You are on page 1of 8

1734 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO.

3, JULY 2010

Optimal Capacitor Placement and Sizing in


Unbalanced Distribution Systems With Harmonics
Consideration Using Particle Swarm Optimization
Abdelsalam A. Eajal, Student Member, IEEE, and M. E. El-Hawary, Life Fellow, IEEE

Abstract—Shunt capacitors installation in distribution systems systems supply single and three-phase loads through distribu-
requires optimal placement and sizing. More harmonics are being tion transformers. Second, the phases of transmission lines are
injected into distribution systems. Adding shunt capacitors may unequally loaded. Third, unlike those in transmission systems
lead to high distortion levels. The capacitor placement and sizing
problem is a nonlinear integer optimization problem, with loca- overhead lines in distribution systems are not transposed.
tions and ratings of shunt capacitors being discrete values. The goal Due to the widespread use of harmonic-producing equipment
is to minimize the overall cost of the total real power loss and that in distribution systems, harmonics are propagated throughout
of shunt capacitors while satisfying operating and power quality those systems. Harmonics are undesirable and cause equipment
constraints. This paper proposes to solve the problem using par- overheating due to the excessive losses and potential malfunc-
ticle swarm optimization (PSO). A discrete version of PSO is com-
bined with a radial distribution power flow algorithm (RDPF) to tioning of electric equipment. Inclusion of shunt capacitors
form a hybrid PSO algorithm (HPSO). The former is employed without considering the presence of harmonic sources in the
as a global optimizer to find the global optimal solution, while the system may lead to an increase in harmonic distortion levels
latter is used to calculate the objective function and to verify bus due to resonance between capacitors and the various inductive
voltage limits. To include the presence of harmonics, the devel- elements in the system.
oped HPSO was integrated with a harmonic power flow algorithm
(HPF). The proposed (HPSO-HPF)-based approach is tested on an Baghzouz developed a local variations-based heuristic ap-
IEEE 13-bus radial distribution system (13-Bus-RDS). The find- proach to find the global optimal ratings of shunt capacitors such
ings clearly demonstrate the necessity of including harmonics in that the cost of total real power loss and that of shunt capacitors
optimal capacitor placement and sizing to avoid any possible prob- were minimized [1]. The optimal capacitor sizing problem was
lems associated with harmonics. formulated as a nonlinear integer programming problem with
Index Terms—Harmonics, particle swarm, shunt capacitors. inequality constraints. The constraints considered were the rms
values of bus voltages and total harmonic distortions. The only
harmonic source assumed was the utility substation. A heuristic
I. INTRODUCTION
algorithm based on local variations was proposed to overcome
the prohibitive computational time associated with considering

S HUNT capacitors are commonly used in distribution


systems to reduce power losses, improve voltage profile,
and release system capacity. The achievement of such bene-
every single potential capacitor size at a given iteration. Yan ac-
counted for the presence of harmonic-producing loads in dis-
tribution systems [2]. A hybrid differential evolution algorithm
fits among other benefits depends greatly on how optimally was developed to optimally locate and rate shunt capacitors in
these shunt capacitors are installed. Studies have indicated distorted distribution systems. A sensitivity test was done prior
that approximately 13% of generated power is consumed as to the optimization process to determine the candidate buses
loss at the distribution level. In addition, with the application for reactive power compensation. The objective was to mini-
of loads, the voltage profile tends to drop along distribution mize the cost of real power losses and that of shunt capacitors
feeders below acceptable operating limits. Along with power while satisfying some practical constraints. The results indi-
losses and voltage drops, the increasing growth in electricity cated that neglecting the presence of harmonic sources could
demand requires upgrading the infrastructure of distribution cause a severe harmonic distortion problem. Carpinelli et al.
systems. Shunt capacitors can be of great help in enhancing the solved the capacitor placement and sizing problem in a way that
performance of distribution systems. Distribution systems are the overall cost was minimized [3]. The cost function involved
inherently unbalanced for several reasons. First, distribution the cost of real power losses, shunt capacitors, and harmonic dis-
tortions. An approximate power flow method and a linear har-
monic power flow method were used to calculate the cost func-
Manuscript received June 27, 2009. Current version published June 23, 2010. tion at the fundamental and various harmonic frequencies.
Paper no. TPWRD-00359-2008.
Another optimization technique used to solve the optimal
A. A. Eajal is with the Department of Electrical Engineering University of
Altahadi, Sirt, Libya (e-mail: eajal2000@yahoo.com). capacitor placement and sizing problem is genetic algorithms
M. E. El-Hawary is with the Department of Electrical Engineering, Dalhousie (GA). Abou-Ghazala proposed a GA to find the best combi-
University, Halifax, NS, Canada (e-mail: elhawary@dal.ca). nation of locations and ratings of shunt capacitors such that
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. the total net savings were maximized [4]. Loss reduction was
Digital Object Identifier 10.1109/TPWRD.2009.2035425 achieved through the proper installation of shunt capacitors
0885-8977/$26.00 © 2010 IEEE
EAJAL AND EL-HAWARY: OPTIMAL CAPACITOR PLACEMENT AND SIZING 1735

while rms values of bus voltages and total harmonic distortions problem with both locations and sizes of shunt capacitors
being kept within allowable limits. Nikham et al. also used a being discrete. The objective function encompasses the total
genetic algorithm to solve the optimal capacitor allocation and cost of the total real power loss and that of shunt capacitors.
sizing problem taking the presence of harmonic sources into The objective function is restricted by equality and inequality
account [5]. The objective function consisted of the cost of real constraints.
power losses and that of shunt capacitors to be installed. The Objective Function: The goal is to minimize the cost of the
cost associated with the reactive power injection was fixed for total real power loss and that of the shunt capacitor installation.
all possible capacitor sizes. In other words, the cost of the re- The cost function is given by
active power injected was assumed to be constant independent
of the capacitor size. Masoum et al. developed a hybrid tool (1)
based on maximum sensitivity selection (MSS) and local vari-
ations (LV) to solve the optimal capacitor placement and sizing
problem [6]. The former was used to enhance the convergence where
speed by narrowing down the search space, while the latter was
annual cost per unit of the real power loss
employed to find the global optimal solution. Three harmonic
($/kW/year);
distortion levels were considered for the system investigated.
The system under investigation involved only one harmonic annual cost per unit of the reactive power injection
source and that was a six-plus converter. The results of the at bus i ($/kVAR/year);
hybrid MSS-LV algorithm were compared with those of the reactive power injection at bus i (kVAR);
MSS-based algorithm. In later work, Masoum et al. applied
a fuzzy logic-based algorithm to solve the same problem [7]. total number of shunt capacitors to be installed;
Both the objective function and the constraints were fuzzified. total real power loss (kW).
Alpha cuts were used to direct the search process and to ensure
that the objective function improved each time. The candidate The total real power loss is defined by
buses were determined according to the objective function,
constraints and reactive power compensation sensitivities. Two
harmonic distortion levels were considered this time to compare
the results obtained with those obtained by the MSS-based al-
gorithm. A conclusion was drawn that the appropriate locations (2)
and ratings of shunt capacitors would not only improve voltage where
profiles but also would reduce harmonic distortion levels.
Masousm et al. took advantage of the capability of genetic number of branches;
algorithms (GAs) to escape local optima [8]. Improvements smallest harmonic order of interest;
in voltage profiles and power quality were achieved through
the proper installation of fixed shunt capacitors in distorted highest harmonic order of interest.
distribution systems. The applicability of GA-based approach The fundamental component of the total real power loss is
was proven to yield to better results compared to the previous calculated using a three phase power flow algorithm (RDPF)
work done by the same authors. [11].
Another method based on particle swarm optimization (PSO) The harmonic component of the total real power loss is com-
was offered in [9] to solve the capacitor placement and sizing puted by a harmonic power flow algorithm (HPF) [12].
problem considering harmonics. The problem was mathemati- Note that the harmonic component of the total real power loss
cally modeled as a nonconvex optimization problem. The ob- is small compared with the fundamental one. However, this por-
jective function was augmented by quadratic penalty functions tion of the total real power loss increases as harmonic-producing
to account for inequality constraints. That is, the objective func- loads continue to increase in RDS. Consequently, the undesir-
tion was penalized whenever the inequality constraints were vi- able presence of harmonics will cause more equipment over-
olated. The proposed PSO algorithm did not account for unbal- heating, stress on equipment insulation, and equipment failure.
anced operating conditions. Khalil et al. [10] proposed a binary Not to mention of course the interference with communication
PSO algorithm to find the best locations and ratings of fixed networks. It should be pointed out that the cost of the real power
shunt capacitors in balanced distribution systems. The only har- loss per unit is fixed. However, the cost of the reactive power in-
monic source considered was the substation voltage. Their ob- jection per unit varies from one capacitor size to another [1].
jective was to properly place and size shunt capacitors while Generally, the larger the capacitor size is, the cheaper it be-
keeping the cost of real power losses and that of shunt capacitors comes.
at a minimum. The objective function was subject to equality Constraints: Along with the objective function, there is an-
and inequality constraints. other significant part of the optimization model that needs to
be defined and that is the constraints. In real applications, there
II. PROBLEM FORMULATION are always limits on the choices of control variables. The con-
The optimal capacitor placement and sizing problem is straints considered in this research are of two types: equality and
formulated as a constrained nonlinear integer optimization inequality.
1736 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 3, JULY 2010

A. Equality Constraints itors that are commercially available come in discrete sizes. That
The equality constraints are those associated with the non- is, the shunt capacitors to be dealt with are multiple integers of
linear power flow equations. It is noted in many published pa- the smallest capacitor size available
pers that the power flow equations are the real and reactive
(7)
power mismatch equations. The reason for this is that modified
versions of conventional power flow programs such as Newton- where
Raphson method and Gauss Siedel method are widely used. In
this work, the power flow representation is based on bus current smallest capacitor size available.
injections and thus the equality constraints are the bus current
It is worth mentioning that the total reactive power injection is
mismatch equations. The equality constraints are expressed in a
not to exceed the total reactive power demand in RDS
vector form as follows:

(3) (8)

where:
where
vector of state (dependent) variables;
total reactive power demand.
vector of control (independent) variables.
III. PARTICLE SWARM OPTIMIZATION
B. Inequality Constraints
PSO is a metaheuristic optimization technique developed in
The inequality constraints are those associated with the bus 1995 by Kennedy and Eberhart [13]–[15]. The fundamental idea
voltages, total harmonic distortion levels, and shunt capacitors behind the PSO algorithm is that a population called a swarm is
to be installed. randomly generated. The swarm consists of individuals called
1) Bus Voltage Limits: The bus voltage magnitudes are to particles. Each particle in the swarm represents a potential solu-
be kept within acceptable operating limits throughout the opti- tion of the optimization problem. Each particle moves through
mization process a D-dimensional search space at a random velocity. Each par-
ticle updates its velocity and position according to the following
(4)
equations:
where

lower bound of bus voltage limits; (9)


upper bound of bus voltage limits; (10)
rms value of the th bus voltage and defined by where

inertia weight;
(5) acceleration constants;
two random numbers in the range of [0, 1];
where
best position ever visited by the particle at the
number of buses. th iteration;
The rms value of the th bus voltage involves only the funda- ;
mental component, the first term of (5), when harmonics are not global best position in the entire swarm;
of interest.
2) Total Harmonic Distortion Limits: The total harmonic dis- .
tortion at each bus is to be kept less or equal to the maximum
allowable harmonic distortion level as shown
IV. SOLUTION METHOD
(6) As one of this research objectives, a hybrid particle swam
optimization algorithm (HPSO) was developed to find the best
where combination of the locations and sizes of single phase shunt ca-
pacitors in unbalanced radial distribution systems (unbalanced-
maximum allowable harmonic distortion RDS). The HPSO algorithm combines a discrete version of PSO
level at each bus. with a three phase power flow algorithm (RDPF). The former
3) Number and Sizes of Shunt Capacitors: There are con- is employed as a global optimizer to optimally locate and rate
straints associated with the shunt capacitors themselves. Capac- shunt capacitors, while the latter is utilized to minimize the bus
EAJAL AND EL-HAWARY: OPTIMAL CAPACITOR PLACEMENT AND SIZING 1737

Fig. 2. Unbalanced-13-bus radial distribution system.

monic distortions. The flowchart of Fig. 1 illustrates the HPSO-


HPF-based algorithm that combines the HPF algorithm with the
HPSO algorithm.

V. RESULTS AND DISCUSSION


The three algorithms adopted in this work, namely, RDPF,
HPF, and PSO, were implemented in MATLAB computing en-
vironment on a Dell Laptop with Intel Pentium M processor
of 1.86 GHz and RAM of 1 GB. The developed algorithms
were tested on an unbalanced-13-bus radial distribution system
(unbalanced-13-bus-RDS) whose single line diagram shown in
Fig. 2. The unbalanced-13-bus-RDS consists of single, double,
Fig. 1. Flowchart of the HPSO-HP-based algorithm. and three phase lines and loads. The total real and reactive power
demand are 3464.1 kW and 1568.9 kVAR respectively. The
system loads are of two types, distributed loads and spot loads.
current mismatch equations (i.e., the power flow equations). The The only supply source in the system is the substation at bus
developed HPSO algorithm starts with generating a swarm of 1. Bus 1 is treated as a slack bus with a constant voltage on
particles randomly in the feasible region of the search space. each phase of its three phases. The other buses (2–13) are mod-
The feasible swarm is passed to the RDPF subroutine as ini- eled as PQ constant buses. A complete description of the system
tial guess to minimize bus current injection mismatch equa- can be found in [17]. The MVA base value is 10 and the line to
tions. Each particle recalls its best position associated with the line base voltage is the same as the feeder nominal voltage 4.16
best fitness value (i.e., the total cost). Each particle records the kV. The bus voltages are to be kept within 10% of the nom-
best position achieved by the entire swarm. The update process inal voltage throughout the optimization process. The cost of
of particles’ positions results in continuous values of particles’ real power losses is 168 U.S.$/kW/year, while the cost of the
positions. Thus, discretization of particles’ position vectors is installed capacitor is a function of the capacitor size [1]. Table I
made. Once the updated particles’ positions are discretized, the lists some commercially available capacitor sizes with their cor-
particles go through feasibility check to ensure that no particle responding costs [1].
flies outside the feasible region [16]. When the presence of har- The number of shunt capacitors to be installed is not to exceed
monics is considered, the total harmonic distortion limit at each 10 banks of a discrete size of 150 kVAR each. That is to say, the
bus is included as constraints in the optimization problem to en- total reactive power injection of these capacitors is not to exceed
sure that the harmonic distortion levels at all busses are within the total reactive power demand (1568.9 kVAR).
the allowable limits. A Harmonic power flow (HPF) subroutine To include the presence of harmonics, the developed HPSO
is incorporated with the HPSO algorithm to calculate the har- was integrated with a harmonic power flow algorithm (HPF).
monic bus voltages, harmonic real power losses, and total har- The proposed (HPSO-HPF) based approach is tested on the
1738 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 3, JULY 2010

TABLE I TABLE II
COMMERCIALLY AVAILABLE CAPACITOR SIZES RESULTS OF THE OPTIMAL PLACEMENT AND SIZING OF ONE SHUNT CAPACITOR
WITH THEIR CORRESPONDING COSTS IN A 13-BUS-RDS

same test system (13-Bus-RDS). For the distorted voltage-13-


Bus-RDS shown in Fig. 2, harmonic-producing loads, namely
fluorescent lighting, adjustable speed drives (ASD), and non-
specific sources such as PCs, TVs, and etc, are considered. The
typical harmonic spectrum of these nonlinear loads is provided
in [18]. All loads are treated as constant PQ spot loads for har- losses is reduced to 30,227 U.S.$/year, while in case 3 (after ca-
monic studies. Load composition in terms of harmonic sources pacitor installation with harmonics consideration), the cost of
is given in [18]. real power losses is reduced to 30,271 U.S.$/year. The net sav-
The developed HPSO-HPF-based approach is applied to find ings in case 2 (when harmonics are neglected) are slightly better
the optimal locations and sizes of shunt capacitors in an unbal- than those obtained in case 3 (when harmonics are considered).
anced-IEEE-13-bus radial distribution system (13-Bus-RDS) However, the maximum total harmonic distortion level of case
while taking harmonics into account. The total harmonic dis- 2 is much higher than that of case 3
tortion levels are to be maintained within 5% of the voltage .
value as recommended by the IEEE standard 519-1992. The total harmonic distortion reduction in case 3 with respect
In the presence of harmonics, three different cases are consid- to case 1 is
ered to investigate the impact of shunt capacitor installation on
the voltage profiles, total harmonic distortions, total real power
loss, and net savings.
• Case 1 represents the system with harmonics consideration
before capacitor installation.
• Case 2 represents the system without harmonics consider-
ation after capacitor installation.
The total harmonic distortion reduction in case 3 with respect to
• Case 3 represents the system with harmonics consideration
case 2 is
after capacitor installation.
The PSO parameters were tuned to enhance the performance
of the proposed algorithm. For one shunt capacitor to be in-
stalled, 20 independent runs were carried out for each PSO pa-
rameter. The maximum number of iterations was taken as 50 for
the tuning process of each parameter. It was found that the PSO
algorithm was less sensitive to its parameters for small problem
dimension (the problem dimension was the shunt capacitor lo- The reduction in the maximum total harmonic distortion level in
cation and size). However, the larger the problem dimension is, case 3 with respect to cases 1 and 2 justifies the inclusion of har-
the more sensitive the PSO algorithm becomes. A swarm size of monics in the optimal capacitor placement and sizing problem.
20 particles, acceleration constants of 2, and a particle’s max- In Table III, the optimal solution of the HPSO-HPF-based al-
imum velocity of 4 were selected. As for the inertia weight (w), gorithm for the optimal placement and sizing of one shunt ca-
it was reduced linearly from 0.9 to 0.4 as recommended in [19]. pacitor yields voltage profile improvement in both cases (2&3),
From the results shown in Table II, installing a shunt capac- (see columns 5 and 7 in Table III). However, installing a shunt
itor of 600 kVAR at phase c of bus 6 in case 2 will reduce the capacitor without taking harmonics into account (case2) caused
total real power losses from 192.7494 kW to 179.1373 kW and a severe harmonic distortion problem (i.e., harmonic distortion
profit the utility 2,099.694 U.S.$/year. The capacitor size re- levels at all load buses violate the maximum allowable distortion
quired to bring the violated bus voltages back within the max- level (5%)), (see column 6 in Table III). In contrast, recognizing
imum and minimum bus voltage limits are the same for cases the fact that harmonics are propagated throughout distribution
2 and 3, while the PSO-based algorithm selected phase c of systems and including their presence will keep the harmonic dis-
bus 5 to be the optimal location of the shunt capacitor in case tortion levels within the limits (see column 8 in Table III).
3. Before capacitor installation (case 1), the cost of real power The convergence characteristics of the proposed HPSO-HPF-
losses is 32,326.694 U.S.$/year. In case 2 (after capacitor instal- based approach for cases 2 and 3 in the optimal placement and
lation without harmonics consideration), the cost of real power sizing of one shunt capacitor problem with the total cost being
EAJAL AND EL-HAWARY: OPTIMAL CAPACITOR PLACEMENT AND SIZING 1739

TABLE III
VOLTAGE PROFILES AND TOTAL HARMONIC DISTORTIONS OF A 13-BUS-RDS
FOR CASES 1, 2, AND 3 OF THE OPTIMAL PLACEMENT AND SIZING OF ONE
SHUNT CAPACITOR

Fig. 3. Convergence characteristics of the HPSO-HPF-based algorithm for


case 2 in the optimal placement and sizing of one shunt capacitors.

Fig. 4. Convergence characteristics of the HPSO-HPF-based algorithm for


case 3 in the optimal placement and sizing of one shunt capacitors.

TABLE IV
RESULTS OF THE OPTIMAL PLACEMENT AND SIZING OF
THREE SHUNT CAPACITORS IN A 13-BUS-RDS

the objective are illustrated in Figs. 3 and 4 respectively. Both


Figures indicate the convergence speed of the proposed HPSO-
HPF-based solution methodology in finding the global optimal
solution of the capacitor allocation and sizing problem.
In order to do more testing on the proposed HPSO-HPF- runs were conducted to find the best settings of the PSO param-
based algorithm, the capacitor placement and sizing problem is eters. 100 iterations were taken as the maximum number of it-
extended to multiple capacitors. Three single phase capacitors erations to adjust each of these parameters. A swarm size of 25
are considered instead of one capacitor. The maximum reactive particles, acceleration factors of 2 each, and a maximum par-
power injection of these capacitors is not to exceed the total re- ticle’s velocity of 3 were selected.
active demand of the system. The developed PSO-based algorithm was able to find the op-
As in the case of one shunt capacitor, the PSO parameters timal locations and ratings of three shunt capacitors such that
have to be properly adjusted. Taking the total real power loss the overall cost was minimized. The simulation results are re-
without harmonic components as an objective, 20 independent ported in Table IV. Without harmonics consideration (case 2)
1740 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 3, JULY 2010

TABLE V
VOLTAGE PROFILES AND TOTAL HARMONIC DISTORTIONS OF A 13-BUS-RDS
FOR CASES 1, 2, AND 3 OF THE OPTIMAL PLACEMENT AND SIZING OF THREE
SHUNT CAPACITORS

Fig. 5. Convergence characteristics of the HPSO-HPF-based algorithm for


case 2 in the optimal placement and sizing of three shunt capacitors.

Fig. 6. Convergence characteristics of the HPSO-HPF-based algorithm for


case 3 in the optimal placement and sizing of three shunt capacitors.

3. However, the optimal solution in case 3 yields a 61.27% re-


duction in total harmonic distortion with respect to case 1 and
90.927% reduction in total harmonic distortion with respect to
case 2. Consequently, the net savings obtained in case 2 can be
justifiably sacrificed to avoid any possible damage to the elec-
tric equipment of both the utility and the customers.
Table V demonstrates that the proper installation of three
shunt capacitors in the 13-Bus-RDS leads to voltage profile im-
provement (see columns 5 and 7 in Table V). The harmonic
distortion levels at some load buses in case 2, however, exceed
the IEEE standard 519-1992 due to neglecting the presence of
harmonic sources in the system (column 6 in Table V). In con-
trast, taking harmonics into account (case 3) maintained the har-
monic distortion levels at load buses within the allowable limits
, (column 8 in Table V). The convergence
characteristics of the developed HPSO-HPF-based approach for
the developed PSO-based algorithm selected bus 6 as the op- cases 2 and 3 in the optimal placement and sizing of three shunt
timal location for three single-phase capacitors with optimal rat- capacitors problem with the total cost being the objective are
ings of 450, 300, and 600 kVAR as shown in Table IV. In case depicted in Figs. 5 and 6.
2, the real power losses were reduced to 164.9870 kW, while in
case 3 (with harmonics consideration), the proposed PSO-algo- VI. CONCLUSION
rithm selected phase a of bus 5 and phases b and c of bus 6 to In this paper, the developed HPSO-HPF-based algorithm was
be the optimal locations of the three shunt capacitors with the tested on an unbalanced 13-bus test system to find the optimal
same ratings. It can be observed that the reactive power injec- locations and sizes of shunt capacitors taking harmonics into ac-
tions required to minimize the total cost in case 2 (when har- count. The objective was to minimize the total cost of the system
monics are neglected) are equal to the reactive power injections real power loss and the shunt capacitors to be installed. The ob-
in case 3 (when harmonics are considered). Moreover, the total jective function was subject to some operating constraints and
real power loss in case 3 is higher than that in case 2. As a re- power quality constraints. The outcome of this research is that
sult, the net savings obtained in case 2 is better than that in case neglecting the presence of harmonics in the system may lead to
EAJAL AND EL-HAWARY: OPTIMAL CAPACITOR PLACEMENT AND SIZING 1741

undesirable harmonic distortion levels causing more damage to [13] J. Kennedy and R. Eberhart, “Particle swarm optimization,” in
the electric equipment of both the electric utility and customers. Proc. IEEE Int. Conf. Neural Networks, Piscataway, NJ, 1995, pp.
1942–1948.
[14] R. Eberhart and J. Kennedy, “A new optimizer using particle swarm
ACKNOWLEDGMENT theory,” in Proc. 6th Int. Symp. Micro Machine and Human Science,
1995, pp. 39–43.
The authors would like to thank the reviewers for their valu- [15] X. Hu, Y. Shi, and R. Eberhart, “Recent advances in particle swarm,”
able comments and recommendations. in Proc. Congr. Evolutionary Computation, 2004, vol. 1, pp. 90–97.
[16] M. R. AlRashidi and M. E. El-Hawary, “Hybrid particle swarm opti-
REFERENCES mization approach for solving the discrete OPF problem considering
the valve loading effects,” IEEE Trans. Power Syst., vol. 22, no. 4, pp.
[1] Y. Baghzouz and S. Ertem, “Shunt capacitor sizing for radial distri- 2030–2038, Nov. 2007.
bution feeders with distorted substation voltages,” IEEE Trans. Power [17] W. H. Kersting, “Radial distribution test feeders,” IEEE Trans. Power
Del., vol. 5, no. 2, pp. 650–657, Apr. 1990. Syst., vol. 6, no. 3, pp. 975–985, Jul. 1991.
[2] Y. Yan, T. Wu, and C. Ho, “Optimal capacitor placement using sensi- [18] Task Force on Harmonics Modeling and Simulation, “Modeling and
tivity index and differential evolution for the three-phase distribution simulation of the propagation of harmonics in electric power networks
systems with harmonic distortion,” in Proc. IASTED Int. Conf. Power part II: Sample systems and examples,” IEEE Trans. Power Del., vol.
and Energy Systems, May 13–15, 2002, pp. 352–353. 11, no. 1, pp. 466–474, Jan. 1996.
[3] G. Carpinelli, P. Varilone, V. Di Vito, and A. Abur, “Capacitor place- [19] Y. Shi and R. Eberhart, “A modified particle swarm optimizer,” in Proc.
ment in three-phase distribution systems with nonlinear and unbal- IEEE Int. Conf. Evolutionary Computation, 1998, pp. 69–73.
anced loads,” Proc. Inst. Elect. Eng., Gen., Transm. Distrib., vol. 152,
no. 1, pp. 47–52, 2005. Abdelsalam A. Eajal (S’00) received the B.S. de-
[4] A. Abou-Ghazala, “Optimal capacitor placement in distribution sys- gree in electrical engineering from the University of
tems feeding nonlinear loads,” in Proc. IEEE Bologna Power Tech Altahadi, Sirt, Libya, in 2001 and the M.A.Sc. degree
Conf., 2003, pp. 97–103. in electrical engineering from Dalhousie University,
[5] T. Niknam, A. M. Ranjbar, H. Arabian, and M. Mirjafari, “Optimal Halifax, NS, Canada, in 2008.
reactive power planning in harmonic distorted power system using ge- Currently, he is a staff member at Altahadi Univer-
netic algorithm,” in Proc. IEEE Region 10 Conf., 2004, pp. 347–350. sity, Sirt, Libya. His research interests involve appli-
[6] M. A. S. Masoum, M. Ladjevardi, E. F. Fuchs, and W. M. Grady, “Ap- cations of optimization techniques in power system
plication of local variations and maximum sensitivities selection for planning and operation.
optimal placement of shunt capacitor banks under nonsinusoidal oper-
ating conditions,” Int. J. Elect. Power Energy Syst., vol. 26, no. 10, pp.
761–769, 2004.
[7] M. A. S. Masoum, A. Jafarian, M. Ladjevardi, E. F. Fuchs, and W. M.
Grady, “Fuzzy approach for optimal placement and sizing of capacitor
banks in the presence of harmonics,” IEEE Trans. Power Del., vol. 19, M. E. El-Hawary (LF’09) received the Bachelor’s
no. 2, pp. 822–829, Apr. 2004. degree in electrical engineering (Hons.) from the
[8] M. A. S. Masoum, M. Ladjevardi, A. Jafarian, and E. F. Fuchs, “Op- University of Alexandria, Egypt, in 1965, and
timal placement, replacement and sizing of capacitor banks in distorted the Ph.D. degree from the University of Alberta,
distribution networks by genetic algorithms,” IEEE Trans Power Del., Edmonton, 1972, where he was a Killam Memorial
vol. 19, no. 4, pp. 1794–1801, Oct. 2004. Fellow.
[9] X. Yu, X. Xiong, and Y. Wu, “A PSO-based approach to optimal capac- Currently, hs is Associate Dean of Engineering
itor placement with harmonic distortion consideration,” Elect. Power and has been Professor of Electrical and Computer
Syst. Res., vol. 71, no. 1, pp. 27–33, 2004. Engineering at Dalhousie University, Halifax, NS,
[10] T. M. Khalil, H. K. M. Youssef, and M. M. A. Aziz, “A binary par- Canada, since 1981. He served on faculty, and was
ticle swarm optimization for optimal placement and sizing of capacitor a chair of the Electrical Engineering Department
banks in radial distribution feeders with distorted substation voltages,” at Memorial University of Newfoundland for eight years. He was Associate
in Proc. AIML Int. Conf., Sharm El Sheikh, Egypt, Jun. 13–15, 2006, Professor of Electrical Engineering at the Federal University of Rio de Janeiro
pp. 129–135. for two years and was Instructor at the University of Alexandria. He pioneered
[11] J. H. Teng, “Network-topology-based three-phase load flow for distri- many computational and artificial intelligence solutions to problems in eco-
bution systems,” Proc. Natl. Sci. Counc. ROC (A), vol. 24, no. 4, pp. nomic/environmental operation of power systems. He has written ten textbooks
259–264, 2000. and monographs, and more than 120 refereed journal articles. He has consulted
[12] J. Teng and C. Chang, “Backward/forward sweep-based harmonic anal- and taught for more than 30 years.
ysis method for distribution systems,” IEEE Trans. Power Del., vol. 22, Dr. El-Hawary is a Fellow of the IEEE, the Engineering Institute of Canada,
no. 3, pp. 1665–1672, Jul. 2007. (EIC), and the Canadian Academy of Engineering (CAE).

You might also like