STARVERT iG5A
0.4~1.5kW 1phase 200~230Volts
0.4~22kW 3Phase 200~230Volts
0.4~22kW 3Phase 380~480Volts
Inverter
STARVERT iG5A
LS Starvert iG5A is very competitive in its price and shows an upgraded functional
strength. User-friendly interface, extended inverter ranges up to 22kW,
superb torque competence and small size of iG5A provides an optimum use environment.
Standard
compliance
Compactness
iG5A
High
performance
User-
friendliness
& Easy
maintenance
2
Compact & Powerful Inverter iG5A
Contents 4 Overview
8 Model & Type
9 Standard Specifications
11 Wiring
13 Terminal Configurations
15 Keypad Features
16 Parameter Setting
18 Trial Run
20 Dimensions
23 Braking Resistors and Peripheral Devices
25 Function List
42 Protective Functions
43 Fault Remedy
3
iG5A
Powerful & Upgraded Performance
iG5A provides sensorless vector control, PID control,
and ground-fault protection through powerful built-in functions.
Torque (%)
the superb speed control and powerful high
torque.
Ground-fault protection
during running
Speed (Hz)
The ground-fault protection of output terminal
is possible during running. Condition: Sensorless Vector Control Mode: Auto tuning Measure maximum
torque (%) at each speed (1/5/10/20/30/40/50/60Hz)
Reverse
-10
Time
Reducing
deceleration time
Built-in 485 communication
The built-in RS-485 communication supports
remote control and monitoring between iG5A
and other equipment.
4
Compact & Powerful Inverter iG5A
RS-485 communication
Connected to PC
Monitoring
Checking operation status
(Voltage, Current, Frequency, etc)
Checking modified parameters
Windows support
Remote Control
Convenient remote control to modify operation status
(Forward/Reverse operation, Frequency, etc)
Easy parameter setting
Available to control up to 31 Inverters
RS-485, Modbus communication
Connected to XGT panel
Monitoring
Checking operation time
Automatic list-up of trip record
Language support (Korean, English, Chinese)
Remote Control
Convenient remote control to modify operation status
(Forward/Reverse operation, Frequency, etc)
Easy parameter setting
Available to control up to 31 Inverters
RS-485, Modbus communication
5
iG5A
User-friendly Interface & Easy Maintenance
The parameter setting becomes easier by adopting the 4 directions key. And iG5A supports
easy maintenance via diagnosis and fan changeable structure.
User-friendly interface
The 4 directions key provides easy handling and
monitoring.
6
Compact & Powerful Inverter iG5A
Compact Size
The compact size achieves cost-efficiency and various applications.
Global standard
iG5A series complies with CE and UL standards.
PNP/NPN input
Both PNP and NPN inputs become possible and these enable to
use the outer power.
To do so, users will be given wider choices of selecting the
controller.
7
iG5A
Model & Type
Applicable motor ranges 1 Phase 200V 3 Phase 200V 3 Phase 400V
SV 015 iG5A 2
STARVERT
iG5A series
Input voltage
(1: 1 phase 200~230[V], 2: 3 phase 200~230[V], 4: 3 phase 380~480[V])
8
Compact & Powerful Inverter iG5A
Standard Specifications
1 Phase 200V
SV ��� iG5A-1 �� 004 008 015
Max. (HP) 0.5 1 2
capacity 1) (kW) 0.4 0.75 1.5
Capacity (kVA) 2) 0.95 1.9 3.0
Output FLA (A) 3) 2.5 5 8
rating Max frequency 400 [Hz] 4)
Max voltage 3 phase 200~230V 5)
Input Rated voltage 1phase 200~230 VAC (+10%, -15%)
rating Rated frequency 50~60 [Hz] (±5%)
Cooling method Forced air cooling
Weight (kg) 0.76 1.12 1.84
3 Phase 200V
SV ��� iG5A-2 �� 004 008 015 022 037 040 055 075 110 150 185 220
Max. (HP) 0.5 1 2 3 5 5.4 7.5 10 15 20 25 30
capacity 1) (kW) 0.4 0.75 1.5 2.2 3.7 4.0 5.5 7.5 11 15 18.5 22
Capacity (kVA) 2) 0.95 1.9 3.0 4.5 6.1 6.5 9.1 12.2 17.5 22.9 28.2 33.5
Output FLA (A) 3) 2.5 5 8 12 16 17 24 32 46 60 74 88
rating Max frequency 400 [Hz] 4)
Max voltage 3 phase 200~230V 5)
Input Rated voltage 3 phase 200~230 (+10%, -15%)
rating Rated frequency 50~60 [Hz] (±
±5%)
Cooling method N/C 6) Forced air cooling
Weight (kg) 0.76 0.77 1.12 1.84 1.89 1.89 3.66 3.66 9.0 9.0 13.3 13.3
3 Phase 400V
SV ��� iG5A-4 �� 004 008 015 022 037 040 055 075 110 150 185 220
Max. (HP) 0.5 1 2 3 5 5.4 7.5 10 15 20 25 30
capacity 1) (kW) 0.4 0.75 1.5 2.2 3.7 4.0 5.5 7.5 11 15 18.5 22
Capacity (kVA) 2) 0.95 1.9 3.0 4.5 6.1 6.5 9.1 12.2 18.3 22.9 29.7 34.3
Output FLA (A) 3) 1.25 2.5 4 6 8 9 12 16 24 30 39 45
rating Max frequency 400 [Hz] 4)
Max voltage 3 phase 380~480V 5)
Input Rated voltage 3 phase 380~480 VAC (+10%, -15%)
rating Rated frequency 50~60 [Hz] (±5%)
Cooling method N/C 6) Forced air cooling
Weight (kg) 0.76 0.77 1.12 1.84 1.89 1.89 3.66 3.66 9.0 9.0 13.3 13.3
1) Indicate the maximum applicable motor capacity when using 4 pole LS standard motor.
2) Rated capacity is based on 220V for 200V series and 440V for 400V series.
3) Refer to 15-3 of user’s manual when carrier frequency setting (39) is above 3kHz.
4) Max. frequency setting range is extended to 300Hz when H40 (Control mode select) is set to 3 (Sensorless vector control).
5) Max. output voltage cannot be higher than the input voltage. It can be programmable below input voltage.
6) Self-Cooling
9
iG5A
Standard Specifications
Control method V/F, Sensorless vector control
Digital command: 0.01Hz
Frequency setting resolution Analog command: 0.06Hz (Max. freq.: 60Hz)
Max. braking
Dynamic 20% 1)
torque
braking
Max. Duty 150% when using optional DB resistor 2)
Operation mode Keypad/ Terminal/ Communication option/ Remote keypad selectable
Analog: 0~10V, -10~10V, 0~20mA
Frequency setting
Digital: Keypad
Multi-function FWD/REV RUN, Emergency stop, Fault reset, Jog operation, Multi-step Frequency-High, Mid, Low,
Input terminal Multi-step Accel/Decel-High, Mid, Low, DC braking at stop, 2nd motor select, Frequency UP/Down,
Operation
P1~P8 3-wire operation, External trip A, B, PID-Inverter (V/F) operation bypass,
Option-inverter (V/F) operation bypass, Analog Hold, Accel/Decel stop
Open collector
Fault output and Less than DC 24V, 50mA
terminal inverter status output
Output Multi-function relay (N.O., N.C.) Less than AC 250V, 1A; Less than DC 30V, 1A
Analog output (AM) 0~10Vdc (less than 10mA): Output freq, Output current, Output voltage, DC link selectable
Over voltage, Under voltage, Over current, Ground fault current detection, Inverter overheat,
Trip Motor overheat, Output phase open, Overload protection, Communication error,
Loss of speed command, Hardware fault, Fan trip
Protective
Alarm Stall prevention, Overload
function
Below 15 msec.: Continuous operation (Should be within rated input voltage, rated output power.)
Momentary power loss
Above 15 msec.: Auto restart enable
10
Compact & Powerful Inverter iG5A
Wiring
0.4~7.5kW
DB resistor
(Optional)
3 phase AC input
(Rated input voltage) B1 B2
R U
S V
T W
G
Ground
24 24V output AM
Multi-function
P1 FX (Forward run) analog output
signal: 0~10V
CM
P2 RX (Reverse run)
P3 BX (Emergency stop)
MO Multi-function open
Potentiometer collector output
(1kohm, 1/2W)
S-
CM Input signal common
11
iG5A
Wiring
11.0~22.0kW
DB resistor
DC reactor (Optional)
3 phase AC input
(Rated input voltage) P1(+) B1 B2 N(-)
R U
S V
T W
G
Ground
24 24V output
AM
Multi-function
P1 FX (Forward run) analog output
signal: 0~10V
P2 RX (Reverse run) CM
P3 BX (Emergency stop)
MO Multi-function open
Potentiometer collector output
(1kohm, 1/2W)
S-
CM Input signal common
12
Compact & Powerful Inverter iG5A
Terminal Configuration
Specifications for power terminal block wiring
• 0.4kW~0.75kW (1 phase) • 0.4kW~1.5kW (3 phase) • 1.5kW (1 phase)
R T B1 B2 R S T B1 B2 R T B1 B2 U V W
• 2.2~4.0kW (3 phase)
U V W U V W
• 5.5kW~7.5kW (3 phase) R S T B1 B2 U V W
• 11~22kW (3 phase)
B1 B2 U V W
R(L1) S(L2) T(L3) P1(+) B1 B2 N(-) U V W
R S T
13
iG5A
Terminal Configuration
Control terminal specifications
MO MG 24 P1 P2 CM P3 P4 S- S+
3A 3B 3C P5 CM P6 P7 P8 VR V1 I AM
14
Compact & Powerful Inverter iG5A
Keypad Features
95
Dimensions 83
70
CL
3.4
SET FWD
36.2
RUN REV
72.4
65.6
RUN STOP
RESET
2-∅4.5 ENT
5 13.9
2.1 23.1
15
iG5A
Moving to Other Groups
Parameter groups
There are 4 different parameter groups in iG5A series as shown below.
1) 1)
1) Target frequency can be set at 0.0 (the 1st code of drive group). Even though the preset value is 0.0, it is user-settable.
The changed frequency will be displayed after it is changed.
16
Compact & Powerful Inverter iG5A
1 ∙In the first code“0.00”, press the Up (▲) key once to go to the second code.
4 ∙The digit 5 in 5.0 is active. Then press the Up (▲) key once.
∙16.0 is set.
∙Press the Ent (●) key once.
7
∙16.0 is blinking. 1)
∙Press the Ent (●) key once again to return to the parameter name.
1) Pressing the Left (◀)/Right (▶)/Up (▲)/Down (▼) key while a cursor is blinking will cancel the parameter value change.
Pressing the Ent (●) key in this status will enter the value into memory.
※ In step 7, pressing the Left (◀) or Right (▶) key while 16.0 is blinking will disable the setting.
17
iG5A
Trial Run
Multi-step operation + Run/Stop via FX/RX + Max. frequency change
Operation condition
Operation command: Frequency command: Max. frequency change:
Run/Stop via FX/RX Multi-step operation [Low (20), Middle (30), High (80)] From 60Hz to 80Hz
Wiring
P1 (Forward)
S1
P2 (Reverse)
S2 R U
3 phase
AC input
S V
P6 (Low)
S3 T W
G
P7 (Middle)
S4
S/W
P8 (High)
S5 P1 (Forward)
P2 (Reverse)
CM
P6 (Low)
P7 (Middle)
P8 (High)
CM
Parameter setting
Step Command Code Description Default After change
1 Max. frequency change (FU1) F21 Change Max. frequency. 60Hz 80Hz
2 Multi-step frequency (DRV) st1 Set‘Low’step. 10Hz 20Hz
3 Multi-step frequency (DRV) st2 Set‘Middle’step. 20Hz 30Hz
4 Multi-step frequency (I/O) I30 Set‘High’step. 30Hz 80Hz
5 Forward run (P1: FX) I17 The default is FX. This value may change. FX FX
6 Reverse run (P2: RX) I18 The default is RX. This value may change. RX RX
18
Compact & Powerful Inverter iG5A
Wiring
0~60Hz
P1 (FX) Forward
P2 (RX) Reverse
CM
Parameter setting
Step Command Code Description Default After change
Operation command
1 Drv Turn on/off motor via terminal. 1 (FX/RX-1) 1 (FX/RX-1)
(DRV group)
Accel/Decel time ACC Set Accel time to 10sec in ACC 5sec (Accel) 10sec (Accel)
3
(DRV group) dEC Set Decel time to 20sec in dEC. 10sec (Decel) 20sec (Decel)
Forward run FX FX
4 I17 The default is FX. This value may change
(P1: FX)
Reverse run RX RX
5 I18 The default is RX. This value may change.
(P2: RX)
19
iG5A
Dimensions
SV004iG5A-2 / SV008iG5A-2, SV004iG5A-4 / SV008iG5A-4
W
W1 A
A
∅
H1
H
D
B
W1
mm (inches)
Inverter model (kW) W (mm) W1 (mm) H (mm) H1 (mm) D (mm) ∅ A (mm) B (mm) (kg)
SV004IG5A-2 0.4 70 65.5 128 119 130 4.0 4.5 4.0 0.76
SV008IG5A-2 0.75 70 65.5 128 119 130 4.0 4.5 4.0 0.77
SV004IG5A-4 0.4 70 65.5 128 119 130 4.0 4.5 4.0 0.76
SV008IG5A-4 0.75 70 65.5 128 119 130 4.0 4.5 4.0 0.77
SV015iG5A-2 / SV015iG5A-4
W
W1 A
A1
∅
H1
H
D
B
W1
mm (inches)
Inverter model (kW) W (mm) W1 (mm) H (mm) H1 (mm) D (mm) ∅ A (mm) B (mm) (kg)
SV015IG5A-2 1.5 100 95.5 128 120 130 4.5 4.5 4.5 1.12
SV015IG5A-4 1.5 100 95.5 128 120 130 4.5 4.5 4.5 1.12
20
Compact & Powerful Inverter iG5A
CL ∅
A
H1
H
D
B B
W1
mm (inches)
Inverter model (kW) W (mm) W1 (mm) H (mm) H1 (mm) D (mm) ∅ A (mm) B (mm) (kg)
SV022IG5A-2 2.2 140 132 128 120.5 155 4.5 4.5 4.5 1.84
SV037IG5A-2 3.7 140 132 128 120.5 155 4.5 4.5 4.5 1.89
SV040IG5A-2 4.0 140 132 128 120.5 155 4.5 4.5 4.5 1.89
SV022IG5A-4 2.2 140 132 128 120.5 155 4.5 4.5 4.5 1.84
SV037IG5A-4 3.7 140 132 128 120.5 155 4.5 4.5 4.5 1.89
SV040IG5A-4 4.0 140 132 128 120.5 155 4.5 4.5 4.5 1.89
W A W ∅
A
H1
D
B B
W
mm (inches)
Inverter model (kW) W (mm) W1 (mm) H (mm) H1 (mm) D (mm) ∅ A (mm) B (mm) (kg)
SV055IG5A-2 5.5 180 170 220 210 170 4.5 5 4.5 3.66
SV075IG5A-2 7.5 180 170 220 210 170 4.5 5 4.5 3.66
SV055IG5A-4 5.5 180 170 220 210 170 4.5 5 4.5 3.66
SV075IG5A-4 7.5 180 170 220 210 170 4.5 5 4.5 3.66
21
iG5A
Dimensions
SV110iG5A-2 / SV150iG5A-2 / SV110iG5A-4 / SV150iG5A-4
W
A W1 ∅
A
H1
D
B B
W1
mm (inches)
Inverter model (kW) W (mm) W1 (mm) H (mm) H1 (mm) D (mm) ∅ A (mm) B (mm) (kg)
SV110iG5A-2 11.0 235 219 320 304 189.5 7.0 8.0 7.0 9.00
SV150iG5A-2 15.0 235 219 320 304 189.5 7.0 8.0 7.0 9.00
SV110iG5A-4 11.0 235 219 320 304 189.5 7.0 8.0 7.0 9.00
SV150iG5A-4 15.0 235 219 320 304 189.5 7.0 8.0 7.0 9.00
W
∅ A W1
A
H1
D
B B
W1
mm (inches)
Inverter model (kW) W (mm) W1 (mm) H (mm) H1 (mm) D (mm) ∅ A (mm) B (mm) (kg)
SV185iG5A-2 18.5 260 240 410 392 208.5 10.0 10.0 10.0 13.3
SV220iG5A-2 22.0 260 240 410 392 208.5 10.0 10.0 10.0 13.3
SV185iG5A-4 18.5 260 240 410 392 208.5 10.0 10.0 10.0 10.0
SV220iG5A-4 22.0 260 240 410 392 208.5 10.0 10.0 10.0 10.0
22
Compact & Powerful Inverter iG5A
Breakers
Model MCCB, ELCB (LS) MC Model MCCB, ELCB (LS) MC
004iG5A-1 TD125U,EBs33 GMC-9 220iG5A-2 TS250U,EBs53 GMC-125
008iG5A-1 TD125U,EBs33 GMC-9 004iG5A-4 TD125U,EBs33 GMC-9
015iG5A-1 TD125U,EBs33 GMC-12 008iG5A-4 TD125U,EBs33 GMC-9
004iG5A-2 TD125U,EBs33 GMC-9 015iG5A-4 TD125U,EBs33 GMC-9
008iG5A-2 TD125U,EBs33 GMC-9 022iG5A-4 TD125U,EBs33 GMC-12
015iG5A-2 TD125U,EBs33 GMC-12 037iG5A-4 TD125U,EBs33 GMC-18
022iG5A-2 TD125U,EBs33 GMC-18 040iG5A-4 TD125U,EBs33 GMC-18
037iG5A-2 TD125U,EBs33 GMC-32 055iG5A-4 TD125U,EBs33 GMC-32
040iG5A-2 TD125U,EBs33 GMC-32 075iG5A-4 TD125U,EBs33 GMC-32
055iG5A-2 TD125U,EBs53 GMC-40 110iG5A-4 TD125U,EBs53 GMC-40
075iG5A-2 TD125U,EBs53 GMC-50 150iG5A-4 TD125U,EBs53 GMC-50
110iG5A-2 TD125U,EBs53 GMC-65 185iG5A-4 TD125U,EBs53 GMC-65
150iG5A-2 TD125U,EBs53 GMC-100 220iG5A-4 TD125U,EBs53 GMC-65
185iG5A-2 TD250U,EBs53 GMC-100
23
iG5A
Braking Resistors and Peripheral Devices
Fuses & AC reactors
AC external fuse
Model AC reactor DC reactor
Current [A] Voltage [V]
004iG5A-1 10 A 600V 4.20 mH, 3.5 A -
008iG5A-1 10 A 600V 2.13 mH, 5.7 A -
015iG5A-1 15 A 600V 1.20 mH, 10 A -
004iG5A-2 10 A 600V 4.20 mH, 3.5 A -
008iG5A-2 10 A 600V 2.13 mH, 5.7 A -
015iG5A-2 15 A 600V 1.20 mH, 10 A -
022iG5A-2 25 A 600V 0.88 mH, 14 A -
037iG5A-2 30 A 600V 0.56 mH, 20 A -
040iG5A-2 30 A 600V 0.56 mH, 20 A -
055iG5A-2 30 A 600V 0.39 mH, 30 A -
075iG5A-2 50 A 600V 0.28 mH, 40 A -
110iG5A-2 70 A 600V 0.20 mH, 59 A 0.74 mH, 56 A
150iG5A-2 100 A 600V 0.15 mH, 75 A 0.57 mH, 71 A
185iG5A-2 100 A 600V 0.12 mH, 96 A 0.49 mH, 91 A
220iG5A-2 125 A 600V 0.10 mH, 112 A 0.42 mH, 107 A
004iG5A-4 5A 600V 18.0 mH, 1.3 A -
008iG5A-4 10 A 600V 8.63 mH, 2.8 A -
015iG5A-4 10 A 600V 4.81 mH, 4.8 A -
022iG5A-4 10 A 600V 3.23 mH, 7.5 A -
037iG5A-4 20 A 600V 2.34 mH, 10 A -
040iG5A-4 20 A 600V 2.34 mH, 10 A -
055iG5A-4 20 A 600V 1.22 mH, 15 A -
075iG5A-4 30 A 600V 1.14 mH, 20 A -
110iG5A-4 35 A 600V 0.81 mH, 30 A 2.76 mH, 29 A
150iG5A-4 45 A 600V 0.61 mH, 38 A 2.18 mH, 36 A
185iG5A-4 60 A 600V 0.45 mH, 50 A 1.79 mH, 48 A
220iG5A-4 70 A 600V 0.39 mH, 58 A 1.54 mH, 55 A
24
Compact & Powerful Inverter iG5A
Function List
Drive Group
LED Address for Parameter Min/Max Factory Adj.
Description
display communication name range defaults during run
This parameter sets the frequency that the inverter is
commanded to output.
During Stop: Frequency Command
[Frequency 0 ~ 400
0.00 A100 During Run: Output Frequency 0.00 O
command] [Hz]
During Multi-step operation:
Multi-step frequency 0.
It cannot be set greater than F21- [Max frequency].
0 Keypad setting 1
Digital
1 Keypad setting 2
2 V1 1: -10 ~ +10 [V]
3 V1 2: 0 ~ +10 [V]
[Frequency 4 Analog Terminal I: 0 ~ 20 [mA]
Frq A104 0~7 0 ×
setting method] 5 Terminal V1 setting 1 + Terminal I
6 Terminal V1 setting 2+ Terminal I
7 RS485 communication
8 Digital Volume
9 Set to Field Bus communication 1)
[Multi-Step
St1 A105 Sets Multi-Step frequency 1 during Multi-step operation. 10.00 O
frequency 1]
[Multi-Step 0 ~ 400
St2 A106 Sets Multi-Step frequency 2 during Multi-step operation. 20.00 O
frequency 2] [Hz]
[Multi-Step
St3 A107 Sets Multi-Step frequency 3 during Multi-step operation. 30.00 O
frequency 3]
CUr A108 [Output current] Displays the output current to the motor. - -
A10A [Inverter DC
dCL Displays DC link voltage inside the inverter. - -
link voltage]
This parameter displays the item selected at H73- [Monitoring
item select].
[User display
vOL A10B vOL Output voltage vOL -
select]
POr Output power
tOr Torque
1) This function can be available with iG5A Communication Option Module.
25
iG5A
Function List
Drive Group
LED Address for Parameter Min/Max Factory Adj.
Description
display communication name range defaults during run
Displays the types of faults, frequency and operating status at the
nOn A10C [Fault Display] - -
time of the fault
Sets the direction of motor rotation when drv - [Drive mode] is set
[Direction of
to either 0 or 1.
drC A10D motor rotation F, r F O
F Forward
select]
r Reverse
0 Run/Stop via Run/Stop key on the keypad
FX: Motor forward run
1
RX: Motor reverse run
Terminal operation
drv2 A10E [Drive mode 2] 0~3 FX: Run/Stop enable 1 ×
2
RX: Reverse rotation select
3 RS-485 communication
4 Set to Filed Bus Communication 3)
0 Keypad setting 1
Digital
1 Keypad setting 2
2 V1 1: -10 ~ +10 [V]
3 V1 2: 0 ~ +10 [V]
[Frequency
1) 4 Analog Terminal I: 0 ~ 20 [mA]
Frq2 A10F setting 0~7 0 ×
5 Terminal V1 setting 1 + Terminal I
method 2]
6 Terminal V1 setting 2+ Terminal I
7 RS485 communication
8 Digital Volume
9 Set to Filed Bus Communication 3)
If H58 is 0, it is expressed as a [Hz] unit.
PID control 0~400[Hz]
If H58 is 1, it is expressed as a [%] unit.
rEF 2) A110 standard or 0.00 0
In [Hz] unit, you can’t set Max. frequency more than (F21).
value setting 0~100 [%]
In [%] unit, 100% means Max. frequency.
PID control It indicates a feedback amount in PID control.
2)
Fbk A111 feedback If H58 is 0, it is expressed as a [Hz] unit. - -
amount If H58 is 1, it is expressed as a [%] unit.
1) Only displayed when one of the Multi-function input terminals 1-8 [I17~I24] is set to “22”.
2) It is indicated when H49(PID control selection) is 1.
3) This function can be available with iG5A Communication Option Module.
Function group 1
LED Address for Parameter Min/Max Factory Adj.
Description
display communication name range defaults during run
26
Compact & Powerful Inverter iG5A
Function group 1
LED Address for Parameter Min/Max Factory Adj.
Description
display communication name range defaults during run
0 Decelerate to stop
[Stop mode 1 DC brake to stop
F4 A204 0~3 0 ×
select] 2 Free run to stop
3 Power Braking stop
[DC Brake 0.1 ~ 60 This parameter sets DC brake start frequency.
F 8 1) A208 5.00 ×
start frequency] [Hz] It cannot be set below F23 - [Start frequency].
[DC Brake 0 ~ 60 When DC brake frequency is reached, the inverter holds the
F9 A209 0.1 ×
wait time] [sec] output for the setting time before starting DC brake.
[DC Brake 0 ~ 200 This parameter sets the amount of DC voltage applied to a motor.
F10 A20A 50 ×
voltage] [%] It is set in percent of H33 - [Motor rated current].
[DC Brake time] 0 ~ 60 This parameter sets the time taken to apply DC current to a
F11 A20B 1.0 ×
[sec] motor while motor is at a stop.
This parameter sets the amount of DC voltage before a motor
[DC Brake start 0 ~ 200
F12 A20C starts to run. 50 ×
voltage] [%]
It is set in percent of H33 - [Motor rated current].
[DC Brake start 0 ~ 60 DC voltage is applied to the motor for DC Brake start time before
F13 A20D 0 ×
time] [sec] motor accelerates.
[Time for This parameter applies the current to a motor for the set time
0 ~ 60
F14 A20E magnetizing before motor accelerates during Sensorless vector control. 0.1 ×
[sec]
a motor]
0 ~ 400 This parameter sets the frequency for Jog operation.
F20 A214 [Jog frequency] 10.00 O
[Hz] It cannot be set above F21 - [Max frequency].
This parameter sets the highest frequency the inverter can output.
It is frequency reference for Accel/Decel (See H70)
40 ~ 400
F21 2) A215 [Max frequency] Caution 60.00 ×
[Hz]
Any frequency cannot be set above Max frequency except Base
frequency
30 ~ 400 The inverter outputs its rated voltage to the motor at this
F22 A216 [Base frequency] 60.00 ×
[Hz] frequency (see motor nameplate).
0.1 ~ 10 The inverter starts to output its voltage at this frequency.
F23 A217 [Start frequency] 0.50 ×
[Hz] It is the frequency low limit.
[Frequency high
F24 A218 0~1 This parameter sets high and low limit of run frequency. 0 ×
/low limit select]
[Frequency 0 ~ 400 This parameter sets high limit of the run frequency.
F25 3) A219 60.00 ×
high limit] [Hz] It cannot be set above F21 - [Max frequency].
This parameter sets low limit of the run frequency.
[Frequency 0.1 ~ 400
F26 A21A It cannot be set above F25 - [Frequency high limit] and below 0.50 ×
low limit] [Hz]
F23 - [Start frequency].
[Torque Boost 0 Manual torque boost
F27 A21B 0~1 0 ×
select] 1 Auto torque boost
[Torque boost in This parameter sets the amount of torque boost applied to a motor
F28 A21C 2 ×
forward direction] 0 ~ 15 during forward run. It is set in percent of Max output voltage.
[Torque boost [%] This parameter sets the amount of torque boost applied to a motor
F29 A21D 2 ×
in reverse direction] during reverse run. It is set as a percent of Max output voltage.
1) Only displayed when F 4 is set to 1 (DC brake to stop).
2) If H40 is set to 3 (Sensorless vector), Max. frequency is settable up to 300Hz.
3) Only displayed when F24 (Frequency high/low limit select) is set to 1.
27
iG5A
Function List
Function group 1
LED Address for Parameter Min/Max Factory Adj.
Description
display communication name range defaults during run
0 {Linear}
F30 A21E [V/F pattern] 0~2 1 {Square} 0 ×
2 {User V/F}
[User V/F 0 ~ 400 It is used only when V/F pattern is set to 2(User V/F)
F31 1) A21F 15.00 ×
frequency 1] [Hz] It cannot be set above F21 - [Max frequency].
[User V/F ] 0 ~ 100
F32 A220 25 ×
voltage 1 [%]
[User V/F 0 ~ 400
F33 A221 30.00 ×
frequency 2] [Hz]
[User V/F 0 ~ 100
F34 A222 50 ×
voltage 2] [%] The value of voltage is set in percent of H70 - [Motor rated
[User V/F 0 ~ 400 voltage].
F35 A223 45.00 ×
frequency 3] [Hz] The values of the lower-numbered parameters cannot be set
[User V/F 0 ~ 100 above those of higher-numbered.
F36 A224 75 ×
voltage 3] [%]
[User V/F 0 ~ 400
F37 A225 60.00 ×
frequency 4] [Hz]
[User V/F 0 ~ 100
F38 A226 100 ×
voltage 4] [%]
[Output voltage 40 ~ 110 This parameter adjusts the amount of output voltage.
F39 A227 100 ×
adjustment] [%] The set value is the percentage of input voltage.
[Energy-saving 0 ~ 30 This parameter decreases output voltage according to load
F40 A228 0 0
level] [%] status.
[Electronic This parameter is activated when the motor is overheated (time-
F50 A232 0~1 0 0
thermal select] inverse).
This parameter sets max current capable of flowing to the motor
[Electronic continuously for 1 minute.
50 ~ 200
F51 2) A233 thermal level for The set value is the percentage of H33 - [Motor rated current]. 150 0
[%]
1 minute] It cannot be set below F52 - [Electronic thermal level for
continuous].
This parameter sets the amount of current to keep the motor
[Electronic
50 ~ 150 running continuously.
F52 A234 thermal level for 100 0
[%] It cannot be set higher than F51 - [Electronic thermal level for 1
continuous]
minute].
Standard motor having cooling fan directly connected to
0
[Motor cooling the shaft
F53 A235 0~1 0 0
method]
1 A motor using a separate motor to power a cooling fan.
28
Compact & Powerful Inverter iG5A
Function group 1
LED Address for Parameter Min/Max Factory Adj.
Description
display communication name range defaults during run
[Overload This parameter turns off the inverter output when motor is
F56 A238 0~1 1 0
trip select] overloaded.
[Overload 30 ~ 200 This parameter sets the amount of overload current.
F57 A239 180 0
trip level] [%] The value is the percentage of H33- [Motor rated current].
This parameter turns off the inverter output when the F57-
[Overload 0 ~ 60
F58 A23A [Overload trip level] of current flows to the motor for F58- 60 0
trip time] [Sec]
[Overload trip time].
This parameter stops accelerating during acceleration,
decelerating during constant speed run and stops decelerating
during deceleration.
During Decel During constant run During Accel
Bit 2 Bit 1 Bit 0
0 - - -
[Stall prevention
F59 A23B 0~7 1 - - 0 ×
select]
2 - -
3 -
4 - -
5 -
6 -
7
This parameter sets the amount of current to activate stall
[Stall prevention 30 ~ 200
F60 A23C prevention function during Accel, Constant or Decel run. 150 ×
level] [%]
The set value is the percentage of the H33- [Motor rated current].
[When Stall
prevention during In Stall prevention run during deceleration, if you want to limit
F61 1) A23D 0~1
deceleration, voltage output voltage, select 1
limit select
This parameter decides whether to save the specified frequency
[Save up/down
F63 A23F 0~1 during up/down operation. 0 ×
frequency select]
When 1 is selected, the up/down frequency is saved in F64.
[Save up/down If ‘Save up/down frequency’ is selected at F63, this parameter
F64 2) A240 0.00 ×
frequency] saves the frequency before the inverter stops or decelerated.
We can select up-down mode among three thing
Increases goal frequency as a standard of Max.
[Up-down mode 0 0 ×
F65 A241 0~2 frequency/Min. frequency
select]
1 Increases as many as step frequency according to edge input
2 Available to combine 1 and 2
[Up-down step 0~400 In case of choosing F65 as a 1 or 2, it means increase or
F66 A242 0.00 ×
frequency] [Hz] decrease of frequency according to up-down input
0 Inverter doesn’t run as a draw mode
[Draw run mode 1 V1(0~10V) input draw run
F70 A246 0~3 0 ×
select] 2 I(0~20mA) input draw run
3 V1(-10~10V) input draw run
29
iG5A
Function List
Function group 2
LED Address for Parameter Min/Max Factory Adj.
Description
display communication name range defaults during run
A30A [Skip frequency 0~1 Sets the frequency range to skip to prevent undesirable
H10 0 ×
select] resonance and vibration on the structure of the machine.
[Skip frequency
H11 1) A30B 10.00 ×
low limit 1]
[Skip frequency
H12 A30C 15.00 ×
high limit 1]
[Skip frequency Run frequency cannot be set within the range of H11 thru H16.
H13 A30D 20.00 ×
low limit 2] 0.1~400 The frequency values of the low numbered parameters cannot be
[Skip frequency [Hz] set above those of the high numbered ones. Settable within the
H14 A30E 25.00 ×
high limit 2] range of F21 and F23.
[Skip frequency
H15 A30F 30.00 ×
low limit 3]
[Skip frequency
H16 A310 35.00 ×
high limit 3]
[S-Curve accel/ 1~100 Set the speed reference value to form a curve at the start during
H17 A311 40 ×
decel start side] [%] accel/decel. If it is set higher, linear zone gets smaller.
[S-Curve accel/ 1~100 Set the speed reference value to form a curve at the end during
H18 A312 40 ×
decel end side] [%] accel/decel. If it is set higher, linear zone gets smaller.
[Input/output 0 Disabled 1 Output phase protection
H19 A313 phase loss 0~3 Input phase Input/output phase 0 O
2 3
protection select] protection protection
This parameter is activated when drv is set to 1 or 2 (Run/Stop
[Power On via Control terminal).
H20 A314 0~1 0 O
Start select] Motor starts acceleration after AC power is applied while FX or
RX terminal is ON.
This parameter is activated when drv is set to 1 or 2 (Run/Stop
[Restart after
via Control terminal).
H21 A315 fault reset 0 ~1 0 O
Motor accelerates after the fault condition is reset while the FX or
selection]
RX terminal is ON.
1) only displayed when H10 is set to 1. # H17, H18 are used when F2, F3 are set to 1 (S-curve)
30
Compact & Powerful Inverter iG5A
Function group 2
LED Address for Parameter Min/Max Factory Adj.
Description
display communication name range defaults during run
This parameter is active to prevent any possible fault when the 0 O
inverter outputs its voltage to the running motor.
1. H20- 2. Restart 3. Operation 4. Normal
[Power after instant after fault accel
On start] power failure
0 - - - -
1 - - -
2 - - -
3 - -
4 - - -
1. H20- 2. Restart 3. Operation 4. Normal
[Power after instant after fault accel
[Speed Search On start] power failure
H22 1) A316 0 ~ 15
Select] Bit 3 Bit 2 Bit 1 Bit 0
5 - -
6 - -
7 -
8 - - -
9 - -
10 - -
11 -
12 - -
13 -
14 -
15
[Current level
80~200 This parameter limits the amount of current during speed search.
H23 A317 during Speed 100 O
[%] The set value is the percentage of the H33- [Motor rated current].
search]
[P gain during
H24 A318 0~9999 It is the Proportional gain used for Speed Search PI controller. 100 O
Speed search]
[I gain during
H25 A319 0~9999 It is the Integral gain used for Speed search PI controller. 200 O
speed search]
This parameter sets the number of restart tries after a fault
occurs. Auto Restart is deactivated if the fault outnumbers the
[Number of Auto
H26 A31A 0 ~10 restart tries. This function is active when [drv] is set to 1 or 2 0 O
Restart try]
{Run/Stop via control terminal}. Deactivated during active
protection function (OHT, LVT, EXT, HWT etc.).
[Auto Restart 0~60
H27 A31B This parameter sets the time between restart tries. 1.0 O
time] [sec]
0.2 0.2kW
[Motor type
H30 A31E 0.2~ 22.0 ~ ~ 7.5 2) ×
select]
22.0 22.0kW
[Number of
H31 A31F 2 ~ 12 This setting is displayed via rPM in drive group. 4 ×
motor poles]
1) Normal acceleration has first priority. Even though #4 is selected along with other bits, Inverter performs Speed search #4.
2) H30 is preset based on inverter rating.
31
iG5A
Function List
Function group 2
LED Address for Parameter Min/Max Factory Adj.
Description
display communication name range defaults during run
fs = fr - [ rpm120× p ]
[Rated slip 0 ~ 10 Where, fs = Rated slip frequency
H32 A320 2.33 1) ×
frequency] [Hz] fr = Rated frequency
rpm = Motor nameplate RPM
p = Number of Motor poles
32
Compact & Powerful Inverter iG5A
Function group 2
LED Address for Parameter Min/Max Factory Adj.
Description
display communication name range defaults during run
0 Terminal I input (0 ~ 20 mA)
H50 1) A332 [PID F/B select] 0~1 0 ×
1 Terminal V1 input (0 ~ 10 V)
0~ 999.9
H51 A333 [P gain for PID] 300.0 O
[%]
[Integral time 0.1~32.0
H52 A334 This parameter sets the gains for the PID controller. 1.0 O
for PID [sec]
[Differential time 0 ~ 30.0
H53 A335 0.0 O
for PID (D gain)] [sec]
Selects PID control mode
[PID control
H54 A336 0~1 0 Normal PID control 0 ×
mode select]
1 Process PID control
[PID output
0.1 ~ 400
H55 A337 frequency high This parameter limits the amount of the output frequency through 60.00 O
[Hz]
limit] the PID control.
[PID output The value is settable within the range of F21 ? [Max frequency]
0.1 ~ 400
H56 A338 frequency low and F23 - [Start frequency]. 0.50 O
[Hz]
limit]
Selects PID standard value.
Standard value is indicated in “rEF” of Drive group.
0 Loader digital setting 1
[PID standard
H57 A339 0~4 1 Loader digital setting 2 0 ×
value select]
2 V1 terminal setting 2: 0~10V
3 I terminal setting: 0~20mA
4 Setting as a RS-485 communication
Selects a unit of the standard value or feedback amount.
PID control
H58 A33A 0~1 0 Frequency[Hz] 0 ×
unit select
1 Percentage[%]
0 Self-diagnostic disabled
[Self-diagnostic 1 IGBT fault/Ground fault
H60 A33C 0~3 0 ×
select] 2 Output phase short & open/ Ground fault
3 Ground fault (This setting is unable when more than 11kW)
H61 2) A33D [Sleep delay time] 0~2000[s] Sets a sleep delay time in PID drive. 60.0 ×
Sets a sleep frequency when executing a sleep function in PID
H62 A33E [Sleep frequency] 0~400[Hz] control drive. 0.00 O
You can’t set more than Max. frequency(F21)
H63 A33F [Wake up level] 0~100[%] Sets a wake up level in PID control drive. 35.0 O
H64 A340 [KEB drive select] 0~1 Sets KEB drive. 0 ×
[KEB action 110~140
H65 A341 Sets KEB action start level according to level. 125.0 ×
start level] [%]
[KEB action 110~145
H66 A342 Sets KEB action stop level according to level. 130.0 ×
stop level] [%]
[KEB action
H67 A343 1~20000 Sets KEB action gain. 1000 ×
gain]
[Frequency 0 Based on Max freq (F21)
H70 A346 Reference for 0~1 0 ×
Accel/Decel] 1 Based on Delta freq.
34
Compact & Powerful Inverter iG5A
Function group 2
LED Address for Parameter Min/Max Factory Adj.
Description
display communication name range defaults during run
[2nd motor
H81 1) A351 5.0 O
Accel time] 0 ~ 6000
[2nd motor [sec]
H82 A352 10.0 O
Decel time]
[2nd motor 30 ~ 400
H83 A353 60.00 ×
base frequency] [Hz]
[2nd motor
H84 A354 0~2 0 ×
V/F pattern]
[2nd motor forward
H85 A355 5 ×
torque boost] 0 ~ 15
[2nd motor reverse [%]
H86 A356 This parameter actives when the selected terminal is ON after 5 ×
torque boost]
I17-I24 is set to 12 {2nd motor select}.
[2nd motor stall 30~150
H87 A347 150 ×
prevention level] [%]
[2nd motor
50~200
H88 A358 Electronic thermal 150 O
[%]
level for 1 min]
[2nd motor
Electronic 50~150
H89 A359 100 O
thermal level for [%]
continuous]
[2nd motor 0.1~100
H90 A35A 26.3 ×
rated current] [A]
Copy the parameters from inverter and save them into remote
H91 2) A35B [Parameter read] 0~1 0 ×
loader.
Copy the parameters from remote loader and save them into
H92 A35C [Parameter write] 0~1 0 ×
inverter.
This parameter is used to initialize parameters back to the factory
default value.
0 -
All parameter groups are initialized to factory default
[Parameter 1
H93 A35D 0~5 value. 0 ×
initialize]
2 Only Drive group is initialized.
3 Only Function group 1 is initialized.
4 Only Function group 2 is initialized.
5 Only I/O group is initialized.
[Password Password for H95-[Parameter lock].
H94 A35E 0 ~ FFFF 0 O
register] Set as Hexa value.
This parameter is able to lock or unlock parameters by typing
password registered in H94.
H95 A35F [Parameter lock] 0 ~ FFFF 0 O
UL (Unlock) Parameter change enable
L (Lock) Parameter change disable
1) It is indicated when choosing I17~I24 as a 12 (2nd motor select).
2) H91,H92 parameters are displayed when Remote option is installed.
35
iG5A
Function List
Input/output group
LED Address for Parameter Min/Max Factory Adj.
Description
display communication name range defaults during run
I0 A400 [Jump code] 0 ~ 87 Sets the code number to jump. 1 O
[NV input 0 ~ -10 Sets the minimum voltage of the NV (-10V~0V) input.
I2 A402 0.00 O
Min voltage] [V]
[Frequency 0 ~ 400 Sets the inverter output minimum frequency at minimum voltage
I3 A403 0.00 O
corresponding to I 2] [Hz] of the NV input.
[NV input 0 ~ -10 Sets the maximum voltage of the NV input.
I4 A404 10.0 O
Max voltage] [V]
[Frequency 0 ~ 400 Sets the inverter output maximum frequency at maximum voltage
I5 A405 60.00 O
corresponding to I 4] [Hz] of the NV input.
[Filter time constant 0 ~ 9999 Adjusts the responsiveness of V1 input (0 ~ +10V).
I6 A406 10 O
for V1 input]
[V1 input Min 0 ~ 10 Sets the minimum voltage of the V1 input.
I7 A407 0 O
voltage] [V]
[Frequency 0 ~ 400 Sets the inverter output minimum frequency at minimum voltage
I8 A408 0.00 O
corresponding to I 7] [Hz] of the V1 input.
[V1 input Max 0 ~ 10 Sets the maximum voltage of the V1 input.
I9 A409 10 O
voltage] [V]
[Frequency 0 ~ 400 Sets the inverter output maximum frequency at maximum voltage
I10 A40A 60.00 O
corresponding to I 9] [Hz] of the V1 input.
[Filter time Sets the input section’s internal filter constant for I input.
I11 A40B 10 O
constant for I input] 0 ~ 9999
[I input Min 0 ~ 20 Sets the minimum current of I input.
I12 A40C 4.00 O
current] [mA]
[Frequency 0 ~ 400 Sets the inverter output minimum frequency at minimum current
I13 A40D 0.00 O
corresponding to I 12] [Hz] of I input.
[I input Max 0 ~ 20 Sets the Maximum current of I input.
I14 A40E 20.00 O
current] [mA]
[Frequency 0 ~ 400 Sets the inverter output maximum frequency at maximum current
I15 A40F 60.00 O
corresponding to I 14] [Hz] of I input.
[Criteria for 0 Disabled
I16 A410 Analog Input 0~2 1 activated below half of set value. 0 O
Signal loss] 2 activated below set value.
[Multi-function 0 Forward run command
I17 A411 input terminal 0 O
P1 define] 1 Reverse run command
[Multi-function 2 Emergency Stop Trip
I18 A412 input terminal 1 O
P2 define] 3 Reset when a fault occurs {RST}
0 ~ 27
[Multi-function 4 Jog operation command
I19 A413 input terminal 2 O
P3 define] 5 Multi-Step freq - Low
[Multi-function 6 Multi-Step freq - Mid
I20 A414 input terminal 3 O
P4 define] 7 Multi-Step freq - High
* See °∞Chapter 14 Troubleshooting and maintenance°± for External trip A/B contact.
* Each multi-function input terminal must be set differently.
36
Compact & Powerful Inverter iG5A
Input/output group
LED Address for Parameter Min/Max Factory Adj.
Description
display communication name range defaults during run
[Multi-function 8 Multi Accel/Decel - Low
I21 A415 input terminal 4 O
P5 define] 9 Multi Accel/Decel - Mid
[Multi-function 10 Multi Accel/Decel - High
I22 A416 input terminal 5 O
P6 define] 11 DC brake during stop
[Multi-function 12 2nd motor select
I23 A417 input terminal 6 O
P7 define] 13 -Reserved-
14 -Reserved-
15 Frequency increase (UP) command
Up-down
0 ~ 27 16 Frequency decrease command (DOWN)
17 3-wire operation
18 External trip: A Contact (EtA)
19 External trip: B Contact (EtB)
[Multi-function
20 Self-diagnostic function
I24 A418 input terminal 7 O
21 Change from PID operation to V/F operation
P8 define]
22 2nd Source
23 Analog Hold
24 Accel/Decel Disable
25 Up/Down Save Freq. Initialization
26 JOG-FX
27 JOG-RX
[Input terminal BIT7 BIT6 BIT5 BIT4 BIT3 BIT2 BIT1 BIT0
I25 A419 0 O
status display] P8 P7 P6 P5 P4 P3 P2 P1
[Output terminal BIT1 BIT0
I26 A41A 0 O
status display] 3AC MO
[Filtering time
constant for If the value is set higher, the responsiveness of the Input terminal
I27 A41B 1 ~ 15 4 O
Multi-function is getting slower.
Input terminal]
[Multi-Step
I30 A41E 30.00 O
frequency 4]
[Multi-Step
I31 A41F 25.00 O
frequency 5] 0 ~ 400
It cannot be set greater than F21 - [Max frequency].
[Multi-Step [Hz]
I32 A420 20.00 O
frequency 6]
[Multi-Step
I33 A421 15.00 O
frequency 7]
[Multi-Accel
I34 A422 3.0 O
time 1]
[Multi-Decel 0~ 6000
I35 A423 3.0
time 1] [sec]
[Multi-Accel
I36 A424 4.0
time 2]
37
iG5A
Function List
Input/output group
LED Address for Parameter Min/Max Factory Adj.
Description
display communication name range defaults during run
[Multi-Decel
I37 A425 4.0
time 2]
[Multi-Accel
I38 A426 5.0
time 3]
[Multi-Decel
I39 A427 5.0
time 3]
[Multi-Accel
I40 A428 6.0
time 4]
[Multi-Decel
I41 A429 6.0
time 4]
[Multi-Accel 0~ 6000
I42 A42A 7.0
time 5] [sec]
[Multi-Decel
I43 A42B 7.0
time 5]
[Multi-Accel
I44 A42C 8.0
time 6]
[Multi-Decel
I45 A42D 8.0
time 6]
[Multi-Accel
I46 A42E 9.0
time 7]
[Multi-Decel
I47 A42F 9.0
time 7]
Output to 10[V]
Output item
200V 400V
[Analog output 0 Output freq. Max frequency
I50 A432 0~3 0 O
item select] 1 Output current 150 %
2 Output voltage AC 282V AC 564V
3 Inverter DC link voltage DC 400V DC 800V
[Analog output 10~200 Based on 10V.
I51 A433 100 O
level adjustment] [%]
[Frequency
I52 A434 30.00 O
detection level]
0 ~ 400 Used when I54 or I55 is set to 0-4.
[Frequency
[Hz] Cannot be set higher than F21.
I53 A435 detection 10.00 O
bandwidth]
[Multi-function 0 FDT-1 12
I54 A436 output terminal 1 FDT-2
select] 2 FDT-3
3 FDT-4
4 FDT-5
0 ~ 19 O
5 Overload (OLt)
[Multi-function
I55 A437 6 Inverter Overload (IOLt) 17
relay select]
7 Motor stall (STALL)
8 Over voltage trip (Ovt)
9 Low voltage trip (Lvt)
38
Compact & Powerful Inverter iG5A
Input/output group
LED Address for Parameter Min/Max Factory Adj.
Description
display communication name range defaults during run
10 Inverter Overheat (OHt)
11 Command loss
12 During Run
13 During Stop
[Multi-function 14 During constant run
I55 A437 0 ~ 19 17 O
relay select] 15 During speed searching
16 Wait time for run signal input
17 Multi-function relay select
18 Warning for cooling fan trip
19 Brake signal select
When setting the When the trip When the
H26 - [Number of other than low low voltage trip
auto restart try] voltage trip occurs
occurs
Bit 2 Bit 1 Bit 0
0 - - -
I56 A438 [Fault relay output] 0~7 1 - - 2 O
2 - -
3 -
4 - -
5 -
6 -
7
Multi-function relay Multi-function output terminal
[Output terminal Bit 1 Bit 0
select when 0 - -
I57 A439 0~3 0 O
communication 1 -
error occurs] 2 -
3
Set communication protocol.
I59 A43B [Communication 0 ~1 0 Modbus RTU 0 ×
protocol select] 1 LS BUS
I60 A43C [Inverter number] 1 ~ 250 Set for RS485 communication 1 O
Select the Baud rate of the RS485.
0 1200 [bps]
1 2400 [bps]
I61 A43D [Baud rate] 0~4 3 O
2 4800 [bps]
3 9600 [bps]
4 19200 [bps]
It is used when freq command is given via V1 /I terminal or
[Drive mode RS485.
select after loss Continuous operation at the frequency before its
I62 A43E 0~2 0 0 O
of frequency command is lost.
command] 1 Free Run stop (Output cut-off)
2 Decel to stop
39
iG5A
Function List
Input/output group
LED Address for Parameter Min/Max Factory Adj.
Description
display communication name range defaults during run
This is the time inverter determines whether there is the input
[Wait time after
0.1 ~ 120 frequency command or not. If there is no frequency command
I63 A43F loss of frequency 1.0 O
[sec] input during this time, inverter starts operation via the mode
command]
selected at I62.
[Communication 2 ~ 100
I64 A440 Frame communication time 5 O
time setting] [ms]
When the protocol is set, the communication format can be set.
0 Parity: None, Stop Bit: 1
[Parity/stop bit
I65 A441 0~3 1 Parity: None, Stop Bit: 2 O O
setting]
2 Parity: Even, Stop Bit: 1
3 Parity: Odd, Stop Bit: 1
[Read address
I66 A442 5
register 1]
[Read address
I67 A443 6
register 2]
[Read address
I68 A444 7
register 3]
[Read address
I69 A445 8
register 4] The user can register up to 8 discontinuous addresses and read
0~42239 O
[Read address them all with one Read command.
I70 A446 9
register 5]
[Read address
I71 A447 10
register 6]
[Read address
I72 A448 11
register 7]
[Read address
I73 A449 12
register 8]
[Write address
I74 A44A 5
register 1]
[Write address
I75 A44B 6
register 2]
[Write address
I76 A44C 7
register 3]
[Write address
I77 A44D 8
register 4] The user can register up to 8 discontinuous addresses and write
0~42239 O
[Write address them all with one Write command
I78 A44E 5
register 5]
[Write address
I79 A44F 6
register 6]
[Write address
I80 A450 7
register 7]
[Write address
I81 A451 8
register 8]
[Brake open 0~180 Sets current level to open the brake.
182 1) A452 50.0 O
1) current] [%] It is set according to H33’s (motor rated current) size
1) It is indicated when choosing I54~I55 as a 19 (Brake signal).
40
Compact & Powerful Inverter iG5A
Input/output group
LED Address for Parameter Min/Max Factory Adj.
Description
display communication name range defaults during run
[Brake open 0~10
183 A453 Sets Brake open dely time. 1.00 ×
delay time] [s]
[Brake open FX 0~400
184 A454 Sets FX frequency to open the brake 1.00 ×
frequency] [Hz]
[Brake open RX 0~400
185 A455 Sets RX frequency to open the brake 1.00 ×
` frequency] [Hz]
[Brake close 0~19
186 A456 Sets delay time to close the brake 1.00 ×
delay time] [s]
[Brake close 0~400
187 A457 Sets frequency to close the brake 2.00 ×
frequency [Hz]
41
iG5A
Protective Functions
Keypad display Protective functions Descriptions
The inverter turns off its output when the output current of the inverter flows more than 200% of the inverter
Overcurrent
rated current.
The inverter turns off its output when a ground fault occurs and the ground fault current is more than the
Ground fault current
internal setting value of the inverter.
The inverter turns off its output when the output current of the inverter flows more than the rated level (150%
Inverter Overload
for 1 minute).
The inverter turns off its output if the output current of the inverter flows at 150% of the inverter rated current
Overload trip
for more than the current limit time (1min).
The inverter turns off its output if the heat sink overheats due to a damaged cooling fan or an alien substance
Heat sink overheat
in the cooling fan by detecting the temperature of the heat sink.
The inverter turns off its output when the one or more of the output (U, V, W) phase is open. The inverter
Output Phase loss
detects the output current to check the phase loss of the output.
The inverter turns off its output if the DC voltage of the main circuit increases higher than 400V when the
Over voltage
motor decelerates. This fault can also occur due to a surge voltage generated at the power supply system.
The inverter turns off its output if the DC voltage is below 180V because insufficient torque or overheating of
Low voltage
the motor can occur when the input voltage of the inverter drops.
The internal electronic thermal of the inverter determines the overheating of the motor. If the motor is
Electronic Thermal overloaded, the inverter turns off the output. The inverter cannot protect the motor when driving a motor
having more than 4 poles or multi motors.
Input phase loss Inverter output is blocked when one of R, S, T is open or the electrolytic capacitor needs to be replaced.
Self-diagnostic
Displayed when IGBT damage, output phase short, output phase ground fault or output phase open occurs.
malfunction
Parameter save error Displayed when user-setting parameters fails to be entered into memory.
Inverter hardware fault Displayed when an error occurs in the control circuitry of the inverter.
Communication Error Displayed when the inverter cannot communicate with the keypad.
Remote keypad Displayed when the inverter and the remote keypad do not communicate with each other.
communication error It does not stop inverter operation.
Cooling fan fault Displayed when a fault condition occurs in the inverter cooling fan.
Used for the emergency stop of the inverter. The inverter instantly turns off the output when the EST terminal is turned on.
Instant cut off Caution: The inverter starts to regular operation when turning off the EST terminal while FX or RX terminal is ON.
42
Compact & Powerful Inverter iG5A
Fault Remedy
Keypad display Cause Remedy
Caution: When an overcurrent fault occurs, operation must be started after the cause is removed
to avoid damage to IGBT inside the inverter.
Accel/Decel time is too short compared to the GD2 of → Increase the Accel/Decel time.
Overcurrent the load. → Replace the inverter with appropriate capacity.
Load is greater than the inverter rating. → Resume operation after stopping the motor or use
Inverter output is issued when the motor is free running. H22 (Speed search).
Output short circuit or ground fault has occurred. → Check output wiring.
Mechanical brake of the motor is operating too fast. → Check the mechanical brake.
Ground fault has occurred at the output wiring of the inverter. → Check the wiring of the output terminal.
Ground fault current The insulation of the motor is damaged due to heat. → Replace the motor.
Inverter overload
Load is greater than the inverter rating. → Upgrade the capacity of motor and inverter or reduce
the load weight.
Torque boost scale is set too large. → Reduce torque boost scale.
Overload trip
Cooling system has faults. → Check for alien substances clogged in the heat sink.
Heat sink overheat An old cooling fan is not replaced with a new one. → Replace the old cooling fan with a new one.
Ambient temperature is too high. → Keep ambient temperature under 50�C.
Faulty contact of magnetic switch at output. → Make connection of magnetic switch
Output Phase loss at output of the inverter securely.
Faulty output wiring. → Check output wiring.
An alien substance is clogged in a ventilating slot. → Check the ventilating slot and remove
Cooling fan fault the clogged substances.
Inverter has been in use without changing a cooling fan. → Replace the cooling fan.
Decel time is too short compared to the GD2 of the load. → Increase the Decel time.
Over voltage Regenerative load is at the inverter output. → Use Dynamic Brake Unit.
Line voltage is too high. → Check whether line voltage exceeds its rating.
Line voltage is low. → Check whether line voltage is below its rating.
Load larger than line capacity is connected to line → Check the incoming AC line.
Low voltage (ex: welding machine, motor with high starting current Adjust the line capacity corresponding to the load.
connected to the commercial line).
Faulty magnetic switch at the input side of the inverter. → Change a magnetic switch.
Motor has overheated. → Reduce load weight and operating duty.
Load is greater than inverter rating. → Change inverter with higher capacity.
ETH level is set too low. → Adjust ETH level to an appropriate level.
Electronic thermal → Select correct inverter capacity.
Inverter capacity is incorrectly selected. → Install a cooling fan with a separate power supply.
Inverter has been operated at low speed for too long.
External fault A
contact input
The terminal set to“18 (External fault- A)”or → Eliminate the cause of fault at circuit connected to
External fault B “19 (External fault-B)”in I20-I24 in I/O group is ON. external fault terminal or cause of external fault input.
contact input
Operating method
→ Check the wiring of V1 and I and frequency
when the frequency No frequency command is applied to V1 and I.
reference level.
command is lost
Remote keypad Communication error between inverter → Check for connection of communication line and
communication error keypad and remote keypad. connector.
43
• For your safety, please read user's manual thoroughly before operating.
• Contact the nearest authorized service facility for examination, repair, or adjustment.
• Please contact a qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
Safety Instructions • Any maintenance and inspection shall be performed by the personnel having expertise concerned.