XLPE Insulated Cables PDF
XLPE Insulated Cables PDF
1A Single-Core 600/1000V Unarmoured Cables (Copper Conductor) 12A-1N BS 5467 / IEC 60502-1
1B Single-Core 600/1000V Armoured Cables (Copper Conductor) 12A-1A BS 5467 / IEC 60502-1
2A Two-Core 600/1000V Unarmoured Cables (Copper Conductor) 12-2N BS5467 / IEC 60502-1
2B Two-Core 600/1000V Armoured Cables (Copper Conductor) 12-2S BS5467 / IEC 60502-1
3A Three-Core 600/1000V Unarmoured Cables (Copper Conductor) 12-3N BS5467 / IEC 60502-1
3B Three-Core 600/1000V Armoured Cables (Copper Conductor) 12-3S BS5467 / IEC 60502-1
4A Four-Core 600/1000V Unarmoured Cables (Copper Conductor) 12-4N BS5467 / IEC 60502-1
4B Four-Core 600/1000V Armoured Cables (Copper Conductor) 12-4S BS5467 / IEC 60502-1
4C Four-Core 600/1000V Armoured Cables (Aluminium Conductor) T13-4S BS5467 / IEC 60502-1
4D Four-Core 600/1000V Copper Tapes Screened Cables (Aluminium Conductor) T13-4C TNB Specification
13
X L P E I N S U L AT E D C A B L E S
LOW VOLTAGE XLPE CABLES. MEDIUM VOLTAGE XLPE CABLES.
UNARMOURED CABLES
Conductor
XLPE Insulation
Sheath
ARMOURED CABLES
Conductor
XLPE Insulation
Bedding
Armour Wire
Outer Sheath
BASIC CONSTRUCTION
CONDUCTOR - COPPER OR ALUMINIUM
INSULATION - XLPE
14
BS 5467 REFERENCE
IEC 60502-1 12A-1N
BS 5467 REFERENCE
IEC 60502-1 12A-1A
15
600/1000V TW0-CORE XLPE INSULATED POWER CABLES
UNARMOURED CABLES
Conductor
Insulation
Filler
Core Wrapping
Outersheath
ARMOURED CABLES
Conductor
Insulation
Filler
Core Wrapping
Bedding
Armour Wire
Outersheath
BASIC CONSTRUCTION
CONDUCTOR - COPPER OR ALUMINIUM
INSULATION - XLPE
16
BS 5467 REFERENCE
IEC 60502-1 12A-2N
BS 5467 REFERENCE
IEC 60502-1 12A-2S
17
600/1000V THREE-CORE XLPE INSULATED POWER CABLES
UNARMOURED CABLES
Conductor
Insulation
Filler
Core Wrapping
Outersheath
ARMOURED CABLES
Conductor
Insulation
Filler
Core Wrapping
Bedding
Armour Wire
Outersheath
BASIC CONSTRUCTION
CONDUCTOR - COPPER OR ALUMINIUM
INSULATION - XLPE
18
BS 5467 REFERENCE
IEC 60502-1 12A-3N
BS 5467 REFERENCE
IEC 60502-1 12A-3S
19
600/1000V FOUR-CORE XLPE INSULATED POWER CABLES
UNARMOURED CABLES
Conductor
Insulation
Filler
Core Wrapping
Outersheath
ARMOURED CABLES
Conductor
Insulation
Filler
Core Wrapping
Bedding
Armour Wire
Outersheath
BASIC CONSTRUCTION
CONDUCTOR - COPPER OR ALUMINIUM
INSULATION - XLPE
20
BS 5467 REFERENCE
IEC 60502-1 12A-4N
BS 5467 REFERENCE
IEC 60502-1 12A-4S
21
TNB REFERENCE
SPECIFICATION T13-4S
TNB REFERENCE
SPECIFICATION T13-4C
22
MEDIUM VOLTAGE SINGLE CORE XLPE INSULATED POWER CABLE
UNARMOURED CABLES
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen
Metallic Screen
Outer Sheath
ARMOURED CABLES
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen
Metallic Screen
Bedding
Armour Wire
Outer Sheath
BASIC CONSTRUCTION
CONDUCTOR - COPPER OR ALUMINIUM
INSULATION - XLPE
23
TNB REFERENCE
SPECIFICATION TC-6-1-N
BS 662 REFERENCE
IEC 60502-2 GC-11-1-N
BS 6622 REFERENCE
IEC 60502-2 GC-11-1-A
24
BS 6622 REFERENCE
IEC 60502-2 GA-11-1-N
BS 6622 REFERENCE
IEC 60502-2 GA-11-1-A
TNB REFERENCE
SPECIFICATION TA-11-1-N
25
MEDIUM VOLTAGE THREE CORE XLPE INSULATED POWEDR CABLE
UNARMOURED CABLES
Conductor
Conductor Screen
Insulation
Insulation Screen
Metallic Screen
Filler
Binder Tape
Outersheath
ARMOURED CABLES
Conductor
Conductor Screen
Insulation
Insulation Screen
Metallic Screen
Binder Tape
Filler
Bedding
Armour Wire
Outersheath
BASIC CONSTRUCTION
CONDUCTOR - COPPER OR ALUMINIUM
INSULATION - XLPE
26
BS 6622 REFERENCE
IEC 60502-2 GC-11-3-N
BS 6622 REFERENCE
IEC 60502-2 GC-11-3-S
27
BS 6622 REFERENCE
IEC 60502-2 GA-11-3-N
BS 6622 REFERENCE
IEC 60502-2 GA-11-3-S
28
TNB REFERENCE
SPECIFICATION TA-11-3-S
BS 6622 REFERENCE
IEC 60502-2 GA-22-3-S
TNB REFERENCE
SPECIFICATION TA-22-1-N
29
BS 6622 REFERENCE
IEC 60502-2 GC-33-1-N
BS 6622 REFERENCE
IEC 60502-2 GC-33-3-S
30
TNB/KLIA SPECIFICATION MEDIUM VOLTAGE XLPE INSULATED POWER CABLE
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen
Metallic Screen
Separator Tape
Semi-Conducting Swellable Tape
Identification Tape
Metallic Tape
Outer Sheath
BASIC CONSTRUCTION
CONDUCTOR - COPPER OR ALUMINIUM
INSULATION - XLPE
31
TNB SPECIFICATRION REFERENCE
KLIA/D/UTO6/O58/95 TA-33-1-W
32
TNB SPECIFICATION MEDIUM VOLTAGE SINGLE-CORE XLPE INSULATED
DOUBLE-SHEATHD POWER CABLE
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen
Metallic Screen
Innersheath
Separator Tape
Outersheath
Conductor
Conductor Screen
Insulation
Insulation Screen
Metallic Screen
Binder Tape
Innersheath
Separator Tape
Outersheath
BASIC CONSTRUCTION
CONDUCTOR - COPPER OR ALUMINIUM
INSULATION - XLPE
33
TNB REFERENCE
SPECIFICATION TA-11-1-DS
TNB REFERENCE
SPECIFICATION TA-22-1-DS
TNB REFERENCE
SPECIFICATION TA-11-3-DS
TNB REFERENCE
SPECIFICATION TA-11-3-T
34
MEDIUM VOLTAGE XLPE INSULATED, MDPE OUTERSHEATED, TRIPLEX CABLE
Conductor
Conductor Screen
Insulation
Insulation Screen
Metallic Screen
Outersheath
BASIC CONSTRUCTION
CONDUCTOR - ALUMINIUM
INSULATION - XLPE
35
600/1000V XLPE INSULATED, PVC OUTERSHEATHED, QUADRUPLEX CABLE
Conductor
Insulation
Outersheath
BASIC CONSTRUCTION
CONDUCTOR - ALUMINIUM
INSULATION - XLPE
36
TABLE A TECHNICAL DATA FOR CABLE INSTALLATION
The calculation:-
P = T/R
Where
37
INSTALLATION CONDITIONS AND CORRECTION FACTORS FOR CONTINUOUS
CURRENT RATING FOR:
INSTALLATION
In Air (Ambient Temperature: 40oC) In the Ground (Ambient Temperature: 25oC)
Ground level
700mm
700mm
Thermal resistivity
120oC cm/w
Thermal resistivity
120oC cm/w
Plus 1 line
Ambient Temperature
(oC)
15 20 25 30 35 40 45 50 55
Installation
In Air 1.22 1.18 1.14 1.10 1.05 1.0 0.95 0.89 0.84
In the Ground 1.07 1.04 1.0 0.96 0.92 0.88 0.83 0.78 0.73
38
SHORT CIRCUIT CURRENT
The thermally permissible short circuit current for a Con-
1000
ductor of specified size may be calculated from the 800
equations below. For the purposes of calculated, the 500 Short current limits
for copper conductor cables
standard short circuit duration period is up to 5 sec. (Thermal threshold)
200
100
80
I = 143 . S (A)
50
1. Copper conductor
0.1 sec
t 0.2 sec
0.5 sec
Current (KA)
20
1.0 sec
2.0 sec
10
8
t
2
0.8
where 0.5
0
1 5 2.5 4 6 10 16 25 50 95 150 300 500 1000
XLPE PROPERTIES
AERIAL SIZE DIAMETER DIAMETER THICKNESS DIAMETER OF RESISTANCE SIZE DIAMETER DIAMETER THICKNESS DIAMETER OF RESISTANCE SIZE DIAMETER DIAMETER THICKNESS DIAMETER OF RESISTANCE OF COEFFICIENT LOAD OVERALL
CABLES STRANDS CONDUCTOR INSULATION CONDUCTOR STRANDS CONDUCTOR INSULATION CONDUCTOR STRANDS CONDUCTOR INSULATION CONDUCTOR EXPANSION OF CABLE
(No/mm & sq.mm) (sq.mm) (No./mm) (mm) (mm) (mm) (Ω/km) (sq.mm) (No./mm) (mm) (mm) (mm) (Ω/km) (sq.mm) (No./mm) (mm) (mm) (mm) (Ω/km) (kg/sq.mm) (1/oC) (kN) (mm)
1x16+25 3x16 7/1.78 4.7 1.0 6.8 1.99 - - - - - - 25 7/2.34 7.0 1.2 9.5 1.430 6 000 2.30E + 05 8.44 16.4
3x16+25 3x16 7/1.78 4.7 1.0 6.8 1.99 - - - - - - 25 7/2.34 7.0 1.2 9.5 1.430 6 000 2.30E + 05 8.44 23.3
3x95+70+16 3x95 19/2.60 11.4 1.6 14.8 0.333 16 7/1.78 4.7 1.0 6.8 1.99 70 19/2.14 10.7 1.4 13.8 0.511 5 700 2.30E + 05 19.6 43.5
3x185+120+16 3x185 37/2.60 16.1 2.0 20.3 0.171 16 7/1.78 4.7 1.0 6.8 1.99 120 19/2.85 14.3 1.6 17.6 0.322 5 700 2.30E + 05 33.6 58.2
CURRENT RATING
SIZES
CONTINUOUS CURRENT RATING MAXIMUM PERMISSIBLE
OF
WITH AN AMBIENT TEMPERATURE SHORT-TIME CURRENT
AERIAL
OF 30oC AT: BASIC CONSTRUCTION
BUNDLED
CABLES (kA)
(No/mm & sq.mm) (A) 0.1 SEC 0.5 SEC 1 SEC 3 SEC
2. Insulated Messenger
TNB
SPECIFICATION
3x50+50 3x50 7/3.06 8.09 3.4 18.5 0.641 0.822 0.300 0.133 50 7/3.00 9.0 1280 3.5 240 52.8
3x70+50 3x70 19W 9.73 3.4 20.1 0.443 0.443 0.338 0.123 50 7/3.00 9.0 1280 3.5 240 56.3
CURRENT RATING
SIZES
OF
CONTINUOUS CURRENT RATING
WITH AN AMBIENT TEMPERATURE
MAXIMUM PERMISSIBLE
SHORT-TIME CURRENT
COPPER TAPE
EARTH FAULT RATING
MAXIMUM
VOLTAGE DROP
BASIC CONSTRUCTION
AT INITIAL TEMPERATURE : 75oC AT 90oC FOR
AERIAL OF 30oC AT:
AT FINAL TEMPERATURE : 180oC 1 PHASE CIRCUIT
CABLES
(kA) (kA)
(No/mm & sq.mm) (A) 0.1 SEC 3 SEC 0.1 SEC 3 SEC (mV/A.m) 1. Conductor
3x50+50 140 4.5 2.6 1.78 1.03 1.665 2. Conductor Screen
3x70+50 175 6.5 3.7 1.94 1.12 1.162
3. Insulation
4. Insulation Screen
5. Messenger
6. Metallic Screen
7. Oversheath
TNB
SPECIFICATION
3x50+50 3x50 7/3.06 8.09 8.0 29.3 0.641 0.822 0.158 0.156 50 7/3.00 9.0 1280 3.5 240 79.3
3x150+50 3x150 37W 14.40 8.0 35.6 0.206 0.205 0.221 0.127 50 7/3.00 9.0 1280 3.5 240 89.6
3x185+50 3x185 37W 16.10 8.0 37.3 0.164 0.211 0.238 0.122 50 7/3.00 9.0 1280 3.5 240 93.3
CURRENT RATING
SIZES
OF
CONTINUOUS CURRENT RATING
WITH AN AMBIENT TEMPERATURE
MAXIMUM PERMISSIBLE
SHORT-TIME CURRENT
COPPER TAPE
EARTH FAULT RATING
MAXIMUM
VOLTAGE DROP
BASIC CONSTRUCTION
AT INITIAL TEMPERATURE : 75oC AT 90oC FOR
AERIAL OF 30oC AT:
AT FINAL TEMPERATURE : 180oC 1 PHASE CIRCUIT
CABLES
(kA) (kA)
(No/mm & sq.mm) (A) 0.1 SEC 3 SEC 0.1 SEC 3 SEC (mV/A.m) 1. Conductor
3x50+50 165 4.5 2.6 2.82 1.63 1.673 2. Conductor Screen
3x150+50 315 14.0 17.5 3.56 2.05 0.587
6. Metallic Screen
7. Oversheath
42
43