External Static Pressure Calculations:

Project: SOMEWHERE RESTAURANT UNIT GL9,10 & 11 @ MARINA MALL, ABU DHABI, UAE

Unit Ref :KEF-1


Duct & Fittings : 0.16
Hood Connection 0.60
Louver 0.30
S.Total : 1.06
Safety 25% : 0.26
Total ESP : 1.32 WG inches
331.16 Pa
Fan Tag -

Total Friction Total


Duct size Airflow Airflow
R.No. Area Description Length M Length Loss in Friction
mm x mm lps cfm
Ft WG Loss in WG

1 GF Straight Duct 300 200 210.00 444.78 1.50 3.28 4.92 0.082 0.004
90 Degree
2 GF 300 200 210.00 444.78 3.28 20.00 0.082 0.016
Bend
3 GF Straight Duct 300 200 210.00 444.78 6.00 3.28 19.68 0.082 0.016

4 GF VCD 0.040

5 GF Reducer - 5.00 0.082 0.004

6 GF Straight Duct 800 550 2,234.00 4,731.61 2.00 3.28 6.56 0.048 0.003
90 Degree
7 GF 800 550 2,234.00 4,731.61 3.28 20.00 0.048 0.010
Bend
8 GF Reducer - 5.00 0.048 0.002

9 GF Straight Duct 800 650 2,545.00 5,390.31 3.00 3.28 9.84 0.040 0.004

10 GF Expansion 900 600 - 3.28 5.00 0.037 0.002

11 GF Expansion 900 600 - 3.28 5.00 0.037 0.002

12 GF Reducer - 5.00 0.040 0.002

13 GF Straight Duct 900 500 2,545.00 5,390.31 5.00 3.28 16.40 0.060 0.010
90 Degree
14 SHAFT 900 500 - 3.28 20.00 0.060 0.012
Bend
15 SHAFT Straight Duct 900 600 2,545.00 5,390.31 7.00 3.28 22.96 0.037 0.008
90 Degree
16 SHAFT 900 600 - 3.28 20.00 0.037 0.007
Bend
17 ROOF Straight Duct 900 600 2,545.00 5,390.31 3.00 3.28 9.84 0.037 0.004
90 Degree
18 ROOF 900 600 - 3.28 20.00 0.037 0.007
Bend
19 ROOF Straight Duct 900 600 2,545.00 5,390.31 3.00 3.28 9.84 0.037 0.004

20 ROOF Expansion 900 600 - 3.28 5.00 0.037 0.002

0.160