Professional Documents
Culture Documents
Abstract
Recently with the progression of distributed generation, the power system needs flexible control of power transfer, bet-
ter power flow control and improvement of transient stability. Additionally for improving the reliability of power system
networks, using various protection strategies, power electronic switches are widely used to include new control strategies
for improvement of quality of power. Cascaded multilevel inverter based STATCOM with higher bandwidth are now thus
more efficient for minimizing voltage fluctuation, flicker mitigation, better reactive power compensation as well as stability
enhancement. In our paper a three level twelve-pulse VSI based STATCOM is proposed in a distribution system for analyz-
ing its effect on voltage profile as well as reactive power compensation under three phase fault condition. The proposed
method for controlling the Statcom clearly shows that by proper utilization of the Statcom in our distribution system, volt-
age profile across the various types of load improves effectively under three phase fault condition and thus sustainability
of the overall system will also improve. The output results show that the value of THD across different load voltages, e.g,
FFT analysis of output voltage across STATCOM in the branch with fault (THD = 4.26%) has been shown. Additionally, FFT
analysis of output voltage across Fixed Load (THD = 5.53%), Variable Load (THD = 2.76%), and Fixed Load current (THD =
2.85%) are within the acceptable limits and thus showing its well effectiveness in our proposed control strategy.
* Corresponding author:
Snehasish Pal (snehasish_pal@yahoo.co.in)
5190 Performance Analysis of a Three Level Twelve-pulse VSC based STATCOM under Fault Condition
However, there are some drawbacks also in FACTS 4) STATCOM device has been chosen and located
technology like the size of the storage systems (particu- optimally in order to control the power flows in the
larly BESS) which may be high enough for application in power system network.
transmission and distribution systems. However multi-
level inverter based STATCOM may offer better quality of The essential component in a VSC based STATCOM are
voltage profile decreased switching frequencies and mini- GTO-VSC bridge (s), DC capacitor (c), working as an
mization of stress in each power electronic switches. energy storage device, interfacing magnetic forming the
While the SVC performs as a controlled reactive admit- electrical coupling between the VSC bridge circuit, AC
tance, the STATCOM functions as a synchronous voltage mains system and controller generating gating signals.
source, as its name suggests. With currently available high- The reactive power exchange between the AC system and
power semiconductor devices, such as IGBTs, IGCTs and the compensator is controlled by varying the fundamental
ETOs (emitter turn-off thyristors), a STATCOM can switch component magnitude of the inverter voltage, above and
at several kilohertz and achieve a closed-loop bandwidth at below the AC system level. The compensator control is
several hundred hertz; hence the response time is much less achieved by small variations in the semiconductor devices
than one cycle. The STATCOM can also provide real power switching angle, so that fundamental component of the
compensation if interfaced with an energy storage unit, all voltage generated by the inverter is forced to lag or lead
of which are unattainable for SVC. With these benefits, the the AC system voltage by a few degrees causing the flow of
STATCOM performs significantly better than SVC [3]. active power into or out of the VSI & the resultant reactive
The advanced solution is the static synchronous power [4]. Figure 1 shows the schematic configuration of
compensator (STATCOM) based on a high frequency STATCOM. The controlled output voltage is maintained in
multi-level VSI. phase with the line voltage, and can be controlled to draw
either capacitive or inductive current from the line rap-
idly. STATCOM has the ability to maintain full capacitive
2. Operating Principle of FACTS output current at low system voltage, which improves the
Devices transient stability output voltage of VSC bridge is governed
by dc capacitor voltage which is controlled by varying the
In the interconnected electrical power system network, it
phase difference between output voltage of VSI and sys-
has been ascertained that the resistance of the transmis-
tem voltage at bus. The magnitude and phase difference of
sion line is much smaller compared to the reactance and
q-axis current determine the magnitude and phase differ-
the power flow obeys the Kirchoff ’s law. The active power
ence between output voltage of VSI and system voltage at
transmitted by a line between the buses i and j can be esti-
bus, which inturn controls reactive power flow.
mated by the following relationship:
ViVj
Pij = sin δ ij (1)
Xij
www.indjst.org | Vol 6 (9) | September 2013 Indian Journal of Science and Technology | Print ISSN: 0974-6846 | Online ISSN: 0974-5645
Snehasish Pal, S. P. Ray, Deepjyoti Dasgupta and Labani Chongdar 5191
www.indjst.org | Vol 6 (9) | September 2013 Indian Journal of Science and Technology | Print ISSN: 0974-6846 | Online ISSN: 0974-5645
5192 Performance Analysis of a Three Level Twelve-pulse VSC based STATCOM under Fault Condition
not only for fast communication to reach a lower THD but 7. Discussion
it can also be effectively used during fault conditions.
Improvement of power quality and increasing the reliabil-
ity of electrical power system has become an important
topic of discussion among the power engineers now-a-
6. Results
days. Power quality determines the fitness of electrical
In Figure 5, the output waveforms of different voltages and power to consumer devices. The STATCOM is a shunt
currents across the output port of Statcom and different load power electronic device used to help in improving the
end in the branch with fault have been shown. In Figure 5, voltage profile in the transmission system and thus helps
the first graph represents the output voltage waveform of to improve the power quality of the system. Reliability of
STATCOM. The second and the third graph represent the a system is achieved by separating the part of the system
output voltage waveform across the Fixed Load (1MW) under fault from the rest of the system and also ensur-
and Variable Load respectively. The last graph of these two ing that all major processes does not undergo any kind
figures represents the output current profile across the fixed of interruption. For this, more than one feeder are used
load. The effect of STATCOM during its operating period for all major loads with circuit breakers installed on
can be observed from these graphs for improving the volt- each feeders. Multipulse or multilevel configuration is
age and current profile across the load ends. Here, we also able to generate better voltage waveforms with a reduced
www.indjst.org | Vol 6 (9) | September 2013 Indian Journal of Science and Technology | Print ISSN: 0974-6846 | Online ISSN: 0974-5645
Snehasish Pal, S. P. Ray, Deepjyoti Dasgupta and Labani Chongdar 5193
Figure 6a. FFT analysis of output voltage across STATCOM Figure 6b. FFT analysis of output voltage across STATCOM
with fault(THD=4.26%). Fixed Load (THD=5.53%).
Figure 6c. FFT analysis of output voltage across STAT- Figure 6d. FFT analysis of current across the Fixed Load
COM Variable Load (THD=2.76%). (THD=2.85%).
harmonic content and thus the value of THD will be much of the high power STATCOM to handle various types of
lesser. The control strategy of dc-link voltage can quickly faults in the system. Due to improved dynamic perfor-
increase system stability and decrease electric impulsion. mance, extended operating range, increased availability,
The proposed model is feasible and reliable since it can be reduced line harmonics and an adjustable power factor at
operated without any interruption even during fault con- the point of common coupling, multilevel VSIs are used as
ditions and will be helpful to the design and development VSC within the STATCOM. So it is more suitable for the
www.indjst.org | Vol 6 (9) | September 2013 Indian Journal of Science and Technology | Print ISSN: 0974-6846 | Online ISSN: 0974-5645
5194 Performance Analysis of a Three Level Twelve-pulse VSC based STATCOM under Fault Condition
power electronic system with the high voltage and large Transmission Systems, Chapter 1, Institute of Electrical
capacity. and Electronic Engineer, New York.
2. XiaoY, SongY H et al. (2003). Available transfer capability
enhancement using FACTS devices, IEEE Transactions on
8. Conclusion Power systems, vol 18, No. 1, 305–312.
In this paper, three level twelve pulse VSI based STATCOM 3. Garlia-Cerrada A, Garcia-Gonzaloz P et al. (2000).
has been applied in parallel to the transmission line in a Comparison of thyristor controlled reactors and voltage-
source inverters for compensation of flickers caused by
distribution system for checking its effect on voltage pro-
arc furnaces, IEEE Transactions on P.D, vol 15, No. 4,
file across the load under three phase fault condition. The
1225–1231.
results are showing that the value of THD across differ-
4. Pal S, and Dalapati S (2012). Digital simulation of eighty-
ent load voltages and current are within the acceptable four pulse statcom for improvement of Power Quality,
limits. Also the voltage and current waveforms across the International Journal of Engineering Research and
load incur negligible changes during fault condition. Thus Applications, vol-V, No. 3, 235–246.
Simulation results are validated the effectiveness of the 5. Rodriguez P, Medeiros G et al. (2010). Safe current injec-
proposed control strategy to control the Statcom in a safe tion strategies for a STATCOM under asymmetrical grid
mode under three phase fault condition in the transmis- faults, Energy Conversion Congress and Exposition (ECCE),
sion line. 3929–3935.
6. Masood T, Aggarwal R K et al. (2010). STATCOM control
reconfiguration technique for steady state and dynamic
9. References performance optimization during network fault condi-
1. Hingorani N G, and Gyugyi L (2000). Understanding tions, International Conference on Renewable Energies and
FACTS: Concepts and Technology of flexible AC Power Quality (ICREPQ’10).
www.indjst.org | Vol 6 (9) | September 2013 Indian Journal of Science and Technology | Print ISSN: 0974-6846 | Online ISSN: 0974-5645