The switchgear conforms to the standards of GB3906,
DL404, IEC298 and etc. The switchgear is provided with called 5-prevention function, that is:
z Prevent the circuit-breaker from misoperation;
z Prevent the truck from being pushed and pulled on-load;
z Prevent the earthing switch from being closed while the switchgear is electrified;
z Prevent the switchgear from being electrified with the earthing switch being closed;
z Prevent entering electrified compartment.
The switchgear can be equipped with type ZN63A (VS1) as well as imported type VD4
vacuum circuit breaker.

1.2 Service Conditions

The switchgear can meet the requirement specified in the national standard GB11022 as well
as the requirement of condensation and dirty grade II.

2 Technical parameter

2.1 Technical Parameter of the Switchgear

The technical parameter of the switchgear is shown in table 1.

KYN28A-12 (GZS1) 2
Tianshui Changcheng Switchgear Factory

Table 1 The Technical Parameter of the Switchgear

Item Unit Data


Rated voltage kV 3.6 7.2 12
Power frequency withstand voltage
Rated kV 42
(1 min) (r.m.s)
insulation
Lightning impulse withstand voltage
level kV 75
(full wave)
Rated frequency Hz 50
Rated current A 630,1250,1600,2000,2500,3150
4s withstand current (r.m.s.) kA 20,25,31.5,40,50
Rated withstand current (peak) kA 50,63,80,100,130
Enclosure IP4X
Protection
degree With the door of circuit-breaker compartment open IP2X

2.2 The Technical Parameter of Type ZN63A Vacuum Circuit-breaker

The Technical parameter of the type ZN63A vacuum circuit breaker is shown in table 2.

Table 2 The Technical parameter of the type ZN63A vacuum circuit-breaker

Item Unit Data


Rated voltage kA 3.6, 7.2, 12
Power frequency withstand voltage
42
(1 min) (r.m.s)
Rated
Lightning impulse withstand voltage
insulation kV 75
(peak value before breaking)
level
Lightning impulse withstand voltage
75
(peak value after breaking)
Rated frequency Hz 50
Rated current A 630,1250,1600,2000,2500.3150
Single and back-to-bank capacitor bank breaking current A 630/400
Rated short-circuit breaking current 20,25,31.5,40,50
Rated short-circuit withstand current (4s r.m.s) 20,25,31.5,40,50
kA
Rated short-circuit marking current (peak) 50,63,100,130
Rated peak withstand current 50,63,100,130
Rated operating sequence O-180s-CO-180s-CO
Auto-reclosing operating sequence O-0.3s-CO-180s-CO
Closing time 100
Opening time ms 50
Arcing time 15
Breaking times aganist rated short-circuit breaking current times 50 (30*)
Mechanical endurance cycles 20000
Accumulating thickness of permissive consumption for
mm 3
fixed and movable contacts
Note:* The breaker times against rated short circuit breaking current is 30 times when the rated short
circuit breaking current is 40kA.

KYN28A-12 (GZS1) 3
Tianshui Changcheng Switchgear Factory

2.3 The Technical Parameter of Operating device

The technical parameter of operating device is shown in table 3.

Table 3 Technical Parameter of Operating Device

Item Unit Data


DC220, 110
Rated operating Closing coil AC220, 110
V
voltage
Opening coil
Closing coil
Power of coil W 245
Opening coil
Power of stored-energy motor W 70
Rated voltage of closing coil of stored-energy motor V DC220, 110
Energy storage time s 15

3 Overall Dimension and Weight

3.1 Cabinet

The overall dimension and weight of cabinet is shown in Figure 1 and table 4.

Table 4 The Overall Dimension and Weight of Cabinet

Height A (mm) 2365


Rated current of sub busbar up to 1250A, raged short time
800
Width B withstand current being 31.5kA
(mm)
Rated current of sub busbar above 1250A 1000

Cable incoming and outgoing feeder 1500


Depth C
(mm)
Overhead incoming and outgoing feeder 1800

Weight (kg) 800 ~ 1200

KYN28A-12 (GZS1) 4
Tianshui Changcheng Switchgear Factory

Fig 1 The overall dimension of the switchgear

3.2 Circuit Breaker

The overall dimension of type ZN63A vacuum circuit breaker is shown in Figure 2(a) and
Figure 2(b).

Figure 2(a) The overall dimension of type ZN63A-12/1250-31.5 vacuum circuit breaker

KYN28A-12 (GZS1) 5
Tianshui Changcheng Switchgear Factory

Figure 2(b) The overall dimension of type ZN63A-12/3150-40 vacuum circuit breaker

4 Structure of Switchgear

The switchgear consists of 2 parts of fixed cabinet and removable parts (called truck). The
typical structure drawing of the switchgear is shown in Figure 3 and Figure 4. The enclosure
and all partitions of each functional units are all made by aluminum-coated zinc plate. The
degree of protection of the enclosure is IP4X, the degree of protection with the door of
circuit-breaker compartment open is IP2X.
The switchgear can be equipped with type ZN63A (VS1) vacuum circuit breaker, The
switchgear can be arranged in double rows, that is, arranged in back-to-back or face-to-
face way. Because the switchgear can be installed and adjusted from the front, it can be
installed against wall to save floor area as well as increase the safety of the switchgear and
the flexibility for installation.

4.1 Enclosure and Partitions

The enclosure and partitions of the switchgear is set up by aluminum-coated zinc plate
which is machined and bent by NC machine, so the finished switchgears are provided with
unity in size. The aluminum-coated zinc plate has excellent corrosion-proof and oxidation-
resistance function as well as high mechanical intensity, The switchgear is separated into
circuit-breaker compartment, busbar compartment, cable compartment, and instrument
compartment (LV compartment) by partitions. The enclosure for every unit is earthed
reliably.

KYN28A-12 (GZS1) 6
Tianshui Changcheng Switchgear Factory

4.2 Truck

The framework of truck is set up by thin steel plate through welding and riveting, the thin
steel plate is processed by laser cutting machine. The truck can be divided into circuit-
breaker truck, voltage transformer truck, measuring truck, and etc. the trucks with same
specification can be interchanged. The truck has test position and service position inside
the cabinet. The locking device is provided to every position in order to prevent the truck
from being moved away from its position. The truck can not be removed unless the
interlocking device being released. For example, the circuit-breaker truck can not be
removed before the circuit-breaker opens.

A ---- Busbar compartment B ---- Circuit breaker truck compartment


C ---- Cable compartment D ---- Instrument compartment
1--Pressure releasing device; 2--Enclosure; 3--Branch busbar; 4--Busbar bushing; 5--Main busbar;
6--Fixed contacts device; 7--Fixed contacts box; 8--Current transformer; 9--Earthing switch;
10--Cable; 11--Surge arrester; 12--Main earthing busbar; 13--Partition; 14--Shutter;
15--Secondary plug; 16--Circuit-breaker truck; 17--Heater; 18--Removable partition;
19--Operating device for earthing switch; 20--Control busbar; 21--Cable cover
Figure 3 Typical structural drawing of the switchgear (being installed free from wall)

KYN28A-12 (GZS1) 7
Tianshui Changcheng Switchgear Factory

A ---- Busbar compartment B ---- Circuit breaker truck compartment


C ---- Cable compartment D ---- Instrument compartment
1--Pressure releasing device; 2--Enclosure; 3--Branch busbar; 4--Busbar bushing; 5--Main busbar;
6--Fixed contacts device; 7--Fixed contacts box; 8--Current transformer; 9--Earthing switch;
10--Cable; 11--Surge arrester; 12--Main earthing busbar; 13--Partition; 14--Shutter;
15--Secondary plug; 16--Circuit-breaker truck; 17--Heater; 18--Removable partition;
19--Operating device for earthing switch; 20--Control busbar; 21--Cable cover
Figure 4 Typical structural drawing of the switchgear (being installed against wall)

KYN28A-12 (GZS1) 8
Tianshui Changcheng Switchgear Factory

4.3 Compartments

4.3.1 Circuit Breaker Compartment


Special rail are located inside the circuit-breaker compartment for the truck to move and work
in, the circuit-breaker can move between service position and test position in the rail. The
shutter (14) is mounted on the rear wall of circuit-breaker compartment. The shutter (14) can
open automatically during moving the truck from test position to service position, the shutter
can close completely after moving the truck from service position to test position, which
prevents the operators from touching the live parts. The truck can be operated with the
cabinet door closed. Through the inspection window, the position of truck, the ON/OFF
buttons (marking the circuit-breaker closing/opening) on the truck, ON/OFF mechanical
position indicator can be observed as well as energy-stored/energy-released indicator can be
observed clearly.

4.3.2 Busbar Compartment


The busbar (5) is led from one switchgear to another, and fixed with branch busbar (3) and
fixed contacts terminal box. All busbar can be sealed with thermal shrinkage insulation
bushing in accordance with the requirement of users. Flat sub busbar is connected with fixed
contact terminal box and main busbar by bolts without any other wire clips and insulators. The
connecting bolts on the busbar can be enclosed with insulation bushing and cap. The busbar
is fixed with busbar bushing (4) when passing through the partitions, which can prevent the
default from extending to adjacent switchgear when internal arc appears, and increase the
intensity of busbar.

4.3.3 Cable Compartment


The current transformer (8) and earthing switch (9) can be mounted at the top, rear wall and
front wall of the cable compartment, the surge arrester (11) can be mounted inside the cable
compartment. The operator can enter the cabinet from front to mount the cable after the truck
(16) and removable partition (18) being removed. Special cable connecting conductor is
located in the cable compartment, the removable metal cable cover (21) with slot is located
under the cable compartment, thereby, the cable connecting at site is made convenient.

4.3.4 LV Compartment
Relays, protective elements, instruments, voltage indicators and secondary devices for
special requirement can all be mounted in LV compartment. The control wires are placed in

KYN28A-12 (GZS1) 9
Tianshui Changcheng Switchgear Factory

the wire channel with enough area and closed with metal cover, the wire channel on the left
side is designed for control wires, the wire channel for the secondary wire of the switchgear
itself is located on the right side.

4.4 Interlocking Device

The switchgear has reliable interlocking device, which can guarantee the safety of operators
and the switchgear. It s function is as following:
a) The truck can be moved from the test position to the service position only when the
earthing switch is in open position.
b) The circuit breaker can not be operated before the truck being locked in the test or the
service position.
c) The secondary plug can not be removed with the truck in the service position.
d) The truck can not be moved from the test position to the service position with the
earthing switch closed.
e) The earthing switch can be operated only when the truck is in the test position.

4.5 Pressure Releasing Device

The pressure releasing devices are designed in truck compartment, busbar compartment as
well as cable compartment. When the air pressure inside the switchgear rises because of the
internal fault arc appearing on the circuit-breaker or busbar, the special seal ring on the door
can seal the front part of the cabinet, and the pressure releasing metal plate on the top can be
opened automatically, thereby, the gas is given out and the pressure inside goes down, so the
operators and the switchgear is in safety.

4.6 Interlocking between secondary plug and truck

The secondary wires of the switchgear and truck are connected by secondary plug, the
movable contacts of the secondary plug are connected with the truck by a nylon blowpipe,
The secondary fixed contact holder is located on the top right of the truck compartment. The
secondary plug can be pushed in and pulled out only when the truck is in the test position, on
the other hand, the secondary plug is licked and can not be removed when the truck is in the
service position.

KYN28A-12 (GZS1) 10
Tianshui Changcheng Switchgear Factory

4.7 Earthing Device

The earthing copper plate (10mm x 40mm) is designed in the cable compartment, it can pass
throng the neighboring switchgears and connected with the cabinet reliably. It is used for the
parts to be directly earthed, because the cabinet is assembled by aluminum-coated zinc plate,
the whole cabinet is earthed reliably, which makes the operators safe when they touch the
enclosure.

5 Installation and Adjustment

5.1 Type of Foundation

5.1.1 The construction of foundation for installing the switchgears should conform to the
Technical Specification for Electric Power Construction and Inspection.
5.1.2 The foundation for the switchgears should be cast for 2 times. For the first time, the
foundation for the structural components used to install the switchgears such as angle
steel, square steel or channel steel, should be cast; for the second time, the
supplementary layer of concrete surface should be cast, the thickness of which is
60mm. The supplementary layer of concrete surface should be lower than the
structural components used to install the switchgears for 1~3mm.
5.1.3 The foundation frame drawing is shown in Figure 5.
5.1.4 The foundation frame should be installed in order, the technical deviation for installing
the foundation frame is 1mm/mm2.

5.2 Installation of the Switchgear

5.2.1 The size of installing foundation and the installing size of the switchgear is shown in
Figure 6 and Figure 7.
5.2.2 The operating corridor in front of the switchgears should be 2.5m when the switchgears
are installed in single row; and the operating corridor between two rows of the
switchgears should be 3m when the switchgears are installed in double rows. The
installing drawing of switchgears installed face to face and against the wall is shown in
Figure 8.
5.2.3 Move the switchgear to the specified position according to the requirement and
drawings. If the switchgears in one roe is too many, the arrangement should begin an
the center.

KYN28A-12 (GZS1) 11
Tianshui Changcheng Switchgear Factory

5.2.4 Special transporting tools, such as cranes and forks, are necessary, it is not permitted
to use rollers and crowbars.
5.2.5 Pull the circuit breaker trucks out of the switchgears, and keep them appropriately.
5.2.6 Loosen the screws mounting the horizontal partition (18) under the circuit-breaker
compartment, and remove the horizontal partition (18).
5.2.7 Loosen and remove the cable cover (21).
5.2.8 Remove the cover of the control wire channel on the left side of the switchgear, and the
one on the right side.
5.2.9 Remove the hoisting plated and fastenings.
5.2.10 The rear cover of the switchgear and the cover of busbar compartment can be moved
away for installing when the switchgear is installed from wall.
5.2.11 Install the switchgear on the foundation in accordance with specified sequence. The
levelness in horizontal and vertical direction should not exceed 2mm.
5.2.12 After being combined (arranged) on the foundation, the switchgears should be
connected with the foundation frame by foundation bolts or by welding.

6 Installation of Busbar

The busbar in the switchgear are rectangular busbar and divided into sections, the busbar for
switchgear with different current are only different from quantity and specification. The
following should be complied with when installing the busbar.

6.1 Cleaning the busbar with soft cloth that is clean and dry, check whether there is
damage on the insulating bushing, apply conductive paste or neutral vaseline on
the connecting position of busbar.

6.2 Install the busbar in sequence, connect the sections of busbars and
corresponding sub busbar together, insert proper pads and then screw down
with bolts.

KYN28A-12 (GZS1) 12
Tianshui Changcheng Switchgear Factory

7 Earthing Device

7.1 Connect the earthing busbar (12) of all switchgear with prepared connection
board.

7.2 Connect all earthing wires inside the switchgear.

7.3 Connect the foundation frame with the earthing plate.

7.4 Connect the earthing wire of earthing contact with the earthing busbar of the
distributing panel.

Width (A) Depth (B) M N L L1


1500 (cable incoming and outgoing) 1450 880
800 630 800
1800 (overhead incoming and outgoing) 1750 1040
1500 (cable incoming and outgoing) 1450 880
1000 830 1000
1800 (overhead incoming and outgoing) 1750 1040

Figure 5 The foundation frame drawing of the switchgear

KYN28A-12 (GZS1) 13
Tianshui Changcheng Switchgear Factory

Figure 6(a) The foundation drawing for the switchgears

KYN28A-12 (GZS1) 14
Tianshui Changcheng Switchgear Factory

Depth L
1500 1450
1800 1750
Figure 6(b) The foundation drawing for the switchgears

KYN28A-12 (GZS1) 15
Tianshui Changcheng Switchgear Factory

A-A
The switchgears installed free from wall

A-A
The switchgears installed against wall

C-direction

Figure 6 (c) The foundation drawing for the switchgears

KYN28A-12 (GZS1) 16
Tianshui Changcheng Switchgear Factory

Width of the
switchgear Depth of the switchgear (b) L1 L2 L3
(A)
1500(cable incoming & outgoing) 880
800 530 630
1500(overhead incoming & outgoing) 990
1500(cable incoming & outgoing) 880
1000 730 830
1500(overhead incoming & outgoing) 990

Figure 7 Drawing for installing dimension of the switchgears

KYN28A-12 (GZS1) 17
Tianshui Changcheng Switchgear Factory

Figure 8 The installing drawing for the switchgears installed face-to-face against wall

KYN28A-12 (GZS1) 18
Tianshui Changcheng Switchgear Factory

8 Installation of Busbar Bridge

The installing dimension of the busbar bridge is shown in Figure 9.

Figure 9 The installing dimension of the busbar bridge

9 Installing dimension for overhead incoming scheme

The installing dimension for overhead incoming scheme is shown in Figure 10.

Figure 10 The installing dimension for overhead incoming scheme

KYN28A-12 (GZS1) 19
Tianshui Changcheng Switchgear Factory

10 Primary Circuit Scheme

The primary circuit scheme of the switchgears is shown in table 5.

11 Secondary Circuit Scheme

11.1 The electric wiring diagram of circuit-breaker truck is shown is Figure 11.

11.2 The typical control circuit (AC operation) of the switchgear with ZN63A vacuum
circuit-breaker (VCB) is shown in Figure 12.

11.3 The typical control circuit (DC operation) of the switchgear with ZN63A vacuum
circuit-breaker (VCB) is shown in Figure 12.

12 Ordering Information

Following information should be supplied when ordering:

12.1 Primary scheme serial No., primary scheme system drawings, arrangement
drawings and layout drawings.

12.2 Secondary functional drawings, arrangement drawings of terminals.

The terminals will be arranged in accordance with the standard mode by the
manufacturer if the arrangement drawings of terminals are not supplied.

12.3 The type, specification and quantity of the electric components inside the
switchgears.

12.4 Summary schedule of electric equipments.

12.5 The span across two rows of switchgears and height when busbar bridge

(busbar bridge between tow rows of switchgears or the ones between the wall
and swtichgear) is needed.

12.6 If the switchgears is used in special condition, it should be specified when


ordering.

12.7 The kinds and quantity of extra accessories and spare parts requited.

KYN28A-12 (GZS1) 20
Tianshui Changcheng Switchgear Factory

The secondary electric diagram of the switchgear with DC control.


(The switchgear without anti-jumping function, the circuit-breaker with anti-jumping function.)

The secondary electric diagram of the switchgear with AC control.


(The switchgear without anti-jumping function, the circuit-breaker with anti-jumping function.)

No. Symbol Name


1 S1 Micro-switch for energy storage
2 S2 Auxiliary switch interlocked with the principal axis
3 K0 Intermediate relay
4 V1~V3 Rectifying elements
5 HQ Closing electromagnet
6 TQ Opening electromagnet
7 M Motor for energy storage
8 Y1~Y3 Electromagnet for over-current release
9 SW, YW Indicator for position of truck

Figure 11(a) The Electric diagram of circuit-breaker (with anti-jumping function)

KYN28A-12 (GZS1) 21
Tianshui Changcheng Switchgear Factory

The secondary electric diagram of the switchgear with DC control


(The switchgear with anti-jumping function, the circuit-breaker without anti-jumping function)

The secondary electric diagram of the switchgear with AC control


(The switchgear with anti-jumping function, the circuit-breaker without anti-jumping function)

No. Symbol Name


1 S1 Micro-switch for energy storage
2 S2 Auxiliary switch interlocked with the principal axis
3 K0 Intermediate relay
4 V1~V3 Rectifying elements
5 HQ Closing electromagnet
6 TQ Opening electromagnet
7 M Motor for energy storage
8 Y1~Y3 Electromagnet for over-current release
9 SW, YW Indicator for position of truck

Figure 11(b) The electric diagram circuit-breaker (without anti-jumping function)

KYN28A-12 (GZS1) 22
Tianshui Changcheng Switchgear Factory

KK:LW2-Z-a.4.6a.40.20/F8; (HA,TA):LA18-22
LD,HD,UD(1LD,1HD):AD1-25/21 220V(XD5) 1RD,2RD,3RD,4RD,HRD:RT19-16/6A
HK:KN3-A 1Z1D; SW,YW:F1-41/Y.H(The indication ;amp of truck position)

The switchgear without anti-jumping function

KK:LW2-Z-a.4.6a.40.20/F8; (HA,TA):LA18-22
LD,HD,UD(1LD,1HD):AS1-25/21 220V(XD5) 1RD,2RD,3RD,4RD,HRD:RT19-16/6A
TBJ:DZ-52/220V;HK:KN3-A 1Z1D SW,YW:F1-41/Y.H(The indication ;amp of truck position)

The switchgear with anti-jumping function

Figure 12 The typical control circuit for the switchgear equipped


with type ZN63A vacuum circuit-breaker (AC operation)

KYN28A-12 (GZS1) 23
Tianshui Changcheng Switchgear Factory

KK:LW2-Z-a.4.6a.40.20/F8; (HA,TA):LA18-22;ZG11-50W/1K
LD,HD,UD(1LD,1HD):AD1-25/21 220V(XD5) 1RD,2RD,3RD,4RD,HRD:RT19-16/6A
HK:KN3-A 1Z1D; SW,YW:F1-41/Y.H(The indication ;amp of truck position)

The switchgear without anti-jumping function

KK:LW2-Z-a.4.6a.40.20/F8; (HA,TA):LA18-22;ZG11-50W/1K
LD,HD,UD(1LD,1HD):AS1-25/21 220V(XD5) 1RD,2RD,3RD,4RD,HRD:RT19-16/6A
TBJ:DZ-284/220V;HK:KN3-A 1Z1D SW,YW:F1-41/Y.H(The indication ;amp of truck position)

The switchgear with anti-jumping function

Figure 13 The typical control circuit for the switchgear equipped


with type ZN63A vacuum circuit-breaker (DC operation)

KYN28A-12 (GZS1) 24
Application example (1) of main circuit scheme

KYN28A-12 (GZS1)
Application example (1) of main circuit scheme
Tianshui Changcheng Switchgear Factory

25
Tianshui Changcheng Switchgear Factory

Table 5 Main Circuit Schemes

Scheme serial No. 001 002 003 004 005

Primary system diagrams

Rated current (A) 630 ~ 3150


ZN63A (VS1)
VCB 1 1 1 1 1
Main Primary components

VD4
LZZBJ1-10GY
CT LZZB1-10GY 2 2 2 3 3
LZZB-10GY
RZL-10
VT
REL-10
HV Fuse RN2-10
Earthing Switch JN15 1 1 1
Surge arrester

Power receiving Power receiving Power receiving Power receiving Power receiving
Application
& Feeding & Feeding & Feeding & Feeding & Feeding

Remarks Width of the switchgears is 1000m when their rated current is above 1600A.

Scheme serial No. 006 007 008 009 010

Primary system diagrams

Rated current (A) 630 ~ 3150


ZN63A (VS1)
VCB 1 1 1 1 1
Main Primary components

VD4
LZZBJ1-10GY
CT LZZB1-10GY 3 2 2 2 2
LZZB-10GY
RZL-10
VT
REL-10
HV Fuse RN2-10
Earthing Switch JN15 1 1 1
Surge arrester 3

Power receiving Coupler Coupler Coupler Coupler


Application
& Feeding (right) (right) (left) (left)

Remarks Width of the switchgears is 1000m when their rated current is above 1600A.

KYN28A-12 (GZS1) 26
Tianshui Changcheng Switchgear Factory

Table 5 Main Circuit Schemes (Continuous)

Scheme serial No. 011 012 013 014 015

Primary system diagrams

Rated current (A) 630 ~ 3150


ZN63A (VS1)
VCB 1 1 1 1 1
Main Primary components

VD4
LZZBJ1-10GY
CT LZZB1-10GY 2 2 2 3 3
LZZB-10GY
RZL-10
VT
REL-10
HV Fuse RN2-10
Earthing Switch JN15 1 1
Surge arrester
Overhead
Coupler Coupler Coupler Coupler
Application incoming (left
(right) (right) (left) (left)
coupler)

Remarks Width of the switchgears is 1000m when their rated current is above 1600A.

Scheme serial No. 016 017 018 019 020

Primary system diagrams

Rated current (A) 630 ~ 3150


ZN63A (VS1)
VCB 1 1 1 1 1
Main Primary components

VD4
LZZBJ1-10GY
CT LZZB1-10GY 3 3 3 3 2
LZZB-10GY
RZL-10
VT
REL-10
HV Fuse RN2-10 3 3
Earthing Switch JN15 1 1 1
Surge arrester
Overhead Overhead Overhead Overhead Overhead
Application incoming (left incoming (right incoming (right incoming (left incoming (left
coupler) coupler) coupler) coupler) coupler)

Remarks Width of the switchgears is 1000m when their rated current is above 1600A.

KYN28A-12 (GZS1) 27
Tianshui Changcheng Switchgear Factory

Table 5 Main Circuit Schemes (Continuous)

Scheme serial No. 021 022 023 024 025

Primary system diagrams

Rated current (A) 630 ~ 3150


ZN63A (VS1)
VCB 1 1 1 1 1
Main Primary components

VD4
LZZBJ1-10GY
CT LZZB1-10GY 3 3 2 2 2
LZZB-10GY
RZL-10
VT
REL-10
HV Fuse RN2-10
Earthing Switch JN15 1 1 1
Surge arrester 3
Overhead Overhead Overhead
Application incoming (right incoming (right incoming and
coupler) coupler) outgoing
1. Width of the switchgears is 1000m when their rated current is above 1600A.
Remarks
2. The depth of No.23, No.24 and No.25 is 1800mm.

Scheme serial No. 026 027 028 029 030

Primary system diagrams

Rated current (A) 630 ~ 3150


ZN63A (VS1)
VCB 1 1 1 1 1
Main Primary components

VD4
LZZBJ1-10GY
CT LZZB1-10GY 3 3 3 2 2
LZZB-10GY
RZL-10
VT RZL-10 2 RZL-10 2
REL-10
HV Fuse RN2-10 3 3
Earthing Switch JN15 1 1 1
Surge arrester 3
Overhead Overhead
Cable incoming Cable incoming
Application incoming and incoming and
& PT & PT
outgoing outgoing
1. Width of the switchgears is 1000m when their rated current is above 1600A.
Remarks
2. The depth of No.26, No.28 and No.29 is 1800mm.

KYN28A-12 (GZS1) 28
Tianshui Changcheng Switchgear Factory

Table 5 Main Circuit Schemes (Continuous)

Scheme serial No. 031 032 033 034 035

Primary system diagrams

Rated current (A) 630 ~ 3150


ZN63A (VS1)
VCB 1 1 1 1 1
Main Primary components

VD4
LZZBJ1-10GY
CT LZZB1-10GY 2 3 3 3 2
LZZB-10GY
RZL-10
VT RZL-10 2 RZL-10 2 RZL-10 2 RZL-10 2 RZL-10 3
REL-10
HV Fuse RN2-10 3 3 3 3 3
Earthing Switch JN15 1
Surge arrester 3 3

Cable incoming Cable incoming Cable incoming Cable incoming Cable incoming
Application
& PT & PT & PT & PT & PT

Remarks Width of the switchgears is 1000m when their rated current is above 1600A.

Scheme serial No. 036 037 038 039 040

Primary system diagrams

Rated current (A) 630 ~ 3150


ZN63A (VS1)
VCB 1 1
Main Primary components

VD4
LZZBJ1-10GY
CT LZZB1-10GY 2 2
LZZB-10GY
RZL-10
VT REL-10 3 REL-10 3 RZL-10 2 REL-10 3 RZL-10 2
REL-10
HV Fuse RN2-10 3 3 3 3 3
Earthing Switch JN15 1
Surge arrester 3
Voltage
Cable incoming Cable incoming Voltage Voltage
Application measuring &
& PT & PT measuring measuring
arrester

Remarks Width of the switchgears is 1000m when their rated current is above 1600A.

KYN28A-12 (GZS1) 29
Tianshui Changcheng Switchgear Factory

Table 5 Main Circuit Schemes (Continuous)

Scheme serial No. 041 042 043 044 045

Primary system diagrams

Rated current (A) 630 ~ 3150


ZN63A (VS1)
VCB
Main Primary components

VD4
LZZBJ1-10GY
CT LZZB1-10GY
LZZB-10GY
RZL-10
VT REL-10 3 RZL-10 2 REL-10 3 RZL-10 2 RZL-10 2
REL-10
HV Fuse RN2-10 3 3 3 3 3
Earthing Switch JN15
Surge arrester 3 3 3
Voltage Voltage Voltage Voltage Voltage
Application measuring & measuring & measuring & measuring & measuring &
arrester arrester arrester busbar coupler busbar coupler

Remarks Width of the switchgears is 1000m when their rated current is above 1600A.

Scheme serial No. 046 047 048 049 050

Primary system diagrams

Rated current (A) 630 ~ 3150


ZN63A (VS1)
VCB
Main Primary components

VD4
LZZBJ1-10GY
CT LZZB1-10GY
LZZB-10GY
RZL-10
VT REL-10 3 REL-10 3 RZL-10 2 RZL-10 2 REL-10 3
REL-10
HV Fuse RN2-10 3 3 3 3 3
Earthing Switch JN15
Surge arrester 3 3 3
Voltage Voltage Voltage
Voltage Voltage
measuring & measuring & measuring &
Application measuring & measuring &
arrester & arrester & arrester &
busbar coupler busbar coupler
busbar coupler busbar coupler busbar coupler
1. Width of the switchgears is 1000m when their rated current is above 1600A.
Remarks
2. The depth of No.69, No.70 is 1800mm.

KYN28A-12 (GZS1) 30
Tianshui Changcheng Switchgear Factory

Table 5 Main Circuit Schemes (Continuous)

Scheme serial No. 051 052 053 054 055

Primary system diagrams

Rated current (A) 630 ~ 3150


ZN63A (VS1)
VCB
Main Primary components

VD4
LZZBJ1-10GY
CT LZZB1-10GY
LZZB-10GY
RZL-10
VT REL-10 3
REL-10
HV Fuse RN2-10 3
Earthing Switch JN15
Surge arrester 3
Voltage
measuring & Isolating &
Application Busbar coupler Busbar coupler Isolating
arrester & coupler (left)
busbar coupler
Remarks Width of the switchgears is 1000m when their rated current is above 1600A.

Scheme serial No. 056 057 058 059 060

Primary system diagrams

Rated current (A) 630 ~ 3150


ZN63A (VS1)
VCB
Main Primary components

VD4
LZZBJ1-10GY
CT LZZB1-10GY
LZZB-10GY
RZL-10
VT RZL-10 2 RZL-10 2
REL-10
HV Fuse RN2-10 3 3
Earthing Switch JN15 1
Surge arrester
Isolating & (left) Isolating &
Outgoing Outgoing
Isolating & coupler & (right) coupler &
Application converting converting
(right) coupler voltage voltage
phase phase
measuring measuring
Remarks Width of the switchgears is 1000m when their rated current is above 1600A.

KYN28A-12 (GZS1) 31
Tianshui Changcheng Switchgear Factory

Table 5 Main Circuit Schemes (Continuous)

Scheme serial No. 061 062 063 064 065

Primary system diagrams

Rated current (A) 630 ~ 3150


ZN63A (VS1)
VCB
Main Primary components

VD4
LZZBJ1-10GY
CT LZZB1-10GY 2 2 3 3 2
LZZB-10GY
RZL-10
VT RZL-10 2 RZL-10 2 RZL-10 2 RZL-10 2 REL-10 3
REL-10
HV Fuse RN2-10 3 3 3 3 3
Earthing Switch JN15
Surge arrester

Measure & left Measure & right Measure & left Measure & right Measure & left
Application
coupler coupler coupler coupler coupler

Remarks Width of the switchgears is 1000m when their rated current is above 1600A.

Scheme serial No. 066 067 068 069 070

Primary system diagrams

Rated current (A) 630 ~ 3150


ZN63A (VS1)
VCB 1 1
Main Primary components

VD4
LZZBJ1-10GY
CT LZZB1-10GY 2 3 3 2 2
LZZB-10GY
RZL-10
VT REL-10 3 REL-10 3 REL-10 3 RZL-10 2 RZL-10 2
REL-10
HV Fuse RN2-10 3 3 3 3 3
Earthing Switch JN15
Surge arrester

Measure & right Measure & left Measure & right Incoming & Incoming &
Application
coupler coupler coupler measure measure

1. Width of the switchgears is 1000m when their rated current is above 1600A.
Remarks
2. The depth of No.69, No.70 is 1800mm.

KYN28A-12 (GZS1) 32
Tianshui Changcheng Switchgear Factory

Table 5 Main Circuit Schemes (Continuous)

Scheme serial No. 071 072 073 074 075

Primary system diagrams

Rated current (A) 630 ~ 3150


ZN63A (VS1)
VCB 1 1
Main Primary components

VD4
LZZBJ1-10GY
CT LZZB1-10GY 2 2 2 3 3
LZZB-10GY
RZL-10
VT RZL-10 2 RZL-10 2 RZL-10 2 RZL-10 2 RZL-10 2
REL-10
HV Fuse RN2-10 3 3 3 3 3
Earthing Switch JN15
Surge arrester

Incoming & Incoming & Incoming & Incoming & Incoming &
Application
measure measure measure measure measure

1. Width of the switchgears is 1000m when their rated current is above 1600A.
Remarks
2. The depth of No.71, No.75 is 1800mm.

Scheme serial No. 076 077 078

Primary system diagrams

Rated current (A) 630 ~ 3150


ZN63A (VS1)
VCB
VD4
Main Primary components

LZZBJ1-10GY
Capacitor
CT LZZB1-10GY 3 3
BM12.7-16-1
LZZB-10GY
RZL-10 Transformer
VT 1
REL-10 SC4-63/10
RN3-10 or RN3-10 or
HV Fuse RN2-10 3 3 3
RN1-10 RN1-10
Earthing Switch JN15
Surge arrester 3 3

Incoming & Station Capacitor


Application
measure transformer protecting

1. Width of the switchgears is 1000m when their rated current is above 1600A.
Remarks
2. The depth of No.76 1800mm.
Note: When the power receiving & power feeding scheme is used as power receiving,
the earthing switch should be taken out.

KYN28A-12 (GZS1) 33