Professional Documents
Culture Documents
4, November 1990
The results of an IEEE working group's study of the Remanent flux, or remanence, results from the
gapped core current transformer (ct) are presented. interruption of the primary current of a ct when the
The characteristics and performance of ct having small core flux is not zero as can happen during severely
gaps are discussed. The effect of remanent flux in ct offset faults. Careless use of dc in testing ct
cores on ct performance, and of small gaps to control circuits or in determining ct polarity also may be
remanence for improved transient performance of ct are responsible for remanence. Remanence is defined as
also discussed. Advantages and disadvantages of the magnetic flux density that remains in a magnetic
gapped core ct are enumerated. Proposed performance circuit after the removal of an applied magnetomotive
requirements for gapped core ct are presented and a force, it should not be confused with residual flux
method of specifying gapped core ct to produce the density, which is the magnetic flux density at which
required performance for protective relaying the magnetizing force is zero when the core material
application of such ct is proposed. A short is in a symmetrically cyclically magnetized
description of terms are included for clarity of the ~0ndition.l~ Depending on the type of steel, the
discussion. remanent flux may be as high as 90 percent of the
saturation flux.6 The effects of remanence on the
Keywords: Protective relaying; instrument performance of protective relays should be fully
transformers. understood and the need for its reduction
stressed.2, lo
INTRODUCTION
During normal load, the core flux may contain a
Current transformers in general use today are commonly remanent component, its magnitude being dependent on
manufactured with continuous steel cores having no the initial trapped flux and the magnitude of flux
intentional gaps. High power system fault current swing. Remanent flux does not gradually disappear,
levels have amplified problems in the response and but remains constant once the appropriate equilibrium
performance characteristics of conventional ct partly condition has been attained. The percentage decrease
because of remanence. A special concern is that due in the remanent flux for a given alternating flux
to remanence the ct may saturate before the high-speed depends upon the core material and the minor B-H loop
protective relaying have a chance to operate. In around which normal operation occurs. It is not,
order to overcome or minimize these problems, current therefore, possible to precisely predict the remanent
transformers which have various sized intentional gaps flux level following a fault. In metering current
in their steel cores are being manufactured. Such transformers, the normal full load flux approaches the
gaps may be filled with non-magnetic material and not saturation level with the result that remanent flux is
necessarily air. Gaps in ct cores limit the remanence reduced to an insignificant level in a very short time
to acceptable levels. The physical and electrical following supply restoration. Remanence in relaying
characteristics of gapped core ct have not been accuracy class ct can therefore remain for an infinite
standardized nor have the results of studies of the period.
performance capabilities and characteristics been
widely published. Once remanent flux is established in the core of a
transformer, it will take special effort to remove. A
The intent of this document is to present the voltage in excess of saturation voltage must be
collective efforts of an IEEE working group formed to applied and gradually reduced to zero in order to
study the characteristics of current transformers reduce the remanent flux to less than 10 percent of
having small gaps in their core, and to propose saturation flux. Such high voltages are not
methods of classifying these ct and of determining ordinarily induced in the winding of current
their performance. This document also furnishes, to transformers under normal operating conditions,
both the user and the manufacturer, a method for because the voltage across the ct winding is limited
specifying gapped core ct. Gaps of 0.0001 to 0.0003 by the burden connected to the ct. The remanent flux,
per unit of mean length of magnetic path will be then, may remain in the ct core until the next
considered. occurrence of a high magnitude fault current or other
transient condition which could provide the necessary
flux to effect demagnetization. Demagnitization by
*Present Members of the PSRC Working Group are: this means is rather unlikely since one would expect
B. Bozoki, Chairman, H.J. Calhoun, C.M. Gadsden, the fault-clearing to occur at, or near, a current
K.J. Khunkhun, W.C. Kotheimer, R.J. Moran. Former zero at which time the ct core will be near maximum
Members were: J. Berdy, F.B. Hunt, E.C. Wentz, excitation and will in all likelihood continue to have
C.F. Burke, J.M. Vanderleck, M . Rosen, J.W. Walton. excessive remanent flux. A transient condition which
produced a flux opposite in polarity to the remanent
flux could possibly reduce the remanence to a more
acceptable level, also an unlikely occurrence.
LH
L 2 . Loop with Gap
as ammeters, wattmeters and current transducers, in accuracy in zero crossing time is desired.
protective relaying circuits is fairly common, the
performance of the ct under steady state conditions 4. Higher magnetizing current will be supplied to the
merits consideration only in particular situations. secondary of a ct, whose primary is
The effect of the gaps on performance is some loss of open-circuited, by a parallel ct. This current
accuracy under steady state conditions. A gapped core may cause the overcurrent relay of a breaker
ct provides a secondary current substantially failure scheme to indicate that a circuit breaker
representative of the primary current, both in ratio is still closed, or may produce a false operation
and phase angle, up to the normal rating of the ct. of a differential relay during an external fault.
This latter case is an argument for using a
In limited applications, such as on large generators, differential restraint winding on each ct and not
gapped core ct can be used for metering purposes. connecting ct in parallel to supply one restraint
Excessive secondary burdens may cause steady state winding .lo
performance which is unacceptable in very sensitive
differential relay circuits or other current balancing 5. Current transformers with core gaps, whether
schemes. filled with air or nonmagnetic material, could be
mechanically weaker and more expensive than those
ADVANTAGES AND DISADVANTAGES OF GAPPED CORES with closed cores.
The study of characteristics and performance of gapped APPLICATION CONSIDERATIONS
ct can perhaps be best done by enumeration of their
advantages and disadvantages. The use of gapped core ct may require additional
application considerations:
There are several significant advantages of gapped ct
over conventional ct, as follows: 1. Ideally, gapped ct should not be mixed with
conventional ct in differential circuits.
1. Reduction in the remanent flux, or remanence, However, such situation might occur in a generator
results in improved transient performance of the unit differential relay scheme in which gapped ct
ct .lo on the generator neutral bushings are used while
the unit high voltage breakers may have continuous
2. Reduction of the time constant of the ct permits core ct. Similarly a breaker with gapped core ct
use of a smaller core cross section and, might be added in a bus differential scheme which
consequently, smaller physical size.3 previously involved only continuous core ct. In
this case it is advisable to confirm that the
3. Less core oversizing is required to avoid stability of the differential relays are not
saturation for a ct with gaps than for a closed affected.
core ct for the same primary current.
2. Replacement of ct or interchanging ct must be done
4. The effect of burden power factor on oversizing to with caution because of the large effect the gap
prevent saturation is less for gapped cores than construction has on the electrical
for closed cores.( characteristics. Operation of gapped ct in
parallel may produce more errors in the output
5. The open circuit voltage across the secondary than with closed core transformers even though
terminals produced by a sinusoidal primary current remanence has been substantially reduced.
is smaller for a gapped ct.3
3. The physical position of the gap or gaps relative
The disadvantages of gaped ct are as follows: to the return conductor, or close proximity to
other phases can affect the accuracy during fault
1. The magnetizing current is higher, resulting in current conditions.
greater ratio and phase angle error. Increasing
the core area partially offsets this effect, but 4. The gaps in the core may increase the secondary
economics and physical size limitations impose leakage reactance and may adversely affect the
practical limits to core area increases.8 settings of high impedance differential relays.8
2. When the core flux decays to its final value after 5. The size and shape of the gaps may change over a
fault interruption, the energy stored in the period of time without detection, if periodic
magnetic circuit must be dissipated in the excitation tests are not made.
secondary circuit and results in a unidirectional
discharge of long duration (approximately 1 sec). PROPOSED PERFORMANCE REQUIREMENTS
Since the change in flux required to reach the
remanence level is greater for a gapped ct, the In order to provide a means of comparison of the
discharge voltage is higher. The time of decay performance characteristics of gapped core ct, it is
may be so long that high-speed reclosing can take essential that practical evaluation of the finished
place before the remanence level is reached. product can be established. The criteria proposed for
use in evaluating the performance of gapped core ct
Another risk associated with this phenomenon is are listed following:
the decay current following fault interruption may
delay a current relay from dropping out to 1. Measurement of the secondary voltage and exciting
indicate that the circuit breaker is open and thus current to establish the upper part of the
cause a false operation of the breaker failure excitation characteristics of a ct. For example,
protection .8,10*11 the exciting current of a CEO0 accuracy class ct
must not exceed 10 A when producing 800 V at the
3. The significant increase in the magnetizing secondary terminals for a burden of 8 ohms.
current falsifies the secondary current,
especially the dc component. The secondary 2. Measurement of the kneepoint. For closed core of
current error is serious if a resultant current is the kneepoint is defined as the 4 5 " target point
generated by paralleling two or more ct, or if on the excitation curve, as shown in Figure 3 .
1735
For gapped ct this dtfinition was changed to a 30° Routine excitation tests on Every unit should be
point because it may not be possible to find a 45O made to verify the excitation curves provided by
tangent point on the gapped ct's excitation the manufacturer, with sufficient points measured
curve. The inability to draw a 30° tangent to the to provide, at a minimum, the kneepoint and the
excitation curve constitutes noncompliance to the general shape of the curve below and above the
proposed limitations on excitation characteristics. kneepoint.
In the next edition of ANSI C57.13 an additional Routine remanence test should be conducted on
relaying rating will be introduced, designated as every unit. Methods have been described in the
'K' classification. The 'K' rating is the same as literaturelo f o r the field measurement of ct
the 'C' rating except that the kneepoint voltage remanence, which can be used to determine
is not to be less than 70% of the accuracy class conformance to specification.
secondary voltage. For example, a K800 ct will
have a kneepoint at 0.7 x 800 V or higher. In all
other respects the class K ct is equal to, or
better than, a class C ct. The class K ct will be
preferred for protective relaying applications.
A",.
CONCLUSIONS
distinguished from remanence by the symmetrically 10. 'Transient Response of Current Transformers',
cyclic requirement.14 Power System Relaying Committee Report 76-CH1130-4
PWR, IEEE Special Publication. As summary report
Saturation and discussion, IEEE Trans. Power Apparatus and
-
Syst., PAS 96, Nov/Dec 1977, pp. 1809-1814.
The state of a ferromaanetic substance placed in a
field so strong that the intensity of magnetization 11. N. E. Korponay, 'Non-gapped Cores, Antiremanence
becomes independent of the field: the substance is Gapped
._ Cores or Linear Cores for Current
then said to be saturated. Transformers,. IEEE Transactions on Power
Apparatus and Systems, March/April 1978 pp. 569-74.
That value of flux below which the corresponding
exciting current can be considered negligible.9 The 12. ANSI/IEEE Standard C57.13-1978, "Requirements for
effective saturation or maximum flux density in Instrument Transformers'.
silicon iron alloys is about 2 T (20,000 Gauss).
13. L. J. Powell, .Current Transformer Burden and
The maximum intrinsic value of induction possible in a Saturation,' IEEE Transactions on Industry
material. Note: This term is often used for the Application, Vol. IA-15 13, May/June, 1979,
maximum value of induction at a stated high value of pp. 294-302.
field strength where further increase in intrinsic
magnetization with increasing field strength is 14. IEEE Standard Dictionary of Electrical and
negligible.l4 Electronics Terms, ANSI/IEEE Std 100-1988.
Saturation Flux
REFERENCES
Following, are some comments on the disadvantages 1. B. C. Hydro has routinely mixed gapped core cts
cited. The comment numbers refer to the disadvantage with solid core cts in differential circuits.
numbers in the Paper. W and E W cts at circuit breaker positions are
normally gapped, transformer bushing cts and
1. In practical terms the increased ratio and phase lower voltages are ungapped so transformer
angle error caused by small gaps is usually differentials routinely include both. We find
negligible except for very low ratio cts. the mismatch no more severe than that for the
Fig. 1 of this discussion shows the calculated much different W and LV solid core cts normally
comparative performances of two of the cts with found in such a differential circuit. Many
the approximate excitation characteristics of year's of experience with numerous installations
Fig. 3 of the Paper. The difference in perfor- has not produced identifiable problems.
mance of the two cts cannot be easily seen until
after saturation, because the difference in 4. In practice small gaps have not been found to
magnetizing currents up to the knee point is significantly affect leakage reactance. This
less than 1% of the fault current. has been demonstrated by several direct
transient performance tests which show that
s actual performance corresponds well with perfor-
mance predicted from the excitation curves.
B. C. Hydro routinely neglects leakage reactance
when setting high impedance bus differential
relays with no known problems so far.
There is no doubt about the stated need for proposals
to specify gapped ct performance requirements. How-
ever, neither the new "K" accuracy class nor the
5
.o existing "C" accuracy specifies the transient perfor-
mance. It would be better to adopt the transient
specification terminology of IEC in their classes
TPS, TPX, TPY and TPZ. This has already been done
successfully for Canadian Standard CSA CAN3-C13-M83
(Ref l ) , which the discussors recommend for consi-
deration. Section 8 of that standard covers cts for
which transient performance is important, including,
0 5 , O , ~ m x ~ ~ 4 4 4 5 ~
TI* I..)
but not limited to, gapped cts. B. C. Hydro has
purchased cts in accordance with this standard since
FIGURE I - COMPARATIVE PERFORMANCE OF SOLI0 h QAPPEO CORE CTS its publication in 1983 with little difficulty.
2. The fact that the flux in a gapped ct may not Could the authors please explain the need for the
have decayed to its steady state remanence level proposed routine remanence tests? It is appreciated
before high speed reclosing takes place, is not that this should be a type test, but remanence is
a disadvantage. The flux in the gapped ct will only a function of the core material (hysterisis) and
still decay to a lower level than in a non- excitation characteristic. Since the excitation
gapped ct. Incomplete decay of flux can be characteristic is proposed to be a routine test (and
catered for by specifying the reclosing duty of indeed, it should be), and the core material perfor-
the ct, using the transient performance specifi- mance is determined by type test, routine remanence
cation of Ref. 1 of this discussion. measurements seem superfluous.
~
1739
It should be noted that there is an additional impor- 2. There may be advantages to using a different core
tant reason to try to reduce the premature ct satura- material having inherently lower remanence, such as
tion caused by remanence. This is the need for an amorphous metal (metallic glass) or hot rolled
protection systems to be secure during external silicon steel. There viability as alternatives to
faults. This is particularly important when gapped GOSS cores should be considered.
reclosing onto a permanent fault with a breaker which
is part of a ring bus. In ring bus arrangements the 3. Should caution not be exercised when applying
adjacent line protection is also a bus protection gapped-core ct for metering purposes? Based on our
system for the line terminal. During reclosing onto limited accuracy measurements on minimally-gapped
a permanent fault, all fault current flows through (0.0001-0.0003 pu length) core protective ct, we
one ct set. If there was remanence in this ct, have found that their ratio error and phase angle
(possibly due to the initial fault) its performance are significantly different than their metering
could be degraded enough to cause misoperation of the councerparts, with the same metering burden
adjacent line protection zone. connected. Also, their accuracy varied
significantly depending upon the location of the gap
In the protection business, good ct transient perfor- in relation to the return conductor.
mance is the name of the game and cts with anti-
remanence gaps (Type TPY) offer more advantages than 4. From what we have observed, there is a wider
disadvantages. Ct saturation problems will manifest variation in the excitation curves for gapped core
themselves for heavy close-in faults, the worst case. ct. This would suggest that wider acceptance
For this reason, there should be further considera- criteria may be advisable for gapped-core ct than
tion of existing IEC terminology and Ref. 1 which has is allowed in the currentANSI/IEEE C57.13-1978 and
been tested and found adequate as a means of defining Canadian Standard CAN3-C13-M83. These standards
et transient performance requirements. As an experi- only allow for +25% variation in the excitation
enced user of gapped core cts, B. C. Hydro is firmly current below the kneepoint.
convinced that the advantage of improved transient
performance outweighs the disadvantages. 5. With regard to the additional specification on
testing for remanent flux, some elaboration on the
REFERENCES subject of driving a gapped-core ct into saturation
may be helpful. With permeability on the order
1. CSA Standard CAN3-Cl3-ME3, Instrument 3,000 (11 mil Allegheny M4 @ 500 At/m) a gap
Transformers. equivalent to 0.00033 pu adds as much additional
reluctance as the steel itself provides. For
example, if 500 At/m were required to fully saturate
Manuscript received July 12, 1989. a given closed core, then twice as much, or 1000
At/m would be required to fully saturate the same
core with a 0.00033 pu gap. Similarly, 2000 At/m
would be required to fully saturate the same core
DISCUSSION with a 0.001 pu gap.
By: P.W. Labaj 6. While the committee's reference 6 appears to be a
Ontario Hydro Research Division fairly simple and straightforward means to measure
Toronto, Ontario, Canada flux excursion and thereby remanence, there may be
some serious drawbacks in its implementation; such
as applied voltages exceeding the ct insulation
strength, suitable kVA rated supply with low source
impedance, and selection of suitable diodes. We
The committee members are to be commended for producing have found up to this point in time, that dc methods
a paper on a subject that is long overdue. The paper, as those discussed in references 5 and 10 and
while full of useful information, lacks clarity in some Canadian Standard CAN3-C13-M83 can be universally
parts and in the terminology section, more use could be applied and are quite reliable.
made of existing instrument transformer standards along
with the IEEE and IEC dictionaries. 7. The definition given for saturation flux appears to
be inconsistdntwithmany standards; can you explain
The discusser has several points to raise with regard why this definition was chosen? A definition of
to this committee report. saturation flux arbitrarily determined as 50%
greater than the flux at the kneepoint might be more
appropriate than 10%. The 50% figure appears to be
1. With regard to metering ct operating at a level a reasonably obtainable flux that would still ensure
approaching saturation under normal full load, this that a ct core was fully saturated for all practical
has never been our experience, and in fact the purposes.
normal operating flux is usually quite low. An
illustration of this fact is the accuracy curve
which normally takes the following form: Manuscript received July 17, 1989.