You are on page 1of 14

Engineering Structures 158 (2018) 110–123

Contents lists available at ScienceDirect

Engineering Structures
journal homepage: www.elsevier.com/locate/engstruct

Comparison of the seismic performance of a partial mass isolation technique T


with conventional TMD and base-isolation systems under broad-band and
narrow-band excitations

Hamidreza Anajafi , Ricardo A. Medina
Department of Civil and Environmental Engineering, University of New Hampshire, Durham, NH, United States

A R T I C L E I N F O A B S T R A C T

Keywords: In the present study a partial mass isolation (PMI) technique is proposed. This approach, through isolating
Mass damper different portions of masses at different stories, can provide a building with multiple inherent vibration sup-
Base isolation pressors without the need to add extra masses. Optimization of the PMI system’s parameters is conducted for
Partial mass isolation reference structural models with 6, 12, and 20 stories to minimize root-mean-square inter-story drift responses
Optimization
under Kanai-Tajimi filtered Gaussian white noise excitations, while parameter constraints are specified to
Modified Kanai-Tajimi (K-T) filter
control isolated components’ (ICs) responses. The seismic performance of the PMI technique under excitations
Soil conditions
with different frequency contents (representing different soil profiles) is compared to that of conventional tuned
mass damper (TMD) and base-isolation (BI) systems as baseline configurations. Simulation results indicate that
the PMI system with extreme isolated mass ratios of 5% or 90% exhibits dynamic behaviors equivalent to those
of an equivalent TMD or an ideal BI systems, respectively. Meanwhile, this technique can resolve some of the
inherent difficulties associated with the implementation of TMD (e.g., weight restriction) and BI (e.g., problems
due to the superstructure flexibility, overturning moments, and heavy loads) in high-rise buildings.

1. Introduction architectural problems. In low-frequency buildings a TMD requires


occupying a large space, usually at a top floor, to accommodate large
Tuned mass damper (TMD) and base isolation (BI) systems are two mass damper’s drift responses (i.e. the relative deflection of the lumped
of the most commonly utilized modern seismic protection techniques TMD mass with respect to its attachment point). Other shortcomings of
involving passive control strategies. These techniques provide building the TMD system, including its performance sensitivity to the tuning
designers with a means to adjust structural periods and damping to frequency, its performance dependency on the input excitation fre-
substantially mitigate the detrimental effects of earthquake ground quency content and the primary structure dynamic characteristics, are
motions. However, these techniques can suffer limitations that prevent well addressed in the literature [2–6].
their application, especially to high-rise buildings. For instance, the One of the first reports of using the BI technique in the modern era
excessive superstructure flexibility and heavy loads experienced by dates back to more than 130 years ago when John Milne isolated a
high-rise buildings can prevent the effective implementation of BI sys- wooden house from the ground by mounting the building on ball
tems, while the large auxiliary mass generally required in TMDs may bearings [7]. BI systems can decouple the dynamic responses of a
present significant practical and architectural constraints. building from the horizontal components of ground excitations by in-
A TMD, initially introduced by Frahm in 1909 [1] and then ex- terposing low-horizontal stiffness bearings at the isolation interface
tended by many others, is a well-known passive control device con- [7,8]. Isolator bearings shift the fundamental frequency of a building
sisting of an auxiliary mass-spring-dashpot system. TMDs are generally away from the dominant frequencies of typical earthquake excitations,
designed to oscillate at the same frequency as a primary system but in protecting the entire building and its potentially vulnerable contents
an opposite phase to attenuate undesired dynamic vibrations induced from detrimental effects caused by system resonance. The frequency
by wind or earthquake excitations. Since a TMD’s effectiveness is highly shift (i.e., the period lengthening) in the BI system is usually associated
dependent on its weight, this system generally requires a heavy mass, with significant drift responses at the isolation interface that impose
especially in high-rise buildings, which may cause practical and large global displacement responses on the superstructure. To limit


Corresponding author.
E-mail address: ha2006@wildcats.unh.edu (H. Anajafi).

https://doi.org/10.1016/j.engstruct.2017.12.018
Received 19 March 2017; Received in revised form 3 November 2017; Accepted 12 December 2017
0141-0296/ © 2017 Elsevier Ltd. All rights reserved.
H. Anajafi, R.A. Medina Engineering Structures 158 (2018) 110–123

these excessive responses, supplementary damping devices (e.g., lead of such concerns, PMI configurations with extreme isolated mass ratios
rubber bearings, viscous dampers, etc.) are generally incorporated into (IMRs) of 5% and 90% are considered. Decoupling a large portion of a
the isolation system. These supplementary dampers can also lead to the story mass such as 90% may not be realistic because of associated
further mitigation of superstructure inter-story drift and acceleration structural and architectural constraints, but it is considered herein to
responses. Alternatively, the global seismic displacement demands fully characterize the behavior of the proposed system and provide a
present in BI systems can be reduced by incorporating a TMD system or comprehensive view of its potential applications and limitations. Given
one of its variants attached to the base slab [9–14]. For example, Adam, the flexibility of the PMI system to isolate different sections of the total
et al. [9], through experimental and numerical analysis of a three-story story mass (e.g., as light as an architectural double-skin façade or as
base-isolated building, illustrated that a tuned liquid column damper heavy as a section of a floor system including its contents), the authors
(TLCD) system could protect the building against the excessive global are currently conducting a parallel study to evaluate the seismic ef-
displacement responses without impairing the efficiency of the BI fectiveness of the PMI system with different IMR values in a wide range
technique. This objective was achieved by tuning the TLCD frequency (i.e., 5–90%) [39].
to the fundamental frequency of the base-isolated building. In this paper, the seismic effectiveness of the PMI technique is ex-
In recent years, researchers have extensively studied different as- amined in structural models with different fundamental frequencies. A
pects of BI systems [e.g., 15–29]. Now it is well acknowledged that the parametric study approach is utilized to optimize the PMI configura-
most suitable candidates for the BI technique are low- to mid-rise tions with the extreme IMRs of 5% and 90%. The response quantity to
buildings situated on dense soils with high-frequency motions [26–29]. be optimized is the sum of root-mean-square inter-story drift responses
However, the BI system has been used recently in Japan even for rather of the superstructure under stochastic excitations. To assess the effec-
tall buildings and low-frequency ground motions. As of 2015, ap- tiveness of these PMI configurations, conventional TMD and BI systems
proximately 170 isolated high-rise buildings, ranging from 60 m to are also presented as baseline configurations.
180 m tall, have been constructed in Japan [30]. The first base-isolated
structure with a height of over 60 m in Japan is the Sendai MTI 18-story
building with a height of 84.9 m (1999). Another example is the re- 2. Local mass isolation technique
sidential Thousand Tower reinforced-concrete building with 41 stories
above the ground and a height of 135.0 m [31]. Some studies have il- A partial/local isolation technique can be considered as an appro-
lustrated that, unlike the US seismic code provisions, the Japanese code priate alternative for the BI technique in tall buildings or in situations in
provisions facilitate the implementation of the BI technique in high-rise which isolating the whole structure is not cost-effective. In this tech-
buildings. For example, Becker et al. [30] evaluated a base-isolated 32- nique, instead of isolating an entire building at the base, specific
story RC building with a fixed-base period of 2.57 s under Japanese and structural systems, components, floors or stories can be selectively
US seismic design codes. They showed that assuming the Japanese isolated. Different types of partial isolation systems included in the
design loads, the isolation system met all the design criteria while the literature are generally “upper-story isolation”, “mega-sub-controlled”,
US code design loads resulted in large overturning moments and con- and “floor isolation” systems (Fig. 1). Utilizing the TMD-related prin-
sequently large tensile and compressive forces beyond the limits re- ciples, the mentioned local isolation systems are capable of converting
commended by the bearings manufacturer. Despite its popularity in isolated components into inherent mass dampers to overcome the tra-
Japan, there is no consensus on the effectiveness of BI systems in high- ditional TMDs’ weight limitations.
rise structures. The concerns about the application of BI systems in In an upper-story isolation approach, seismic isolators are installed
high-rise buildings primarily arise from the relatively long fundamental at a higher story level unlike a conventional BI system in which iso-
period of the fixed-base superstructure and the heavy loads imposed on lators are installed at the base. This technique separates roof story or
the isolator bearings. Considering the practical range of isolation- several upper stories from the rest of a building to provide a heavy mass
system parameters, the ratio of the isolated building’s fundamental damper for the non-isolated part underneath the isolation interface
period to the fixed-base superstructure’s fundamental period in high- [32,40–45]. A “mega-sub-controlled” building approach, proposed by
rise structures is typically below two, hence, the isolation technique is Feng and Chai [46], consists of a mega structure as the main structural
less beneficial than for shorter buildings [30]. Furthermore, P-delta frame and several isolated multi-story substructures. This technique can
effects and large overturning moments resulting from the high center of convert a flexural tall building, where a typical BI is not suitable, into
gravity in high-rise buildings may lead to difficulties in the design and several shear sub-buildings that can benefit from the seismic isolation
operation of isolation systems [32,33]. technology. Meanwhile, isolated substructures can function as multiple
While a TMD primarily applies to mitigate the wind-induced vi- TMDs for the entire building without imposing any unnecessary extra
brations [34,35], BI systems cannot benefit buildings against wind ex- weight to the building.
citations. This limitation has its roots in the difference between the A floor isolation technique is typically applied to protect local
nature of earthquake and wind loads; unlike the earthquake induced- contents (e.g., sensitive equipment in a specific room) in a building. In
loads, which are transmitted from the ground to the structure, wind
loads directly apply to the building rendering the BI technique practi- Mega sub-controlled
cally ineffective. In moderate and strong wind excitations, base-isolated
Roof isolation
buildings can be even exposed to undesirable vibrations arising from
the inserted flexibility at their base, which have been comprehensively
addressed in the literature [36–38].
Upper-story
In the present paper the authors propose a partial mass isolation
isolation
(PMI) approach that, by isolating portions of masses at different stories,
can provide a building with multiple inherent vibration suppressors Floor isolation
partially resolving the abovementioned deficiencies associated with the
application of conventional TMD and BI systems. In a PMI system, the
lower and upper bounds of the isolated mass ratios (i.e., the mass of the
isolated components to the total mass of the story) may be dictated by
Base isolation
many parameters, such as the structural skeleton’s weight, non-
structural components’ details, the architectural layout of a building,
Fig. 1. Schematic models of different seismic isolation systems.
construction and economic considerations, etc. In this study, regardless

111
H. Anajafi, R.A. Medina Engineering Structures 158 (2018) 110–123

xnIC (t )
Fig. 2. Schematic models of the three passive
mis + miIC = mie control strategies in an n-story linear elastic shear
TMD
c mTMD mnIC xns (t ) building.
k TMD knIC cnIC
n-th mne mne mns
mns mnIC
IC
k s
n cs
n k s
n c s
n k s
n
m n −1 cs
n
knIC−1 cnIC−1
(n-1)th mne−1 mne−1 mns −1
kns−1 cns −1 kns−1 cns −1 kns−1 m1IC cns −1
k1IC c1IC
1st m1e m1e m1s

GF
k1s c1s k1s c1s k1s c1s
m BI = m1e
c BI
k BI xg (t )

(a) Tuned mass damper (b) Base isolation (c) Partial mass isolation
(TMD) (BI) (PMI)

this system, only a particular part of a floor, which requires a higher utilized to minimize inter-story drift responses of the superstructure
level of seismic protection than a traditionally-designed structure, is while constraints are specified to limit the isolated components (ICs)
decoupled from the rest of a building through a secondary isolated responses. The seismic performance of the optimized PMI configura-
raised floor [47–50]. This version of the partial isolation system, which tions is compared with that of conventional passive TMD and BI sys-
is also known as a content-protection system, has been rarely designed tems, which are used as baseline configurations in this study. The
to reduce seismic responses of an entire building. However, when main ground excitation is modeled as a filtered white noise process to re-
floors are isolated from the structural frame, the floor isolation tech- present earthquake motions with different frequency contents (i.e.,
nique can locally and globally benefit a building. When properly de- narrow- and broad-band excitations). The advantages and limitations of
signed, this approach can reduce isolated floors’ acceleration responses the PMI configurations with extreme IMRs of 5% and 90% are dis-
while making them serve as inherent earthquake vibration suppressors cussed, which provide motivation for further studies to evaluate the
for the entire building. In this system isolator bearings installed at PMI configurations with intermediate IMRs.
several floor levels can provide additional reliability and redundancy
with respect to the conventional TMD and BI systems, such that if a
bearing fails, alternative ones are available to dissipate earthquake 3. Model formulation
energy. This advantage would be present at the expense of installing the
isolation system at multiple floor levels, which might impair con- The building superstructure is modeled as a linear-elastic shear-type
structability and increase the building’s initial cost. To the best of the two-dimensional frame (in this manuscript the term “superstructure”
authors’ knowledge, only limited research works have been conducted refers to the non-isolated portion of the PMI system including the
on this version of the partial isolation system. Some of these relevant structural frame). In this model story masses are lumped at floor levels,
works are briefly outlined herein. and a single translational (lateral) degree of freedom is assigned at each
In 2015, Sakr [51] applied a partial isolation system in 5-, 25-, and floor level. The masses of ICs are ideally lumped at floor levels as ad-
50-story shear-type buildings under harmonic loads and three historical ditional degrees of freedom attached to the superstructure through a
records. Sakr used identical isolated floors at upper stories and con- spring-dashpot system. The same assumption is adopted for modeling
ducted a parametric study to optimize different configurations. Xiang the mass damper in the TMD system. For the BI system, isolation layers
and Nishitani [52] optimized a floor isolation system in a 25-story are modeled with linear Kelvin-Voigt elements (i.e., linear stiffness and
building utilizing a Non-dominated Sorting Genetic Algorithm based on equivalent viscous damping). The mathematical models of different
the minimization of the magnitude of the frequency response of the passive control systems for an n-story shear building are illustrated in
system. They applied identical characteristics for the isolated floors at Fig. 2a-c.
different stories, and assumed that 1/3 of each story’s mass was iso- To examine the efficiency of the proposed PMI technique in a wide
lated. The two mentioned works illustrated that a floor isolation tech- structural frequency range, structural models with 6, 12, and 20 stories
nique, using the TMD-related principle, could significantly reduce inter- are selected, which can represent low-, mid- and high-rise buildings,
story drift responses of the superstructure. In another study, Pourmo- respectively. The story mass and the story stiffness coefficient are
hammad et al. [53] applied a mass isolation system in a 10-story shear constant along the height of each test-bed building (i.e., for each
building assuming that 95% of the mass of each story was isolated with building m1s = m2s = ⋯mns and k1s = k 2s = ⋯kns ). The most salient dy-
identical bearings. Through exposing the building to a single historical namic characteristics of the structural models are presented in Table 1.
record, they illustrated that the proposed system could considerably
reduce acceleration responses of the isolated floors as well as the su- Table 1
perstructure inter-story drift responses. Dynamic characteristics of the uncontrolled test-bed buildings.

The present paper studies a PMI system in which masses at different Building Stiffness Coeff. (107 N/m) Story Mass (103 kg) Fundamental Freq. (rad/s)
stories are isolated from the superstructure. The PMI system is ex-
amined in three reference structural models with 6, 12, and 20 stories 6-story 3.77 20.00 10.50
that can represent typical low-, mid- and high-rise building, respec- 12-story 3.48 20.00 5.23
20-story 3.36 20.00 3.14
tively. To account for various structural responses, multiple perfor-
mance objectives are defined and evaluated. Parametric studies are

112
H. Anajafi, R.A. Medina Engineering Structures 158 (2018) 110–123

Stiffness proportional damping, assuming 2% of the critical damping at kBI + k1s − k1s ⎤
the fundamental mode, is applied to the uncontrolled structures as well M = diag(mBI,m1s,⋯,mns ); K = ⎡ ;
⎢− k1s Ks ⎥
⎣ ⎦(n + 1)(n + 1)
as to the superstructure (non-isolated part) in the controlled buildings.
The 2%-damping assumption implies that the structural frame is mildly
c BI + c1s − c1s ⎤
damped. For the two passive baseline configurations (i.e., conventional C=⎡ ; c BI = 2ξ BI kBI (nm1s + mBI) .
⎢− c1s Cs ⎥
TMD and BI systems illustrated in Fig. 2a and b), two-dimensional ⎣ ⎦(n + 1)(n + 1)
models with the same superstructure characteristics as those mentioned
above for the PMI system are developed. The damper’s mass in the and for the TMD system are:
baseline TMD system is equal to the overall isolated mass in the iPMI
Ks + φ k TMD − k TMD ⎤
configuration with an IMR of 5%. M = diag(m1s,⋯,mns,mTMD); K = ⎡ ;

⎣− k
TMD k TMD ⎥ ⎦(n + 1)(n + 1)
The equations of motion for an n-story linear elastic shear-type
building equipped with a PMI system, schematically illustrated in
Fig. 2c, can be expressed as ⎡0 ⋯ 0⎤
Cs + φ c TMD − c TMD ⎤ ⋮ ⋱ ⋮⎥
C=⎡ ; φ=⎢ ; c TMD
Mx¨ (t ) + Cẋ (t ) + Kx (t ) = −Mrx¨g (t ) (1) ⎢
⎣− c
TMD c TMD ⎥ ⎦(n + 1)(n + 1) ⎢0 … 0⎥

⎣0 ⋯ 0 1⎥
⎦n × n
where
= 2ξ TMD k TMDmTMD .
M s 0 ⎤
M=⎡ ;
⎣ 0 MIC ⎦2n × 2n
4. Ground excitation
Cs + CIC −CIC ⎤
C=⎡ IC
;

⎣ −C CIC ⎥
⎦2n × 2n The earthquake-induced ground acceleration is modeled as a fil-
Ks + KIC −KIC ⎤ tered Gaussian white noise process corresponding to the Kanai-Tajimi
K=⎡ IC
;
⎣ −K KIC ⎦2n × 2n (K-T) spectrum [54]. This model has been widely used in the literature
for studying control systems [e.g., 16,39,55,56]. In this model, the
Ms = diag(m1s,m2s,⋯,mns ); MIC = diag(m1IC,m2IC,⋯,mnIC); mis + miIC ground acceleration of the earth surface layer is approximated by the
absolute acceleration response of a linear single-degree-of-freedom
= mie;
(SDOF) oscillator subjected to a Gaussian white noise process. The
white noise represents the earthquake acceleration at the bedrock, and
Cs = 2ξ1s/ ω1s Ks; CIFS = diag(c1IC,c2IC,⋯,cnIC); ciIC = 2ξiIC kiIC miIC ; the linear SDOF oscillator characterizes the filtering effects caused by
the soil layers. As demonstrated in Fig. 3, the oscillator can be defined
s s s
⎡ k1 + k 2 − k 2 … 0 ⎤ by two parameters, ωg and ξg , which are interpreted as the character-
⎢ − k 2s ⋱ ⋮ ⎥ istics frequency and damping ratio of the ground layers, respectively.
s
K =⎢ ⎥; The process of deriving the K-T excitation can be expressed as
⎢ ⋮ … kns− 1 + kns − kns ⎥
⎢ 0 … − kn s
kn ⎥
s
⎣ ⎦ x¨gr (t ) + 2ξg ωg x ġ r (t ) + ωg2 x gr (t ) = −x¨b (t ). (3)
M, C and K are the global mass, damping, and stiffness coefficient where x gr (t )
is the oscillator’s (i.e., the ground surface’s) displacement
matrices of the PMI system, respectively. The superscripts s and IC relative to the bedrock, and x¨b (t ) is the bedrock acceleration, which is
stand for the superstructure and isolated components, respectively. assumed to be a Gaussian zero mean white noise signal, w¨ (t ) . The
x = [x1s x 2s⋯x ns x1IC x 2IC⋯x nIC]T is the displacement vector of the system
Laplace transform of Eq. (3) is
relative to the ground displacement, x g (t ) . r is the influence vector;
since displacements are measured relative to the ground, r is a column Xgr (s )[s 2 + 2ξg ωg s + ωg2] = −X¨b (s ). (4a)
vector of ones. mis , miIC and mie are the masses of the superstructure, of
the IC, and of the entire story at the i-th story, respectively. ξ1s and ξiIC which can be expressed as
are the damping ratio of the superstructure at the fundamental mode
Xgr (s ) −1
and the damping ratio of the IC at the i-th story, respectively. ω1s is the = 2 .
superstructure fundamental frequency. kis and kiIC are the stiffness X¨b (s ) s + 2ξg ωg s + ωg2 (4b)
coefficients of the superstructure and of the IC at the i-th story, re-
spectively. Eq. (1) can be represented in the state space form given by The transfer function with respect to the absolute acceleration of the
Eq. (2) oscillator, x¨g (t ) , is
r
0 I2n × 2n ⎤ x X¨ g (s ) X¨ g (s ) Xgr (s ) 2
⎡ ẋ ⎤ = ⎡ 2n × 2n ⎡ ⎤ FKT (s ) = =1+ =1+ s.
⎣ x¨ ⎦4n × 1 ⎣− M−1K − M−1C ⎦4n × 4n ⎣ ẋ ⎦4n × 1 ¨
Xb (s ) ¨
Xb (s ) X¨b (s ) (5a)
02n × 1 02n × 2n ⎤
+⎡ ⎡ x¨g ⎤ Substituting Eq. (4b) into Eq. (5a) results in
⎢− r M −1 ⎥
⎣ 2 n × 1 ⎦4n × (2n + 1) ⎣ 0 ⎦(2n + 1) × 1 (2)

or ż = Az + Bu where z is the state vector [x ẋ ]T ; A and B are the


Structure M
coefficient matrices, and u is the system input vector. Solving Eq. (2) K C
results in displacement and acceleration responses that are relative to xg (t )
the ground. Since relative acceleration responses are not relevant Ground ξg , ωg
seismic demands for design and evaluation, the ground acceleration
responses are added to theses relative responses to obtain absolute Bedrock
acceleration responses that are used in the evaluation of the control
systems. Equations of motion for a structure equipped with TMD and BI xb (t ) = w(t )
systems take forms similar to Eq. (1) where the global mass, damping
Fig. 3. Modeling of the ground excitation as a K-T filtered white noise process.
and stiffness coefficient matrices for the BI system are:

113
H. Anajafi, R.A. Medina Engineering Structures 158 (2018) 110–123

2 White Modified Ground


Noise Structure Response
K-T Filter Excitation

Amplification
1.5
w(s ) X g (s)
S( )/S0

K-T
F (s ) H (s ) X(s )
1

Attenuation
Modified K-T F ( s ) = FKT ( s ) FCP ( s )
0.5 = 15.0 rad/sec ,
M −1[Ms 2 + Cs + K ]X( s ) = −1 X g ( s )
g g
= 0.6
= 1.5 rad/sec , = 0.6 B( s ) = M −1[Ms 2 + Cs + K ]
c c
0 H ( s ) = [B( s )]−1
1 1.5 10 15 50
Fig. 5. Block diagram of the structural K-T model.
Frequency (rad/sec)
Fig. 4. Power Spectral Density of the K-T excitation. losses associated with damages to nonstructural components (e.g.,
suspended ceilings), equipment (e.g., HVAC systems), and contents
−s 2 2ξg ωg + ωg2 (e.g., computer servers). In this study, the root-mean-square inter-story
FKT (s ) = 1 + = . drift response of the superstructure is selected as the primary objective
s 2 + 2ξg ωg s + ωg2 s 2 + 2ξg ωg s + ωg2 (5b)
(OF) to be minimized. As illustrated in the results section (Figs. 10–12),
The normalized power spectral density function (Sω/ S0) of an example adopting this strategy has the added benefit of also improving the
K-T excitation versus the frequency is displayed in Fig. 4 where S0 is the global acceleration responses of the considered passive control systems.
power spectral density of the white noise. As shown, the K-T filter The optimization procedure adopted in this paper is described in the
amplifies frequency components of the input white noise around ωg , following paragraphs.
attenuates its high-frequency components, but does not influence the For a given passive control system (e.g., a TMD, PMI or BI system),
amplitude of low-frequency components. The lack of attenuation at low excited by an assumed K-T process, an optimal solution of the system
frequencies incorporates an inconsistency with respect to real ground parameters (e.g., tuning frequency and damping ratio in a TMD system)
motions. To modify the K-T spectral shape at low frequencies, a low-cut can be derived by minimizing the average normalized root-mean-
second order filter is typically added to the K-T filter [57]. The transfer square (ANRMS) of inter-story drift responses:
function representation of the modifier filter in the Laplace domain is n
1 RMS(x s−x s )
s2
s
Jdrift =
n
∑ RMS(x is−x is−1) c .
FCP (s ) = 2 . i=1 i i−1 u (8)
s + 2ξc ωc s + ωc2 (6)
where is the superstructure displacement at the i-th floor level; x is ’s
x is
where ωc and ξc are the parameters of the additional filter, introduced to are relative displacements with respect to the ground (i.e., x 0s = 0 ). The
produce the desired filtering of low frequencies. Finally, the modified subscripts u and c stand for the uncontrolled and controlled systems,
K-T filter is obtained as respectively. After designing the control systems through the mini-
s
F (s ) = FKT (s ) FCP (s ). (7) mization of Jdrift , the overall acceleration responses of the optimized
w
system can be evaluated using a weighted OF, Jaccel. , as shown in Eq.
which can be incorporated into the state space formulation presented in (9a) for the PMI and BI systems, and in Eq. (9b) for the TMD system:
Eq. (2). In this approach, the state variables can be obtained by solving
n
a Lyapunov equation (for detailed descriptions of the Lyapunov equa- w 1 RMS(¨yis )c (1−IMRi ) + RMS(¨yiMoving )c IMRi
tion, readers are referred to [58]).
Jaccel. =
n
∑ RMS(¨yis ) u
.
i=1 (9a)
The filter parameters expressed in Eqs. (5) and (6) control the fre-
n
quency content of the stochastic excitations. As shown in Table 2, the w 1 RMS(¨yis )c + RMS(¨yiMoving )c ρi
filter parameters are calibrated to represent different soil conditions,
Jaccel. =
n
∑ RMS(¨yis ) u (1 + ρi )
.
i=1 (9b)
and consequently excitations with different characteristics [59]. The
central frequency of each excitation, ωg , is in the vicinity of the fun- where ÿis
and ÿiMoving
are the absolute acceleration responses (i.e., the
damental frequency of each one of the three reference buildings to si- total acceleration including the ground acceleration) of the super-
mulate a near-resonance condition. The block diagram of the structural structure and of the moving components (i.e., damper’s mass in TMD,
K-T model is illustrated in Fig. 5. ICs in iPMI, and the entire floor in BI system) at the i-th story, respec-
tively. IMRi = miIC / mie is the isolated component’s mass ratio at the i-th
5. Performance objectives and design limitations story. The vector ρ = [zeros(1,n−1),mTMD/M e], where M e is the entire
mass of the building, defines the mass ratio of the TMD system at dif-
Conventionally, the primary aim in structural seismic design has ferent floor levels that in this case has only one non-zero element (i.e., a
w
single mass damper at the roof level). The term w in Jaccel. implies a
been to reduce inter-story drift responses because excessive inter-story w
drifts cause seismic damage to structural (e.g., beam and columns) and weighted OF; according to Eq. (9a), Jaccel. combines the non-isolated part
and ICs acceleration responses in the PMI system, and renders a single
nonstructural (e.g., partition walls) components. During the last few
decades, additional emphasis has been placed on reducing floor accel- OF which allows for the comparison of the overall acceleration response
of the controlled system with that of the uncontrolled system. Eq. (9a)
eration responses to prevent injuries, loss of functionality and mitigate
can be directly implemented for a BI system equating all IMRs to 1.0
while, for consistency purposes, this equation should be modified as Eq.
Table 2
Clough and Penzien K-T model parameters. (9b) for a TMD system.
In the conventional BI and TMD systems, optimizing the control
Soil type ωg (rad/s) ξg ωc (rad/s) ξc Resultant Excitation system parameters through the minimization of the ANRMS inter-story
drift responses as the primary OF, can lead to significantly large seismic
Firm 15.0 0.6 1.5 0.6 High Frequency (Broad-band)
responses of the isolator bearings and damper’s mass, respectively. A
Soft I 5.0 0.2 0.5 0.6 Low Frequency (Narrow-band)
Soft II 3.0 0.2 0.3 0.6 Low Frequency (Narrow-band) similar behavior can cause significant problems in a PMI system given
that the ICs may contain sensitive equipment/contents or living areas.

114
H. Anajafi, R.A. Medina Engineering Structures 158 (2018) 110–123

Hence, in order to assess displacement and acceleration responses of the of the K-T excitation is near the fundamental frequency of the building
s
moving components in the optimally designed systems, two additional (i.e., Fig. 6b), Jdrift exhibits the minimum values. In other words in the
Moving Moving
secondary OFs, denoted as Jdispl. and Jaccel. , are defined as Eqs. (10) resonance situation the TMD is more effective. Such a behavior was also
and (11), respectively. These equations provide a quantitative evalua- reported by [60,61]. For example, [60] showed that in the case of ex-
tion of the magnitude of the seismic responses of the moving compo- citations with narrow band and long duration, such as those recorded
nents in the controlled systems (i.e., ICs in the PMI system) with respect on soft soils in Mexico City during the September 1985 earthquake, a
to those of their corresponding parts in the uncontrolled systems. properly designed TMD may be able to provide high reductions in
n structural responses in the resonance situation. Fig. 6c shows that when
Moving 1 RMS(x iMoving )c the soil profile is softer than the structure (i.e., the K-T model’s central
Jdispl. =
n
∑ RMS(x is) u
.
i=1 (10) frequency is less than the superstructure’s fundamental frequency), an
optimal TMD system is less effective. This behavior was also illustrated
n
Moving 1 RMS(¨yiMoving )c by [4]. As consistently observed in Fig. 6a–c, when the tuning period
Jaccel. =
n
∑ RMS(¨yis ) u
.
ratio is less than 0.5, in most cases a TMD could amplify the NRMS
i=1 (11)
inter-story drift responses compared to the uncontrolled situation (i.e.,
where the parameters were defined in Eqs. (8) and (9). s
Jdrift > 1.0 ). This amplification is more pronounced when the TMD’s
Preliminary simulation results illustrate that, consistent with fun- damping ratio is low (e.g., 4% and 6%) and the soil profile is softer than
damental structural dynamics principles, if no constrains are applied on the building (i.e. Fig. 6c).
the characteristics of the BI system and the PMI system with a high IMR, Fig. 7a–c illustrates the performance of the BI system in terms of
the optimization process leads to isolator bearings with unreasonably s Moving
Jdrift and Jdispl. in the 12-story building assuming different soil condi-
long periods and high damping ratios. To obtain reasonable and prac- tions. According to Fig. 7a–c, in all cases these two metrics are in
tical design characteristics, two constraints are incorporated into the s
conflict with one another. As seen, the minimum Jdrift occurs at the
optimization process. First, the damping ratio of the moving compo- maximum possible isolation system’s period and damping ratio, while
Moving
nents (ICs in the PMI) is bounded to [2–30%] of the critical, which is at this point Jdispl. is significantly high (i.e., between 1.58 and 20.0 for
deemed to be reasonable for civil engineering structures. Second, using different cases in the considered period range).
an approximate method, which is mostly based on engineering judg- Similar to the observed trend in the TMD case, the best BI’s per-
ment, the fundamental period of the moving components is limited to a formance corresponds to the near-resonance situation (i.e., Fig. 7b in
selected design level (see Appendix A). Adopting this approach, the which the frequency of the fixed-base superstructure is near the central
equivalent elastic period of the moving components, frequency of the K-T excitation), which is consistent with [62]. As seen
Moving
TEquiv. = (T Moving/ βL ) , in which βL = (ξ Moving/0.05)0.30 , is limited to in Fig. 7a–c, increasing the isolation system’s period consistently re-
2.50 s. This constraint implies that, for example, for the two extreme duces NRMS inter-story drift responses except for when the soil profile
damping values of 0.02 and 0.30 the maximum elastic period of moving is softer than the fixed-base superstructure (i.e., Fig. 7c) and the isola-
Moving
components, TMax , is limited to 1.90 and 4.28 s, respectively. tion system’s damping ratio is low; as depicted in Fig. 7c, for example,
In a generic form of a PMI system with arbitrary ICs at each story, a when ξ BI = 0.04 and 0.10, increasing T BI/ T UNC up to 2.6 and 2.1, re-
total of 3n parameters, where n is the number of stories, should be spectively, can even amplify inter-story drift responses
optimized (i.e., stiffness, damping, and mass ratio of ICs at each story). s
(i.e. , Jdrift > 1.0 ). In this situation, for example when ξ BI = 0.04 , to
However, a PMI system may not be ideal for the design and construc- s
achieve a 10% improvement in Jdrift , the isolation system’s normalized
tion of a building when ICs parameters, especially IMRs, vary from story BI UNC
period, T / T , should be larger than 2.9. This implies accepting
to story. Hence, in this study ICs are assigned identical characteristics at significantly large displacement responses compared to the un-
different stories (i.e., miIC = mIC , kiIC = kIC and ξiIC = ξ IC , for controlled case (i.e., Jdispl. Moving
= 14.6 in this example). Hence, applying
i = 1,2,3,…,n ). For an identical PMI (iPMI) system once the IMR is spe- the BI system for the 12-story building located on this soil profile is not
cified, only two parameters (i.e., stiffness coefficient and damping ratio an appropriate solution.
of ICs) should be optimized. In this paper, considering the limited According to the results depicted in Figs. 6a–c and 7a–c, both TMD
number of the unknown parameters to be optimized, a parametric study and BI systems are consistently effective in mitigating inter-story drift
approach is utilized. As a part of a parallel study the authors evaluate a responses under a firm soil condition (i.e., a broad-band excitation),
generic form of the PMI system with dissimilar ICs at different stories, however, under the narrow-band excitation they are effective only at
which have the potential to provide a better seismic performance [39]. the near-resonance condition. Another important conclusion obtained
form Figs. 6a–c and 7a–c is that neither BI nor TMD is robust against
6. Seismic performance of BI and TMD systems considering changes in the primary structure’s period and the input excitation
different K-T model parameters characteristics. For example, as seen in Fig. 6b, a TMD with an 11%
damping ratio at the tuning ratio of 1.18 is very effective (i.e., it can
s
Before optimizing the passive control strategies implemented in this decrease Jdrift by 56%), however, its effectiveness rapidly decreases with
study, it is informative to evaluate the seismic responses of TMD and BI a reduction in the tuning ratio (e.g., for the tuning ratio of 0.90 re-
s
systems with different characteristics (e.g., different tuning period and duction in Jdrift is only 24%). Such performance sensitivity is not de-
damping ratio of the damper’s mass in a TMD) exposed to various sirable given that estimating fundamental period of a building is asso-
ground excitation types. The results of this evaluation will also serve as ciated with significant uncertainties. The robustness features of the
a benchmark for the assessment of the seismic performance of the conventional TMDs and BI systems are well addressed in the literature
proposed PMI system. As an example, Fig. 6a–c illustrates the variation [e.g., see 4,63–65].
s
of Jdrift with respect to the normalized period, T TMD/ T UNC , and the
damping ratio of the TMD system in the 12-story frame exposed to 7. Optimizing the passive control systems considering different K-
different ground excitations (TUNC is the uncontrolled building funda- T model parameters
mental period). Since in this paper the evaluation of the seismic re-
sponses of the control systems is conducted in relative terms, i.e., with For all passive control systems the primary OF used in this study
s
respect to the seismic responses of the uncontrolled structure, an OF (i.e., Jdrift defined by Eq. (8)) is calculated over a wide range of design
with a value smaller than or larger than 1.0 implies a performance parameters (e.g., tuning ratio and damping ratio in the TMD system).
s
improvement or a performance degradation, respectively. The minimum value of Jdrift that is associated with design parameter
IC
An evaluation of Fig. 6a–c reveals that when the central frequency values within the admissible ranges (e.g., TEquiv. ≤ 2.50 and ξ IC ≤ 0.30

115
H. Anajafi, R.A. Medina Engineering Structures 158 (2018) 110–123

s
Fig. 6. Variation of Jdrift versus TMD’s parameters in the 12-story building (ωs = 5.23 rad/s ).

s Moving
Fig. 7. Variation of Jdrift and Jdispl. versus isolator parameters for the BI system in the 12-story building, (ωs = 5.23 rad/s) .

s
Fig. 8. Variation of Jdrift versus passive
control systems’ parameters for the 12-story
1 (b) TMD System = 5% building under the firm soil based K-T ex-
citation (red dots denote the optimal solu-
1
(a) iPMI System IMR = 5% tions satisfying the defined constraints).
drift

0.75
J s
drift

0.75
J s

0.5
0.5 0.6
0.6 0.4 2.5
2
0.4 2.5 0.2 1.5 UNC
2 TM 1
TM /T
0.2 1.5 0 0.5 D
D
0 0.5
1 UNC T
IC IC /T
T
1

1 0.75 (d) BI System


(c) iPMI System IMR = 90%
drift

0.75 0.5
J s
drift

0.5
J s

0.25
0.25
0 0.6
1.5 2.5 3.5 0.4
0 0.6 4.5 5.5 6.5 0.2
1.5 2.5 0.4 T BI/T UNC 0 BI
3.5 4.5 0.2
5.5 6.5 0 IC
T IC/T UNC

for the iPMI system) is the optimal solution. As an example, Fig. 8 de- brevity.
s
monstrates the variation of Jdrift versus the control systems’ parameters An evaluation of Fig. 8a and b reveals that the iPMI system with a
for the 12-story building exposed to the firm soil based K-T excitation. low IMR of 5% behaves similarly to its equivalent TMD, while
These results are representative of those obtained for the 6- and 20- Fig. 8c and d illustrates that for a large IMR of 90%, the iPMI system is
story buildings too, but such additional results are omitted herein for akin to an ideal BI system. Unlike the TMD-like systems (i.e., the TMD

116
H. Anajafi, R.A. Medina Engineering Structures 158 (2018) 110–123

10-1
Fig. 9. Optimal parameters of the 12-story building
Firm soil 0.3 under different K-T excitation models (i.e., different
soil conditions): (a) normalized stiffness; (b) damping
Soft soil-I ratio.
10-2 Soft soil-II 0.2
ksys. /ks

sys.
10-3 0.1

10-4 0
iPMI5% TMD5%iPMI90% BI iPMI5% TMD5%iPMI 90% BI

(a) Normalized stiffness (b) Damping ratio

and iPMI with a 5% IMR), Jdrift s


graphs for the BI-like systems (i.e., the (2) In the firm soil based K-T excitation (i.e., Fig. 10a–c) in terms of
s
ideal BI and iPMI with a 90% IMR) are no longer cone-shaped with a Jdrift the TMD’s performance for all three test-bed buildings is ap-
discernible global minimum. In other words, the optimal solutions for proximately the same as the iPMI system at a 5% IMR.
the BI-like systems are dictated by the specified design characteristics (3) When the soil profile is softer than the uncontrolled structure (i.e.,
sys.
upper bounds (i.e., TEquiv. = 2.50 s and ξ sys. = 0.30 ). The optimal stiffness Figs. 10b, c, and 11c), the iPMI at a 5% IMR is more effective than
coefficient normalized to the superstructure stiffness coefficient and the s
the TMD in terms of Jdrift . However, in terms of other seismic re-
Moving
optimal damping ratio of different passive control systems for the 12- sponses, especially Jaccel. in Fig. 11c, the TMD significantly sur-
story building exposed to different K-T excitation models are presented passes the iPMI system. In fact, because the entire damper’s mass in
in Fig. 9a and b, respectively. As shown in Fig. 9a, the stiffness term in a TMD system is placed at the roof floor, as compared to the iPMI
the optimally designed TMD and BI systems is significantly larger than system with the same overall mass uniformly distributed at all
that of individual ICs in the equivalent iPMI configurations. For ex- s
stories, it experiences less motions to minimize Jdrift .
ample, k sys./ k s for the TMD system under the firm soil based excitation (4) When the soil profile is softer than the uncontrolled superstructure
is 7.1 × 10−3 while this parameter for the iPMI with a 5% IMR is (i.e., Figs. 10b, c, and 11c), the effectiveness of both BI- and TMD-
7 × 10−4 . The reason for this observation is that in an iPMI system in- like systems significantly decreases (as compared to the reverse case
herent energy absorbers/reflectors are distributed at all stories rather when the soil profile is stiffer); in this case a relatively small im-
than at a single level. Fig. 9b illustrates that the optimal damping term s
provement in Jdrift can be achieved at the expense of significant
of the BI-like systems are the same while this parameter for the TMD- increases in other OFs.
like systems is different (especially under Soft Soil II). Furthermore, (5) Under the firm soil condition (i.e., the broad-band excitation) all
while for the BI-like systems soil type has a negligible effect on the passive control systems in all three test-bed buildings are effective
optimal damping ratio or the stiffness term, in the TMD-like systems s
in reducing Jdrift . However, for the narrow-band motions, con-
optimal parameters, especially damping ratio, depend on the soil type. sidering the achieved benefits (i.e., overall responses reductions in a
Optimization for all passive control strategies for the three test-bed building) and the associated detrimental effects (e.g., significant
buildings assuming different K-T excitation models is performed, and movements of the ICs), it can be concluded that the studied passive
the OFs defined in Eqs. (8)–(11) are presented in Figs. 10–12 (the ap- strategies are effective only in the resonance condition.
plication of the BI system in a 20-story building, although challenging, (6) The best performance of all passive control systems is achieved
is presented as an ideal baseline to assess the iPMI system’s performance when the K-T excitation central frequency is near the fundamental
at a high IMR). frequency of the building (i.e., the resonance case). This observa-
s
As seen in Figs. 10–12, in terms of the global behavior (i.e., Jdrift and tion is consistent with the results obtained by [4] for the TMD and
w
Jaccel. ), for all cases the iPMI system at a low or high IMR, on average, [62] for the BI.
performs similarly to an equivalent TMD or ideal BI system, respec- (7) As illustrated in Figs. 10–12, optimizing the iPMI system following
tively. The most important observations from Figs. 10–12 are sum- the adopted procedure in this paper can cause the average RMS
marized below. responses of the ICs to become larger than those of the floors in the
uncontrolled buildings (i.e., J Moving > 1.0 ). For example, according
s
(1) For most situations, in terms of improving Jdrift the iPMI system at a to Fig. 10a, the optimized iPMI system with a 5% IMR is associated
Moving
90% IMR outperforms the BI system; other performance criteria of with Jaccel. > 1.0 . This amplification occurs because ICs operate as
these two systems are very close. sacrificial TMDs for the entire building. This behavior should be

s .
Fig. 10. Performance objectives of optimized passive control systems in the 6-story building, ωs = 10.5 rad/s , assuming different soil conditions and minimizing Jdrift

117
H. Anajafi, R.A. Medina Engineering Structures 158 (2018) 110–123

s .
Fig. 11. Performance objectives of optimized passive control systems in the 12-story building, ωs = 5.23 rad/s , assuming different soil conditions and minimizing Jdrift

Moving
carefully accounted for and evaluated in the design process. For increase in the tuning period ratio has the same positive effect on Jdispl.
s
instance, since acceleration responses of the uncontrolled 6-story without deteriorating Jdrift . Similar trends are observed in Fig. 14a and b
building, because of its short fundamental period, are already large, for the iPMI system with a 5% IMR. As an example, various OFs for a
Moving
Jaccel. > 1.0 may cause significant problems in ICs, especially if modified TMD and iPMI system are presented in Table 3. In the mod-
they contain acceleration-sensitive components or living areas. A ified configurations (i.e., the intentionally detuned cases), the damping
similar discussion applies to the displacement responses of ICs (i.e., ratios of the ICs and of the damper’s mass are increased from their
Moving
Jdispl. ) in the 20-story building that is long period and exposed to optimal values of 10 and 13%, respectively, to 25%. For both systems
large displacement responses. In these cases, the optimum solution the tuning period ratio, T sys./ T UNC , is also increased by a factor of 1.25
might not be the preferred one, and an alternative solution would with respect to the optimal parameters. As seen in Table 3, for example,
Moving
be required in the design process in order to avoid high demands on for the iPMI system, the applied modifications decrease Jdispl. from
the ICs (see Section 8). Moving
2.22 to 1.19, and Jaccel. s
from 1.73 to 0.81, while the increase in Jdrift
(i.e., the performance degradation) is only from 0.45 to 0.57. This
8. A partial solution for controlling the relatively large seismic evaluation reveals that a simultaneous detuning with respect to the
responses of the damper’s mass and ICs in optimally-designed optimal characteristics is an effective solution to limit the moving
TMD-like systems component seismic responses.

In Section 7 it was shown that the proposed optimization procedure


can result in relatively large displacement and acceleration demands on 9. Evaluation of the near-optimal passive control systems
the moving components (i.e., the damper’s mass and ICs) in the TMD- subjected to historical earthquakes
like systems. These large seismic responses can prevent the effective
application of the PMI system. On the one hand, the amplified accel- To further verify the iPMI technique’s effectiveness, as an example,
eration responses can damage isolated units’ contents in the PMI passive control systems optimized in Section 7 assuming the firm soil
system. On the other hand, the large induced IC displacements require based K-T model are examined by exposing them to the 44 ground
large seismic gaps and special bearings, which generate significant ar- motion records of the FEMA P695 far-field set [66]. For the TMD and
chitectural and construction challenges. Tributsch and Adam [6] illu- iPMI system with a 5% IMR the modified characteristics, as those dis-
strated that a TMD’s damping ratio larger than the optimal one can cussed in Section 8, are used. The FEMA P695 record set includes 22
significantly reduce the damper’s mass responses, whereas the response pairs selected from the PEER NGA database with the following char-
reduction of the main structure remains almost unaffected. This ap- acteristics: moment magnitude between M6.5 and M7.6; either strike-
proach is investigated for the TMD-like systems studied in this paper. slip or reverse fault mechanism; site class C (soft rock/very dense soil)
s Moving
As an example, variation of Jdrift and Jdispl. versus the control or D (stiff soil) according to the NEHRP classification; site-source dis-
system parameters for the TMD system in the 12-story building exposed tance between 11.1 and 26.4 km; peak ground acceleration (PGA) be-
to the excitation corresponding to Soft Soil I (the resonant K-T excita- tween 0.21 and 0.82 g; peak ground velocity (PGV) between 19 and
tion for this building) is illustrated in Fig. 13a and b, respectively. As 115 cm/s. The 0.05-damped pseudo-spectral acceleration responses for
s
shown in Fig. 13a, Jdrift is not very sensitive to the change in the TMD’s the selected records are illustrated in Fig. 15. As seen, some of these
damping ratio. However, according to Fig. 13b, a relatively small in- records exhibit large spectral ordinates at long periods (i.e., the po-
Moving
crease in the TMD’s damping ratio can significantly decrease Jdispl. . An tential forward directivity effects) suggesting that the fault distance

s .
Fig. 12. Performance objectives of optimized passive control systems in the 20-story building, ωs = 3.14 rad/s , assuming different soil conditions and minimizing Jdrift

118
H. Anajafi, R.A. Medina Engineering Structures 158 (2018) 110–123

s ; and (b) J Moving ; versus


Fig. 13. Variation of: (a) Jdrift displ.
the TMD system’s parameters in the 12-story building
exposed to the resonant K-T excitation model
(ωs = 5.23 rad/s ; ωg = 5.0 and ξg = 0.2 ).

s Moving
Fig. 14. Variation of (a) Jdrift and (b) Jdispl. versus the
iPMI system’s parameters in the 12-story building ex-
posed to the resonant K-T excitation model
(ωs = 5.23 rad/s ; ωg = 5.0 and ξg = 0.2 ).

Table 3
Various OFs for the optimally designed (tuned case) and modified (detuned case) TMD and iPMI systems with a 5% mass ratio in the 12-story building under the Soft Soil I excitation.

Sys. type TMD 5% iPMI 5%

T sys ξ sys s
Jdrift w
Jaccel. Moving Moving T sys ξ sys s
Jdrift w
Jaccel. Moving Moving
Jdispl. Jaccel. Jdispl. Jaccel.
TUNC TUNC

Tuned case 1.18 13% 0.44 0.49 1.31 0.96 1.08 10% 0.45 0.58 2.22 1.73
Detuned case 1.48 25% 0.53 0.58 0.78 0.54 1.35 25% 0.57 0.64 1.19 0.81

2.5 44
RMS(ui ) = 1/44 ∑ [RMS(ui )] j .
(12)
2 j=1

Individuals where ui is the response of interest (e.g., inter-story drift) at the i-th
1.5 Mean floor level. Fig. 16a and b depicts RMS acceleration and displacement
Sa (g)

responses of the TMD-like systems for the 12-story building, respec-


1 tively. Fig. 17a and b illustrates similar results for the BI-like systems.
As seen in Fig. 16a and b, the RMS acceleration and displacement
0.5 responses of the superstructure, in both TMD-like systems at all stories,
are consistently reduced with respect to the uncontrolled system re-
0 sponses. The acceleration responses of the ICs at all stories are less than
0 1 2 3 4 the corresponding floor accelerations in the uncontrolled system while
T (s) their displacement responses, especially at the bottom stories, exceed
Fig. 15. 0.05-damped ground response spectra for the 44 selected ground motions re- the floor displacement responses of the uncontrolled system. An eva-
cords. luation of Fig. 17a and b illustrates that the iPMI with an IMR of 90%
can divide the building into two parts: flexible ICs with significantly
reduced acceleration responses and a relatively stiff superstructure with
criterion might not be sufficient to avoid the presence of near-field,
significantly reduced displacement responses with respect to those ex-
forward-directivity effects.
perienced by the uncontrolled structure. As seen, the displacement
The “average of the root-mean-square” (RMS ) responses under the
demands on the ICs are consistent with those generated by the rigid
44 earthquake records are utilized to calculate OFs introduced in Eqs.
body movement in the BI system.
(8)–(11):
Table 4 presents different OFs in the three test-bed buildings sub-
jected to the earthquake records. As shown in Table 4, all considered
passive control strategies could significantly decrease inter-story drift

119
H. Anajafi, R.A. Medina Engineering Structures 158 (2018) 110–123

Fig. 16. RMS acceleration (m/s2 ) and displacement


12 12 (m ) responses of the 12-story building equipped with
10 10 near-optimal TMD-like strategies subjected to the 44
ground motion records.
8 8
Floor i

Floor i
6 6
4 Uncontrolled
TMD (Frame)
4
2 TMD (Damper) 2
iPMI 5% (Frame)
Base iPMI 5% (IC) Base
0 0.5 1 1.5 2 0 0.02 0.04 0.06

(a) (b)

Fig. 17. RMS acceleration (m/s2 ) and displacement


12 12 (m ) responses of the 12-story building equipped with
10 10 near-optimal BI-like strategies subjected to the 44
ground motion records.
8 8
Floor i

Floor i

6 6
4 Uncontrolled 4
BI (Frame)
2 BI (Base) 2
iPMI 90% (Frame)
Base iPMI 90% (IC) Base
0 0.5 1 1.5 2 0 0.02 0.04 0.06

(a) (b)

Table 4
Various OFs (based on RMS responses) for the near-optimal control strategies in the three test-bed buildings subjected to the 44 ground motion records.

Sys. Type 6-story 12-story 20-story

s
Jdrift w
Jaccel. Moving Moving s
Jdrift w
Jaccel. Moving Moving s
Jdrift w
Jaccel. Moving Moving
Jdispl. Jaccel. Jdispl. Jaccel. Jdispl. Jaccel.

TMD 5% 0.61 0.66 0.98 0.65 0.60 0.69 0.90 0.56 0.65 0.76 0.86 0.50
iPMI 5% 0.68 0.71 1.41 0.91 0.64 0.75 1.34 0.77 0.68 0.82 1.36 0.66
iPMI 90% 0.06 0.12 3.29 0.08 0.10 0.16 1.62 0.11 0.14 0.20 1.19 0.16
BI 0.06 0.09 3.29 0.09 0.11 0.16 1.59 0.16 0.20 0.26 1.13 0.26

responses in the three selected test-bed buildings. Similar to the results In the evaluation of the control systems in the previous sections,
obtained in the previous sections, the iPMI system with a low or high RMS responses were used. RMS depends on duration and provides an
IMR performs like an equivalent TMD or BI system, respectively. The order of magnitude of the intensity (amplitude) of the response. RMS
TMD system consistently exhibits a better performance than its amplitudes can be interpreted as effective amplitudes that can be scaled
equivalent iPMI configuration (i.e., an IMR of 5%) in all example by a peak factor to obtain design responses. From this point of view,
buildings. An iPMI system with a high IMR of 90% in most cases out- RMS responses can be used as surrogates to conduct the evaluation of
performs the ideal BI system. design responses or as responses useful to evaluate serviceability

Fig. 18. MAX acceleration (m/s2 ) and displacement


12 Uncontrolled 12
TMD (Frame) (m ) responses of the 12-story building equipped with
10 TMD (Damper) 10 near-optimal TMD-like strategies subjected to the 44
iPMI 5% (Frame) ground motion records.
8 iPMI 5% (IC) 8
Floor i

Floor i

6 6
4 4
2 2
Base Base
0 1.5 3 4.5 6 7.5 9 0 0.05 0.1 0.15 0.2 0.25

(a) (b)

120
H. Anajafi, R.A. Medina Engineering Structures 158 (2018) 110–123

Fig. 19. MAX acceleration (m/s2) and displacement


12 12
(m ) responses of the 12-story building equipped with
10 10 near-optimal BI-like strategies subjected to the 44
ground motion records.
8 8

Floor i
Floor i

6 6
4 Uncontrolled 4
BI (Frame)
2 BI (Base)
iPMI 90% (Frame)
2
iPMI 90% (IC) Base
Base
0 1.5 3 4.5 6 7.5 9 0 0.05 0.1 0.15 0.2 0.25

(a) (b)

Table 5
Various OFs (based on maximum responses) for the near-optimal control strategies in the three test-bed buildings subjected to the 44 ground motion records.

Sys. Type 6-story 12-story 20-story

s
Jdrift w
Jaccel. Moving Moving s
Jdrift w
Jaccel. Moving Moving s
Jdrift w
Jaccel. Moving Moving
Jdispl. Jaccel. Jdispl. Jaccel. Jdispl. Jaccel.

TMD 5% 0.76 0.81 1.25 0.78 0.78 0.85 1.17 0.60 0.84 0.91 1.18 0.49
iPMI 5% 0.82 0.86 1.74 1.00 0.80 0.88 1.74 0.76 0.83 0.92 1.86 0.60
iPMI 90% 0.08 0.11 2.87 0.07 0.14 0.15 1.79 0.11 0.20 0.16 1.53 0.16
BI 0.07 0.10 2.87 0.10 0.16 0.19 1.75 0.19 0.29 0.32 1.44 0.32

Fig. 20. Normalized maximum inter-story drift re-


12 12 sponses of the superstructure for the 12-story building
10 10 under individual ground motion records: (a) near-
optimal TMD; (b) near-optimal iPMI with a 5% IMR.
8 8
Floor i

Floor i

6 6
4 4
2 2
0 0
0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2
TMD UNC PMI UNC
(Max dx)s / (Max dx)s (Max dx) s / (Max dx)s

(a) (b)

criteria. However, because (i) design responses are usually based on the 0.66, respectively, these metrics calculated based on peak responses
estimated peak (maximum value) of the response parameters of in- (shown in Table 5) are 0.76 and 0.81, respectively.
terest, and (ii) the variability in peak responses is different from the one Some previous studies [e.g., 6] have shown that under certain
observed in RMS responses, this section explicitly investigates the ef- conditions TMD could even amplify the maximum structural responses.
ficiency of the studied passive control systems in reducing the max- As an example, this potential adverse effect is investgated herein for the
imum seismic responses. The average of the maximum absolute accel- 12-story building equipped with the TMD-like systems. Fig. 20a illus-
eration and displacement responses, computed based on Eq. (13), for trates the inter-story drift responses of the superstructure at different
the TMD-like systems exposed to the 44 records are illustrated in floor levels in the TMD system normalized to those of the uncontrolled
Fig. 18a and b, respectively. Fig. 19a and b shows similar graphs for the system for each ground motion record. The same results for the iPMI
BI-like systems. with a 5% IMR are shown in Fig. 20b. These figures illustrate a sig-
nificant record-to-record variability in the inter-story drift responses. As
44
seen, while for some cases the normalized responses are as low as 0.55
MAX(ui ) = 1/44 ∑ [abs(Max(ui ))]j .
j=1 (13) (i.e., 45% response reduction), for some other records the control
system has amplified inter-story drift responses (see normalized values
To compare the efficiency of the control systems in reducing maximum larger than 1.0). This drawback is more highlighted in the TMD system
responses with their efficiency in reducing RMS responses, the OFs (Fig. 20a). The same analysis is conducted for the BI-like systems but
introduced through Eqs. (8)–(11) are re-computed using the MAX re- the results are not plotted here for brevity. The simulation results show
sponses and are illustrated in Table 5. An evaluation of different OFs that for the iPMI with an IMR of 90% and the ideal BI systems the
values shown in Tables 4 and 5 reveals that all passive control systems, normalized maximum inter-story drift responses under different records
especially the TMD-like systems, are less effective in reducing the peak range between [0.05–0.47] and between [0.06–0.48], respectively.
responses than in reducing RMS responses. For example, consider the These observations reveal that the BI-like systems consistently reduce
s
TMD system in the 6-story structure. While for this case Jdrift w
and Jaccel. maximum inter-story drift responses under all selected ground motion
calculated based on RMS responses (shown in Table 4) are 0.61 and records because the period lengthening in these systems is sufficient to

121
H. Anajafi, R.A. Medina Engineering Structures 158 (2018) 110–123

avoid the response spectral regions that exhibit relatively large spectral Future research in this area should consider applying intermediate
accelerations. IMR values that can lead to a more effective and robust system.
Configurations with dissimilar ICs along the building height, which
10. Conclusions have the potential to provide a better seismic performance, could be
also studied. Appling ICs at all stories can significantly increase the
In this paper, the seismic performance of a partial mass isolation construction cost of a building. Hence, optimizing the number and lo-
(PMI) system, in which different portions of masses at all stories are cations of ICs along the height should be investigated.
isolated from the superstructure, is studied. It is shown that this system
could effectively integrate the benefits of conventional tuned mass
damper (TMD) and base isolation (BI) techniques while resolving some Acknowledgments
of their deficiencies particularly in high-rise buildings (e.g., practical
and architectural challenges associated with the heavy additional mass The study conducted in this paper was partially supported by a CEPS
in a TMD, and problems due to the inherent flexibility, heavy loads and Fellowship provided by the College of Engineering and Physical
overturning moments imposed on isolator bearings in a base-isolated Science, University of New Hampshire to the first author. This support
tall building). The PMI system is examined in linear elastic shear- is gratefully appreciated.
building models with 6, 12, and 20 stories representing low-, mid- and
high-rise buildings, respectively. Optimization is carried out on the PMI
system’s parameters to minimize average normalized root-mean-square Appendix A. Design constraints for the passive control strategies
of inter-story drift responses of the structural frame under earthquake
excitations with different frequency contents, while constraints are Parametric studies illustrate that in the BI-like systems, with in-
specified to control the isolated components (ICs) seismic responses. creasing either the damping ratio or the fundamental period of the
Two well-adopted passive control strategies (i.e., TMD and BI systems) moving components (i.e., ICs in the PMI), the ANRMS inter-story drift
s
are also studied as baseline configurations for assessing the effective- values generally tend to decrease (see Fig. 8c). In other words, Jdrift
ness of the proposed PMI strategy. presents no discernible global optimum, and the optimization process
Simulation results indicate that an iPMI system (i.e., a PMI with results in extremely large ICs’ damping ratio and fundamental period.
identical ICs at all stories) with a low isolated mass ratio (IMR), e.g., For practical purposes the equivalent viscous damping ratio of common
5%, could perform as effectively as an equivalent TMD system, with the isolator systems is rarely greater than 30% (e.g., see the characteristics
advantage of implementing inherent mass dampers without the weight of lead rubber bearings in the FIP INDUSTRIALE catalogs at http://
restrictions of common TMDs. At a high IMR (e.g., 90%), the system www.fipindustriale.it/public/S03_LRB-eng.pdf). Hence, in this paper
could perform similarly to an ideal BI. It is illustrated that for the test- the maximum permissible damping ratio of the studied control systems
bed buildings evaluated in this study, all three considered passive is considered to be 30%. A 2% lower bound is also specified on the
control strategies are effective under broad-band excitations. However, damping ratio. On the other hand, significantly large ICs periods are
under narrow-band excitations, the control systems are effective only if associated with excessive drifts, which can be unacceptable because ICs
the uncontrolled superstructure is stiffer than the soil profile. In all test- may contain sensitive equipment or living areas. Furthermore, accom-
bed buildings, the most efficient passive control system is associated modating large ICs’ drifts requires wide seismic gaps and especial iso-
with the near-resonance case. A BI-like system for a structure located on lator bearings, which can result in significant architectural challenges.
a soft soil site (i.e., under a narrow-band excitation) is highly effective An iPMI system with a BI-like behavior (i.e., IMR = 90% ) basically
for the resonance situation. However, the performance of this system is divides a building into two parts: a relatively stiff structural frame and
very sensitive to the dynamic characteristics of the fixed-base super- flexible ICs. Hence, assuming a completely rigid structural frame, iso-
structure as well as the soft soil. This observation implies that any lated units can be oversimplified as SDOF systems, and then the ad-
misestimation of these influential parameters could cause significantly missible period upper bound can be calculated by bounding the al-
large structural responses, especially isolator drifts. Hence, the appli- lowable ICs’ drift response to a given design period value. Because K-T
cation of a BI system for a soft soil profile needs particular care, and it is excitations are used as the earthquake excitations, the output ICs’ drift
not recommended. responses are normalized RMS quantities and cannot be directly linked
As it is observed, all three studied passive control strategies are to a design period value. In this appendix the authors attempt to esti-
associated with unique advantages and disadvantages. A TMD system mate this period criterion based on an ASCE 7 [67] design spectrum. It
with a 5% damper’s mass ratio seems to be effective for all test-bed is acknowledge that the adopted strategy is associated with an inherent
buildings. However, when the number of stories increases, the mass inconsistency (because of using a design spectrum that is different than
required for a single TMD to achieve such a performance improvement the K-T excitations), and also the interaction between ICs and structural
increases significantly. For example, a 5% damper’s mass ratio at the frame in tall buildings may invalidate the concept of an equivalent
roof floor of the 20-story building weighs as much as the roof itself, SDOF system. However, it can lead to a reasonable upper bound for the
significantly affecting its structural and architectural design, while each period of ICs. The allowable design drift under the Design Basis
IC in the proposed PMI system weighs as little as 5% of the weight of Earthquake (DBE) is assumed to be 0.35 m (meaning that the allowable
each story. ICs in an iPMI strategy with a low IMR, because of their role design drift under the Risk-targeted Maximum Considered Earthquake
as sacrificial mass dampers, sustain relatively large seismic responses (a (MCER) is approximately 0.50 m). The spectral drift of an IC re-
similar behavior is observed for the damper’s mass in the TMD system). presented by a SDOF system can be computed using the simple equation
Hence, floors that contain components sensitive to large seismic re- of Sd = Sa T 2/4π 2βL in which βL = (ξ IC/0.05)0.30 , and T is the target iso-
sponses, and components that are themselves sensitive to large seismic lation period. An ASCE 7 [67] design spectrum for a site of high seis-
response are not appropriate candidates to be used as ICs in the PMI micity (a region in San Francisco, soil type C: Sa = 0.563g/T ) is as-
system. A BI technique can effectively reduce inter-story drift and ab- sumed. If the isolator’s drift demand under DBE is to be 0.35 m, the IC’s
solute floor acceleration responses but the entire isolated superstructure fundamental period and damping ratio should satisfy the inequality of
may sustain excessive displacements relative to the base ground. In an T IC/ βL ≤ 2.50 . This approximate approach limits T IC to 1.90 s and 4.28 s
iPMI configuration with a high IMR of 90%, while retaining the struc- for the two extreme damping values of 2% and 30%, respectively. The
tural response improvements of the BI system, the structural frame same period limitation is applied to the BI system to control excessive
remains almost stationary. However, in this iPMI configuration the drifts at the isolation interface.
problem of large isolators’ drift affects all stories.

122
H. Anajafi, R.A. Medina Engineering Structures 158 (2018) 110–123

References structural control systems. J Vib Control 2015;21:919–37.


[35] Lin C-C, Wang J-F, Ueng J-M. Vibration control identification of seismically excited
mdof structure-PTMD systems. J Sound Vib 2001;240:87–115.
[1] Den Hartog JP. Mechanical vibrations. 4th ed. New York; London: McGraw-Hill [36] Kelly JM, Chitty DE. Testing of a wind restraint for aseismic based isolation. Eng
Book Company; 1956. Struct 1980;2:176–86.
[2] Constantinou MC, Soong TT, Dargush GF. Passive energy dissipation systems for [37] Liang B, Shishu X, Jiaxiang T. Wind effects on habitability of base-isolated build-
structural design and retrofit. Buffalo, N.Y.: Multidisciplinary Center for Earthquake ings. J Wind Eng Ind Aerodyn 2002;90:1951–8.
Engineering Research; 1998. [38] Chen Y, Ahmadi G. Wind effects on base-isolated structures. J Eng Mech
[3] Sgobba S, Marano GC. Optimum design of linear tuned mass dampers for structures 1992;118:1708–27.
with nonlinear behaviour. Mech Syst Sig Process 2010;24:1739–55. [39] Anajafi H, Medina RA. Partial mass isolation system for seismic vibration control of
[4] Wang JF, Lin CC. Seismic performance of multiple tuned mass dampers for soil- buildings. Structral Control Health Monit 2017. http://dx.doi.org/10.1002/stc.
irregular building interaction systems. Int J Solids Struct 2005;42:5536–54. 2088.
[5] Marano GC, Greco R, Chiaia B. A comparison between different optimization cri- [40] Chey MH, Chase JG, Mander JB, Carr AJ. Semi-active tuned mass damper building
teria for tuned mass dampers design. J Sound Vib 2010;329:4880–90. systems: application. Earthquake Eng Struct Dyn 2010;39:69–89.
[6] Tributsch A, Adam C. Evaluation and analytical approximation of tuned mass [41] Chey MH, Chase JG, Mander JB, Carr AJ. Innovative seismic retrofitting strategy of
damper performance in an earthquake environment. Smart Struct Syst added stories isolation system. Front Struct Civil Eng 2013;7:13–23.
2012;10:155–79. [42] Tsuneki Y, Torii S, Murakami K, Sueoka T. Middle-story isolated structural system
[7] Naeim F, Kelly JM. Design of seismic isolated structures: from theory to practice. of high-rise building. J Disaster Res 2009;4:229–38.
New York; Chichester: John Wiley; 1999. [43] Villaverde R. Aseismic roof isolation system: feasibility study with 13-story
[8] Skinner RI, McVerry GH, Robinson WH. An introduction to seismic isolation. building. J Struc Eng-Asce 2002;128(2):188–96. http://dx.doi.org/10.1061/(ASCE)
Chichester: Wiley; 1993. 0733-9445(2002.
[9] Adam C, Di Matteo A, Furtmüller T, Pirrotta A. Earthquake excited base-isolated [44] Villaverde R, Mosqueda G. Aseismic roof isolation system: analytic and shake table
structures protected by tuned liquid column dampers: design approach and ex- studies. Earthquake Eng Struct Dyn 1999;28:217–34.
perimental verification. Proc Eng 2017. http://dx.doi.org/10.1016/j.proeng.2017. [45] Johnson JG, Pantelides CP, Reaveley LD. Nonlinear rooftop tuned mass damper
09.060. frame for the seismic retrofit of buildings. Earthquake Eng Struct Dyn
[10] Taniguchi T, Der Kiureghian A, Melkumyan M. Effect of tuned mass damper on 2015;44:299–316.
displacement demand of base-isolated structures. Eng Struct 2008;30:3478–88. [46] Feng MQ, Chai W. Design of a mega-sub-controlled building system under sto-
[11] Palazzo B, Petti L. Seismic response control in base isolated systems using tuned chastic wind loads. Probab Eng Mech 1997;12:149–62.
mass dampers. In: Seismic engineering–1994: Volume 2. PVP-Volume 275-2; 1994. [47] Hamidi M, El Naggar MH. On the performance of SCF in seismic isolation of the
[12] Tsai H-C. The effect of tuned-mass dampers on the seismic response of base-isolated interior equipment of buildings. Earthquake Eng Struct Dyn 2007;36:1581–604.
structures. Int J Solids Struct 1995;32:1195–210. [48] Liu S, Warn GP. Seismic performance and sensitivity of floor isolation systems in
[13] Palazzo B, Petti L. Combined control strategy: base isolation and tuned mass steel plate shear wall structures. Eng Struct 2012;42:115–26.
damping. ISET J Earthq Technol 1999;36:121–37. [49] Jia GF, Gidaris I, Taflanidis AA, Mavroeidis GP. Reliability-based assessment/design
[14] Di Matteo A, Furtmüller T, Adam C, Pirrotta A. Optimal design of tuned liquid of floor isolation systems. Eng Struct 2014;78:41–56.
column dampers for seismic response control of base-isolated structures. Acta Mech [50] Lu LY, Lee TY, Juang SY, Yeh SW. Polynomial friction pendulum isolators (PFPIs)
2017:1–18. for building floor isolation: an experimental and theoretical study. Eng Struct
[15] Anajafi H, Zandi AP, Khanmohammadi M. Seismic-Isolation effects on bridge 2013;56:970–82.
seismic performance, a case study. In: 13th World conference on seismic isolation, [51] Sakr TA. Vibration control of buildings by using partial floor loads as multiple tuned
energy dissipation and active vibration control of structures, The Japan Society of mass dampers. HBRC J 2015. http://dx.doi.org/10.1016/j.hbrcj.2015.04.004.
Seismic Isolation (JSSI), Sendai, Japan; 2013. [52] Xiang P, Nishitani A. Optimum design of tuned mass damper floor system integrated
[16] Ramallo JC, Johnson EA, Spencer BF. “Smart” base isolation systems. J Eng Mech- into bending-shear type building based on H-infinity, H-2, and stability max-
Asce 2002;128(10):1088–99. http://dx.doi.org/10.1061/(ASCE)0733-9399(2002. imization criteria. Struct Control Health Monit 2015;22:919–38.
[17] Branco M, Guerreiro LM. Seismic rehabilitation of historical masonry buildings. Eng [53] Pourmohammad H, Ghafory Ashtiany M, Ziyaeifar M. Buildings with local isolation
Struct 2011;33:1626–34. system: performance and simplified method of dynamic analysis. Asian J Civil Eng
[18] Providakis CP. Effect of LRB isolators and supplemental viscous dampers on seismic (Build Housing) 2006;7:501–16.
isolated buildings under near-fault excitations. Eng Struct 2008;30:1187–98. [54] Soong TT, Grigoriu M. Random vibration of mechanical and structural systems.
[19] Kilar V, Koren D. Seismic behaviour of asymmetric base isolated structures with Englewood Cliffs, N.J.: PTR Prentice Hall; 1993.
various distributions of isolators. Eng Struct 2009;31:910–21. [55] Schmelzer B, Oberguggenberger M, Adam C. Efficiency of tuned mass dampers with
[20] Shi ZF, Cheng ZB, Xiang HJ. Seismic isolation foundations with effective attenua- uncertain parameters on the performance of structures under stochastic excitation.
tion zones. Soil Dyn Earthquake Eng 2014;57:143–51. Proc Inst Mech Eng, Part O: J Risk Reliab 2010;224:297–308.
[21] Hong WK, Kim HC. Performance of a multi-story structure with a resilient-friction [56] De Angelis M, Perno S, Reggio A. Dynamic response and optimal design of struc-
base isolation system. Comput Struct 2004;82:2271–83. tures with large mass ratio TMD. Earthquake Eng Struct Dyn 2012;41:41–60.
[22] Jangid RS. Optimum lead-rubber isolation bearings for near-fault motions. Eng [57] Clough RW, Penzien J. Dynamics of structures. 2nd ed. New York: McGraw-Hill;
Struct 2007;29:2503–13. 1993.
[23] Constantinou MC, Whittaker A, Kalpakidis Y, Fenz D, Warn GP. Performance of [58] Lutes LD, Sarkani S. Stochastic analysis of structural and mechanical vibrations.
seismic isolation hardware under service and seismic loading; 2006. Upper Saddle River, N.J.: Prentice Hall; 1997.
[24] Huang YN, Whittaker AS, Luco N. Seismic performance assessment of base-isolated [59] Der Kiureghian A, Neuenhofer A. A response spectrum method for multiple-support
safety-related nuclear structures. Earthquake Eng Struct Dyn 2010;39:1421–42. seismic excitations. Earthquake Engineering Research Center, College of
[25] Chen M, Pantoli E, Wang X, Astroza R, Ebrahimian H, Mintz S, et al. BNCS Report# Engineering, University of California, Berkeley, Calif.; 1991.
1: Full-scale structural and nonstructural building system performance during [60] Villaverde R, Koyama LA. Damped resonant appendages to increase inherent
earthquakes and post-earthquake fire-specimen design, construction and test pro- damping in buildings. Earthquake Eng Struct Dyn 1993;22:491–507.
tocol. San Diego: University of California; 2013. [61] Bernal D. Influence of ground motion characteristics on the effectiveness of tuned
[26] Jangid R, Datta T. Nonlinear response of torsionally coupled base isolated structure. mass dampers. In: 11th World Conference on Earthquake Engineering; 1996.
J Struct Eng 1994;120:1–22. [62] Islam AS, Hussain RR, Jameel M, Jumaat MZ. Non-linear time domain analysis of
[27] Hall JF, Heaton TH, Halling MW, Wald DJ. Near-source ground motion and its base isolated multi-storey building under site specific bi-directional seismic loading.
effects on flexible buildings. Earthquake Spectra 1995;11:569–605. Autom Constr 2012;22:554–66.
[28] Ariga T, Kanno Y, Takewaki I. Resonant behaviour of base-isolated high-rise [63] Marano GC, Greco R. Robust optimization for TMD with uncertain bounded system
buildings under long-period ground motions. Struct Des Tall Spec Build parameters and stochastic excitation. Asian J Civil Eng (Build Housing)
2006;15:325–38. 2008;9:433–55.
[29] Li HN, Wu XX. Limitations of height-to-width ratio for base-isolated buildings under [64] Greco R, Marano GC. Robust optimization of base isolation devices under uncertain
earthquake. Struct Des Tall Spec Build 2006;15:277–87. parameters. J Vib Control 2016;22:853–68.
[30] Becker TC, Yamamoto S, Hamaguchi H, Higashino M, Nakashima M. Application of [65] Chung W-J, Yun C-B, Kim N-S, Seo J-W. Shaking table and pseudodynamic tests for
isolation to high-rise buildings: a Japanese design case study through a US design the evaluation of the seismic performance of base-isolated structures. Eng Struct
code lens. Earthquake Spectra 2015;31:1451–70. 1999;21:365–79.
[31] Komuro T, Nishikawa Y, Kimura Y, Isshiki Y. Development and realization of base [66] FEMA P695 (Federal Emergency Management Agency). Quantification of building
isolation system for high-rise buildings. J Adv Concr Technol 2005;3:233–9. seismic performance factors. Federal Emergency Management Agency, Washington,
[32] Ziyaeifar M, Noguchi H. Partial mass isolation in tall buildings. Earthquake Eng D.C.; 2009.
Struct Dyn 1998;27:49–65. [67] ASCE (American Society of Civil Engineers). Minimum design loads for buildings
[33] De Silva CW. Vibration and shock handbook. Boca Raton: Taylor & Francis; 2005. and other structures. ASCE/SEI 7–10, Reston, Va.; 2010.
[34] Saaed TE, Nikolakopoulos G, Jonasson J-E, Hedlund H. A state-of-the-art review of

123

You might also like