You are on page 1of 6

UTILITY PROJECTS & SERVICES PVT. LTD.

Pressure Drop Calculation - Al-Muhaidib


(SECONDARY PUMP)
2 WAY/MOT.
SL. BENDS BUTTERFLY Bellow NRV STRANIER BALANCING REDUCER TOTAL
SIZE DIA PIPE BUTT. VALVES FLOW FRICTION PR.HEAD
NO DESCRIPTION EQUILVALENT
in MM (MTS) NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS GPM LOSS (MTS)
. (MTS)
1 Secondary Pump Outlet Tapping 250 2.8 0 0 1 3.7 3.7 1 3.7 3.7 0 1 30 30 0 0 1 2.6 2.6 42.8 1680 1.35 0.58
2 Secondary Pump Header to Plant 400 24.99 5 7.9 39.5 0 0 0 0 0 0 0 64.49 3360 0.615 0.40
room Trench
3 BURRIED line - From Plantroom 400 15.8 0 7.9 0 0 15.8 3360 0.615 0.10
trench to Pit (Building side)
4 Burried & Riser - From Pit to shaft 200 40 8 4 32 0 72 1420 3.075 2.21
riser
5 Terrace - From shaft riser to B12 200 80 2 4 8 1 2.6 2.6 90.6 1420 3.075 2.79
Shaft
6 Terrace - From Shaft B12 to B06 150 47 0 1 1.8 1.8 48.8 770 3.803 1.86
7 Terrace - From Shaft B06 to B03 125 37 0 1 1.6 1.6 38.6 445 3.374 1.30
8 Terrace - From Shaft B03 to B01 100 27 3 3 9 1 1.5 1.5 37.5 250 3.315 1.24
9 Shaft B01 100 2 0 1 1.5 1.5 3.5 185 1.997 0.07
10 Shaft B01 & Burried to TMB &TMB 80 85 6 2.7 16.2 0 101.2 120 3.433 3.47
12 AHU Inlet Tapping 65 12 2 1.2 2.4 1 0.9 0.9 0 0 0 1 11 11 1 21 21 0 47.3 60 2.7 1.28
13 AHU 7500 CFM PRESSURE DROP 0 0 0 0 0 0 0 0 0 1.50
14 AHU out let Tapping 65 12 5 1.2 6 4 0.9 3.6 0 0 0 0 11 0 0 21 0 0 21.6 60 2.7 0.58
16 Shaft B01 & Burried to TMB &TMB 80 84 6 2.7 16.2 0 100.2 120 3.433 3.44
17 Shaft B01 100 2 0 1 1.5 1.5 3.5 185 1.997 0.07
18 Terrace - From Shaft B01 to B03 100 27 3 3 9 1 1.5 1.5 37.5 250 3.315 1.24
19 Terrace - From Shaft B03 to B07 125 37 0 1 1.6 1.6 38.6 445 3.374 1.30
20 Terrace - From Shaft B07 to B12 150 47 0 1 1.8 1.8 48.8 770 3.803 1.86
21 Terrace - From B12 Shaft to shaft 200 80 2 4 8 1 2.6 2.6 90.6 1420 3.075 2.79
riser
22 Burried & Riser - From shaft riser to 200 40 8 4 32 0 72 1420 3.075 2.21
Pit
23 BURRIED line - From Pit to 400 16 0 7.9 0 0 16 3360 0.615 0.10
Plantroom trench
24 Primary Pump Header - From 400 25 5 7.9 39.5 0 64.5 3360 0.615 0.40
Trench to Primary pump Inlet
25 Air separator 400 0 1.00
26 Primary Pump Inlet Tapping 250 3.5 1 4.9 4.9 1 3.7 3.7 1 3.7 3.7 0 0 1 32 32 0 0 0 47.8 1680 1.35 0.65
TOTAL 32.4

TOTAL 32.4
TOTAL+10% 35.7

SELECTED HEAD 36M


UTILITY PROJECTS & SERVICES PVT. LTD.
Pressure Drop Calculation - Al-Muhaidib
(SECONDARY PUMP)
2 WAY/MOT.
SL. BENDS BUTTERFLY Bellow NRV STRANIER BALANCING REDUCER TOTAL
SIZE DIA PIPE BUTT. VALVES FLOW FRICTION PR.HEAD
NO DESCRIPTION EQUILVALENT
in MM (MTS) NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS GPM LOSS (MTS)
. (MTS)
1 Secondary Pump Outlet Tapping 250 2.8 0 0 1 3.7 3.7 1 3.7 3.7 0 1 30 30 0 0 1 2.6 2.6 42.8 1680 1.35 0.58
2 Secondary Pump Header to Plant 400 24.99 5 7.9 39.5 0 0 0 0 0 0 0 64.49 3360 0.615 0.40
room Trench
3 BURRIED line - From Plantroom 400 15.8 0 7.9 0 0 15.8 3360 0.615 0.10
trench to Pit (Building side)
4 Burried & Riser - From Pit to shaft 200 40 8 4 32 0 72 1420 3.075 2.21
riser
5 Terrace - From shaft riser to B12 200 63 2 4 8 1 2.6 2.6 73.6 1420 3.075 2.26
Shaft
6 Terrace - From Shaft B12 to B06 150 54 0 1 1.8 1.8 55.8 910 5.123 2.86
7 Terrace - From Shaft B06 to B03 125 37 0 1 1.6 1.6 38.6 510 4.371 1.69
8 Terrace - From Shaft B03 to B01 100 33 3 3 9 1 1.5 1.5 43.5 250 3.315 1.44
9 Shaft B01 100 2 0 1 1.5 1.5 3.5 185 1.997 0.07
10 Shaft B01 & Burried to TMB &TMB 80 85 6 2.7 16.2 0 101.2 120 3.433 3.47
12 AHU Inlet Tapping 65 12 2 1.2 2.4 1 0.9 0.9 0 0 0 1 11 11 1 21 21 0 47.3 60 2.7 1.28
13 AHU 7500 CFM PRESSURE DROP 0 0 0 0 0 0 0 0 0 1.50
14 AHU out let Tapping 65 12 5 1.2 6 4 0.9 3.6 0 0 0 0 11 0 0 21 0 0 21.6 60 2.7 0.58
16 Shaft B01 & Burried to TMB &TMB 80 84 6 2.7 16.2 0 100.2 120 3.433 3.44
17 Shaft B01 100 2 0 1 1.5 1.5 3.5 185 1.997 0.07
18 Terrace - From Shaft B01 to B03 100 33 3 3 9 1 1.5 1.5 43.5 250 3.315 1.44
19 Terrace - From Shaft B03 to B07 125 37 0 1 1.6 1.6 38.6 510 4.371 1.69
20 Terrace - From Shaft B07 to B12 150 54 0 1 1.8 1.8 55.8 910 5.123 2.86
21 Terrace - From B12 Shaft to shaft 200 63 2 4 8 1 2.6 2.6 73.6 1420 3.075 2.26
riser
22 Burried & Riser - From shaft riser to 200 40 8 4 32 0 72 1420 3.075 2.21
Pit
23 BURRIED line - From Pit to 400 16 0 7.9 0 0 16 3360 0.615 0.10
Plantroom trench
24 Primary Pump Header - From 400 25 5 7.9 39.5 0 64.5 3360 0.615 0.40
Trench to Primary pump Inlet
25 Air separator 400 0 1.00
26 Primary Pump Inlet Tapping 250 3.5 1 4.9 4.9 1 3.7 3.7 1 3.7 3.7 0 0 1 32 32 0 0 0 47.8 1680 1.35 0.65
TOTAL 34.6

TOTAL 34.6
TOTAL+10% 38.0

SELECTED HEAD 38M


UTILITY PROJECTS & SERVICES PVT. LTD.
Pressure Drop Calculation - Nxtra Data Centre
(PRIMARY PUMP) - 788 GPM (4W+1S)
2 WAY/MOT.
SL. BENDS BUTTERFLY Bellow NRV STRANIER BALANCING REDUCER TOTAL
SIZE DIA PIPE BUTT. VALVES FLOW FRICTION PR.HEAD
NO DESCRIPTION EQUILVALENT
in MM (MTS) NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS GPM LOSS (MTS)
. (MTS)
1 Pump Discharge 150 8 2 4.9 9.8 1 2.1 2.1 1 2.1 2.1 0 1 18 18 0 0 1 3.4 3.4 43.4 608 2.429 1.05
2 Pump Discharge Header 200 23.5 4 6.1 24.4 0 0 0 0 0 0 0 47.9 1216 2.288 1.10
3 Chiller suction 150 8 2 4.9 9.8 1 2.1 2.1 1 2.1 2.1 0 0 0 0 1 3.4 3.4 25.4 608 2.429 0.62
4 Chiller Discharge 150 8 2 4.9 9.8 1 2.1 2.1 1 2.1 2.1 1 2.1 2.1 0 0 1 52 52 1 3.4 3.4 79.5 608 2.429 1.93
5 Discharge Headder 200 30 5 6.1 30.5 2.7 0 0 0 0 0 0 0 60.5 1216 2.288 1.38
6 Header From PR to MPDS supply 200 13 1 6.1 6.1 2.7 0 0 1 4.6 4.6 23.7 1216 2.288 0.54
7 Header From PR to MPDS supply 150 218 8 4.9 39.2 2.1 257.2 373 1.8 4.63
8 MPDS Shaft Supply 100 18 1 3 3 1.4 21 133 1.081 0.23
9 Shaft to AHU Supply 65 60 2 1.8 3.6 0.9 1 1.5 1.5 65.1 54 2.281 1.48
10 AHU inlet 50 12 2 1.5 3 3 0.73 2.19 0 0 1 7.3 7.3 1 1.2 1.2 25.69 27 1.6 0.41
11 AHU Outlet 50 12 2 1.5 3 1 0.73 0.73 1 17 17 1 1.2 1.2 33.93 27 1.6 0.54
12 AHU Return to Shaft 65 40 2 1.8 3.6 0.9 0 0 0 0 1 1.5 1.5 45.1 54 2.281 1.03
13 MPDS Shaft Return 100 15 1 3 3 1.4 0 18 133 1.081 0.19
14 Header from MPDS to PR Return 150 218 8 4.9 39.2 2.1 0 0 0 0 0 257.2 373 1.8 4.63
15 Header From PR to MPDS Return 200 13 1 6.1 6.1 2.7 0 0 1 2.7 2.7 21.8 1216 2.288 0.50
16 PR pump Suction header 200 24 5 6.1 30.5 2.7 0 0 0 54.5 1216 2.288 1.25
17 Pump suction 150 8 3 4.9 14.7 1 2.1 2.1 1 2.1 2.1 1 21 21 0 1 3.4 3.4 51.3 608 2.429 1.25
18 Additional Header Length Supply 150 1 1 4.9 4.9 5.9 608 1.8 0.11
19 Additional Header Length Supply 150 1 1 4.9 4.9 5.9 608 1.8 0.11
20 AHU Pressure Drop 0 0 0 0 0 0 0.50
21 Pump Pressure Drop 0 0 0 0 1.00
22 AHU 3 way valve 4.00
23 Chiller Pressure Drop 5.05
TOTAL 33.5

TOTAL 33.5
TOTAL+10% 36.9

SELECTED HEAD 40 M
Pressure Drop Calculation (LOOP TO LCSS1) - Tata Steel
2 WAY/MOT.
SL. BENDS BUTTERFLY Bellow NRV STRANIER BALANCING REDUCER TOTAL
SIZE DIA PIPE BUTT. VALVES FLOW FRICTION PR.HEAD
NO DESCRIPTION EQUILVALENT
in MM (MTS) NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS GPM LOSS (MTS)
. (MTS)
1 Pump Discharge 150 8 2 4.9 9.8 1 2.1 2.1 1 2.1 2.1 0 1 18 18 0 0 1 3.4 3.4 43.4 608 2.429 1.05
2 Pump Discharge Header 200 23.5 4 6.1 24.4 0 0 0 0 0 0 0 47.9 1216 2.288 1.10
3 Chiller suction 150 8 2 4.9 9.8 1 2.1 2.1 1 2.1 2.1 0 0 0 0 1 3.4 3.4 25.4 608 2.429 0.62
4 Chiller Discharge 150 8 2 4.9 9.8 1 2.1 2.1 1 2.1 2.1 1 2.1 2.1 0 0 1 52 52 1 3.4 3.4 79.5 608 2.429 1.93
5 Discharge Headder 200 30 5 6.1 30.5 0 0 0 0 0 0 0 60.5 1216 2.288 1.38
6 Header From PR to MPDS supply 200 13 1 6.1 6.1 0 0 1 4.6 4.6 23.7 1216 2.288 0.54
7 Header From MPDS to LCSS 2 supply 200 58 4 6.1 24.4 82.4 843 1.1444 0.94
8 Header LCSS2 to LCSS1 150 152 8 4.9 39.2 191.2 221 0.7 1.34
9 Shaft to AHU Supply 100 40 4 3 12 1 1.5 1.5 53.5 102.6 0.7 0.37
10 AHU inlet 65 12 3 1.8 5.4 3 0.9 2.7 0 0 1 8.8 8.8 1 1.2 1.2 30.1 53 2.12 0.64
11 AHU Outlet 65 12 3 1.8 5.4 1 0.9 0.9 1 21 21 1 1.2 1.2 40.5 53 2.12 0.86
12 AHU Return to Shaft 100 60 2 3 6 0 0 0 0 1 1.5 1.5 67.5 102.6 0.7 0.47
13 Header LCSS1 to LCSS2 return 150 152 8 4.9 39.2 191.2 221 0.7 1.34
14 Header LCSS 2 to MPDS tapping 200 58 1 6.1 6.1 0 64.1 843 1.1444 0.73
15 Header from MPDS to PR Return 200 13 4 6.1 24.4 0 0 0 0 0 37.4 1216 2.288 0.86
16 PR pump Suction header 200 30 5 6.1 30.5 0 0 0 60.5 1216 2.288 1.38
17 Pump suction 150 8 3 4.9 14.7 1 2.1 2.1 1 2.1 2.1 1 21 21 0 1 3.4 3.4 51.3 608 2.429 1.25
18 Additional Header Length Supply 100 1.5 1 4.9 4.9 6.4 221 0.7 0.04
19 Additional Header Length Supply 100 1.5 1 4.9 4.9 6.4 221 0.7 0.04
20 AHU Pressure Drop 0 0 0 0 0 0 1.60
21 Pump Pressure Drop 0 0 0 0 1.00
22 AHU 3 way valve 4.00
23 Chiller Pressure Drop 5.05
TOTAL 28.5

TOTAL 28.5
TOTAL+10% 31.4

SELECTED HEAD 40 M
UTILITY PROJECTS & SERVICES PVT. LTD.
Pressure Drop Calculation - Al-Muhaidib
(SECONDARY PUMP)
2 WAY/MOT.
SL. BENDS BUTTERFLY Bellow NRV STRANIER BALANCING REDUCER TOTAL
SIZE DIA PIPE BUTT. VALVES FLOW FRICTION PR.HEAD
NO DESCRIPTION EQUILVALENT
in MM (MTS) NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS GPM LOSS (MTS)
. (MTS)
1 Secondary Pump Outlet Tapping 250 2.8 0 0 1 3.7 3.7 1 3.7 3.7 0 1 30 30 0 0 1 2.6 2.6 42.8 1680 1.35 0.58
2 Secondary Pump Header to Plant 400 24.99 5 7.9 39.5 0 0 0 0 0 0 0 64.49 3360 0.615 0.40
room Trench
3 BURRIED line - From Plantroom 400 15.8 0 7.9 0 0 15.8 3360 0.615 0.10
trench to Pit (Building side)
4 Burried & Riser - From Pit to shaft 200 40 8 4 32 0 72 1420 3.2 2.30
riser
5 Terrace - From shaft riser to B12 200 81 2 4 8 1 2.6 2.6 91.6 1420 3.2 2.93
Shaft
6 Terrace - From Shaft B12 to B06 150 47 0 1 1.8 1.8 48.8 770 4.091 2.00
7 Terrace - From Shaft B06 to B02 125 41 0 1 1.6 1.6 42.6 445 3.818 1.63
8 Terrace - From Shaft B02 to B01 100 8 3 3 9 1 1.5 1.5 18.5 250 2.646 0.49
9 Shaft B01 100 2 0 1 1.5 1.5 3.5 185 2.646 0.09
10 Shaft B01 & Burried to TMB &TMB 100 54 6 2.7 16.2 0 70.2 143 1.523 1.07
12 TMB 65 54 4 1.2 4.8 0.9 0 0 0 0 0 58.8 64 2.7 1.91
13 TMB 40 28 6 0 0 0 0 0 0 0 0 1.68
14 AHU INLET TAPPING 25 2.35
15 FCU KITCHEN PRESSURE DROP 2.76
19 Shaft B01 & Burried to TMB &TMB 100 84 6 2.7 16.2 0 100.2 143 2.8 1.97
20 Shaft B01 100 2 0 1 1.5 1.5 3.5 185 2.646 0.09
21 Terrace - From Shaft B01 to B02 100 8 3 3 9 1 1.5 1.5 18.5 250 2.646 0.49
22 Terrace - From Shaft B02 to B06 125 41 0 1 1.6 1.6 42.6 445 3.818 1.63
23 Terrace - From Shaft B06 to B12 150 47 0 1 1.8 1.8 48.8 770 4.091 2.00
24 Terrace - From B12 Shaft to shaft 200 81 2 4 8 1 2.6 2.6 91.6 1420 3.2 2.93
riser
25 Burried & Riser - From shaft riser to 200 40 8 4 32 0 72 1420 3.2 2.30
Pit
26 BURRIED line - From Pit to 400 16 0 7.9 0 0 16 3360 0.615 0.10
Plantroom trench
27 Primary Pump Header - From 400 25 5 7.9 39.5 0 64.5 3360 0.615 0.40
Trench to Primary pump Inlet
28 Air separator 400 0 1.00
29 Primary Pump Inlet Tapping 250 3.5 1 4.9 4.9 1 3.7 3.7 1 3.7 3.7 0 0 1 32 32 0 0 0 47.8 1680 1.35 0.65
TOTAL 33.8

TOTAL 33.8
TOTAL+10% 37.2

SELECTED HEAD 38
(CONDENSOR PUMP)
2 WAY/MOT.
SL. BENDS BUTTERFLY Bellow NRV STRANIER BALANCING REDUCER TOTAL
SIZE DIA PIPE BUTT. VALVES FRICTION PR.HEAD
NO DESCRIPTION EQUILVALENT
in MM (MTS) NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS NOS EQUI. MTRS LOSS (MTS)
. (MTS)

1 Condensor Pump INlet Tapping 300 1.5 0 0 1 4 4 1 4 4 0 30 0 1 40 40 0 1 5.5 5.5 55 2.5 1.38

2 Condensor Pump Header to CT 600 27 1 7.9 7.9 0 0 0 0 0 0 0 34.9 0.4 0.14

1 CT Outlet Tapping 300 1.5 0 0 1 4 4 1 4 4 1 98 98 30 0 0 0 1 5.5 5.5 113 2.5 2.83

3 Chiller inlet Tapping 300 9.5 1 5.8 5.8 1 4 4 0 0 0 0 19.3 2.5 0.48
0 0 TOTAL 4.8

TOTAL 4.8 m 15.81649 ft

You might also like