You are on page 1of 17

introduction

VPRS-400

POWER TOTAL SOLUTION


I. PRODUCT OVER VIEW

† Designed for Stability, Convenience , High Efficiency & High


Capacity

† Configured with 8 rectifier modules, control module can adjustment


12 rectifier modules, distribution module

† Various Monitoring Methods thought computer (RS-422, RS-485,


RS-232 )

† Centralized Monitoring with Network Management LAN, SNMP


(option)

POWER SOLUTION PROVIDER


II. SPECIFICATION

1 Input Characteristics

1. Nominal Input Voltage :


1Φ 3W 220VAC / 3Φ 4W 380VAC

2. Range of Input Voltage :


Nominal Input Voltage ± 150VAC ~ 280VAC

3. Range of Input Frequency : 45Hz ~ 70Hz

4. Inrush Current : ≤ 30A/Module

5. Efficiency : ≥ 92%

6. Power Factor : ≥ 99%

POWER SOLUTION PROVIDER


2. Output Characteristics

1. Nominal Output Voltage : -53.5V

2. Range of Operating Voltage : -44.0V ~ -60.0V

3. Output Current : Max 400A (50A × 8 modules)

* Module : DRM-550V (50A)

* Can expanded maximum 600A when adding extra rack (4 modules)

4. Output Distribution : 200A × 2 circuits

50A × 8 circuits

Can expended when customer option ( plug & play)

5. Output Voltage Regulation : ±1.0 %

6. Output Current Limitation : 40% ~ 110%

7. Output Over Voltage Protection : 59.0V ~ 60.0V

Adjustment : -48V ~ 60V

8. 8) Battery Low Voltage Disconnect : 42.0V ± 0.2V

Adjustment : 40V ~ 50V

POWER SOLUTION PROVIDER


3. General Characteristics

1. Operating Temperature : -45℃ ∼ 50 ℃

2. Storage Temperature : - 45℃ ∼ 80 ℃

3. Relative humidity : 5% ~ 95% ( non-condensing)

4. Cooling : Forced cooling

5. Electro Magnetic Interference (EMI) :

FCC PART 15 SUBPART B, CLASS A

1. Lightning Surge : ANSI/IEEE C62.41

2. Thermal Protection Surge : 6 KV (1.2x 50μs), 3KA (8x12μs)

3. Electrostatic Discharge (ESD) : EN61000-4-2

POWER SOLUTION PROVIDER


4. Physical Characteristics

1. Dimension (mm) :

† System Rack : 1015(H) × 600(W) × 600(D)

† Rectifier Module : 175(H) × 106(W) × 396.7(D)

2. Weight (kg):

† System Rack : 150kg (including 08 modules)

† Rectifier Module : 6.5kg

3. Power Density of Rectifier Module :

6.77 (W/inch³)

POWER SOLUTION PROVIDER


III. CONFIGURATION

1. Rectifier System Configuration

Item Q’ty Functions

- Supplying DC power to load


Rectifier Module
8
(DRM-550V)
- Charging batteries
- Controlling 12 modules
Control Module
1 - Measuring voltage/current
(VPRC-400)
- Monitoring/issuing alarms

AC Distribution 1 - Receiving AC power input

- Distributing DC outputs
DC Distribution 1
- Connecting batteries

POWER SOLUTION PROVIDER


2. Block Diagram

2.1. Rectifier System

VPRC-
VPRC-400

POWER SOLUTION PROVIDER


2.2 Rectifier Module

Inrush Current
Input Switch Rectifying Circuit Protection Circuit PFC Circuit

Input
+

PFC Circuit
PWM Control Feedback
PWM Output Vr
-
Control
Main Switching Circuit +
Amplifier Reference

High Speed Current Reverse Flow


Filter Circuit
Rectifying Circuit Protection Circuit

Output
+

Feedback
Main Circuit
PWM Control
PWM Output Vr
-
Control
+
Amplifier Reference

POWER SOLUTION PROVIDER


2.3 Controller

10

POWER SOLUTION PROVIDER


2.4 CABLE DIAGRAM vprs-400

R S T N

EARTH BUSBAR AC TERMINAL

AC SENSE SURGE
PROTECTION NFB NFB NFB
AC-R AC-S AC-T

DRM-550V DRM-550V DRM-550V DRM-550V


VPRC-400
#1 #4 #2 #3

DRM-550V DRM-550V DRM-550V DRM-550V


#5 #6 #8 #7

I. LOAD I. BATT

LVD

LOAD #3 LOAD #2 LOAD #1 BATT #1

AC-R (Red) 8mm2 (+) BUSBAR


AC-S (Blue) 8mm2 (-) BUSBAR
AC-T (Black) 8mm2 Sign Control
AC-N (White) 8mm2 Cabinet
Ground (Green-Yelow) 8mm2

11

POWER SOLUTION PROVIDER


IV. MAIN FUNTIONS

1. Input/Output Measuring
† Input Voltage Measuring
† Output Voltage, Output Current Measuring
† Battery Charging Current, Discharging Current Measuring
† Current Measuring for Each Rectifier Module

2. Battery Management
† Float / Equalize Charge (Automatic & Manual)
† Battery Cell Monitoring : Available for Max. 6 Sets (through RS-
485)
† Temperature Compensation Charge
† Auto-discharge Function
† Battery charge current limited

3. Rectifier Module Management


† Monitoring & Controlling Module Status at Control System through
RS-485
12

POWER SOLUTION PROVIDER


V. EMS (Environment Management System)

Systematic Network
Real-time System
Connection
Monitoring
(MSC, BSC, BTS)

Uninterruptible
Communication Service Database
Graphic User Interface & Accumulation
Maintenance Cost Saving

Alarm Control
& Report Publishing
Analysis

13

POWER SOLUTION PROVIDER


1. Management Points

Item Classification Points

AC Input Voltage

DC Output Voltage

Measured Data Load Current

Battery Charge/Discharge Current

Operating Current for Each Rectifier


Module

Battery Cell Normal/Abnormal Status


Battery Monitoring
Points
Battery Room Temperature
Rectifier

& Measured Value High/Low Limit Alarm

Battery Alarm Points Rectifier Module Abnormal Alarm

Distribution Abnormal Alarm (BATT NFB,


LVD, etc)

Measured Value High/Low Setting

Rectifier Module ON/OFF

Control & Set Points Rectifier Voltage Change

Setting Value Change (Temperature


Compensation, Float/Equalize Charge, etc)

14

POWER SOLUTION PROVIDER


• Management function abstract
Remote Site
Centralized Monitoring for System Name, ID,
Config. Location, Model No., Installed Date, etc. through
Unmanned Station 1 Network Configuration Screen.

Rectifier Fault Real-time Alarm Monitoring & Displaying on Screen


ROUTER
Storage
battery Perform. Monitoring & Analyzing Rectifier Operation Status

SNMP data Prevention from System Operation for Unauthorized


Security
User & Encoded Management Data

Account Different Priority for Each Operator’s Account


HUB
Reporting Report Document Publishing & Printing
2. Configuration( OPTION )

Central Management Office

...
Rectifier Management
Server
INTERNET
Printer

Unmanned Station N
Rectifier SNMP data
ROUTER
Storage
battery LAN
IPC Message
HUB
SNMP data

HUB ROUTER

Client Client

15
VI. ALARM MONITORING

1. Rectifier Module Error


2. Output High Voltage
3. Output Low Voltage
4. Output Over Current
5. Input Low Voltage
6. Input High Voltage
7. Power Failure
8. Battery Fuse Open
9. LVD (Low Voltage Disconnection)
10. Battery Cell Failure
11. Battery Over-discharge Pre-alert Signal
12. Control System Failure

16

POWER SOLUTION PROVIDER


VPRS-400

©2005 Dongahelecomm Corp.

All rights reserved


Information in this document is proprietary to Dongahelecomm
No information contained here may be copied, translated,
transcribed or duplicated by any form without the prior written
consent of Dongahelecomm.
http://www. Dongahelecomm.co.kr

Headquarters : 167 Namgok-ri, Yangji-myeon, Yongin Si, Gyeonggi-do Province, Korea


Tel. +82-31-330-5500/5555 Fax. +82-31-330-9040 http://www.dongahelecomm.co.kr
USA Branch : Suit 103 400 Morris Avenue Denville, NJ07834 USA
Tel. +1-973-664-1480 Fax. +1-973-664-1134
Japan Branch : 5-7-8 Negishi Saitama-shi Saitama-ken 336-0024 Japan
CP. +81-90-5776-3733 Fax. +81-48-861-6402

You might also like