Professional Documents
Culture Documents
AN-T8/0006
Application Note
Issue Record
Floating systems
It is generally assumed that a floating system will be capable of withstanding an earth fault without
either causing a control action or having a control action inhibited. In theory this is true but in practice
no system really floats. It is merely referenced to earth by one or more impedances. A typical system
will use two resistors connected between the positive and negative potentials of the supply with the
centre point connected to earth. The current in the earth connection is monitored and if it increases
above a predetermined level the alarm will be sounded indicating that a fault exists somewhere in the
system.
UPS Positive
R1
EARTH To system
R2
Negative
In such a system the value of the earth resistances is critical. If they are high resistance the earth
Fault monitor will need to be very sensitive but if they are of a low value high circulating currents can be
generated by a single earth fault. Unfortunately the latter is normally the case which means this type of
installation offers no protection from the effects of earth faults, but increases the potential for un
revealed failures.
If for example an earth fault is generated on a digital input loop it is possible that the loop will be
bypassed. The equivalent circuit of an earth faulted input is shown below.
UPS
R1 Series
Impedance
EARTH
In this case an earth fault is generated on the positive connection to the field switch which causes
current to flow through R2 if the field switch is opened. If R2 is not significantly higher in impedance
than the series impedance the switch will be bypassed and will not operate when required to do so.
UPS
R1 Field
Switch
EARTH
If the circuit design has the series impedance in the negative return the same effect occurs with current
flowing in R1 bypassing the field switch. In both of these scenarios there may be no indication of the
problem because the loop current is low compared to the earth fault detection current.
The same effect is seen on outputs if the output is of higher or similar impedance to R1 or R2.
This scenario means that the protection of the system is compromised by a single earth fault.
A further scenario exists which is even more dangerous should two or more earth faults exist.
Take for example two field switches each of which have an earth fault (Water in a junction assembly)
Series Series
Impedance Impedance
Earth
Field Field
Switch Switch
If two switches have an earth fault then they are effectively connected together and both
have to open to be registered by the Safety System.
Earth
Series Series
Impedance Impedance
Outputs
Safety Safety
Output Output
Earth
Field Field
Solenoid Switch
Solenoid
The diagram above illustrates how a pair of earth faults can effectively bypass a safety output so that a
required shutdown will not operate. Both safety outputs have to de-energise before the field solenoids
de-energise.
None of these scenarios are related to a particular manufacturers’ equipment but rely solely on Ohms
Law.
Earthed systems
In negative earthed systems the action of an earth fault is much more deterministic. Field circuits are
selected with the input switch in the positive potential.
Earth
Series Series
Impedance Impedance
Earth
One or more earth faults will fail safe. If the system is fitted with line monitoring components, a fault
can be indicated which need not cause a shutdown.
In the case of outputs, the load will normally be connected with one side to the negative potential.
Safety Safety
Output Output
Earth
Field Field
Solenoid Switch
Solenoid
In this case the current in the load can be measured and alarmed but should it reach an unacceptable
level the output will disengage and fail safe.
Conclusion
Regional Headquarters:
Americas:
4325 West Sam Houston
Parkway North, Suite 100
Houston
Texas 77043-1219
USA
Tel: +1 713 353 2400
Fax: +1 713 353 2401
Asia Pacific:
Unit 2/12 Keegan Street
O’Connor
Western Australia
Tel: +61 89 314 7787
Fax: +61 89 314 7786
www.icstriplex.com
For technical support email: support@icstriplex.com
Sales enquiries: sales@icstriplex.com