You are on page 1of 9

1732 IEEE Transactionson Power Delivery,Vol. 5, No.

4, November 1990

GAPPED CORE CURRENT TRANSFORMER CHARACTERISTICS AND PERFORMANCE

An IEEE Power System Relay Committee Report*

ABSTRACT REMANENCE FLUX

The results of an IEEE working group's study of the Remanent flux, or remanence, results from the
gapped core current transformer (ct) are presented. interruption of the primary current of a ct when the
The characteristics and performance of ct having small core flux is not zero as can happen during severely
gaps are discussed. The effect of remanent flux in ct offset faults. Careless use of dc in testing ct
cores on ct performance, and of small gaps to control circuits or in determining ct polarity also may be
remanence for improved transient performance of ct are responsible for remanence. Remanence is defined as
also discussed. Advantages and disadvantages of the magnetic flux density that remains in a magnetic
gapped core ct are enumerated. Proposed performance circuit after the removal of an applied magnetomotive
requirements for gapped core ct are presented and a force, it should not be confused with residual flux
method of specifying gapped core ct to produce the density, which is the magnetic flux density at which
required performance for protective relaying the magnetizing force is zero when the core material
application of such ct is proposed. A short is in a symmetrically cyclically magnetized
description of terms are included for clarity of the ~0ndition.l~ Depending on the type of steel, the
discussion. remanent flux may be as high as 90 percent of the
saturation flux.6 The effects of remanence on the
Keywords: Protective relaying; instrument performance of protective relays should be fully
transformers. understood and the need for its reduction
stressed.2, lo
INTRODUCTION
During normal load, the core flux may contain a
Current transformers in general use today are commonly remanent component, its magnitude being dependent on
manufactured with continuous steel cores having no the initial trapped flux and the magnitude of flux
intentional gaps. High power system fault current swing. Remanent flux does not gradually disappear,
levels have amplified problems in the response and but remains constant once the appropriate equilibrium
performance characteristics of conventional ct partly condition has been attained. The percentage decrease
because of remanence. A special concern is that due in the remanent flux for a given alternating flux
to remanence the ct may saturate before the high-speed depends upon the core material and the minor B-H loop
protective relaying have a chance to operate. In around which normal operation occurs. It is not,
order to overcome or minimize these problems, current therefore, possible to precisely predict the remanent
transformers which have various sized intentional gaps flux level following a fault. In metering current
in their steel cores are being manufactured. Such transformers, the normal full load flux approaches the
gaps may be filled with non-magnetic material and not saturation level with the result that remanent flux is
necessarily air. Gaps in ct cores limit the remanence reduced to an insignificant level in a very short time
to acceptable levels. The physical and electrical following supply restoration. Remanence in relaying
characteristics of gapped core ct have not been accuracy class ct can therefore remain for an infinite
standardized nor have the results of studies of the period.
performance capabilities and characteristics been
widely published. Once remanent flux is established in the core of a
transformer, it will take special effort to remove. A
The intent of this document is to present the voltage in excess of saturation voltage must be
collective efforts of an IEEE working group formed to applied and gradually reduced to zero in order to
study the characteristics of current transformers reduce the remanent flux to less than 10 percent of
having small gaps in their core, and to propose saturation flux. Such high voltages are not
methods of classifying these ct and of determining ordinarily induced in the winding of current
their performance. This document also furnishes, to transformers under normal operating conditions,
both the user and the manufacturer, a method for because the voltage across the ct winding is limited
specifying gapped core ct. Gaps of 0.0001 to 0.0003 by the burden connected to the ct. The remanent flux,
per unit of mean length of magnetic path will be then, may remain in the ct core until the next
considered. occurrence of a high magnitude fault current or other
transient condition which could provide the necessary
flux to effect demagnetization. Demagnitization by
*Present Members of the PSRC Working Group are: this means is rather unlikely since one would expect
B. Bozoki, Chairman, H.J. Calhoun, C.M. Gadsden, the fault-clearing to occur at, or near, a current
K.J. Khunkhun, W.C. Kotheimer, R.J. Moran. Former zero at which time the ct core will be near maximum
Members were: J. Berdy, F.B. Hunt, E.C. Wentz, excitation and will in all likelihood continue to have
C.F. Burke, J.M. Vanderleck, M . Rosen, J.W. Walton. excessive remanent flux. A transient condition which
produced a flux opposite in polarity to the remanent
flux could possibly reduce the remanence to a more
acceptable level, also an unlikely occurrence.

Under operating conditions, remanent flux can be left


89 SM 802-0 PWRD A paper recommended and approved in the core when the primary current is interrupted
by the IEEE Power System Relaying Committee of the IEEE while the flux density in the core of the transformer
Power Engineering Society for presentation at the IEEE/ is high. The flux in the core depends on many
PES 1989 Summer Meeting, Long Beach, California, July 9 factors, the most important of which are the magnitude
- 14, 1989. Manuscript submitted March 16, 1989; of the primary current, the magnitude of dc offset
made available for printing May 19, 1989. transient, and the impedance of the secondary circuit.

0885-8977/90/1100-1732$01.00 Q 1990 IEEE


1733

Remanent flux in a ct contributes to distortion in the


secondary current, particularly in the first few 1. Loop for Iron
cycles after the inception of a fault. The distortion B
of the secondary current is greatly influenced by the
amount of remanent flux as can be seen in Figure 1, 4 ,Air Gap Line
which is reproduced from reference 5. The distortion
can have an adverse effect on the operation of the
high-speed relays.

LH
L 2 . Loop with Gap

Figure 2. How air gap reduces remnant flux


(a) zero T-emnent flux
-200 I 1
1 I 1 EFFECTS OF GAPS ON TRANSIENT PERFORMANCE

Some loss in the transformation of the dc transient in


fault current will result in gapped core ct, but this
loss can be minimized by appropriate sizing the
gap(s). When a good replica of the dc transient in
the primary of a ct is not needed in the secondary
relaying circuits, then the time-to-saturation can be
substantially increased by the embodiment of larger
gaps in the core. Increasing the gaps reduces the ct
shunt impedance and magnetizing time constant.
(b) " e n t flux = 50%of saturation flu> Although the loss in the transformation of the dc
-200 I
transient may be quite large, the ct can be designed
+ma 1
I
- I
PRIMARY
1
to conform to a standard relaying accuracy class. It
should be recognized that because of the higher
exciting currents of gapped cores at current levels
below 20 times rated, errors approaching 10% in ratio
and 3 O in phase angle may also occur over an operating
range from one to 20 times rated current.

Since gapped cores cause higher exciting current, the


magnified effects of idle ct should be considered.
For example, bus differential relays are desensitized
by ct on bus connections not contributing current to
(c) "nt flux = 75% of saturation flu: an internal fault. Similarly, the unfaulted phase(s)
-200
0 I 2 3 4 exciting current desensitizes the ground relays.
CYCLES
Undesired breaker failure relay operation can occur
where two or more gapped core ct are paralleled, such
Figure 1 -
Distortion of secondary fault current due as on a ring bus.
to remanence for a ct operating under transient fault
conditions. At the instant of fault clearing, the flux in the core
can be at saturation level. While this flux decays to
CONTROLLING REMANENCE IN CURRENT TRANSFORMERS the remanence level a secondary current will flow.
With a closed core there is relatively little flux
The remanent flux in the core can be effectively change to sustain a secondary current after the
reduced by inserting gaps in the magnetic circuit of primary circuit opened, because the remanent flux
the core. The amount of remanent flux can be limited value is not much lower than the value at time of
to a low value, such as 10% of the saturation flux, by fault clearing. With the gapped core ct the flux is
addition of quite small gaps in the core. The effect heading for a much lower remanence value so the
of adding gaps in the iron core of a ct is shown in secondary current is sustained by a larger flux
Figure 2 . Gaps in the order of 0.0001 - 0.0003 per change, consequently its decay will take a longer
unit of mean length of magnetic path will reduce the time .lo
remanent flux to acceptably low levels. The actual
size of gaps depend on the physical dimensions of the EFFECTS OF GAPS ON STEADY STATE PERFORMANCE
ct core and the magnetic properties of the core
material. The reduction of remanence in the core It is assumed that steady state conditions in a power
provides a proportional increase in the amount of the system involve normal current levels associated with
core available for flux excursions, thus improving the loading and power flows within the system. For these
transient performance of the ct. conditions, the ct used in the system would be
operating at current levels well below those which
might produce saturation in the ct cores. In general,
the steady state performance of gapped ct is of
greater concern for instrumentation and measuring
devices than for protective relaying. Since the
practice of inserting various measuring devices, such
1734

as ammeters, wattmeters and current transducers, in accuracy in zero crossing time is desired.
protective relaying circuits is fairly common, the
performance of the ct under steady state conditions 4. Higher magnetizing current will be supplied to the
merits consideration only in particular situations. secondary of a ct, whose primary is
The effect of the gaps on performance is some loss of open-circuited, by a parallel ct. This current
accuracy under steady state conditions. A gapped core may cause the overcurrent relay of a breaker
ct provides a secondary current substantially failure scheme to indicate that a circuit breaker
representative of the primary current, both in ratio is still closed, or may produce a false operation
and phase angle, up to the normal rating of the ct. of a differential relay during an external fault.
This latter case is an argument for using a
In limited applications, such as on large generators, differential restraint winding on each ct and not
gapped core ct can be used for metering purposes. connecting ct in parallel to supply one restraint
Excessive secondary burdens may cause steady state winding .lo
performance which is unacceptable in very sensitive
differential relay circuits or other current balancing 5. Current transformers with core gaps, whether
schemes. filled with air or nonmagnetic material, could be
mechanically weaker and more expensive than those
ADVANTAGES AND DISADVANTAGES OF GAPPED CORES with closed cores.
The study of characteristics and performance of gapped APPLICATION CONSIDERATIONS
ct can perhaps be best done by enumeration of their
advantages and disadvantages. The use of gapped core ct may require additional
application considerations:
There are several significant advantages of gapped ct
over conventional ct, as follows: 1. Ideally, gapped ct should not be mixed with
conventional ct in differential circuits.
1. Reduction in the remanent flux, or remanence, However, such situation might occur in a generator
results in improved transient performance of the unit differential relay scheme in which gapped ct
ct .lo on the generator neutral bushings are used while
the unit high voltage breakers may have continuous
2. Reduction of the time constant of the ct permits core ct. Similarly a breaker with gapped core ct
use of a smaller core cross section and, might be added in a bus differential scheme which
consequently, smaller physical size.3 previously involved only continuous core ct. In
this case it is advisable to confirm that the
3. Less core oversizing is required to avoid stability of the differential relays are not
saturation for a ct with gaps than for a closed affected.
core ct for the same primary current.
2. Replacement of ct or interchanging ct must be done
4. The effect of burden power factor on oversizing to with caution because of the large effect the gap
prevent saturation is less for gapped cores than construction has on the electrical
for closed cores.( characteristics. Operation of gapped ct in
parallel may produce more errors in the output
5. The open circuit voltage across the secondary than with closed core transformers even though
terminals produced by a sinusoidal primary current remanence has been substantially reduced.
is smaller for a gapped ct.3
3. The physical position of the gap or gaps relative
The disadvantages of gaped ct are as follows: to the return conductor, or close proximity to
other phases can affect the accuracy during fault
1. The magnetizing current is higher, resulting in current conditions.
greater ratio and phase angle error. Increasing
the core area partially offsets this effect, but 4. The gaps in the core may increase the secondary
economics and physical size limitations impose leakage reactance and may adversely affect the
practical limits to core area increases.8 settings of high impedance differential relays.8

2. When the core flux decays to its final value after 5. The size and shape of the gaps may change over a
fault interruption, the energy stored in the period of time without detection, if periodic
magnetic circuit must be dissipated in the excitation tests are not made.
secondary circuit and results in a unidirectional
discharge of long duration (approximately 1 sec). PROPOSED PERFORMANCE REQUIREMENTS
Since the change in flux required to reach the
remanence level is greater for a gapped ct, the In order to provide a means of comparison of the
discharge voltage is higher. The time of decay performance characteristics of gapped core ct, it is
may be so long that high-speed reclosing can take essential that practical evaluation of the finished
place before the remanence level is reached. product can be established. The criteria proposed for
use in evaluating the performance of gapped core ct
Another risk associated with this phenomenon is are listed following:
the decay current following fault interruption may
delay a current relay from dropping out to 1. Measurement of the secondary voltage and exciting
indicate that the circuit breaker is open and thus current to establish the upper part of the
cause a false operation of the breaker failure excitation characteristics of a ct. For example,
protection .8,10*11 the exciting current of a CEO0 accuracy class ct
must not exceed 10 A when producing 800 V at the
3. The significant increase in the magnetizing secondary terminals for a burden of 8 ohms.
current falsifies the secondary current,
especially the dc component. The secondary 2. Measurement of the kneepoint. For closed core of
current error is serious if a resultant current is the kneepoint is defined as the 4 5 " target point
generated by paralleling two or more ct, or if on the excitation curve, as shown in Figure 3 .
1735

For gapped ct this dtfinition was changed to a 30° Routine excitation tests on Every unit should be
point because it may not be possible to find a 45O made to verify the excitation curves provided by
tangent point on the gapped ct's excitation the manufacturer, with sufficient points measured
curve. The inability to draw a 30° tangent to the to provide, at a minimum, the kneepoint and the
excitation curve constitutes noncompliance to the general shape of the curve below and above the
proposed limitations on excitation characteristics. kneepoint.

In the next edition of ANSI C57.13 an additional Routine remanence test should be conducted on
relaying rating will be introduced, designated as every unit. Methods have been described in the
'K' classification. The 'K' rating is the same as literaturelo f o r the field measurement of ct
the 'C' rating except that the kneepoint voltage remanence, which can be used to determine
is not to be less than 70% of the accuracy class conformance to specification.
secondary voltage. For example, a K800 ct will
have a kneepoint at 0.7 x 800 V or higher. In all
other respects the class K ct is equal to, or
better than, a class C ct. The class K ct will be
preferred for protective relaying applications.

Measurement of the remanent flux should be


conducted after the core has been subjected to a
magnetizing force of 500 ampere-turns per meter
and the flux has been allowed to subside to a
constant value after removal of the magnetizing
force. A test procedure is described in
reference 10.

It should be noted that all of the foregoing


statements apply to the entire secondary winding if
the ct being considered is multi-ratio.

A",.

Figure 4. Typical gapped ct excitation curve.

CONCLUSIONS

In some cases the use of gapped core ct can offer a


significant physical size reduction and accordingly
provide an economic advantage. Gapped core ct can
offer improved transient performance over that
available from similarly sized closed core ct, which
may contribute to greater reliability in relay
operation. The chief advantage of gapped core ct is
that remanence can be kept to a low level resulting In
improved transient performance. This is significant
where consistant high speed operation of the
protection is important.
Exciting Current (Amperes)
The advantages of using gapped core ct must be weighed
Figure 3. The effect of gaps on the excitation curves. against possible disadvantages in any given protective
relay application.
ADDITIONAL SPECIFICATION
The method of specifying gapped core ct presented in
Since there is no special classification in ANSI this paper should supplement the relaying requirements
C57. 13-197812 for relaying requirements of gapped now contained in ANSI C57.13-1978, and may be used in
core current transformers, they must be specified as a specifying gapped core ct for relaying applications.
class C or class K ct with the following additional Perhaps in the future a special classification should
requirements: be developed for gapped core ct which will include
these requirements.
1. The remanent flux in the core shall not exceed 10%
of the saturation flux after the core has been TERMINOLOGY
saturated with a magnetizing force of 50b
ampere-turns per meter, and the flux has subsided Accuracy Class Secondary Voltage
to a constant value after removal of the
magnetizing force. The voltage the ct will deliver to a standard burden
at 20 times rated secondary current without exceeding
2. Excitation curves on log-log coordinate paper 10% ratio error. Furthermore, the ratio error must be
shall be made available by the manufacturer. The limited to 10% at any current from 1 to 20 times rated
curves and tolerances shall conform to ANSI secondary current at the standard burden or any lower
C57.13. An example of such curves is shown in standard burden used for secondary terminal voltage
Figure 4. rat io. 12
1736

Burden For a Class C c t , t h e t y p i c a l e x c i t a t i o n c u r v e s are


p l o t t e d w i t h log-log c o o r d i n a t e s , w i t h s q u a r e d e c a d e s ,
The e x t e r n a l l o a d i n ohms or volt-amperes at a f o r e a c h p u b l i s h e d r a t i o , e x t e n d i n g from 1% of t h e
s p e c i f i e d c u r r e n t , on a c t is p r o p e r l y c a l l e d t h e accuracy c l a s s secondary terminal voltage t o a voltage
burden. t h a t w i l l c a u s e a n e x c i t a t i o n c u r r e n t o f 5 times r a t e d
secondary current.
C o n t r o l l e d Remanent Flux
I t must b e k e p t i n mind t h a t t h e c u r r e n t shown on t h e
A c t c o n s t r u c t e d t o meet c e r t a i n r e q u i r e m e n t s f o r f l u x c u r v e i s n o t even a p p r o x i m a t e l y s i n u s o i d a l . Yet this
e x c u r s i o n from maximum down t o a remanence v a l u e a f t e r s o r t o f c u r v e h a s found so many p r a c t i c a l u s e s t h a t i t
t h e primary c u r r e n t i s i n t e r r u p t e d . Usually, a c t i s recognized a s a useful c h a r a c t e r i s t i c of a
having small gaps i n t h e c o r e t o l i m i t t h e remanent transformer.I2
f l u x t o no more t h a n 10% o f t h e maximum f l u x . The g a p
is sufficient to absorb about twice as many F l u x Excursion Measurement
ampere-turns as t h e i r o n c o r e .
The f l u x e x c u r s i o n , remanent f l u x t o maximum, can b e
Core O v e r s i z i n g measured by t h e v o l t a g e induced by p u l s a t i n g d c ,
c o n v e n i e n t l y f u r n i s h e d by a half-wave r e c t i f i e r , which
The d e s i g n of a c o r e l a r g e r t h a n n e c e s s a r y f o r r a t e d c a u s e s a f l u x v a r i a t i o n from remanent t o a maximum
s t e a d y s t a t e o p e r a t i o n i n o r d e r t o produce a c c u r a t e value.6
operation during t r a n s i e n t conditions.
F u l l y D i s t r i b u t e d Windings
DC O f f s e t T r a n s i e n t
The w i n d i n g s o f a c t a r e e v e n l y d i s t r i b u t e d around t h e
The magnitude of d c o f f s e t c a n v a r y between z e r o and c i r c u m f e r e n c e o f t h e t o r o i d a l c o r e , and between each
t h e p e a k v a l u e of t h e t r a n s i e n t ac c u r r e n t O K f a u l t t a p , making t h e l e a k a g e r e a c t a n c e n e g l i g i b l y small and
current. The d c c u r r e n t is r e q u i r e d t o match ( w i t h normally c o n s i d e r e d zero.13
o p p o s i t e p o l a r i t y ) any c u r r e n t t h a t t e n d s t o change
t h e e x i s t i n g c u r r e n t a t t h e i n s t a n t o f f a u l t . The I d l e CT
d e g r e e of o f f s e t i s t h e f r a c t i o n o f t h e maximum
p o s s i b l e c u r r e n t t h a t a c t u a l l y a p p e a r s or i s assumed A c t having no primary c u r r e n t , b u t having i t s
f o r d e s i g n purposes.7 s e c o n d a r y i n p a r a l l e l w i t h , and e x c i t e d by, a c t
having p r i m a r y and secondary c u r r e n t .
D e t e r m i n a t i o n of t h e E x c i t a t i o n C h a r a c t e r i s t i c s
Kneepoin t
An e x c i t a t i o n c u r v e s h a l l e x t e n d a t l e a s t up t o t h a t
p o i n t a t which a 10% i n c r e a s e i n t h e v o l t a g e r e s u l t s For a gapped c t , t h e k n e e p o i n t is d e f i n e d a s a p o i n t
i n a 100% i n c r e a s e i n c u r r e n t . The v o l t a g e s h a l l be on t h e e x c i t a t i o n c u r v e where a s t r a i g h t l i n e a t 30°
measured by means of a n a v e r a g e v o l t a g e r e a d i n g is t a n g e n t when p l o t t e d on a log-log c o o r d i n a t e s
v o l t m e t e r and by a n rms r e a d i n g v o l t m e t e r . When t h e h a v i n g s q u a r e d e c a d e s .lo,l2
s u p p l y is measured w i t h o u t l o a d t h e measured v a l u e on
t h e a v e r a g e v o l t m e t e r s h a l l n o t d e v i a t e from t h a t Large Gaps
measured on t h e rms v o l t m e t e r by more t h a n 2% o f t h e
measured v a l u e o v e r t h e i n t e n d e d measuring range. The One or more g a p s i n t h e c o r e having a t o t a l l e n g t h of
s u p p l y s o u r c e s h a l l be c o n s i d e r e d a d e q u a t e i f t h e a t l e a s t 0.0005 p e r u n i t o f t h e mean c i r c u m f e r e n c e .
e r r o r between i n s t r u m e n t r e a d i n g s d o e s n o t exceed 10%
of t h e measured v a l u e s o v e r t h e range o f a p p l i e d Leakage F l u x
v o l t a g e s .9
CT a r e c l a s s i f i e d on t h e b a s i s o f l e a k a g e f l u x . Where
E f f e c t i v e Flux C a p a c i t y t h e l e a k a g e f l u x is n e g l i g i b l e , such a s a bushing c t ,
a c c u r a c y c a l c u l a t i o n s a r e p e r m i t t e d and a C class is
The p o s s i b l e f l u x e x c u r s i o n s from t h e remanent f l u x used. For a T ( f o r t e s t ) class c t t h a t h a s
v a l u e t o a maximum n e a r s a t u r a t i o n is t h e s i g n i f i c a n t a p p r e c i a b l e l e a k a g e or s t r a y f l u x i t is n o t p r a c t i c a l
quantity which determines the actual transient t o r e p r e s e n t t h e c t by a n e q u i v a l e n t c i r c u i t and
performance o f a c t . The c o r e w i l l s a t u r a t e i n a much c a l c u l a t e accuracy.
s h o r t e r time i f t h e remanent f l u x is n o t n e g l i g i b l e
( w i t h remanent f l u x i n t h e u n f a v o r a b l e d i r e c t i 0 n 1 . l ~ Maximum Flux D e n s i t y

E f f e c t i v e Remanent Flux ANSI C57.13 now s p e c i f i e s i n e f f e c t a maximum f l u x


d e n s i t y a t which c t i s u s a b l e . This is t h e f l u x
The remanent f l u x t o u s e f o r c a l c u l a t i o n s . When a c t d e n s i t y a t t a i n e d when 10 amperes rms e x c i t i n g c u r r e n t
h a s small g a p s i n t h e c o r e t o c o n t r o l t h e remanent is c i r c u l a t e d i n t h e secondary winding, a d e n s i t y
f l u x , t h i s f l u x may b e i n t h e o r d e r o f 1 0 % o f t h e f l u x t y p i c a l l y i n t h e neighborhood of 1.8 T, a d e n s i t y n o t
produced by a n e x c i t a t i o n t e s t c u r r e n t o f 1 0 amperes. g r e a t l y a f f e c t e d by r a t h e r l a r g e changes i n e x c i t i n g
A c t w i t h no c o r e gaps may have a remanent f l u x a s c u r r e n t , and a d e n s i t y a t which t h e f l u x e x c u r s i o n
high as 90% of a r e c e n t e x c i t a t i o n peak. from remanence t o maximum is meaningful.6

E x c i t a t i o n Curve P e r c e n t Remanent Flux

An e x c i t a t i o n c u r v e is a p l o t of e x c i t i n g c u r r e n t The p e r c e n t of t h e peak f l u x remaining i n the core


versus voltage applied t o t h e secondary with t h e when t h e primary c u r r e n t r e t u r n s t o z e r o .
p r i m a r y open. The e x c i t a t i o n c u r r e n t produces t h e
f l u x required t o induce t h e voltage f o r transformer Residual Flux Density, Residual Induction
action. I n normal s e r v i c e t h i s c u r r e n t i s s u p p l i e d by
t h e p r i m a r y winding and i n a c t i t is t h e e r r o r The magnetic f l u x d e n s i t y , ( i n d u c t i o n ) a t which t h e
current. magnetizing f o r c e i s z e r o when t h e material is i n a
s y m m e t r i c a l l y c y c l i c a l l y magnetized c o n d i t i o n . It is
1737

distinguished from remanence by the symmetrically 10. 'Transient Response of Current Transformers',
cyclic requirement.14 Power System Relaying Committee Report 76-CH1130-4
PWR, IEEE Special Publication. As summary report
Saturation and discussion, IEEE Trans. Power Apparatus and
-
Syst., PAS 96, Nov/Dec 1977, pp. 1809-1814.
The state of a ferromaanetic substance placed in a
field so strong that the intensity of magnetization 11. N. E. Korponay, 'Non-gapped Cores, Antiremanence
becomes independent of the field: the substance is Gapped
._ Cores or Linear Cores for Current
then said to be saturated. Transformers,. IEEE Transactions on Power
Apparatus and Systems, March/April 1978 pp. 569-74.
That value of flux below which the corresponding
exciting current can be considered negligible.9 The 12. ANSI/IEEE Standard C57.13-1978, "Requirements for
effective saturation or maximum flux density in Instrument Transformers'.
silicon iron alloys is about 2 T (20,000 Gauss).
13. L. J. Powell, .Current Transformer Burden and
The maximum intrinsic value of induction possible in a Saturation,' IEEE Transactions on Industry
material. Note: This term is often used for the Application, Vol. IA-15 13, May/June, 1979,
maximum value of induction at a stated high value of pp. 294-302.
field strength where further increase in intrinsic
magnetization with increasing field strength is 14. IEEE Standard Dictionary of Electrical and
negligible.l4 Electronics Terms, ANSI/IEEE Std 100-1988.

Saturation Flux

That value of flux in a core which is arbitrarily


determined as 10% greater than the flux at the
kneepoint of the excitation curve.

REFERENCES

1. R. A. Pfuntner, 'The Accuracy of Current


Transformers Adjacent to High Current Busses,'
AIEE Transactions on Power Apparatus and Systems,
1951, pp. 1656-61.

2. R.G. Bruce and A. Wright, 'Remanent flux in


current-transformer Cores. Proc. of IEE, Vol. 113,
No. 5, May 1966, pp. 915-920.

3. Jagsich, Mowa and Wuss, 'Transient Conditions in


Current Transformers and Their Repercussion on the
Reduction of Operating Time of Protective
Devices,. CIGRE Paper 131-07, Paris, 1968

4. N.E. Korponay, 'The Transient Behaviour and Uses


of Current Transformers", Brown Boveri Review,
Nov/Dec 1969, pp. 597-608.

5. 0. W. Iwanusiw, 'Remanent Flux in Current


TKanSfOKmeKS,. Ontario Hydro Research Quarterly,
Third Quarter, 1970, pp. 18-21. .
6. E. E. Conner, R. W. Greb and E. C. Wentz, 'Control
of Residual Flux in Current Transformers,' IEEE
Transactions on Power Apparatus and Systems,
JUl/AUg, 1973, pp. 1226-33.

7. W. J. Smolinski, 'Design Considerations in the


Application of ct for Protective Relaying
Purposes,. IEEE Transactions on Power Apparatus
and Systems, Jul/Aug, 1973, pp. 1329-36.

8. B.L. Avent, 'Current Transformer Transient


Response,' Western Protective Relay Conference,
Spokane, WA, Oct, 1974.

9. E. E. Conner, E. C. Wentz and D. W. Allen,


.Methods for Estimating Transient Performance of
Practical ct for Relaying,' IEEE Transactions on
Power Apparatus and Systems, Vol. 94 11 Jan/Feb,
1975, pp. 116-122.
1738
DISCUSSION It is theoretically possible for the decay
current to cause misoperation of breaker failure
B. L. AVENT and C. F. HENVILLE protection, but B. C. Hydro has no known such
B. C. Hydro, Vancouver, B. C. Canada misoperations with the conventional breaker
failure protection routinely applied at 132-
230 kV. The breaker failure protection B. C.
This Paper is a useful addition to the literature for Hydro provided on 500 kV breakers is designed to
dissemination of information about the application of be immune to this decay current.
cts with small air gaps. However, the discussors
feel the authors have painted an unnecessarily 3. The discussors are not aware of any serious
pessimistic picture of the drawbacks. Although all error in secondary current caused by paralleling
the application concerns mentioned in the Paper are two or more sets of three phase cts, providing
true to a degree, B. C. Hydro's experience is that both sets are gapped, as B. C. Hydro routinely
cts with anti-remanence gaps can be applied with does. There could be significant neutral
little concern about the drawbacks. Experience in current error if dissimilar cts are connected in
this regard extends back 20 years and includes a three phase set. Computer programs exist,
virtually all 500 kV cts associated with circuit which allow the determination of ct performance
breakers on a system of over 5000 km of 500 kV lines. when dissimilar cts are parallelled.
In addition, gapped core cts are B. C. Hydro's
standard for circuit breaker associated cts above 4. The possible misoperation of a breaker failure
138 kV, and have been for about 15 years. relay due to magnetizing current in an idle ct
is real. One way to avoid the problem is to
Several years ago, there were some manufacturing size the cores such that the magnetizing current
problems in maintaining stability of the gaps, but is below the sensitivity of breaker failure
there have been negligible problems in the field with relays at the voltage of the shared burden.
stability in the last eight years. Since B. C. Hydro
specifies excitation tests as routine production Following, are some comments on the application
tests, any gap problems in new cts are discovered and considerations cited. The comment numbers refer to
corrected before they leave the factory. the consideration numbers cited in the Paper.

Following, are some comments on the disadvantages 1. B. C. Hydro has routinely mixed gapped core cts
cited. The comment numbers refer to the disadvantage with solid core cts in differential circuits.
numbers in the Paper. W and E W cts at circuit breaker positions are
normally gapped, transformer bushing cts and
1. In practical terms the increased ratio and phase lower voltages are ungapped so transformer
angle error caused by small gaps is usually differentials routinely include both. We find
negligible except for very low ratio cts. the mismatch no more severe than that for the
Fig. 1 of this discussion shows the calculated much different W and LV solid core cts normally
comparative performances of two of the cts with found in such a differential circuit. Many
the approximate excitation characteristics of year's of experience with numerous installations
Fig. 3 of the Paper. The difference in perfor- has not produced identifiable problems.
mance of the two cts cannot be easily seen until
after saturation, because the difference in 4. In practice small gaps have not been found to
magnetizing currents up to the knee point is significantly affect leakage reactance. This
less than 1% of the fault current. has been demonstrated by several direct
transient performance tests which show that
s actual performance corresponds well with perfor-
mance predicted from the excitation curves.
B. C. Hydro routinely neglects leakage reactance
when setting high impedance bus differential
relays with no known problems so far.
There is no doubt about the stated need for proposals
to specify gapped ct performance requirements. How-
ever, neither the new "K" accuracy class nor the
5
.o existing "C" accuracy specifies the transient perfor-
mance. It would be better to adopt the transient
specification terminology of IEC in their classes
TPS, TPX, TPY and TPZ. This has already been done
successfully for Canadian Standard CSA CAN3-C13-M83
(Ref l ) , which the discussors recommend for consi-
deration. Section 8 of that standard covers cts for
which transient performance is important, including,
0 5 , O , ~ m x ~ ~ 4 4 4 5 ~

TI* I..)
but not limited to, gapped cts. B. C. Hydro has
purchased cts in accordance with this standard since
FIGURE I - COMPARATIVE PERFORMANCE OF SOLI0 h QAPPEO CORE CTS its publication in 1983 with little difficulty.

2. The fact that the flux in a gapped ct may not Could the authors please explain the need for the
have decayed to its steady state remanence level proposed routine remanence tests? It is appreciated
before high speed reclosing takes place, is not that this should be a type test, but remanence is
a disadvantage. The flux in the gapped ct will only a function of the core material (hysterisis) and
still decay to a lower level than in a non- excitation characteristic. Since the excitation
gapped ct. Incomplete decay of flux can be characteristic is proposed to be a routine test (and
catered for by specifying the reclosing duty of indeed, it should be), and the core material perfor-
the ct, using the transient performance specifi- mance is determined by type test, routine remanence
cation of Ref. 1 of this discussion. measurements seem superfluous.
~

1739
It should be noted that there is an additional impor- 2. There may be advantages to using a different core
tant reason to try to reduce the premature ct satura- material having inherently lower remanence, such as
tion caused by remanence. This is the need for an amorphous metal (metallic glass) or hot rolled
protection systems to be secure during external silicon steel. There viability as alternatives to
faults. This is particularly important when gapped GOSS cores should be considered.
reclosing onto a permanent fault with a breaker which
is part of a ring bus. In ring bus arrangements the 3. Should caution not be exercised when applying
adjacent line protection is also a bus protection gapped-core ct for metering purposes? Based on our
system for the line terminal. During reclosing onto limited accuracy measurements on minimally-gapped
a permanent fault, all fault current flows through (0.0001-0.0003 pu length) core protective ct, we
one ct set. If there was remanence in this ct, have found that their ratio error and phase angle
(possibly due to the initial fault) its performance are significantly different than their metering
could be degraded enough to cause misoperation of the councerparts, with the same metering burden
adjacent line protection zone. connected. Also, their accuracy varied
significantly depending upon the location of the gap
In the protection business, good ct transient perfor- in relation to the return conductor.
mance is the name of the game and cts with anti-
remanence gaps (Type TPY) offer more advantages than 4. From what we have observed, there is a wider
disadvantages. Ct saturation problems will manifest variation in the excitation curves for gapped core
themselves for heavy close-in faults, the worst case. ct. This would suggest that wider acceptance
For this reason, there should be further considera- criteria may be advisable for gapped-core ct than
tion of existing IEC terminology and Ref. 1 which has is allowed in the currentANSI/IEEE C57.13-1978 and
been tested and found adequate as a means of defining Canadian Standard CAN3-C13-M83. These standards
et transient performance requirements. As an experi- only allow for +25% variation in the excitation
enced user of gapped core cts, B. C. Hydro is firmly current below the kneepoint.
convinced that the advantage of improved transient
performance outweighs the disadvantages. 5. With regard to the additional specification on
testing for remanent flux, some elaboration on the
REFERENCES subject of driving a gapped-core ct into saturation
may be helpful. With permeability on the order
1. CSA Standard CAN3-Cl3-ME3, Instrument 3,000 (11 mil Allegheny M4 @ 500 At/m) a gap
Transformers. equivalent to 0.00033 pu adds as much additional
reluctance as the steel itself provides. For
example, if 500 At/m were required to fully saturate
Manuscript received July 12, 1989. a given closed core, then twice as much, or 1000
At/m would be required to fully saturate the same
core with a 0.00033 pu gap. Similarly, 2000 At/m
would be required to fully saturate the same core
DISCUSSION with a 0.001 pu gap.
By: P.W. Labaj 6. While the committee's reference 6 appears to be a
Ontario Hydro Research Division fairly simple and straightforward means to measure
Toronto, Ontario, Canada flux excursion and thereby remanence, there may be
some serious drawbacks in its implementation; such
as applied voltages exceeding the ct insulation
strength, suitable kVA rated supply with low source
impedance, and selection of suitable diodes. We
The committee members are to be commended for producing have found up to this point in time, that dc methods
a paper on a subject that is long overdue. The paper, as those discussed in references 5 and 10 and
while full of useful information, lacks clarity in some Canadian Standard CAN3-C13-M83 can be universally
parts and in the terminology section, more use could be applied and are quite reliable.
made of existing instrument transformer standards along
with the IEEE and IEC dictionaries. 7. The definition given for saturation flux appears to
be inconsistdntwithmany standards; can you explain
The discusser has several points to raise with regard why this definition was chosen? A definition of
to this committee report. saturation flux arbitrarily determined as 50%
greater than the flux at the kneepoint might be more
appropriate than 10%. The 50% figure appears to be
1. With regard to metering ct operating at a level a reasonably obtainable flux that would still ensure
approaching saturation under normal full load, this that a ct core was fully saturated for all practical
has never been our experience, and in fact the purposes.
normal operating flux is usually quite low. An
illustration of this fact is the accuracy curve
which normally takes the following form: Manuscript received July 17, 1989.

B. BOZOKI: The interest expressed and the


informative comments included in the
discussions is greatly appreciated by the
working group. The discussers contributions
Secondary Current significantly increased the value of our
'rated paper.
If the ct were operating beyond the point of maximum Mr Labaj asked why we did not discuss issues
permeability, the accuracy curve would look more related to the use of gapped ct for meterin?.
like a parabola. We did not consider these issues because it
1740
was assumed that most utilities would use working group. The discussers contributions
gapped ct only for relaying and would specify significantly increased the value of our
a separate closed core ct for metering. paper.
Mr. Labaj also asked why the saturation flux Mr Labaj asked why we did not discuss issues
was defined differently from the standard related to the use of gapped ct f o r meterinq.
definitions. In our opinion the definition We did not consider these issues because it
given in the paper is in agreement with the was assumed that most utilities would use
IEEE dictionary, where a note allows for a gapped ct only for relaying and would specify
Itstated high valuell of flux to be defined as a separate closed core ct for metering.
a practical value of the saturation flux. The
flux level 10% above that at the kneepoint Mr. Labaj also asked why the saturation flux
was selected in order to limit the was defined differently from the standard
magnetizing current to a relatively low value definitions. In our opinion the definition
during testing. For example, the kneepoint given in the paper is in agreement with the
of the ct described in Figure 4 is IEEE dictionary, where a note allows for a
approximately 800 V on the 1200-5 A tap. The "stated high value" of flux to be defined as
magnetizing current required to bring the a practical value of the saturation flux. The
flux level 10% above the kneepoint is 2 A. flux level 10% above that at the kneepoint
To raise it 50% above the kneeDoint value was selected in order to limit the
would require approximately 100 A-magnetizing magnetizing current to a relatively low value
current. during testing. For example, the kneepoint
of the ct described in Figure 4 is
Messrs. Avnet and Henville questioned the approximately 800 V on the 1200-5 A tap. The
need for routine remanence tests. The answer magnetizing current required to bring the
depends on the accuracy limits placed on the flux level 10% above the kneepoint is 2 A.
excitation test. In the Canadian Standard a To raise it 50% above the kneepoint value
close tolerance is placed on the calculated would require approximately 100 A magnetizing
excitation curve, therefore, a test based on current.
the CSA standard is sufficient to verify the
existence of the gap in the core. The Messrs. Avnet and Henville questioned the
tolerance on the excitation curve in ANSI need for routine remanence tests. The answer
C57.13, however, only limits the magnetizing depends on the accuracy limits placed on the
current in the positive direction, excitation test. In the Canadian Standard a
consepently a routine test based on it ?ay close tolerance is placed on the calculated
not indicate if a closed core ct is supplied excitation curve, therefore, a test based on
in place of gapped ct. Our recommendation the CSA standard is sufficient to verify the
was based on the assumption that it is more existence of the gap in the core. The
economical to request routine remanence tests tolerance on the excitation curve in A N S I
than to specify close tolerance on the C57.13, however, only limits the magnetizing
calculated excitation curve. This question current in the positive direction,
underscores the conclusion of our paper that consepently a routine test based on it may
there is a need for a special classification not indicate if a closed core ct is supplied
in ct standards for gapped ct. in place of gapped ct. Our recommendation
was based on the assumption that it is more
economical to request routine remanence tests
than to specify close tolerance on the
calculated excitation curve. This question
B. BOZOKI: The interest expressed and the underscores the conclusion of our paper that
informative comments included in the there is a need for a special classification
discussions is greatly appreciated by the in ct standards for gapped ct.

You might also like