You are on page 1of 7

EXTERNAL STATIC PRESSURE SUMMARY

CALCULATED ESP
SR.NO UNIT NO. CFM CMH in of wc mm 0f wc pascal
HRV 2nd F-01 172
1 338 574.6 0.69 18
HRV 1st F-01 208
2 674 1145.8 0.83 21
3 HRV Gr F-01 945 1606.5 0.79 20 198
4 HRV Gr F-02 541 919.7 0.64 16 159
5 HRV Gr F-03 1170 1989 0.68 17 170
SELECTED MODEL
HRV PLUS-750
HRV PLUS-2000
HRV PLUS-2000
HRV PLUS-1000
HRV PLUS-2500
PROJECT: ERBIL BANK SITE : BAGHDAD Date : 11-Jan-20
UNIT.NO. : HRV MEZZANINE FLOOR BUILDING : BANK Revision : 1
Rev.0
GENERAL DATA By MOHSIN
DUCT MATERIAL : PRE INSULATD DUCT
ROUGHNESS COEF. :
ALTITUDE : 0 Meters
ALTITUDE COEF. : 0.000
AIR DENSITY : 1.09 Kg/m3
DUCTS PRESSURE LOSSES TABLE External Static Pressure for Supply MEZZANINE floor

SECTION 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 TOTAL

FLOW CFM 338 338 238 128


FLOW M3/H 574.6 574.6 404.6 217.6 0 0 0 0 0 0 0
LENGTH M 5.13 0.27 12.42 22.28 40.1 ml
DIAM. mm 254.00 254.00 231.00 197.00 159.00 100.00 756.00 756.00 756.00 756.00 456.00
DIAM. EQUIV. 254.00 254.00 231.00 197.00 159.00 100.00 756.00 756.00 756.00 756.00 456.00
WIDTH mm 220 200 200 150 100 100 800 800 800 800 500
HEIGHT mm 250 250 220 220 220 150 600 600 600 600 350
AREA M2 4.82 0.24 10.43 16.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00
VELOCITY M/S 5.00 5.80 5.80 5.80 5.30 5.30 5.30 5.30 5.30 5.30 4.00
PD per Meter Pa 1.31 1.71 1.92 2.34 2.57 4.53 0.38 0.38 0.38 0.38 0.43
PD x LENGTH Pa 6.70 0.46 23.89 52.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 83.09 Pa

Co 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 TOTAL
ELBOW 30° 0.0945
ELBOW 45° 0.9585
ELBOW 90° 0.3105 2 2
TEE 45° 0.405
TEE 90° 1.5
END TEE 2.025
BRANCH TEE 0.0675 2 2
TRANSITION 0.297 1 1
CONTRACTION 0.065 1
WIRE MESH 0.06

TOTAL Co 0.30 0.30 0.82 0.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.17
DUCTS PD Pa 4.05 5.45 15.06 13.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 38.41 Pa
PRESSURE DROP Pa 10.75 5.91 38.95 65.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 121.51 Pa

SPECIAL FITTING PRESSURE DROPS 0.63 W.g


STATIC PRESSURE AT 100% 157 Pa
DESIGNATION PD (PA) QTY TOTAL FLOW AT 100% 575 m³/h
FIRE DAMPER 10 0 0 * DUCTS PRESSURE DROP : 122 Pa
VOLUME DAMPER 10 0 0 * FITTING PRESSURE DROP : 35 Pa
SUPPLY GRILL 10 1 10
RETURN GRILLE 10 0 0 0.69 W.g
FRESH AIR LOUVER 10 1 10 STATIC PRESSURE AT 110% 172 Pa
SAND TRAP LOUVER 100 0 0 FLOW AT 110% 632 m³/h
ALUMINUM FILTER 80 0 0 * DUCTS PRESSURE DROP : 134 Pa
BAG FILTER 150 0 0 * FITTING PRESSURE DROP : 39 Pa
GREASE FILTER 100 0 0
DUCT HEATER 5 0 0 0.75 W.g
DISC EXHAUST VALVE 70 0 0 STATIC PRESSURE AT 120% 188 Pa
FLEXIBLE DUCT CONNECTION 15 1 15 FLOW AT 120% 695 m³/h
SOUND ATTENUATOR 75 0 0 * DUCTS PRESSURE DROP : 146 Pa
TOTAL 35 Pa * FITTING PRESSURE DROP : 42 Pa

Calculated External Static Pressure is 139 Pa.


MAR ESP Calculation is 547 Pa.
PROJECT: ERBIL BANK SITE : BAGHDAD Date : 11-Jan-20
UNIT.NO. : HRV MEZZANINE FLOOR BUILDING : BANK Revision : 1
Rev.0
GENERAL DATA By MOHSIN
DUCT MATERIAL : PRE INSULATD DUCT
ROUGHNESS COEF. : 0.93
ALTITUDE : 0 Meters
ALTITUDE COEF. : 0.000
AIR DENSITY : 1.09 Kg/m3
DUCTS PRESSURE LOSSES TABLE External Static Pressure for RETURN mezzanine floor

SECTION 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 TOTAL

FLOW CFM 674 674 311 134 67


FLOW M3/H 1145.8 1145.8 528.7 227.8 113.9 0 0 0 0 0 0
LENGTH M 1.89 42.80 4.59 14.85 1.62 65.7 ml
DIAM. mm 320.00 320.00 254.00 230.00 160.00 756.00 756.00 756.00 756.00 756.00 456.00
DIAM. EQUIV. 320.00 320.00 254.00 230.00 160.00 756.00 756.00 756.00 756.00 756.00 456.00
WIDTH mm 400 400 250 200 100 800 800 800 800 800 500
HEIGHT mm 220 200 220 220 220 600 600 600 600 600 350
AREA M2 2.34 51.35 4.31 12.47 1.04 0.00 0.00 0.00 0.00 0.00 0.00
VELOCITY M/S 5.00 5.80 5.80 5.80 5.30 5.30 5.30 5.30 5.30 5.30 4.00
PD per Meter Pa 0.99 1.29 1.71 1.93 2.55 0.38 0.38 0.38 0.38 0.38 0.43
PD x LENGTH Pa 1.86 55.31 7.86 28.72 4.14 0.00 0.00 0.00 0.00 0.00 0.00 97.89 Pa

Co 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 TOTAL
ELBOW 30° 0.105 1
ELBOW 45° 0.9585
ELBOW 90° 0.3105 4 1 1 1
TEE 45° 0.405
TEE 90° 1.35
END TEE 2.025
BRANCH TEE 0.0675 3 1
TRANSITION 0.297 1 1
CONTRACTION 0.0675 1
WIRE MESH 0.054

TOTAL Co 0.40 1.74 0.45 0.31 0.31 0.00 0.00 0.00 0.00 0.00 0.00 3.21
DUCTS PD Pa 5.48 31.94 8.17 5.69 4.75 0.00 0.00 0.00 0.00 0.00 0.00 56.03 Pa
PRESSURE DROP Pa 7.34 87.25 16.03 34.41 8.89 0.00 0.00 0.00 0.00 0.00 0.00 153.92 Pa

SPECIAL FITTING PRESSURE DROPS 0.76 W.g


STATIC PRESSURE AT 100% 189 Pa
DESIGNATION PD (PA) QTY TOTAL FLOW AT 100% 1146 m³/h
FIRE DAMPER 10 0 0 * DUCTS PRESSURE DROP : 154 Pa
VOLUME DAMPER 10 0 0 * FITTING PRESSURE DROP : 35 Pa
SUPPLY DISC 10 1 10
RETURN DISC 10 0 0 0.83 W.g
FRESH AIR LOUVER 10 1 10 STATIC PRESSURE AT 110% 208 Pa
SAND TRAP LOUVER 100 0 0 FLOW AT 110% 1260 m³/h
ALUMINUM FILTER 80 0 0 * DUCTS PRESSURE DROP : 169 Pa
BAG FILTER 150 0 0 * FITTING PRESSURE DROP : 39 Pa
GREASE FILTER 100 0 0
DUCT HEATER 5 0 0 0.91 W.g
DISC EXHAUST VALVE 70 0 0 STATIC PRESSURE AT 120% 227 Pa
FLEXIBLE DUCT CONNECTION 15 1 15 FLOW AT 120% 1386 m³/h
SOUND ATTENUATOR 75 0 0 * DUCTS PRESSURE DROP : 185 Pa
TOTAL 35 Pa * FITTING PRESSURE DROP : 42 Pa

Calculated External Static Pressure is 139 Pa.


MAR ESP Calculation is 547 Pa.
PROJECT: ERBIL BANK SITE : BAGHDAD Date : 11-Jan-20
UNIT.NO. : HRV FIRST FLOOR BUILDING : BANK Revision : 1
Rev.0
GENERAL DATA By MOHSIN
DUCT MATERIAL : PRE INSULATD DUCT
ROUGHNESS COEF. : 0.93
ALTITUDE : 0 Meters
ALTITUDE COEF. : 0.000
AIR DENSITY : 1.09 Kg/m3
DUCTS PRESSURE LOSSES TABLE External Static Pressure for Supply first floor

SECTION 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 TOTAL

FLOW CFM 945 945 675 432 224


FLOW M3/H 1606.5 1606.5 1147.5 734.4 380.8 0 0 0 0 0 0
LENGTH M 1.35 12.15 14.85 12.15 8.64 49.1 ml
DIAM. mm 385.00 385.00 320.00 280.00 230.00 756.00 756.00 756.00 756.00 756.00 456.00
DIAM. EQUIV. 385.00 385.00 320.00 280.00 230.00 756.00 756.00 756.00 756.00 756.00 456.00
WIDTH mm 600 600 400 300 200 800 800 800 800 800 500
HEIGHT mm 220 220 220 220 220 600 600 600 600 600 350
AREA M2 2.21 19.93 18.41 12.64 7.26 0.00 0.00 0.00 0.00 0.00 0.00
VELOCITY M/S 5.00 5.80 5.80 5.80 5.30 5.30 5.30 5.30 5.30 5.30 4.00
PD per Meter Pa 0.79 1.03 1.29 1.52 1.64 0.38 0.38 0.38 0.38 0.38 0.43
PD x LENGTH Pa 1.06 12.53 19.19 18.48 14.17 0.00 0.00 0.00 0.00 0.00 0.00 65.44 Pa

Co 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 TOTAL
ELBOW 30° 0.0945
ELBOW 45° 0.9585
ELBOW 90° 0.3105 2 1 1 1 1
TEE 45° 0.405
TEE 90° 1.5
END TEE 2.025 1
BRANCH TEE 0.0675 1 1
TRANSITION 0.297 1 1
CONTRACTION 0.065
WIRE MESH 0.06

TOTAL Co 0.92 0.31 0.68 2.40 0.31 0.00 0.00 0.00 0.00 0.00 0.00 4.62
DUCTS PD Pa 12.50 5.69 12.38 44.07 4.75 0.00 0.00 0.00 0.00 0.00 0.00 79.40 Pa
PRESSURE DROP Pa 13.56 18.23 31.57 62.55 18.92 0.00 0.00 0.00 0.00 0.00 0.00 144.84 Pa

SPECIAL FITTING PRESSURE DROPS 0.72 W.g


STATIC PRESSURE AT 100% 180 Pa
DESIGNATION PD (PA) QTY TOTAL FLOW AT 100% 1607 m³/h
FIRE DAMPER 10 0 0 * DUCTS PRESSURE DROP : 145 Pa
VOLUME DAMPER 10 0 0 * FITTING PRESSURE DROP : 35 Pa
SUPPLY GRILLE 10 1 10
RETURN GRILLE 10 0 0 0.79 W.g
FRESH AIR LOUVER 10 1 10 STATIC PRESSURE AT 110% 198 Pa
SAND TRAP LOUVER 100 0 0 FLOW AT 110% 1767 m³/h
ALUMINUM FILTER 80 0 0 * DUCTS PRESSURE DROP : 159 Pa
BAG FILTER 150 0 0 * FITTING PRESSURE DROP : 39 Pa
GREASE FILTER 100 0 0
DUCT HEATER 5 0 0 0.87 W.g
DISC EXHAUST VALVE 70 0 0 STATIC PRESSURE AT 120% 216 Pa
FLEXIBLE DUCT CONNECTION 15 1 15 FLOW AT 120% 1944 m³/h
SOUND ATTENUATOR 75 0 0 * DUCTS PRESSURE DROP : 174 Pa
TOTAL 35 Pa * FITTING PRESSURE DROP : 42 Pa

Calculated External Static Pressure is 139 Pa.


MAR ESP Calculation is 547 Pa.
PROJECT: ERBIL BANK SITE : BAGHDAD Date : 11-Jan-20
UNIT.NO. : HRV FIRST FLOOR BUILDING : BANK Revision : 1
Rev.0
GENERAL DATA By MOHSIN
DUCT MATERIAL : PRE INSULATD DUCT
ROUGHNESS COEF. : 0.93
ALTITUDE : 0 Meters
ALTITUDE COEF. : 0.000
AIR DENSITY : 1.09 Kg/m3
DUCTS PRESSURE LOSSES TABLE External Static Pressure for RETURN first floor

SECTION 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 TOTAL

FLOW CFM 541 541 416 416


FLOW M3/H 919.7 919.7 707.2 707.2 0 0 0 0 0 0 0
LENGTH M 3.38 12.15 14.85 1.35 31.7 ml
DIAM. mm 280.00 280.00 254.00 310.00 133.00 756.00 756.00 756.00 756.00 756.00 456.00
DIAM. EQUIV. 280.00 280.00 254.00 310.00 133.00 756.00 756.00 756.00 756.00 756.00 456.00
WIDTH mm 300 300 250 600 100 800 800 800 800 800 500
HEIGHT mm 220 220 220 150 150 600 600 600 600 600 350
AREA M2 3.51 12.64 13.96 2.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00
VELOCITY M/S 5.00 5.80 5.80 5.80 5.30 5.30 5.30 5.30 5.30 5.30 4.00
PD per Meter Pa 1.16 1.52 1.71 1.34 3.20 0.38 0.38 0.38 0.38 0.38 0.43
PD x LENGTH Pa 3.92 18.48 25.44 1.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 49.66 Pa

Co 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 TOTAL
ELBOW 30° 0.105
ELBOW 45° 0.9585
ELBOW 90° 0.3105 2 3
TEE 45° 0.405
TEE 90° 1.35
END TEE 2.025 1
BRANCH TEE 0.0675 1
TRANSITION 0.297 1 1
CONTRACTION 0.0675 1
WIRE MESH 0.054

TOTAL Co 0.92 0.43 2.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.31
DUCTS PD Pa 12.50 7.92 54.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 74.65 Pa
PRESSURE DROP Pa 16.42 26.41 79.66 1.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 124.30 Pa

SPECIAL FITTING PRESSURE DROPS 0.64 W.g


STATIC PRESSURE AT 100% 159 Pa
DESIGNATION PD (PA) QTY TOTAL FLOW AT 100% 920 m³/h
FIRE DAMPER 10 0 0 * DUCTS PRESSURE DROP : 124 Pa
VOLUME DAMPER 10 0 0 * FITTING PRESSURE DROP : 35 Pa
SUPPLY GRILLE 10 1 10
RETURN GRILLE 10 0 0 0.70 W.g
FRESH AIR LOUVER 10 1 10 STATIC PRESSURE AT 110% 175 Pa
SAND TRAP LOUVER 100 0 0 FLOW AT 110% 1012 m³/h
ALUMINUM FILTER 80 0 0 * DUCTS PRESSURE DROP : 137 Pa
BAG FILTER 150 0 0 * FITTING PRESSURE DROP : 39 Pa
GREASE FILTER 100 0 0
DUCT HEATER 5 0 0 0.77 W.g
DISC EXHAUST VALVE 70 0 0 STATIC PRESSURE AT 120% 191 Pa
FLEXIBLE DUCT CONNECTION 15 1 15 FLOW AT 120% 1113 m³/h
SOUND ATTENUATOR 75 0 0 * DUCTS PRESSURE DROP : 149 Pa
TOTAL 35 Pa * FITTING PRESSURE DROP : 42 Pa

Calculated External Static Pressure is 139 Pa.


MAR ESP Calculation is 547 Pa.
PROJECT: ERBIL BANK SITE : BAGHDAD Date : 11-Jan-20
UNIT.NO. : HRV FIRST FLOOR BUILDING : BANK Revision : 1
Rev.0
GENERAL DATA By MOHSIN
DUCT MATERIAL : PRE INSULATD DUCT
ROUGHNESS COEF. : 0.93
ALTITUDE : 0 Meters
ALTITUDE COEF. : 0.000
AIR DENSITY : 1.09 Kg/m3
DUCTS PRESSURE LOSSES TABLE External Static Pressure for Supply second floor

SECTION 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 TOTAL

FLOW CFM 1170 1170 1050 40


FLOW M3/H 1989 1989 1785 0 68 0 0 0 0 0 0
LENGTH M 1.35 28.35 1.62 31.3 ml
DIAM. mm 385.00 385.00 310.00 197.00 159.00 756.00 756.00 756.00 756.00 756.00 456.00
DIAM. EQUIV. 385.00 385.00 310.00 197.00 159.00 756.00 756.00 756.00 756.00 756.00 456.00
WIDTH mm 600 600 600 150 100 800 800 800 800 800 500
HEIGHT mm 220 220 150 220 220 600 600 600 600 600 350
AREA M2 2.21 46.49 2.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
VELOCITY M/S 5.00 5.80 5.80 5.80 5.30 5.30 5.30 5.30 5.30 5.30 4.00
PD per Meter Pa 0.79 1.03 1.34 2.34 2.57 0.38 0.38 0.38 0.38 0.38 0.43
PD x LENGTH Pa 1.06 29.24 2.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 32.48 Pa

Co 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 TOTAL
ELBOW 30° 0.0945
ELBOW 45° 0.9585 2
ELBOW 90° 0.3105 1
TEE 45° 0.405
TEE 90° 1.5
END TEE 2.025 1
BRANCH TEE 0.0675 1
TRANSITION 0.297 1 1
CONTRACTION 0.065
WIRE MESH 0.06

TOTAL Co 0.61 4.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.91
DUCTS PD Pa 8.27 78.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 87.26 Pa
PRESSURE DROP Pa 9.34 108.22 2.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 119.74 Pa

SPECIAL FITTING PRESSURE DROPS 0.62 W.g


STATIC PRESSURE AT 100% 155 Pa
DESIGNATION PD (PA) QTY TOTAL FLOW AT 100% 1989 m³/h
FIRE DAMPER 10 0 0 * DUCTS PRESSURE DROP : 120 Pa
VOLUME DAMPER 10 0 0 * FITTING PRESSURE DROP : 35 Pa
SUPPLY GRILLE 10 1 10
RETURN GRILLE 10 0 0 0.68 W.g
FRESH AIR LOUVER 10 1 10 STATIC PRESSURE AT 110% 170 Pa
SAND TRAP LOUVER 100 0 0 FLOW AT 110% 2188 m³/h
ALUMINUM FILTER 80 0 0 * DUCTS PRESSURE DROP : 132 Pa
BAG FILTER 150 0 0 * FITTING PRESSURE DROP : 39 Pa
GREASE FILTER 100 0 0
DUCT HEATER 5 0 0 0.75 W.g
DISC EXHAUST VALVE 70 0 0 STATIC PRESSURE AT 120% 186 Pa
FLEXIBLE DUCT CONNECTION 15 1 15 FLOW AT 120% 2407 m³/h
SOUND ATTENUATOR 75 0 0 * DUCTS PRESSURE DROP : 144 Pa
TOTAL 35 Pa * FITTING PRESSURE DROP : 42 Pa

You might also like