Chilled Equivlent
Chilled Pipe Wall Cross Pipe
Pipe No. of Out side water length for Total head loss
Fittings type water size thickness sectional section
section fitting dia mm velocity fitting& length ft ft
flow Lps. mm mm. area m2 length m
m/s valves ft
Pipe 42.0
Tee branch 12 180
363.6 17.461
Elbow 90ْ 6 45
SK 42.0 225
9.2 80 88.9 5.49 0.0047661 1.93
Check valve 1 1.990 NIBCO(Approved)
Globe valve 1 4.320 NIBCO (will submit)
Gate valve 4 0.720 NIBCO (will submit)
Air Sep WATER PRESSURE DROP THROUGH AIR SEPARATOR (FT) 1.82 Wessels (Approved)
Gate valve 2 9.2 80 88.9 5.49 0.0047661 1.93 0 0.360
Pipe 70.0
Tee branch 2 30
306.0 14.695
1 2 Elbow 90ْ 6 9.2 80 88.9 5.49 0.0047661 1.93 45
SK 70.0 75
Motorized valve 2 0.360
Pipe 28.0
2 3 Tee branch 2 6.9 80 88.9 5.49 0.0047661 1.45 30 122.4 3.450
SK 28.0 30
Pipe 28.0
3 4 Tee branch 2 4.6 80 88.9 5.49 0.0047661 0.97 30 122.4 1.628
SK 28.0 30
Pipe 38.0
Tee branch 2 30
4 5 2.3 80 88.9 5.49 0.0047661 0.48 155.4 0.573
Elbow 90ْ 2 15
SK 38.0 45
Gate valve 2 2.3 80 88.9 5.49 0.0047661 0.48 0 0.023
Balance valve 1 2.3 80 88.9 5.49 0.0047661 0.48 0 0.246
CENT
WATER PRESSURE DROP FOR COIL OF COMPRESSOR CHILLER (FT),5000 TR 14.50 YORK (Approved)
CHILLER
SCROLL
WATER PRESSURE DROP THROUGH SCROLL CHILLER (FT), 60 TR 14.98 YORK (Resubmit)
CHILLER
TOTAL PRESSURE DROP FOR NETWORK (MT) WITH SAFETY 25% 30.4218
Remarks
*Equivlent length for fitting from carrier standard.