Technical Data
Industrial Condensing Units
EEDEN10-742
LRYEQ-AY1
Refrigeration
Technical Data
Industrial Condensing Units
EEDEN10-742
LRYEQ-AY1
• Conveni-pack • LRYEQ-AY1
TABLE OF CONTENTS
LRYEQ-AY1
1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3 Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Cooling Capacity Tables ............................................. 5
5 Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Dimensional Drawings ............................................... 6
6 Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Centre of Gravity ..................................................... 7
7 Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Wiring Diagrams ..................................................... 8
9 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Sound Pressure Spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
10 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Installation Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Fixation and Foundation of Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
11 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Operation Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1 Features
s k y c S a p 1 c - Y i iA n n- o eQ r vE dnY yRo •CHL Integrates high and low temperature refrigeration and air conditioning • The modularity of the Conveni-pack system maximises installation
(including heating) into one system flexibility. Outdoor units can be grouped into blocks or rows, or
• By using heat recovery, optimised controls and state of the art distributed around the building, to meet individual installation
compressor technology, Conveni-pack can reduce annual energy constraints
1 •
consumption up to 50%, compared to conventional systems
Lower associated CO2 emissions thanks to the heat pump
• The heat extracted from the refrigeration showcases or evaporators
can be re-used for comfort heating of the shop at no extra cost
2 Specifications
3 Electrical data
3-1 Electrical Data
LRYEQ16AY1
50
Volts
380
400
Min.
342
Max.
456
MCA
35.2
TOCA
48.3
MFA
40
MSC
89
84
RLA
10.8+11.1X2
10.4+10.4X2
kW
0.75x2
FLA
0.7X2
(kVA)
1038 0.24
3 415 81 9.9+10.1X2
220 EN61000-3-2: Equipment complying
LCBKQ3AV1(E) 50 198 264 15.0 15.0 20 X 14.1 X 0.06 Professional equipment with EN61000-3-3
240
NOTES Symbols
1 RLA is based on the following conditions: MCA Min. Circuit Amps (A)
LRYEQ16AY1 (E) TOCA Total Over Current Amps (A)
- Outdoor temperature 32°C DB MFA Max. Fuse Amps (A)
- Suction SH 10K MSC Max. Starting Current
- Saturated temperature equivalent to suction pressure -10°C RLA Rated Load Amps (A)
LCBKQ3AV1(E) OFM Outdoor Fan Motor
- Saturated temperature equivalent to discharge pressure -10°C kW Rated motor output (kW)
- Saturated temperature equivalent to suction pressure -35°C FLA Full Load Amps (A)
- Suction SH 10K
2 TOCA means the total value of each OC set
3 MSC means the max. current during the starting of compressor.
4 Voltage range
Units are suitable for use on electrical systems where voltage supplied to
unit terminal is not below or above listed range limits. Inverter Comp.
5 Maximum allowable voltage variation between phases is 2% Non-inverter Comp.
Starting current
Starting time
The relationship between the
starting time and the starting
current
3D066973
4 Capacity tables
4-1 Cooling Capacity Tables
LRYEQ16AY1
(Symbol) Q: Cooling capacity
3
W: Power consumption
°C DB
Q
kW
W
kW
Q
kW
W
kW
Q
kW
W
kW
Q
kW
W
kW
Q
kW
W
kW
Q
kW
W
kW
Q
kW
W
kW
1
Refrigeration
Air conditioner
4
Refrigeration
Air conditioner
Refrigeration
Mode 24
Air conditioner
Refrigeration
Air conditioner
Refrigeration
Air conditioner
Refrigeration
Mode 29
(Refrigeration)
Notes:
1 ` Is specified point.
2 The condition of characteristics of the table
Suction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10K
Equivalent length (Piping) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5m
Level difference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0m
Indoor humidity (Gas injection line) . . . . . . . . . . . . . . . . . . . . . . RH95%
Indoor humidity
(Air conditioner (Cooling)) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . RH80%
3 Consider decrease of capacity depended on frosting, and time of
defrosting, please select larger model (about 15%)
3D066971
5 Dimensional drawings
5-1 Dimensional Drawings
LRYEQ16AY1
4-15X22,5-mm-Oblong holes
(Pitch of foundation bolt holes) (foundation bolt hole)
Detail A
(Knock-out hole)
Detail A
(Knock-out hole)
(Knock-out hole) 3D066895A
LRYEQ16AY1
MODEL
LRYEQ16AY1
3D065355A
6 Centre of gravity
6-1 Centre of Gravity
LRYEQ16AY1 3
1
6
Center of foundation
bolt hole
4D066966
7 Wiring diagrams
7-1 Wiring Diagrams
LRYEQ16AY1
POWER SUPPLY
Y1:380-415V 3N∼50Hz Wiring diagram
Terminal of M1C∼M3C
(Front)
Operating output
(Refrigeration)
Note) 4 (Back)
remote
To in/d unit To out/d unit To multi unit OFF ON
A1P Printed circuit board (Main) HAP Pilotlamp (service monitor - green) (A1P, A2P) M1F,M2F Motor (Fan) S1S Operation switch (Remote/OFF/ON) Y3E Electronic expansion valve (Oil (inv))
Notes:
1 This wiring diagram is applied only to the outdoor unit. A2P Printed circuit board (Sub) V1CP Safety devices input (A1P, A2P) PS Switching power supply (A1P,A2P,A4P) T1A current sensor (A7P,A8P) Y4E Electronic expansion valve (Oil (non1))
2 g: Field wiring A3P Printed circuit board (Noise filter) K2M, K4M Magnetic contactor (M1C) (A3P,A4P) Q1RP Phase reversal detect circuit (A1P,A2P) T2A current sensor (A10P) Y5E Electronic expansion valve (Oil (non2))
3 D : Terminal strip F : Connector A4P Printed circuit board (Inv. for comp) K2M Magnetic contactor (M2C) (A1P) R10 Resistor (current sensor) (A5P,A9P) V1R Power module (A4P,A5P,A9P) Y1R 4 way valve (Main)
R : Protective earth (screw) G : Terminal A5P Printed circuit board(Inv. for fan) K3M Magnetic contactor (M3C) (A2P) R50, R59 Resistor (A4P) V2R Diode bridge (A4P) T2R 4 way valve (Sub)
4 At the time of factory shipment, setting of ’’off’’, when operating, setting of ’’on’’ K1R Magnetic relay (K2M) (A1P) R95 Resistor (current limiting) (A4P)
A6P Printed circuit board (Power input) (Option) X1A∼4A Connector (M1F,M2F) Y3R 4 way valve (Suction)
or ’’remote’’, the point of contact of the input must use the one for a slight
current. A7P, A8P Printed circuit board (current sensor) K1R Magnetic relay(K3M) (A2P) R1T Thermistor (air) (A1P) X5A Connector (In-Out Main-Sub)) Y1S Solenoid valve (Liquid)
(for the remote switch, use non-voltage contact for microcurrent (Not more A9P Printed circuit board (Inv. for fan) K3R Magnetic relay (Y6S) (A1P) R21T Thermistor (Suction) (A1P) X6A Connector (Power supply) Y6S Solenoid valve (gas)
than 1mA DC12V))
A10P Printed circuit board (Earth leakage detector) K4R Magnetic relay (Y2R) (A1P) R22T Thermistor (Suction) (A1P) X7A Connector (Power supply) Z1C∼10C Noise filter (Ferrite core)
5 RY1 point contact is open before turning on power supply
Refer to technical guide for the operation timing diagram Push button switch (Mode, set, return, test, K5R Magnetic relay (Y1R) (A1P) R31T∼R35T Thermistor (M1C,M2C,M3C Discharge (A1P) X1M Terminal strip (Power supply) Z1F Noise filter (with surge absorber) (A3P)
BS1∼5 reset)
6 How to use (BS1-5) and (DS1-2) switch, refer to ’’service precaution’’ label on el. K6R Magnetic relay (Y3R) (A1P) R4T Thermistor (Middle inv.) (A1P) X1M Terminal strip (Control) (A1P,A2P)
compo. box cover C1 Capacitor
K7R Caution output (A2P) R5T Thermistor (Fin) (A1P) X1M Terminal strip (Operating input) (A6P)
7 When operating, don’t shorcircuit the protection device (S1PH - S3PH, S1PL) DS1, DS2 Dip switch (A1P, A2P)
K9R Warning output (A2P) S1MPH1 Pressure sensor (high) (A1P) X2M Terminal strip (Operating output)
8 Be noted that the capacity of contact is AC220-240V, 110-120VA (Total of F1U, F2U Fuse (T, 3.15A, 250V) (A1P, A2P)
caution output, warning output) K10R Magnetic relay (Operating output) (A1P) S1MPL1 Pressure sensor (Low) (A1P) X3M Terminal strip (Remote switch)
F3U, F4U Fuse (T, 1A, 250V) (A1P, A2P) S1MPH2 Pressure sensor (middle) (A2P)
9 Be noted that the capacity of contact is AC220-240V, 110-120VA (Operating K11R Magnetic relay (Y1S) (A1P) X4M Terminal strip (Warning output)
output (Refrigeration)) F1U Fuse (8A, DC650V) (A5P, A9P) S1MPL2 Pressure sensor (Low) (A2P)
RY1 Magnetic relay (A10P) X5M Terminal strip (Power supply)
10 Colors: F400 Fuse (T, 6,3A, 250V) (A3P) S1PH,SP2H Pressure switch (high) (A1P)
L1R Reactor (A4P) X6M Terminal strip (Low noise mode input)
BLK = Black RED = Red WHT = White GRN = Green BLU = Blue Pilot lamp (service monitor-orange)
M1C Motor (Compressor (inv.)) S3PH Pressure sensor (high) (A2P) Y1E Electronic expansion valve (Main)
H1P∼8P (H2P) Prepare, Test --------- Flickering
Malfunction Detection -- Light up M2C,M3C Motor (Compressor (STD)) S1PL Pressure sensor (Low) (A1P) Y2E Electronic expansion valve (Liquid)
3D059983F
(Contact capacity
AC220-240V, O,5A.)
Case of remote
switch fixing Switch
Defrost completion
thermostat
1
Power supply
220-240V
Power supply
220-240V
Warning
output Outdoor unit LRYEQ16AY1)
Defrosting indication
lamp 8
Caution
output
Operating input
Timer (Freezer) (Freezer)
Single phase 220-240V Overcurrent circuit
Earth leakage circuit breaker Fuse breaker (To booster unit)
(High-frequency type)
For earth fault, overload, and Grounding
short-circuit protection
Remote
controller
To in/d unit To out/d Timer (Refrigerator)
unit
Freezer
Operating output
Operating output Refrigerator
(Freezer)
Grounding
Note
1 All wiring, components and materials to be produced on the site must comply with the applicable local and national codes.
2 Use copper conductors only.
3 As for details, see wiring diagram.
4 Install a circuit breaker for safety.
5 All field wiring and components must be provided by a licensed electrician.
6 Unit shall be grounded in compliance with the applicable local and national codes
7 Wiring shown are general points-of-connection guides only and are not intended for or to include all details for a specific installation.
8 If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while the product is operating,
attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
9 In case of used remote switch, use non-voltage contact for microcurrent (not more than 1mA, 12V DC)
10 Total capacity for caution, warning: AC 220-240V, 110-120VA.
Capacity for operation output: AC 220-240V, 110-120VA. 3D066960
11 Must install earth leakage circuit breaker
9 Sound data
9-1 Sound Pressure Spectrum
LRYEQ16AY1
1
Octave band sound pressure level dB(0dB=0.0002μ bar)
approximate
threshold hearing
for continuous
noise
Measuring place
Anechoic chamber (conversion value)
10 Installation
10 - 2 Fixation and Foundation of Units
LRYEQ16AY1 3
For single unit installation For installation in rows For centralized group layout
<Pattern 1> <Pattern 1> <Pattern 1>
<Front>
50 or more <Front> 50 or more 50 or more 100 or more 100 or more 50 or more
500 or more 500 or more
<Pattern 2>
50 or more <Front> 100 or more 50 or more 50 or more <Front> 100 or more 50 or more
500 or more 500 or more <Front>
<Unit: mm>
Notes:
MODEL
1 Heights of walls in case of Patterns 1 and 2: LRYEQ16AY1(E)
Front: 1500 mm
suction side: 500 mm
Side: Height unrestricted.
Installation space to be shown in this drawing is based on the cooling operation at 32 degrees outdoor air temperature.
<suction side>
<Front side>
When the design outdoor air temperature exceeds 32 degrees or the load exceeds maximum ability because of much generation load of heat in all outdoor
unit, take the suction side space more broadly than the space to be shown in this drawing.
2 If the above wall heights are exceeded then h1/2 and h2/2 should be added to the front and suction side service spaces respectively as shown in the figure
on the right.
500 mm
h1=A (Actual height) - 1500
h2=B (Actual height) - 500
x=500+h1/2 or over
Y=300+h2/2 or over
(Y=100+h2/2 or over)
[Values in parentheses are for pattern 2]
3 When installing the units most appropriate pattern should be selected from those shown above in order to obtain the best fit in the space available always
bearing in mind the need to leave enough space for a person to pass between units and wall and for the air to circulate freely.
(If more units are to be installed than are catered for in the above patterns your layout should take account of the possibility of short circuits.)
4 The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out comfortably. 3D065029A
Foundation bolt
LRYEQ16AY1 Nut Type: JA
Size: M12
Spring washer
Frame Four bolts are required
Y ditch
Note). 6
Drain ditch
When building a When building a
foundation on the foundation on the When installing multiple units in connection
ground concrete floor
X - XCross section
NOTES
1 The proportions of cement: sand: gravel for the concrete shall be 1:2:4, and the reinforcement bars that their diameter are 10mm, (approx. 300mm intervals) shall be placed.
2 The surface shall be finished with mortar. The corner edges shall be chamfered.
3 When the foundation is built on a concrete floor, rubble is not necessary. However, the surface of the section on which the foundation is built shall have rough finish.
4 A drain ditch shall be made around the foundation to thoroughly drain water from the equipment installation area.
5 When installing the equipment on a roof, the floor strength shall be checked, and water-proofing measures shall be taken.
6 Y ditch is not necessary for the following model. LRMEQ5AY1(E), LRMEQ6AY1(E), LRLEQ5AY1(E), LRLEQ6AY1(E)
3D065348A
11 Operation range
11 - 1 Operation Range
LRYEQ16AY1
Air conditioner (cooling)
Refrigeration
Range for pull down operation
Range for continuous operation
Outdoor temperature (°CDB)
NOTES
1 Range for humidity (Air-conditioner (cooling))...RH80% or below
Range for humidity (Refrigeration)...RH95% or below
2 ″Range for continuous operation″ Shows possible range of continuous operation
3 ″Range for pull-down operation″ Shows possible range of short-time operation
- Do not select the model in the range for pull down operation
- To be more than 3°C/hour that the temperature of indoor unit drops, do not open the door and do not enter the goods in pull down operation as possible (Refrigeration)
3D066959
Daikin’s unique position as a manufacturer of air The present publication is drawn up by way of information only and does not constitute an offer binding
conditioning equipment, compressors and refrigerants upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this publication to the best of its
has led to its close involvement in environmental issues. knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for
for the environment is set in the EMAS and ISO 14001 systems.
For several years Daikin has had the intention to become particular purpose of its content and the products and services presented therein. Specifications are subject
a leader in the provision of products that have limited to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect
impact on the environment. This challenge demands the damage, in the broadest sense, arising from or related to the use and/or interpretation of this publication. All
eco design and development of a wide range of products content is copyrighted by Daikin Europe N.V..
The present publication supersedes EEDEN09-742