Professional Documents
Culture Documents
Abstract—The transmission capacity of high voltage - the maximum voltage drop allowed across the line,
overhead power transmission lines (OHLs) can be increased ǻVMAX;
in different ways. One of these is to increase the number of - the maximum power losses allowed, ǻPMAX;
standard ACSR (Aluminium Conductor Steel Reinforced) - the steady-state stability limit.
conductors forming the bundles of OHLs. This paper Each of these items limits the current (power)
analyzes the performance of 400 kV, four-conductor transported. The thermal limit depends on the conductor
bundled (4B) OHLs in terms of loadability, i.e. the
maximum power that can be transmitted as a function of
and is independent on the length of the line. Conversely,
the length of the line. First, we calculate the loadability all the other items limit the current (power) under a
curve of 4B OHLs and then we compare it with that of maximum value that is a function of the line length. In
three-conductor bundled (3B) OHLs, the common solution general, for short lines, the line loadability corresponds to
adopted in Italy and in other countries for the 400 kV the thermal limit. For intermediate lengths, the limiting
voltage level. We calculate the loadability curves up to a factor is the voltage drop limit, whereas the steady-state
length of 500 km, assuming the same standard conductor
for both 3B and 4B lines, and keeping into account the
stability limit affects the line loadability only in case of
conductor thermal limit, maximum voltage drop, maximum very long lines [1-4]. Power losses can affect the
power losses, and steady-state stability limit. loadability of HVDC lines, but usually does not prevail
on the voltage drop limit in HVAC lines [3-4]. Thus, we
Index Terms—Line loadability, Overhead transmission devote a special attention to the voltage drop limit (that is
lines, Power transmission, Transmission lines. treated in Section 3) whereas, for the goal of this paper,
the power losses limit (treated in Section 4) and the
I. INTRODUCTION
stability limits (treated in Section 5) are less important.
To improve the transmission capacity of high voltage It is worth of noting that the emphasis of this paper is
overhead power transmission lines (OHLs) is an on the increase of OHLs transmission capacity. But there
important goal in many western countries, where are also environmental benefits that can derive from the
authorizations and local oppositions obstacle the adoption of 4B lines. One of these concerns CO2
expansion of power systems. This objective can be emissions: with the same power transported, 4B lines
reached through different approaches. One of these is to have lower losses than 3B lines, and this results in lower
increase the number of the standard ACSR (Aluminium CO2 emissions. A second benefit concerns the audible
Conductor Steel Reinforced) conductors used in the noise: as known, e greater number of bundled conductors
bundles of OHLs. reduces the electric field in the bundle proximity and,
This paper analyzes the performance of 400 kV, four- thus, the “corona effect” and the related audible noise,
conductor bundled (4B) OHLs in terms of loadability, which may be significant in case of adverse weather
which is the maximum power that can be transported by a conditions.
line as a function of its length L [1, 2]. We first calculate
II. LINE PARAMETERS AND THERMAL LIMIT
the loadability curve of 4B OHLs, assuming that the four
conductors per phase are disposed on the vertexes of a We assume the usual ACSR standard conductor with
square with 400 mm side. Then we compare the 4B S=585 mm2 cross section for both 3B and 4B lines. The
loadability curve with the loadability curve of the relevant per unit length line parameters are reported in
traditional three-conductor bundled (3B) solution adopted Table 1.
in Italy for 400 kV OHLs, with the three conductors
placed at the distance of 400 mm to form an equilateral TABLE I
3B AND 4B LINE PARAMETERS
triangle.
Resistance Reactance Conductance Susceptance
The loadability characteristics are calculated up to a
x3B=0.271 b =4.1010-6
maximum line length of 500 km, keeping into account: 3B r3B=0.021 :/km g3B=410-9 S/km 3B
:/km S/km
- the conductor thermal limit, IMAX;
x4B=0.247 b4B=4.5010-6
4B r4B=0.75r3B g4B=410-9 S/km
:/km S/km
This work was financially supported by the Università degli Studi di
Trieste – Finanziamento di Ateneo per progetti di ricerca scientifica –
FRA 2014. These values yield:
161
2- two different models for the maximum voltage drop
allowed, ǻVMAX. The first model considers a constant 0.12
value (we assume the classical value ǻVMAX=5%),
whereas in the second model ǻVMAX is an increasing 0.1
function of L [km]. More precisely, we assume ǻVMAX
3B cos I 2=1
Power losses (p.u)
3B cos I 2=0.95
1000 0.03
0.02
500
0.01
0
0 100 200 300 400 500
Length (km) 0
0 100 200 300 400 500
Fig. 3. 4B 400 kV OHLs loadability, for the two different voltage drop Length (km)
limits (case: cosij2=1). Fig. 5. Power losses in 3B and 4B 400 kV OHLs.
162
Equation (2) refers to the line in series with the
Thévenin equivalent of the network at one line end. 1.35
Therefore, X=Xnet+XL is the total system reactance, XL 'VMAX variable, cos I 2=1
the line reactance, Xnet=V2/Asc the network equivalent 1.3
cos I 2=0.99
reactance, Asc the short-circuit power at one line end, ES
1.25 cos I 2=0.95
and E2 the phase-to-ground voltages at either end of X.
163
VII. CONCLUSIONS The advantage of 4B lines in terms of loadability is
The analysis performed in this paper, relevant to the equal to the expected value 33% only up to a limited line
400 kV voltage level, allows to quantify the improvement length, which we call “useful length”, roughly in the
of transmission capacity that would be allowed passing range between 40 and 100 km, and hereafter it decreases
from the 3B OHLs, which is the most frequent sharply and then settles at a much lower value, in the
arrangement in Italy and in other countries, to the 4B range between 10% and 13%, depending on the length of
OHLs. the line. The useful length depends mainly on the power
The analysis is based on the calculation and factor, and decreases with it.
comparison of the loadability curves of 3B and 4B lines. As a final remark, these results show that the 4B
The loadability curves are computed accounting for the solution can be fully exploited to increase power
conductor thermal limit, the voltage drop limit, the power transmission in case of short lines and, thus, could find
losses limit, and the steady-state stability limit. However, useful applications especially in highly meshed power
for line lengths up to 500 km, only the first two items systems.
affect the loadability curves of the considered OHLs.
The methodological approach used in this paper is
REFERENCES
theoretical, and does not considers the security margins
imposed in power systems for frequency control needs [1] R. D. Dunlop, R. Gutman, and P. P. Marchenko,
and N-1 security criterium but, on the other hand, it has “Analytical development of loadability characteristics for
EHV and UHV transmission lines”, IEEE Transactions
the advantage to provide general results, since the results
Power Apparatus and Systems, vol. PAS-98, no. 2, pp.
are not affected by the local features of any individual 606–613, Mar./Apr. 1979.
real OHL and the network around it. [2] P. Kundur, Power System Stability and Control. McGraw-
As the maximum voltage drop ǻVMAX has a strong Hill, the EPRI Power System Engineering Series, 1994, pp.
impact on the loadability curves of OHLs, we performed 228-230.
calculations using different voltage drop limit models. [3] D. Lauria, G. Mazzanti, and S. Quaia, “The Loadability of
The results demonstrate that the power ratio between 4B Overhead Transmission Lines. Part I: Analysis of Single-
and 3B lines changes just a little with the specific model Circuits”, IEEE Transactions on Power Delivery, vol. 29,
assumed. no. 1, February 2014, pp. 29-37.
[4] D. Lauria, G. Mazzanti, and S. Quaia, “The Loadability of
The main result of this work is that the advantage
Overhead Transmission Lines. Part II: Analysis of Double-
provided by 4B lines strongly depends on the line length Circuits and Overall Comparison”, IEEE Transactions on
and on the load power factor. Concerning this, notice Power Delivery, vol. 29, no. 2, April 2014, pp. 518-524.
that, for any individual line, the length is a fixed and [5] “Portata al Limite Termico Delle Linee Elettriche Aeree
known parameter, whereas the power factor changes with Esterne con Tensione Maggiore di 100 kV” (in Italian),
time. Italian Standard CEI 11-60, June 2002, 2nd Ed.
164