Professional Documents
Culture Documents
in
ELECTRICAL ENGINEERING
By
AVINASH TANTI
PREM BADHE
SHALAKA GHULE
POOJA KOKATE
2017-18
Jawaharlal Nehru Institute Of Education Science & Technological Research Trust, Nanded (M. S.)
Certificate
This is to certify that the project synopsis title “THREE PHASE FAULT
ANALYSIS WITH AUTO RESET ON TEMPORARY FAULT AND
PERMANENT TRIP OTHERWISE” is submitted in partial fulfillment of the
project work for the Bachelor’s degree in Electrical Engineering from University of
Mumbai in academic year 2017-18.
By
We, the undersigned, declare that the project entitled ‘THREE PHASE FAULT
TRIP OTHERWISE’, being submitted in partial fulfillment for the award of Bachelor of
OTHERWISE".
The completion of the project work is a millstone in student life and its
execution is inevitable in the hands of guide. We are highly indebted the project
guide Asst. Prof. Mrs. Monalisa Dash for her invaluable guidance and appreciation
for giving form and substance to this report. It is due to her enduring efforts,
patience and enthusiasm, which has given a sense of direction and purposefulness
We would also like to thank our head of department Prof. Mrs. Rama Pantar
for giving us this opportunity and guidance and encouragement. We would also like
to express our deep regards and gratitude to the Principal Dr. Sunil P. Chavan.
We would wish to thank the non - teaching staff and our friends who have
helped us all the time in one way or the other. Really it is highly impossible to
repay the debt of all the people who have directly or indirectly helped us for
Introduction
Various studies have shown that anywhere from 70%, to as high as 90%, of
faults on most overhead lines are transient. A transient fault, such as an insulator
flashover, is a fault which is cleared by the immediate tripping of one or more
circuit breakers to isolate the fault, and which does not recur when the line is re-
energized. Faults tend to be less transient (near the 80% range) at lower,
distribution voltages and more transient (near the90% range) at higher, sub
transmission and transmission voltages.
Lightning is the most common cause of transient faults, partially resulting
from insulator flashover from the high transient voltages induced by the lightning.
Other possible causes are swinging wires and temporary contact with foreign
objects. Thus, transient faults can be cleared by momentarily de-energizing the line,
in order to allow the fault to clear. Auto reclosing can then restore service to the
line.
The remaining 10 - 30% of faults are semi-permanent or permanent in
nature. A small branch falling onto the line can cause a semi-permanent fault. In
this case, however, an immediate de-energizing of the line and subsequent auto
reclosing does not clear the fault. Instead, a coordinated time-delayed trip would
allow the branch to be burned away without damage to the system. Semi-permanent
faults of this type are likely to be most prevalent in highly wooded areas and can be
substantially controlled by aggressive line clearance programs.
Permanent faults are those that will not clear upon tripping and reclosing. An
example of a permanent fault on an overhead line is a broken wire causing a phase
to open, or a broken pole causing the phases to short together. Faults on
underground cables should be considered permanent. Cable faults should be cleared
without auto reclosing and the damaged cable repaired before service is restored.
There may be exceptions to this, as in the case of circuits composed of both
underground cables and overhead lines.
Although auto reclosing success rates vary from one company to another, it
is clear that the majority of faults can be successfully cleared by the proper use of
tripping and auto reclosing. This de-energizes the line long enough for the fault
source to pass and the fault arc to de-energize, then automatically recloses the line
to restore service. Thus, auto reclosing can significantly reduce the outage time due
to faults and provide a higher level of service continuity to the customer.
Furthermore, successful high-speed reclosing auto reclosing. on transmission
circuits can be a major factor when attempting to maintain system stability. For
those faults that are permanent, auto reclosing will reclose the circuit into a fault
that has not been cleared, which may have adverse effects on system stability
(particularly at transmission levels).
Chapter 2
Review of Literature
2.1 General
Electric power is generated, transmitted and distributed via large
interconnected power systems. The generation of electric power takes place in a
power plant. Then the voltage level of the power will be raised by the transformer
before the power is transmitted. Electric power is proportional to the product of
voltage and current this is the reason why power transmission voltage levels are
used in order to minimize power transmission losses.
Any power system can be analyzed by calculating the system voltages and
currents under normal & abnormal scenarios.
The process of evaluating the system voltages and currents under various
types of short-circuits is called fault analysis which can determine the necessary
safety measures & the required protection system to guarantee the safety of public.
The severity of the fault depends on the short-circuit location, the path taken
by fault current, the system impedance and its voltage level. In order to maintain
the continuation of power supply to all customers which is the core purpose of the
power system existence, all faulted parts must be isolated from the system
temporary by the protection schemes. When a fault exists within the relay
protection zone at any transmission line, a signal will trip or open the circuit
breaker isolating the faulted line.
There are two types of faults which can occur on any transmission lines;
balanced faults and unbalanced faults also known as symmetrical and asymmetrical
faults respectively. Most of the faults that occur on power systems are not the
balanced three-phase faults, but the unbalances faults. In addition, faults can be
categorized as the shunt faults, series faults and simultaneous faults. In the analysis
of power system under fault conditions, it is necessary to make a distinction
between the types of fault to ensure the best results possible in the analysis.
However, for this project only shunt faults are to be analyzed.
The shunt faults are the most common type of fault taking place in the field.
They involve power conductors or conductor-to-ground or short circuits between
conductors. One of the most important characteristics of shunt faults is the
increment the current suffers and fall in voltage and frequency. Shunt faults cab be
classified into four categories.
1. Line-to-ground fault: this type of fault exists when one phase of any
transmission lines establishes a connection with the ground either by ice,
wind, falling tree or any other incident. 70% of all transmission lines
faults are classified under this category.
2. Line-to-line fault: as a result of high winds, one phase could touch anther
phase & line-to-line fault takes place. 15% of all transmission lines faults
are considered line-to-line faults.
3. Double line-to-ground: falling tree where two phases become in contact
with the ground could lead to this type of fault. In addition, two phases
will be involved instead of one at the line-to-ground faults scenarios. 10%
of all transmission lines faults are under this type of faults.
4. Three phase fault: in this case, falling tower, failure of equipment or even
a line breaking and touching the remaining phases can cause three phase
faults. In reality, this type of fault not often exists which can be seen from
its share of 5% of all transmission lines faults.
The first three of these faults are known as asymmetrical faults.
2.3 Method of Analysis
PROJECT OVERVIEW
3. FILTER
4. RECTIFIER
5. 555 TIMER
6. LM358
7. RELAY
8. 1N4007
9. RESISTOR
10. CAPACITOR
3.3 Description
Three single phase transformers are wired in star input and star output
having input 220 volt and output at 12 volt. The contact relays which are
used energized from the output of comparators in the event of fault
conditions by tracking the input voltage conditions for each phase at the
input of the comparators. Two 555 timers are used, one in monostable and
the other in astable mode to drive a power relay that handles the load. A Set
of switches are used to introduce LL fault, LG fault ,3L short to get the
comparator output to drive both the relays to disconnect the load. Short
duration fault returns the load immediately while long duration shall result in
permanent trip.
Chapter 4
This project is designed in the form of Hardware for three single phase
transformers 230v to 12V of output for to develop an automatic tripping
mechanism for the three phase supply system while temporary fault and permanent
fault occurs. Here we are using 555 -timer with relay for the determination
wheather the fault is temporary or permanent. Short duration fault returns the
supply to the load immediately called as temporary trip while long duration shall
result in permanent trip.
The concept in the future can be extended to developing a mechanism to
send message to the authorities via SMS by interfacing a GSM modem.
References