Professional Documents
Culture Documents
TH 108
CaH 81
M-alk 130
Cl 22
Silica 16
Raw water 140 m3/hr
135 m3/hr Clarifier Unit
EC 300 RO Unit
TH 100
CaH 75
M-alk 120 Brine RO Return to Clarifier 33% Reject Rate
Cl 20 5 m3/hr
Silica 15
EC 972
TH 324
CaH 243
M-alk 389
Cl 65
Silica 49
Assumption
For simplicity and safety, we assume that there is no ion in the deminerrized water and all ions go to reject wa
How to use
Input the data in the red cells which are ion concentration in the raw water and thte flow of water at point of use
- Ion concentration in the raw water
- Flow of wtaer at each point of use
- The desire reject rate of the R/O unit
- Press F9 to calculate the concentration of water at each point
EC 324
TH 108
CaH 81
M-alk 130
Cl 22
Silica 16
120 m3/hr
Utility, Process
15 m3/hr
Demin Water
EC 0
TH 0
CaH 0
M-alk 0
Cl 0
Silica 0