Sarikei
132/33kV T2 (old) 22 22 - - - - - - 120 1 0.50 1.00 - - 400 1 0.20 0.40 - - Directional
132/33kV T1 (new) 80 80 - - - - - - 400 1 - - - - 1600 1 0.10 0.10 - - Directional
Sarikei 132/33kV T2 (new) 80 80 - - - - - - 400 1 - - - - 1600 1 0.10 0.10 - - Directional
132/36kV T1 80 80 - - - - - - 400 1 0.30 0.275 1600 1 0.10 0.70 - - Directional
Sejingkat 132/36kV T2 80 80 - - - - - - 400 1 0.30 0.275 1600 1 0.10 0.70 - - Directional
275/132/33kV T1 (Auto) 240 80 600 1 - - - - 1200 1 - - - - 800 1 0.10 0.10 - - Directional
Selangau 275/132/33kV T2(Auto) 240 80 600 1 - - - - 1200 1 - - - - 800 1 0.10 0.10 - - Directional
132/36kV T1 80 80 - - - - - - 400 1 0.30 0.275 - - Line CB 1500 1 0.15 0.575 Non - Directional
Semenggo 132/36kV T2 80 80 - - - - - - 400 1 0.30 0.275 - - Line CB 1600 1 0.15 0.575 Directional
132/36kV T1 80 80 - - - - - - - - - - - - No CB 1600 1 0.20 0.10 . - Non - Directional
Sg.Biawak 132/36kV T2 80 80 - - - - - - - - - - - - No CB 1600 1 0.20 0.10 - - Non - Directional
275/33kV T1 120 120 300 1 - - - - - - - - - - 2500 1 - - - - Directional
Similajau 275/33kV T2 120 120 300 1 - - - - - - - - - - 2500 1 - - - - Directional
132/36kV T1 80 80 - - - - - - 400 1 - - - - 1600 1 0.10 0.10 - - Directional
Stakan 132/36kV T2 80 80 - - - - - - 400 1 - - - - 1600 1 0.10 0.10 - - Directional
132/33kV T1 80 80 - - - - - - 360 1 - - - - 1200 1 0.20 0.10 - - Directional
Tg. Manis 1 132/33kV T2 80 80 - - - - - - 360 1 - - - - 1200 1 0.20 0.10 - - Directional
132/33kV T1 (new) 80 80 - - - - - - 400 1 - - - - 1600 1 0.10 0.10 - - Directional
Tg.Manis 2 132/33kV T2 (new) 80 80 - - - - - - 400 1 - - - - 1600 1 0.10 0.10 - - Directional
132/33kV T1 120 120 - - - - - - - - - - - - No CB 2500 1 0.10 0.80 - - Directional
Tg.Kidurong 132/33kV T2 120 120 - - - - - - - - - - - - No CB 2500 1 0.10 0.80 - - Directional
Tudan 275/34.9kV T1 120 120 300 1 0.20 0.50 - - - - - - - - 2500 1 0.10 0.80 - - Directional
275/34.9kV T2 120 120 300 1 0.20 0.50 - - - - - - - - 2500 1 0.10 0.80 - - Directional
SBEF Setting Only
Transformer 33kV
Substation Circuit Rating(MVA)
CT Ratio Stage 1 Stage 2 Remarks
HV LV Plug TMS
Betong 275/33kV T1 10 10 300 5 - - - -
275/132/33kV T1 (Auto) 240 240 - - - - - -
275/132/33kV T2(Auto) 240 240 - - - - - -
275/33kV T1 120 120 2500 1 - - - -
Bintulu 275/33kV T2 120 120 2500 1 - - - -
ok to change
1600 1 0.1 - 4 5
135.4/36.2kV T1 (old) 82.3 82.3 stage 1 = 3s
ok to change
1600 1 0.1 - 4 5
135.4/36.2kV T2 (Old) 82.3 82.3 stage 1 = 3s
132/33kV T1 ( New) 120 120 2400 1 0.1 - 3 5
Deshon 132/33kV T2( New) 120 120 2400 1 0.1 - 3 5
275.8/35.6kV T1 32.4 32.4 800 1 0.15 - 3 5
Engkilili 275/35.6kV T2 30 30 600 1 0.2 - 3 5
275/132/33kV T1 (Auto) 240 80 1600 1 0.1 - 3 5
Entinggan 275/132/33kV T2(Auto) 240 80 1600 1 0.1 - 3 5
275/34.9kV T1 120 120 2100 1 0.2 - 3 5 *confirm on 31/07/17
Kemena 275/34.9kV T2 120 120 2100 1 0.2 - 3 5
Kemantan 289/146/36kV T1 (Auto) 88.5 45 800 1 0.2 - 4 8 *simulate
289/146/36kV T2 (Auto) 88.5 45 800 1 0.2 - 4 8
132.4/35.6kV T1 21.6 21.6 500 1 0.20 - 5 - trip txf only
Kapit 132/36kV T1 30 30 600 1 0.20 - 60 min 3
Lachau 275/36kV T1 30 30 800 1 0.10 - 3 5 *check 08.09.2017
275/143 T1 (Auto) 200 200 - - - - - -
275/143 T2 (Auto) 200 200 - - - - - -
132/36kV T1 80 80 1600 1 0.05 - 0 0.5 LTI curve 0.65 *simulate
Mambong 132/36kV T2 80 80 1600 1 0.05 - 0 0.5 LTI curve 0.65
275/33kV T1 120 120 2500 1 0.1 - 3 5 Commissioning 12.06.2017
Mapai 275/33kV T2 120 120 2500 1 0.1 - 3 5 Commissioning 12.06.2017
Proposed: 0.2A
2500 1 0.1 - Stage 1 = 4s
275/33kV T1 120 120 2 5 Stage 2 = 5s
Proposed: 0.2A
2500 1 0.1 - Stage 1 = 4s
Matang 275/33kV T2 120 120 2 5 Stage 2 = 5s
275/36kV T1 30 30 800 1 0.1 - 3 5
Murum Junction 275/36kV T2 30 30 800 1 0.1 - 3 5
132/36kV T1 80 80 1600 1 0.2 - 0 0.5 Simulation: fault current is too small (~40A) and SBEF has no operation
132/36kV T2 80 80 1600 1 0.2 - 0 0.5 "
132/36kV T3 80 80 1600 1 0.2 - 2 3 "
Muara Tabuan 132/36kV T4 80 80 1600 1 0.2 - 2 3 "
ok to change
800 1 0.2 - 2 5
132/33kV T1 40 40 stage 1 = 3s
ok to change
800 1 0.2 - 2 5
Matadeng 132/33kV T2 40 40 stage 1 = 3s
275/132/33kV T1 (Auto) 240 80 800 1 0.2 - 3 5 revised on 08.07.2017 ** remarks on 33kV
Oya 275/132/33kV T2(Auto) 240 80 800 1 0.2 - 3 5 revised on 08.07.2017 ** remarks on 33kV
132/33kV T1 40 40 800 1 0.2 - 3 5 revised on 06.07.2017
Petian 132/33kV T2 40 40 800 1 0.2 - 3 5 revised on 06.07.2017
275/33kV T1 120 120 2400 1 0.1 - 3 5
Samajaya
Transformer 33kV
Substation Circuit Rating(MVA)
CT Ratio Stage 1 Stage 2 Remarks
HV LV Plug TMS
Samajaya 275/33kV T2 120 120 2400 1 0.1 - 3 5
275/143/35kV T1 (Auto) 240 240 - - - - - -
275/143/35kV T2 (Auto) 240 240 - - - - - -
275/143/35kV T3(Auto) 240 240 - - - - - -
275/143/35kV T4 (Auto) 240 240 - - - - - -
132/36kV T1 80 80 1600 1 0.10 - 3.00 5.00
132/36kV T2 80 80 1600 1 0.10 - 3.00 5.00
Stage 1
= 2.5
1600 1 - 1.00 3.00
Stage 2=
Samalaju 132/36kV T3 80 80 0.1 *simulate
Proposed: 0.2A
800 1 0.2 - 2 5 Stage 1 = 3s
132/36kV T2 80 80 Stage 2 = 5s
Proposed: 0.2A
800 1 0.2 - 2 5 Stage 1 = 3s
Salim 132/36kV T3 80 80 Stage 2 = 5s
132/33kV T1 (old) 22 22 400 1 0.1 - 4 5 *CT ratio of 400/1A is insufficient
132/33kV T2 (old) 22 22 400 1 0.1 - 4 5
132/33kV T1 (new) 80 80 1600 1 0.1 - 3 5
Sarikei 132/33kV T2 (new) 80 80 1600 1 0.1 - 3 5
132/36kV T1 80 80 800 1 0.05 - 0 0.5 SI CURVE 0.65 *grading is sufficient
Sejingkat 132/36kV T2 80 80 800 1 0.05 - 0 0.5 SI CURVE 0.65
275/132/33kV T1 (Auto) 240 80 1600 1 0.2 - 3 5
Selangau 275/132/33kV T2(Auto) 240 80 1600 1 0.2 - 3 5
132/36kV T1 80 80 - - - - - -
Semenggo 132/36kV T2 80 80 800 1 0.2 - 0 5.0 *grading is sufficient
132/36kV T1 80 80 1600 1 0.2 - 5 5.05 *LV EF to set directional in order to have sufficient grading
Sg.Biawak 132/36kV T2 80 80 1600 1 0.2 - 5 5.05
275/33kV T1 120 120 2500 1 0.5 - 3 5 *ok to change plug setting to 0.1A
Similajau 275/33kV T2 120 120 2500 1 1.0 - 2 5
132/36kV T1 80 80 1600 1 0.10 - 3.00 5.00
Stakan 132/36kV T2 80 80 1600 1 0.10 - 3.00 5.00
132/33kV T1 80 80 1600 1 0.2 - 4 5 *grading is sufficient
Tg.Manis A 132/33kV T2 80 80 1600 1 0.2 - 4 5
132/33kV T1 (new) 80 80 1600 1 0.1 - 3 5
Tg.Manis B 132/33kV T2 (new) 80 80 1600 1 0.1 - 3 5
132/33kV T1 120 120 2500 1 0.2 - 0.30 0.50 SPAJ11C
Tg.Kidurong 132/33kV T2 120 120 2500 1 0.2 - 0.30 0.50
Stage 1=
0.1
2500 1 - 0.8 1
Stage 2=
275/34.9kV T1 ∞ *simulate
Stage 1=
0.1
2500 1 - 0.8 1
Stage 2=
Tudan 275/34.9kV T2 ∞
Over Current Setting Only
Date Version : 01/04/2019
132/33kV T2 120 120 - 577 2309 - N/A 0.924 - - - - - - - - - - - - - NO OC PROTECTION 2500 1 0.930 0.500 - - 30⁰ Directional HV intertrip LV LV NoIntertrip HV
Tudan 275/34.9kV T1 120 120 277 - 2309 0.924 - 0.924 300 1 0.930 0.43 - - Non-Directional - - - - - - - 2500 1 1.000 0.400 - - 30⁰ Directional HV intertrip LV LV Intertrip HV
275/34.9kV T2 120 120 277 - 2309 0.924 - 0.924 300 1 0.930 0.43 - - Non-Directional - - - - - - - 2500 1 1.000 0.400 - - 30⁰ Directional HV intertrip LV LV Intertrip HV
275/132/33kV T1 (Auto) 240 80 554 - 1540 0.924 - 0.962 600 1 0.930 0.37 - - Non-Directional 1200 1 0.97 0.29 - - Non-Directional 1600 1 1.000 0.100 - - 30⁰ Directional HV intertrip LV LV Intertrip HV
275/132/33kV T2 (Auto) 240 80 554 - 1540 0.924 - 0.962 600 1 0.930 0.37 - - Non-Directional 1200 1 0.97 0.29 - - Non-Directional 1600 1 1.000 0.100 - - 30⁰ Directional HV intertrip LV LV Intertrip HV
Earth Fault (EF) Setting Only