TRANSFORMER CONNECTORS
TYPE NSSM / NSM
DUAL-RATED CONNECTORS W
FOR ALUMINUM OR COPPER CONDUCTORS 600V
L
• NSSM with patented Keyhole mounting.
• Clear plated for low-contact resistance. H
• Fully tested to ANSI C119.4 for Class ‘A’ connectors.
• Offers fast, economical, reusable, dependable connections for right or left-hand installations.
• Supplied with aluminum radial-tipped set-screws.
• Connector fabricated from 6061-T6 aluminum alloy for conductivity and strength.
• 105°C Rated black plastisol cover available.
In-
• Includes CO-OX oxide inhibitor in all conductor holes and stud-mounting hole.
• Each unit individually wrapped and labeled for ease of identification and cleanliness.
• For installation, CMC® recommends the use of a 9” insulated Allen wrench.
• A torque wrnch should be used to ensure the proper torque is achieved.
PATENTED
Catalog Number Cond. Range H W L Black
No. of Trans.
AWG Dimensions - Inches Plastisol Slip-On
Slip On Screw On Cond. Stud
MM2 Dimensions - (mm) Cover Keyhole
250-12 1.13 0.88 3.74
NSSM250-2I NSM250-2I 2 5/8-11 SLCC2-250
120-4 28.70 22.35 95.00
250-12 1.13 0.88 4.65
NSSM250-3I NSM250-3I 3 5/8-11 SLCC4-250
120-4 28.70 22.35 118.11
250-12 1.13 0.88 5.56
NSSM250-4I NSM250-4I 4 5/8-11 SLCC4-250
120-4 28.70 22.35 141.22 Patented
NSSM NSM
PATENTED
Cond
Catalog Number H W L Black
No of Range Trans.
Plastisol
Cond. AWG Stud Dimensions - Inches Slip-On
Slip On Screw On Cover
MM2 Dimensions - (mm) Keyhole
500-10 1.75 1.38 4.45
NSSM500-2I NSM500-2I 2 1-14 SLCC2-500
240-4 44.5 35.05 113.03
500-10 1.75 1.38 5.64
NSSM500-3I NSM500-3I 3 1-14 SLCC4-500
240-4 44.5 35.05 143.26
500-10 1.75 1.38 6.83
NSSM500-4I NSM500-4I 4 1-14 SLCC4-500
240-4 44.5 35.05 173.48
Patented
500-10 1.75 1.38 9.20
NSSM500-6I NSM500-6I 6 1-14 SLCC6-500
240-4 44.5 35.05 233.68
500-10 1.75 1.38 11.57
NSSM500-8I NSM500-8I 8 1-14 SLCC8-500
240-4 44.5 35.05 293.88
750-2 1.88 1.38 4.77
NSSM750-2I NSM750-2I 2 1-14 SLCC2-750 SLCC
300-25 47.75 35.05 121.16
750-2 1.88 1.38 6.08
NSSM750-3I NSM750-3I 3 1-14 SLCC4-750
300-25 47.75 35.05 154.43
750-2 1.88 1.38 7.39
NSSM750-4I NSM750-4I 4 1-14 SLCC4-750
300-25 47.75 35.05 187.71
750-2 1.88 1.38 10.01
NSSM750-6I NSM750-6I 6 1-14 SLCC6-750
300-25 47.75 35.05 254.25
750-2 1.88 1.38 12.63
NSSM750-8I NSM750-8I 8 1-14 SLCC8-750
300-25 47.75 35.05 320.80
Note: Street light tap available — add suffix “SL” to catalog number. For clear plastisol cover add suffix “C”.
For omission of CO-OX oxide inhibitor delete suffix - “I”. Add suffix “A” for 5/8-11 stud
E- Transformer Connectors
-2- 2/15
STUD-MOUNT
TRANSFORMER CONNECTORS
Allows left or right-hand mounting
TYPE NSSC / NSC
Insulated Stud-Mount Connectors
DUAL-RATED CONNECTORS RUS Approved
FOR ALUMINUM OR COPPER CONDUCTORS
• NSSC with patented with Keyhole mounting. • Clear plated for low-contact resistance.
• Injection-molded clear plastic cover insulating a • Connector fabricated from 6061-T6
NSSM or NSM connector. aluminum alloy for conductivity and
• Injection-molded black rubber cover (NSSR/NSR strength.
series) available upon request. Consult factory • Includes CO-OX oxide inhibitor in all
for availability and minimum order quantities. conductor holes and stud-mounting hole.
• Fully tested to ANSI C119.4 for Class ‘A’ • Each unit individually wrapped and
connectors. labeled for ease of identification and
• Offers fast, economical, reusable, dependable cleanliness.
connections for right or left-hand installations. • For installation, CMC® recommends
• Supplied with radial-tipped set-screws. the use of a 9” insulated Allen wrench.
• A torque wrnch should be used to ensure
PATENTED the proper torque is achieved.
Cond
Catalog Number H W L
No of Range Trans.
Cond. AWG Stud Dimensions - Inches
Slip On Screw On
MM2 Dimensions - (mm)
250-12 3.17 3.17 5.13
NSSC250-2I NSC250-2I 2 5/8-11
120-4 80.52 80.52 130.3
250-12 3.17 3.17 6.04
NSSC250-3I NSC250-3I 3 5/8-11
120-4 80.52 80.52 153.42
250-12 3.17 3.17 6.95
NSSC250-4I NSC250-4I 4 5/8-11
120-4 80.52 80.52 176.53
250-12 3.17 3.17 7.86
NSSC250-5I NSC250-5I 5 5/8-11
120-4 80.52 80.52 199.64
250-12 3.17 3.17 8.77
NSSC250-6I NSC250-6I 6 5/8-11
120-4 80.52 80.52 222.76
250-12 3.17 3.17 10.59
NSSC250-8I NSC250-8I 8 5/8-11
120-4 80.52 80.52 268.99 W
350-12 3.17 3.17 5.13
NSSC350-2I NSC350-2I 2 5/8-11
185-4 80.52 80.52 130.3
350-12 3.17 3.17 6.04 L
NSSC350-3I NSC350-3I 3 5/8-11
185-4 80.52 80.52 153.42
350-12 3.17 3.17 6.95
NSSC350-4I NSC350-4I 4 5/8-11 H
185-4 185.4 185.4 273.6
350-12 3.17 3.17 7.86
NSSC350-5I NSC350-5I 5 5/8-11
185-4 185.4 185.4 199.64
350-12 3.17 3.17 8.77
NSSC350-6I NSC350-6I 6 5/8-11
185-4 80.52 80.52 222.76 Note: Street light tap available by adding
350-12 3.17 3.17 10.59 suffix “SL”. For omission of
NSSC350-8I NSC350-8I 8 5/8-11 CO-OX Inhibitor, delete suffix “I”.
185-4 80.52 80.52 268.99
E- Transformer Connectors
-3- 2/15
STUD-MOUNT
TRANSFORMER CONNECTORS
Allows left or right-hand mounting
TYPE RLS / RLSS 600V
Insulated Stud-Mounted Transformer Connectors RUS Approved
DUAL-RATED CONNECTORS
FOR ALUMINUM OR COPPER CONDUCTORS
• RLSS with patented Keyhole mounting.
• Clear plated for low-contact resistance.
• Fully tested to ANSI C119.4 for Class ‘A’ connectors.
• Supplied with radial-tipped set-screws.
• Offers fast, economical, reusable, and dependable
connections for right or left hand installations.
• Connector fabricated from 6061-T6
aluminum alloy for conductivity and strength.
• Includes CO-OX oxide inhibitor in all
conductor holes and stud-mounting hole.
• Each unit individually wrapped and labeled for L W
ease of identification and cleanliness.
• For installation, CMC® recommends the use of
H
a 9” insulated Allen wrench.
• A torque wrnch should be used to ensure the
proper torque is achieved.
PATENTED
Catalog Number No. of Cond. Range Trans. H W L
Slip On Screw On Cond. AWG Stud Dimensions - Inches
RLSS350-2I RLS350-2I 2 350-12 5/8-11 2.26 2.50 4.11
E- Transformer Connectors
-4- 2/15
STUD-MOUNT
TRANSFORMER CONNECTORS
TYPE NUB 600V
Slip-Fit with Patented Sharkbite™ Mount
• Connector fabricated from 6061-T6 aluminum alloy for conductivity and strength.
• Supplied with aluminum radial-tipped set screws.
• Includes inhibitor in all ports and stud-mounting hole.
• Patented two-in-one Sharkbite™ mounting hole feature allows the connector to fit on a 5/8” - 11 or
1” - 14 transformer stud. Both sizes fit in the same hole.
• Sharkbite™ mounting hole feature provides 10 times the surface area contact on the stud over
traditional connectors.
• The Sharkbite™ feature also securely locks the connector onto the stud to eliminate wobble when
installing the conductors.
• Fully tested to ANSI C119.4 for Class ‘A’ connectors.
• 105°C Rated black plastisol cover available.
PATENTED
Catalog No. Cond. Range H W L Black
SharkbiteTM
Number of AWG Trans. Stud Dimensions - Inches Plastisol
Slip On Cond. MM2 Dimensions - (mm) Cover
500-10 5/8-11 or 1.75 1.38 4.45
NUB500-2I 2 SLCC2-500
240-4 1-14 44.5 35.05 113.03
49
º
49
500-10 5/8-11 or 1.75 1.38 5.64
º
NUB500-3I 3 SLCC4-500
240-4 1-14 44.5 35.05 143.26
500-10 5/8-11 or 1.75 1.38 6.83
NUB500-4I 4 SLCC4-500
240-4 1-14 44.5 35.05 173.48
500-10 5/8-11 or 1.75 1.38 9.20
NUB500-6I 6 SLCC6-500
240-4 1-14 44.5 35.05 233.68 H
E- Transformer Connectors
-5- 2/15
STUD-MOUNT
TRANSFORMER CONNECTORS
Allows left or right-hand mounting
TYPE RLB
Insulated Slip-Fit with Patented Sharkbite™ Mount
600V
DUAL-RATED CONNECTORS
FOR ALUMINUM OR COPPER CONDUCTORS
• Connector fabricated from 6061-T6 aluminum • The Sharkbite™ feature also securely
alloy for conductivity and strength. locks the connector onto the stud to
• Supplied with aluminum radial-tipped set eliminate wobble when installing
screws. the conductors.
• Includes inhibitor in all ports and stud mounting
hole.
• Patented two-in-one Sharkbite™ mounting
hole feature allows the connector to fit on a
5/8” - 11 or 1” - 14 transformer stud. Both
sizes fit in the same hole.
PATENTED
No. of Cond. Range H W L
Catalog Number Trans. Stud
Cond. AWG Dimensions - Inches
RLB500-4I 4 500-10 5/8-11 or 1-14 2.73 3.00 4.59
RLB500-5I 5 500-10 5/8-11 or 1-14 2.73 3.00 6.99
RLB500-6I 6 500-10 5/8-11 or 1-14 2.73 3.00 9.39
RLB500-7I 7 500-10 5/8-11 or 1-14 2.73 3.00 10.59
RLB500-8I 8 500-10 5/8-11 or 1-14 2.73 3.00 11.78
Street light tap available - add suffix “SL” to catalog number.
RLB750-4I 4 750-2 5/8-11 or 1-14 2.95 4.91 9.28
RLB750-6I 6 750-2 5/8-11 or 1-14 2.95 4.91 12.00
RLB750-8I 8 750-2 5/8-11 or 1-14 2.95 4.91 14.73
SharkbiteTM
H
49
º
49
º
E- Transformer Connectors
-6- 2/15
SPACE-SAVER STUD-MOUNT
TRANSFORMER CONNECTORS
Keyhole
L
Patented
L W
Number of
Catalog Number Conductor Range
Outlets
Dimensions - Inches
E- Transformer Connectors
-7- 2/15
SPACE-SAVER STUD-MOUNT
TRANSFORMER CONNECTORS
PATENTED
Number of L W
Catalog Number Conductor Range
Outlets Dimensions - Inches
SHB6-350SLXB 6 350-12 5.23 2.73
SHB8-350SLXB 8 350-12 6.31 2.73
SHB10-350SLXB 10 350-12 7.39 2.73
SHB6-500SLXB 6 500-10 5.23 2.73
SHB8-500SLXB 8 500-10 6.31 2.73
SHB10-500SLXB 10 500-10 7.39 2.73
SHB12-500SLXB 12 500-10 8.47 2.73
E- Transformer Connectors
-8- 2/15
SPACE-SAVER STUD-MOUNT
TRANSFORMER CONNECTORS
TYPE SH-C / SHB-C (Quick Disconnect)
Clear Insulated Offset, Compact Secondary Transformer Stud Connectors
DUAL-RATED CONNECTORS
FOR ALUMINUM OR COPPER CONDUCTORS
L
Industry Standard Shark-Bite™ with Shark-Bite™ with
Slip Fit Design 1” Stud Seated 5/8” Stud Seated W
3% Contact Area 31% Contact Area 22% Contact Area
E- Transformer Connectors
-9- 2/15
SPACE-SAVER STUD-MOUNT
TRANSFORMER CONNECTORS
TYPE ZQ (Slip Fit)
DUAL-RATED CONNECTORS 600V
FOR ALUMINUM OR COPPER CONDUCTORS
• Fully tested to ANSI C119.4 for Class • Includes CO-OX oxide inhibitor in all
“A” connectors. conductor holes and stud mounting hole.
• Supplied with aluminum radial-tipped set-screws. • Each unit individually wrapped and labeled
• 105°C Rated clear plastisol cover available. for ease of identification and cleanliness.
• Connector fabricated from 6061-T6 • For installation, CMC® recommends the
aluminum alloy for conductivity and strength. use of a 9” insulated Allen wrench.
• A torque wrnch should be used to ensure
the proper torque is achieved.
E- Transformer Connectors
-10- 2/15
SPACE-SAVER
TRANSFORMER CONNECTORS
TYPE ZS (Screw On)
DUAL-RATED CONNECTORS
FOR ALUMINUM OR COPPER CONDUCTORS
• Includes CO-OX oxide inhibitor in all conductor • Clear plated for low-contact resistance.
holes and stud-mounting hole. • Fully tested to ANSI C119.4 for Class
• Each unit individually wrapped and labeled for ‘A’ connectors.
ease of identification and cleanliness. • Supplied with aluminum radial-tipped set screws.
• For installation, CMC® recommends the use • 105°C Rated clear plastisol cover available.
of an insulated Allen wrench. • Connector fabricated from 6061-T6 aluminum
• A torque wrnch should be used to ensure alloy for conductivity and strength.
the proper torque is achieved.
Cond. H W L
Catalog No. of Range Trans. Dimensions - Inches Plastisol
Number Cond. AWG Stud Cover
MM2 Dimensions - (mm)
UNIVERSAL For 5/8” and 1” Studs
ZSU Series
350-12 2.88 2.38 5.13
ZSU6-350SLI 6 UNIV. ZLC-3
185-4 73.15 60.45 130.30
350-12 2.88 2.38 6.04
ZSU8-350SLI 8 UNIV. ZLC-4
185-4 73.15 60.45 154.69
500-12 2.88 2.38 5.63
ZSU6-500SLI 6 UNIV. ZLC-4
240-4 73.15 60.45 143
500-10 2.88 2.38 6.75
ZSU8-500SLI 8 UNIV. ZLC-5
240-4 73.15 60.45 171.45
ZS Series
For 5/8” Studs Only
350-12 2.38 2.00 4.25
ZS6-350SLI 6 5/8-11 ZLC-1
185-4 60.45 50.80 107.95
350-12 2.38 2.00 5.16
ZS8-350SLI 8 5/8-11 ZLC-2
185-4 60.45 50.80 131.06
500-10 2.88 2.38 5.13
ZS6-500ASLI 6 5/8-11 ZLC-4
185-4 73.15 60.45 130.30
ZLC
500-10 2.88 2.38 6.25
ZS8-500ASLI 8 5/8-11 ZLC-5
185-4 73.15 60.45 158.75
For 1” Studs Only
W
350-12 2.38 2.00 4.25
ZS6-350BSLI 6 1-14 ZLC-1
185-4 60.45 50.80 107.95
350-12 2.38 2.00 5.16 L
ZS8-350BSLI 8 1-14 ZLC-4
185-4 60.45 50.80 131.06
500-10 2.88 2.38 5.13
ZS6-500SLI 6 1-14 ZLC-4
185-4 73.15 60.45 130.30 H
500-10 2.88 2.38 6.25
ZS8-500SLI 8 1-14 ZLC-5 Other sizes available. Please contact
185-4 73.15 60.45 158.75 factory for more details.
Note: For omission of CO-OX oxide inhibitor delete suffix - “I”.
E- Transformer Connectors
-11- 2/15
STUD-MOUNT
TRANSFORMER CONNECTORS
TYPE ZQ-C / ZQU-C and ZS-C / ZSU-C 600V
Space-Saver Transformer Connectors
DUAL-RATED CONNECTORS
FOR ALUMINUM OR COPPER CONDUCTORS
Note: For omission of CO-OX inhibitor delete suffix - “I”. Right handed option available.
E- Transformer Connectors
-12- 2/15
SPACE-SAVER STUD-MOUNT
TRANSFORMER CONNECTORS
Allows left or right-hand mounting
TYPE USSM / USM 600V
DUAL-RATED CONNECTORS
FOR ALUMINUM OR COPPER CONDUCTORS
• Designed to reduce cantilever stress on the bushing by 50% and increase available safe space.
• Clear plated for low-contact resistance.
• Allows left or right-hand installation
• Fully tested to ANSI C119.4 for Class ‘A’ connectors.
• Offers fast, economical, reusable, dependable connections for right or left-hand installations.
• Supplied with aluminum radial-tipped set-screws.
• Connector fabricated from 6061-T6 aluminum alloy for conductivity and strength.
• 105°C Rated clear plastisol cover available.
• Includes CO-OX oxide inhibitor in all conductor holes and stud-mounting hole.
• Each unit individually wrapped and labeled for ease of identification and cleanliness.
• For installation, CMC® recommends the use of a 9” insulated Allen wrench.
• For use on both 5/8” and 1” studs in screw-on and quick-disconnect models.
E- Transformer Connectors
-13- 2/15
SPACE-SAVER STUD-MOUNT
TRANSFORMER CONNECTORS
600V
TYPE RLUSS / RLUS
DUAL-RATED CONNECTORS
FOR ALUMINUM OR COPPER CONDUCTORS RUS Approved
L W
E- Transformer Connectors
-14- 2/15
SPACE-SAVERS STUD-MOUNT
TRANSFORMER CONNECTORS
TYPE DQ / DS / SDQ / SDS 600V
DUAL-RATED CONNECTORS
FOR ALUMINUM OR COPPER CONDUCTORS
• Clear plated for low-contact resistance.
• Fully tested to ANSI C119.4 for Class ‘A’ connectors.
• Offers fast, economical, reusable, and dependable connections.
• Supplied with aluminum radial-tipped set-screws.
• Connector fabricated from 6061-T6 aluminum alloy for conductivity and strength.
• Includes CO-OX oxide inhibitor in all conductor holes and stud-mounting hole.
• Each unit individually wrapped and labeled for ease of identification and cleanliness.
• For installation, CMC® recommends the use of a 9” insulated Allen wrench.
• A torque wrnch should be used to ensure the proper torque is achieved.
Catalog Number H W L
No. of Cond. Trans.
Dimensions - Inches
Slip On Screw On Cond. Range Stud
Dimensions - (mm)
2.00 1.00 4.25
DQ6-250I DS6-250I 6 250-12 5/8-11
50.80 25.40 107.95
2.00 1.00 5.00
DQ8-250I DS8-250I 8 250-12 5/8-11
540.8 25.40 127.00
2.50 1.25 4.75
DQ6-350I DS6-350I 6 350-12 5/8-11
63.5 31.75 120.65 W
2.50 1.25 4.75 L
DQ8-350I DS8-350I 8 350-12 5/8-11
63.5 31.75 120.65
2.50 1.38 5.55
SDQ350-4I SDS350-4I 4 350-12 5/8-11 H
63.5 35.01 140.97
2.50 1.38 7.05
SDQ350-6I SDS350-6I 6 350-12 5/8-11
63.5 35.01 179.97
2.50 1.38 8.55
SDQ350-8I SDS350-8I 8 350-12 5/8-11
63.5 35.01 217.17
2.50 1.38 6.20
SDQ500-4I SDS500-4I 4 500-10 1-14
63.5 25.05 157.05
2.50 1.38 8.07
SDQ500-6I SDS500-6I 6 500-10 1-14 Type SDQ
63.5 35.01 204.45
Note: For omission of CO-OX oxide inhibitor delete suffix - “I”.
Street light tap available — add suffix “SL” to catalog number
W L
E- Transformer Connectors
-15- 2/15
STUD-MOUNT
TRANSFORMER CONNECTORS
TYPE NSA
DUAL-RATED CONNECTORS UNI-JOINT
FOR ALUMINUM OR COPPER CONDUCTORS
600V
• Clear plated for low-contact resistance.
• Fully tested to ANSI C119.4 for Class ‘A’ connectors.
• Supplied with aluminum radial-tipped set-screws.
• Connector fabricated from 6061-T6 aluminum alloy for conductivity and strength.
• Includes CO-OX oxide inhibitor in all conductor holes and stud-mounting hole.
• Each unit individually wrapped and labeled for ease of identification and cleanliness.
• For installation, CMC® recommends the use of a 9” insulated Allen wrench.
• A torque wrnch should be used to ensure the proper torque is achieved.
Figure 2
Figure 1
H
E- Transformer Connectors
-16- 2/15
NEMA MOUNTING
TRANSFORMER CONNECTORS
TYPE NNM 600V
DUAL-RATED CONNECTORS
FOR ALUMINUM OR COPPER CONDUCTORS • Clear plated for low-contact resistance.
• Fully tested to ANSI C119.4 for Class ‘A’
Cond. H W L
Catalog No. of Range Mtg.
connectors.
Dimensions - Inches • Supplied with aluminum radial-tipped set-
Number Cond. AWG Hole
MM2 Dimensions - (mm) screws.
250-12 0.56 1.13 0.88 5.78 • Connector fabricated from 6061-T6
NNM250-3I 3
120-4 14.30 28.70 22.35 146.81 aluminum alloy for conductivity and
250-12 0.56 1.13 0.88 6.65 strength.
NNM250-4I 4
120-4 14.30 28.70 22.35 168.91
• Includes CO-OX oxide inhibitor in all
conductor holes.
250-12 0.56 1.13 0.88 8.41
NNM250-6I 6 • Each unit individually wrapped and
120-4 14.30 28.70 22.35 213.61
labeled for ease of identification and
250-12 0.56 1.13 0.88 10.16 cleanliness.
NNM250-8I 8
120-4 14.30 28.70 22.35 258.06 • For installation, CMC® recommends
350-12 0.56 1.25 1.00 6.02 the use of a 9” insulated Allen wrench.
NNM350-3I 3 • A torque wrnch should be used to ensure
185-4 14.30 35.05 25.40 152.91
the proper torque is achieved.
350-12 0.56 1.25 1.00 6.93
NNM350-4I 4
185-4 14.30 35.05 25.40 176.02
350-12 0.56 1.25 1.00 8.75
NNM350-6I 6
185-4 14.30 35.05 25.40 222.25
NNM350-8I 8
350-12 0.56 1.25 1.00 10.57 NEMA Spaced 1.75”
185-4 14.30 35.05 25.40 268.48 Mounting Holes
500-10 0.56 1.63 1.00 6.71
NNM500-3I 3
240-4 14.30 41.40 25.40 170.43
500-10 0.56 1.63 1.00 7.9
NNM500-4I 4
240-4 14.30 41.40 25.40 200.66
500-10 0.56 1.63 1.00 10.28
NNM500-6I 6
240-4 14.30 41.40 25.40 261.11
500-10 0.56 1.63 1.00 12.65
NNM500-8I 8
240-4 14.30 41.40 25.40 321.31
750-2 0.56 1.75 1.38 7.28
NNM750-3I 3
300-25 14.30 44.45 35.05 184.91
750-2 0.56 1.75 1.38 8.59
NNM750-4I 4 L W
300-25 14.30 44.45 35.05 218.19
750-2 0.56 1.75 1.38 11.21
NNM750-6I 6 H
300-25 14.30 44.45 35.05 284.73
E- Transformer Connectors
-17- 2/15
TRANSFORMER
EYEBOLT CONNECTORS
TYPE NP / PTS
DUAL-RATED CONNECTORS
FOR ALUMINUM OR COPPER CONDUCTORS
600V
• Clear plated for low-contact resistance.
• Fully tested to ANSI C119.4 for Class ‘A’ connectors.
• For installation on equipment secondary transformers.
• Stud is electro-tin plated.
NP
• Supplied with aluminum radial-tipped set-screws.
• Connector fabricated from 6061-T6 aluminum alloy for conductivity and strength.
• Includes CO-OX oxide inhibitor in all conductor holes.
• Each unit individually wrapped and labeled for ease of identification and cleanliness.
• For installation, CMC® recommends the use of a 9” insulated Allen wrench.
• A torque wrnch should be used to ensure the proper torque is achieved.
H W L
Cond. Stud Stud
*Catalog No. of Dimensions - Inches Cover
Range Dia. Length
Number Cond. Only
AWG Inches Inches Dimensions - (mm)
NP2-1/0I 2 1/0-14 0.38 3.50 0.75 0.56 1.97 NPC2-1/0
NP3-1/0I 3 1/0-14 0.38 3.50 0.75 0.56 2.59 NPC3-1/0
NP4-1/0I 4 1/0-14 0.38 3.50 0.75 0.56 3.22 NPC4-1/0
NP2-250I 0.50 4.00 1.13 0.88 2.69
2 250-12 NPC2-250
12.70 101.60 28.70 22.35 68.33 NPC
NP3-250I 0.50 4.00 1.13 0.88 3.64
3 250-12 NPC3-250
12.70 101.60 28.70 22.35 92.46
0.50 4.00 1.13 0.88 4.58
NP4-250I 4 250-12 NPC4-250
12.70 101.60 28.70 22.35 116.33
0.50 4.00 1.13 0.88 6.46
NP6-250I 6 250-12 NPC6-250
12.70 101.60 28.70 22.35 164.08
0.50 4.00 1.13 0.88 8.36
NP8-250I 8 250-12 NPC8-250
12.70 101.60 28.70 22.35 212.34
0.50 4.00 1.25 1.00 2.97
NP2-350I 2 350-12 NPC3-350
12.70 101.60 35.05 25.40 75.44
0.50 4.00 1.25 1.00 4.00
NP3-350I 3 350-12 NPC3-350
12.70 101.60 35.05 25.40 101.60
0.50 4.00 1.25 1.00 5.03
NP4-350I 4 350-12 NPC4-350
12.70 101.60 35.05 25.40 127.76
0.50 4.00 1.25 1.00 7.09
NP6-350I 6 350-12 NPC6-350
12.70 101.60 35.05 25.40 180.09
0.50 4.00 1.25 1.00 9.14
NP8-350I 8 350-12 NPC8-350
12.70 101.60 35.05 25.40 232.16
Notes: *Add suffix “C” to order with black plastisol cover W
For omission of co-ox oxide inhibitor, delete suffix “I”.
L
E- Transformer Connectors H
-18- 2/15
TRANSFORMER
EYEBOLT CONNECTORS
TYPE NP
Transformer Eyebolt Connectors
600V
DUAL-RATED CONNECTORS
FOR ALUMINUM OR COPPER CONDUCTORS
• Clear plated for low-contact resistance. W
• Fully tested to ANSI C119.4 for Class ‘A’ connectors. L
• For installation on equipment secondary transformers.
• Copper stud is electro-tin plated. H
• Supplied with aluminum radial-tipped set-screws.
• Connector fabricated from 6061-T6 aluminum alloy for conductivity and strength.
• Includes CO-OX oxide inhibitor in all conductor holes.
• Each unit individually wrapped and labeled for ease of identification and cleanliness.
• For installation, CMC® recommends the use of a 9” insulated Allen wrench.
• A torque wrnch should be used to ensure the proper torque is achieved.
NPC NP
E- Transformer Connectors
-19- 2/15
TRANSFORMER
EYEBOLT CONNECTORS
TYPE NPP
600V
DUAL-RATED CONNECTORS
FOR ALUMINUM OR COPPER CONDUCTORS
E- Transformer Connectors
-20- 2/15
TRANSFORMER
EYEBOLT CONNECTORS
• For moisture resistance, conductor ports are not drilled through the body.
• Clear plated for low-contact resistance.
• Fully tested to ANSI C119.4 for Class ‘A’ connectors.
• For installation on equipment secondary adaptors.
• Stud is electro-tin plated.
• Supplied with aluminum radial-tipped set-screws.
• Connector fabricated from 6061-T6 aluminum alloy for conductivity and strength.
• Includes CO-OX oxide inhibitor in all conductor holes.
• Each unit individually wrapped and labeled for ease of identification and cleanliness.
• For installation, CMC® recommends the use of a 9” insulated Allen wrench.
• A torque wrnch should be used to ensure the proper torque is achieved.
Stud Stud H W L
Catalog No. of Cond.
Dia. Length
Number Cond. Range Dimensions - Inches
Inches Inches
NPB4-4/0I 4 4/0-14 0.50 4.00 1.87 1.35 4.00
NPB2-350I 2 350-12 0.50 4.00 1.375 1.59 2.98
NPB3-350I 3 350-12 0.50 4.00 1.375 1.59 3.99
NPB4-350I 4 350-12 0.50 4.00 1.375 1.59 5.03
NPB6-350I 6 350-12 0.50 4.00 1.375 1.59 7.09
NPB2-500I 2 500-10 0.75 4.00 1.75 2.00 3.59
NPB2-750I 2 750-2 0.75 4.00 1.75 2.00 4.00
NPB4-500I 4 500-10 0.75 4.00 1.75 2.00 6.06
Note: For omission of CO-OX oxide inhibitor, delete suffix “I”..
Also, street light tap available, add suffix “SL” to the catalog number.
E- Transformer Connectors
-21- 2/15
COMPRESSION CONNECTORS
TYPE PT 600V
Aluminum Pin Terminal
• Tinned copper rod factory crimped into an aluminum compression sleeve. Cavities are pre-filled with
electrical joint compound and capped.
• Pin terminals are widely used in clamp-type plated bronze connectors, common to pole-type
transformers, disconnect switches, cutouts and lightning arrestors, to allow aluminum conductors to
be connected. The transition from copper to aluminum is made within a sealed compression joint to
assure protection from bi-metallic corrosion.
Wire Range
“D” “P” “L”
Catalog Dia. Range
Nom. Pin Length Length Common Crimping Die Codes
Number Aluminum ACSR
Min. - Max. Diameter Inches Inches
D
300-350 Str.
PT34940-6 .618-.684 4/0 Sol.
350 Comp.
250-300 Str.
4/0 & 200-
PT30050-6 300-350 Comp. .564-.630
18/1
Str.
336-18/1 EE1-13A; Alcoa 13 AH
300-350 Str. 350 Kearney 11/8
PT35050-6 & 336- .618-.684 P
Comp. 4/0 Sol. 6.00 11.00 Burndy 316, 655 or 706
36/1
Somerset - T&B 96
336-400 Str. 336-18/1 Anderson VC6
PT40050-6 .666-.741
500 Comp. Str. 397-36/1
450-500 Str. 397-18/1
L
PT50050-6 .743-.814
600 Comp. Str. 477-36/1
450-500 Str. 397-18/1-
PT45062-6 .743-.814 5/8 6.00 12.00
600 Comp. Str. 477-341
477-18/1- EE1-14A; Alcoa 13 AH;
PT55062-6 500-556.5 Str. .811-.879 Kearney 1-15/16;
556-18/1
Anderson VC Burndy 317, 327 or 719
600-700 Str. 5/8
605-36/1- Somerset - T&B 106 Burndy 301, 342,
PT70062-6 750-800 Comp. .883-.996 Various pin
636-36/1 608, 722 or 786
Str. 6.00 12.25 Kearney 11/2 Alcoa 24AH lengths
715-54/7 Somerset-T&B 125 available.
795-36/1 Anderson VC8
PT90075-6 800-900 Str. 1.031-1.094 3/4
& 795-
54/7
795-
Burndy 292, 302, 352, 579 or 725;
PT100087-6 900-1033 Str. 26/17- 1.092-1.196 7/8 6.00 12.50
Alcoa 30 AH; T&B 150; Kearney 13/4
954-54/7
E- Transformer Connectors
-22- 2/15
COMPRESSION CONNECTORS
600V
TYPE SPT
Shrouded Aluminum Pin Terminals
• Shroud accepts insulation of conductors.
• Tinned copper rod factory crimped into an aluminum compression sleeve. Cavities are pre-filled
with electrical joint compound and capped.
• Pin terminals are widely used in clamp-type plated bronze connectors, common to pole-type
transformers, disconnect switches, cutouts and lightning arrestors, to allow aluminum conductors to
be connected. The transition from copper to aluminum is made within a sealed compression joint to
assure protection from bi-metallic corrosion.
Wire Range
Catalog “D” Nom. Pin “P” “L” Common Crimping
Number Dia. Range Diameter Length Length Die Codes
Aluminum ACSR
Min.-Max
2Sol. 3-4
SPT44 Str. & 4 4 .024-.258 2.00 5.37
Comp. 4 Sol. EE1-81
1-2 Str. 2 Burndy BG, 243
SPT24 2 .268-.328 2.00 5.50 Kerny 5/8
Comp. Str.
Alcoa 08AH
1/0 Str. 1/0 T&B TU (52)
SPT102S 1/0 .336-.398 2 Sol. 2.00 5.75
Comp. Anderson VC5, VC6
2/0 Str. 3/0
SPT2010 2/0 .388-.448 1/0 Sol. 4.00 7.00
Comp.
3/0 Str. 4/0
SPT3010 3/0 .442-.502 4.00 7.25
Comp. EE1-11A
4/0-250 3/8 Sol. Burndy 249 or 840
SPT4020 Str. 250 4/0 .511-.575 3.72 7.00 Kearny 840
Comp. Somerset TX or 76
300-350 Alcoa 11 AH
SPT34940 Str. 350 - .618-.684 4/0 Sol. 6.00 11.00 Anderson VC6
Comp.
L
P D
E- Transformer Connectors
-23- 2/15
GENERAL PURPOSE
TRANSFORMER CONNECTORS
TYPE L-A
DUAL-RATED CONNECTORS 600V
FOR ALUMINUM OR COPPER CONDUCTORS
• Clear Plated for low-contact resistance.
• Fully tested to ANSI C119.4 for Class ‘A’ connectors.
• Supplied with aluminum radial tipped set-screws.
• Connector fabricated from 6061-T6 aluminum alloy for conductivity and strength.
• Designed for installation on standard two and four-hole spades.
• All mounting holes 1.75” on center line.
• For installation, CMC® recommends the use of a 9” insulated Allen wrench.
• A torque wrnch should be used to ensure the proper torque is achieved.
L2A2 L3A2
L1A1
E- Transformer Connectors
-24- 1/15
2/15
GENERAL PURPOSE
TRANSFORMER CONNECTORS
TYPE L-M
600V
DUAL-RATED CONNECTORS
FOR ALUMINUM OR COPPER CONDUCTORS
• Clear Plated for low-contact resistance. • Designed for installation on standard two
• Fully tested to ANSI C119.4 for Class and four-hole spades.
‘A’ connectors. • All mounting holes 1.75” on center line.
• Supplied with aluminum radial tipped set-screws. • For installation, CMC® recommends
• Connector fabricated from 6061-T6 the use of a 9” insulated Allen wrench.
aluminum alloy for conductivity and strength. • A torque wrnch should be used to ensure
the proper torque is achieved.
Cond. H W L D L1M2
No. of
Catalog No. of Range Dimensions - Inches
Mtg.
Number Cond. AWG
Holes Dimensions - (mm)
MM2
350-12 1.38 1.25 4.25 0.56
L1M2-350I 2 1
185-16 35.05 31.75 114.30 14.22
L2M4
350-12 1.38 3.00 4.25 0.56
L2M4-350I 4 2
185-16 35.05 76.20 114.30 14.22
350-12 1.38 3.00 4.25 0.56
L3M4-350I 4 3
185-16 35.05 76.20 114.30 14.22
350-12 1.38 4.75 4.25 0.56
L4M6-350I 6 4
185-16 35.05 120.65 114.30 14.22
350-12 1.38 6.50 4.25 0.56
L6M8-350I 8 6 L3M4
185-16 35.05 165.10 114.30 14.22
350-12 1.38 8.25 4.25 0.56
L8M10-350I 10 8
185-16 35.05 209.55 114.30 14.22
500-10 1.56 1.25 4.63 0.56
L1M2-500I 2 1
240-25 39.62 31.75 117.60 14.22
500-10 1.56 3.00 4.63 0.56
L2M4-500I 4 2
240-25 39.62 76.20 117.60 14.22
L8M10
500-10 1.56 3.62 4.63 0.56
L3M4-500I 4 3
240-25 39.62 91.95 117.60 14.22
500-10 1.56 4.87 4.63 0.56
L4M6-500I 6 4
240-25 39.62 123.70 117.60 14.22
500-10 1.56 6.75 4.63 0.56
L6M8-500I 8 6
240-25 39.62 171.45 117.60 14.22
500-10 1.56 8.75 4.63 0.56
L8M10-500I 10 8
240-25 39.62 222.25 117.60 14.22
Note: For omission of CO-OX oxide inhibitor, delete suffix - “I”.
E- Transformer Connectors
-25- 2/15
HEAVY-DUTY
TRANSFORMER CONNECTORS
TYPE L-D
UNI-JOINT
DUAL-RATED CONNECTORS 600V
FOR ALUMINUM OR COPPER CONDUCTORS
• Clear Plated for low-contact resistance. • Designed for installation on standard two
• Fully tested to ANSI C119.4 for Class and four-hole spades.
‘A’ connectors. • All mounting holes 1.75” on center line.
• Supplied with aluminum radial tipped set-screws. • For installation, CMC® recommends the
• Connector fabricated from 6061-T6 aluminum use of a 9” insulated Allen wrench.
alloy for conductivity and strength. • A torque wrnch should be used to ensure the
proper torque is achieved.
No. of Cond. H W L D
Catalog No. of
Mtg. Range
Number Cond. Dimensions - Inches
Holes AWG
L1D2-350I 2 1 350-12 1.50 1.00 5.31 0.56
L2D4-350I 4 2 350-12 1.50 2.88 5.31 0.56
L3D4-350I 4 3 350-12 1.50 3.00 5.31 0.56
L1D2-500I 2 1 500-10 1.50 1.25 5.50 0.56
L2D4-500I 4 2 500-10 1.50 2.88 5.50 0.56
L3D4-500I 4 3 500-10 1.50 3.50 5.50 0.56
L1D2-750I 2 1 750-2 1.88 1.50 6.19 0.56
L2D4-750I 4 2 750-2 1.88 3.00 6.19 0.56
L3D4-750I 4 3 750-2 1.88 4.00 6.19 0.56
L1D2-1000I 2 1 1000-350 1.88 1.56 6.19 0.56
L2D4-1000I 4 2 1000-350 1.88 3.25 6.19 0.56
L3D4-1000I 4 3 1000-350 1.88 4.92 6.19 0.56
Note: For omission of co-ox oxide inhibitor, delete suffix “I”.
L2D4
L1D2
L3D4
E- Transformer Connectors
-26- 2/15
HEAVY-DUTY
TRANSFORMER CONNECTORS
No. of Cond. H W L D
Catalog No. of
Mtg. Range Cover L4D6
Number Cond. Dimensions - Inches
Holes AWG
W H
D
D
E- Transformer Connectors
-27- 2/15
TRANSFORMER CONNECTORS
TYPE ABV 600V
General Purpose Transformer Connectors
DUAL-RATED CONNECTORS
Material: Aluminum
FOR ALUMINUM OR COPPER CONDUCTORS
• Compact design relieves cantilever stress.
• Clear Plated for low contact resistance.
• Fully tested to ANSI C119.4 for Class ‘A’ connectors.
• Fabricated from 6061-T6 aluminum alloy for conductivity and strength.
• Supplied with aluminum radial tipped set-screws.
PATENTED
Cond. Range Number of
Figure No. of
Catalog Number Mounting W L H
No. Cond. AWG - kcmil Holes
6ABV-500 1 6 500-2 2 3.75 4.90 3.00
Fig. 1 Fig. 2
.406
.531
1.75
1.75
W
L 1.75
Fig. 3 1.75
.562
E- Transformer Connectors
-28- 7/16
2/15
TRANSFORMER CONNECTORS
TYPE ABV-M
General Purpose Transformer Connectors 600V
DUAL-RATED CONNECTORS
FOR ALUMINUM OR COPPER CONDUCTORS
• Compact design relieves cantilever stress.
• Clear Plated for low contact resistance.
• Fully tested to ANSI C119.4 for Class “A” connectors.
• Designed for installation on standard NEMA bolt holes.
• Fabricated from 6061-T6 aluminum alloy for conductivity and strength.
• Supplied with aluminum radial-tipped set-screws.
PATENTED
No. L W
No. of Cond. Range
Catalog Number Fig. No. Mounting
Cond. AWG - kcmil Dimensions - Inches
Holes
2ABV-350MS 1 2 350-12 1 3.25 1.00
4ABV-350MS 1 4 350 - 12 1 3.25 1.85
6ABV-350MS 1 6 350 - 12 2 3.25 3.00
8ABV-350MS 1 8 350 - 12 3 3.25 4.75
10ABV-350MS 1 10 350 - 12 3 3.25 4.75
12ABV-350MS 1 12 350 - 12 4 3.25 6.50
2ABV-350M 2 2 350 - 12 2 5.00 1.00
4ABV-350M 2 4 350 - 12 2 5.00 1.85
6ABV-350M 2 6 350 - 12 4 5.00 3.00
8ABV-350M 2 8 350 - 12 6 5.00 4.75
10ABV-350M 2 10 350 - 12 6 5.00 4.75
12ABV-350M 2 12 350 - 12 8 5.00 6.50
2ABV-750M 2 2 750 - 2 2 6.37 1.50
4ABV-750M 2 4 750 - 2 4 6.37 3.00
6ABV-750M 2 6 750 - 2 6 6.37 4.75
8ABV-750M 2 8 750 - 2 6 6.37 5.37
10ABV-750M 2 10 750 - 2 8 6.37 6.81
12ABV-750M 2 12 750 - 2 10 6.37 8.25
Note: For co-ox oxide inhibitor, add suffix “I”.
Fig. 1 Fig. 2
E- Transformer Connectors
-29- 2/15
HEAVY-DUTY
TRANSFORMER CONNECTORS
DUAL-RATED CONNECTORS
FOR ALUMINUM OR COPPER CONDUCTORS
• Connector fabricated from 6061-T6 aluminum alloy for conductivity and strength.
• Clear plated for low-contact resistance.
• Supplied with aluminum radial-tipped set-screws.
• All mounting holes 1.75” on center line.
• For installation, CMC® recommends the use of a 9” insulated Allen wrench.
• A torque wrnch should be used to ensure the proper torque is achieved.
E- Transformer Connectors
1/15
-30- 2/15
HEAVY DUTY
LAY-IN CONNECTORS
E- Transformer Connectors
-31- 2/15
STUD MOUNT
TRANSFORMER CONNECTORS
TYPE UATS
For Threaded Secondary Studs 600V
• Universal adapter for use on 1” or 5/8” studs.
• Connector fabricated from 6061-T6 aluminum alloy for conductivity and strength.
• Fully assembled with stainless steel hardware and 1/2 - 13 studs.
• Accepts standard side form lugs.
• Fully tested to ANSI C119.4 for Class ‘A’ connectors.
• Can be ordered with or without hardware (belleville washers, flat washers, silicon bronze nuts).
• Allows installation or removal of conductor without affecting other energized conductors.
• SAFETY - Can be worked live with one hand.
Fig. 1
Fig. 2
E- Transformer Connectors
-32- 2/15
1/14
TRANSFORMER STUD
RELOCATION BAR
TYPE NTS
Transformer Stud Drop-Down Connector
FOR INSTALLATION ON EQUIPMENT 600V
SECONDARY PADMOUNT TRANSFORMERS.
H W
L
S
E- Transformer Connectors
-33- 2/15
ALUMINUM PAD
EXTENSIONS
TYPE FPX-2S
• Adapters provide the means to connect virtually any required number of conductors to a
transformer using NEMA two-hole terminal lugs. Stacking type terminal lugs can also be used
where more conductor connections are required than available mounting positions.
• Slotted rail allows for adjustable height for easy transformer reconnection/replacement.
• Meets the performance requirements of ANSI C119.4.
• Tin plated.
• Other pad extensions are available. Consult factory.
FPX-6-2S-50T
FPX-12-2S-50T
L
1050A
H
H
E- Transformer Connectors
-34- 10/16
2/15
COPPER PAD
EXTENSIONS
TYPE CFPX-2S
• Adapters provide the means to connect virtually any required number of conductors to a
transformer using NEMA two-hole terminal lugs. Stacking type terminal lugs can also be used
where more conductor connections are required than available mounting positions.
• Slotted rail allows for adjustable height for easy transformer reconnection/replacement.
• Meets the performance requirements of ANSI C119.4.
• Tin plated.
• Other pad extensions are available. Consult factory.
H L S Pad Width Hole
Catalog Number Material:
Dimensions - Inches Diameter Extruded - C110 Copper
L CFPX-12-2S-50T
1500A
E- Transformer Connectors
-35- 10/16