You are on page 1of 68

TB012309

Chilled Beam
Design Guide

Trox USA, Inc. Telephone 770-569-1433


4305 Settingdown Circle Facsimile 770-569-1435
Cumming
Georgia www.troxusa.com
USA 30028 e-mail trox@troxusa.com
Contents

Introduction to Chilled Beams 3 Chilled Beam Selection 27

Passive chilled beams 3 Passive beams selection 27


Active chilled beams 5 Passive beam performance data 28
Selection examples 31
System Application Guidelines 8 Active beam selection 32
Active beam selection examples 35
Benefits of chilled beams 8
Chilled beam applications 9 Performance Notes 38

Multiservice Chilled Beams 11 Active Beam Performance Data 39

System Design Guidelines 14 Coil pressure loss data 39


DID600 series beams 44
Comfort considerations 14 DID620 series beams 52
DID300 series beams 62
Air side design 15
Water side design 19 Chilled Beam Specifications 68
Control considerations 21
Installation and commissioning 24

Notice to Users of this Guide


This Guide is intended for the sole use of professionals involved in the design and specification of TROX chilled
beam systems. Any reproduction of this document in any form is strictly prohibited without the written consent of
TROX USA.

The content herein is a collection of information from TROX and other sources that is assumed to be correct and
current at the time of publication. Due to industry and product development, any and all of such content is subject
to change. TROX USA will in no way be held responsible for the application of this information to system design
nor will they be responsible for keeping the information up to date.

2
Introduction

Chilled beams have been employed in European HVAC There are two basic types of chilled beams (see figure
sensible cooling only applications for over twenty years. 2). Passive chilled beams are simply finned tube heat
Within the past few years they have become a popular exchanger coil within a casing that provides primarily
alternative to VAV systems in North America. The convective cooling to the space. Passive beams do not
growing interest in chilled beams has been fueled by incorporate fans or any other components (ductwork,
their energy saving potential, ease of use as well as nozzles, etc.) to affect air movement. Instead they rely
their minimal space requirements. on natural buoyancy to recirculate air from the
conditioned space and therefore needs a high free area
Chilled beams were originally developed to supersede passage to allow room air to get above the coil and
the outputs achieved by passive radiant cooling ceiling cooled air to be discharge from below the coil. As they
systems. Sensible cooling capacities of “chilled” ceilings have no provisions for supplying primary air to the
are limited by the chilled water supply temperature space, a separate source must provide space
(must be maintained above dew point to prevent ventilation and/or humidity control, very typically
condensation from forming on their surfaces) and the combined with, but not limited to, UFAD. The air source
total surface area available that can be „chilled‟. commonly contributes to the sensible cooling of the
Obviously, this area is limited as other services space as well as controlling the space latent gains.
(lighting, fire protection, air distribution & extract etc.)
limit the degree of employment of the active ceiling
surface such that their maximum space sensible cooling
capacity is very typically less than 25 BTUH per square
foot of floor area. As this is not sufficient for maintaining
comfort especially in perimeter areas, chilled beams
very quickly became the preferred solution in so much
as they occupied less space, had fewer connection and
most importantly offered sensible cooling outputs 2 to 3
times that of „chilled‟ ceilings.

INTRODUCTION TO CHILLED BEAMS


Passive Chilled Beam
Chilled beams feature finned chilled water heat (Exposed Beam Shown)
exchanger cooling coils, capable of providing up to
1100 BTUH of sensible cooling per foot of length and
are designed to take advantage of the significantly
higher cooling efficiencies of water. Figure 1 illustrates
that a one inch diameter water pipe can transport the
same cooling energy as an 18 inch square air duct. The
use of chilled beams can thus dramatically reduce air
handler and ductwork sizes enabling more efficient use
of both horizontal and vertical building space.

18“ x 18“
Air Duct

Active Chilled Beam

Figure 2: Basic Beam Types


1“ diameter
Water Pipe
Active chilled beams utilize a ducted (primary) air
supply to induce secondary (room) air across their
Figure 1: Cooling Energy Transport integral heat transfer coil where it is reconditioned prior
to its mixing with the primary air stream and subsequent
Economies of Air and Water discharge into the space. The primary air supply is
typically pretreated to maintain ventilation and humidity
control of the space. The heat transfer coil

3
Passive Chilled Beams

provides sensible cooling, it is not used to condense or combine resulting in a higher velocity in the occupied
provide latent cooling. space. Air discharge across the face of the beam
should be avoided as this can reduce the cooling output
Further discussion of the performance, capacities and by inhibiting the flow of warm air into the heat ex-
design considerations for each type of beam is provided changer coil.
in the following sections of this document.
Passive Chilled Beam Variations
PASSIVE CHILLED BEAMS
Passive chilled beams may be located above or below
Passive chilled beams are completely decoupled from the ceiling plane. When used with a suspended ceiling
the space air supply and only intended to remove sensi- system recessed beams, TROX TCB-RB, are located a
ble heat from the space. They operate most efficiently few inches above the ceiling and finished to minimize
when used in thermally stratified spaces. their visibility from below. Figure 4. illustrates such a
recessed beam application.
Figure 3. illustrates the operational principle of a pas-
sive beam. Warm air plumes from heat sources rise
naturally and create a warm air pool in the upper portion
of the space (or ceiling cavity). As this air contacts the
coil surface, the heat is removed which causes it to drop
back into the space due to its negative buoyancy
relative to the air surrounding it. The heat is absorbed
lifting the chilled water temperature and is removed
from the space via the return water circuit. About 85%
of the heat removal is by convective means, therefore
the radiant cooling contribution of passive chilled beams
is minimal and typically ignored.

Figure 4: Recessed Beam Installation


Recessed beams are concealed above the hung ceiling
and should also include a separation skirt (TCB-RB-
Skirt) which assures that the cooled air does not short
circuit back to the warm air stream feeding the beam.

Recessed beams (TROX series TCB) may be either


uncapped (standard) or capped (more commonly
known as shrouded) (see figure 5). Capped or
shrouded beams have a sheet metal casing which
maintains separation between the beam and the ceiling
air cavity which is often used for the space return air
passage. This also provides acoustical separation be-
tween adjacent spaces.

Figure 3: Passive Beam Operation

Passive chilled beams are capable of removing 200 to


650 BTUH of sensible heat per linear foot of length Separation Skirt
depending upon their width and the temperature
difference between their entering air and chilled water
mean temperature. The output of the chilled beam is Figure 5: Capped Passive Beam
usually limited to ensure that the velocity of the air
dropping out of the beam face and back into the Passive beams mounted flush with or below the ceiling
occupied zone does not create drafts. surface are referred to as exposed beams. Most ex-
posed beams (e.g., TROX TCB-EB and PKV series) are
It should also be noted that the air descending from a furnished within cabinets designed to enhance the ar-
passive beam „necks‟ rather like slow running water out chitectural features of the space as well as assure the
of a faucet. This slow discharge can be effected by necessary air passages for the beam.
other air currents around it and should passive beams
be installed side by side, the two airstreams will join and

4
Active Chilled Beams

TROX Passive Chilled Beams

TROX USA offers 2 ranges of passive chilled beam as Primary air


the core engine behind the variants. supply

TCBU series beams offer a full range of 1 & 2 row


recessed and exposed passive beams.
Suspended
PKVU series beams are 1 row passive beams ceiling
with or without exposed cabinets.

Figure 6 illustrates an exposed passive beam in whose


cabinet other space services (lighting, smoke and
occupancy detectors, etc.) have been integrated. Such
integrated beams are referred to as integrated or multi-
service chilled beams (MSCB). As with recessed
beams, it is generally recommended that the cross Figure 7: Active Chilled Beam Operation
sectional free area of the passage into an exposed
chilled beam be equal to at least one its width. For more
information on these beams see pages 27-31. well. In these cases, displacement ventilation and con-
ditioning will be used to produce a thermally stratified
room environment.

Active chilled beams typically operate at a constant air


volume flow rate, producing a variable temperature
discharge to the space determined by the recirculated
air heat extraction. As the water circuit can generally
extract 50 to 70% of the space sensible heat genera-
tion, the ducted airflow rate can often be reduced ac-
cordingly, resulting in reduced air handling requirements
as well as significantly smaller supply (and ex-
haust/return) ductwork and risers.

Active chilled beams can provide sensible cooling rates


as high as 1100 BTUH per linear foot, depending on
their induction capabilities, coil circuitry, and chilled
water supply temperature. Later in this guide, you will
Figure 6: Exposed Beam Installation see that careful selection of the beam must be made to
ensure that high terminal velocities are avoided to main-
tain comfort, a beam is not just a method of providing
ACTIVE CHILLED BEAMS cooling, but also a terminal discharge device that has to
be selected to suit the location, space and how the
In addition to chilled water coil(s), active chilled beams space is being utilized.
incorporate ducted air connections to receive pretreated
supply air from a central air handling unit. This air is Active chilled beams can be used for heating as well,
injected through a series of nozzles within the beam to provided the façade heat losses are moderate.
entrain room air. Figure 7 illustrates an active beam that
induces room air through a high free area section within Active Chilled Beam Variations
its face and through the integral heat transfer coil where
it is reconditioned in response to a space thermostat Active chilled beams come in a number of lengths and
demand. The reconditioned air then mixes with the widths allowing their use in exposed mounting or
ducted (primary) air and is discharged into the space by integration into suspended ceiling systems, (their weight
means of linear slots located along the outside edges of requires they be independently supported). They can be
the beam. furnished with a variety of nozzle types that affect the
induction rate of room air. Their discharge pattern can
Active beams mounted above the occupied zone be supplied as either one or two way while some beams
maintain a sufficient discharge velocity to maintain a allow modification of their discharge characteristics
fully mixed room air distribution. As such, they employ a once installed. Finally, some variants are available with
dilution ventilation strategy to manage the level of condensate trays designed to collect a limited amount
airborne gaseous and particulate contaminants. Certain of unexpected condensation.
variants of active beams (see discussion below) may be
mounted in low sidewall or floor level applications as

5
Active Chilled Beams

DID620 series beams are a low profile beam designed to allow inte-
gration into standard 24 inch wide ceiling grids. They are ideal for
applications with limited ceiling plenum spaces.

DID600 series beams are also designed to allow their integration into
standard 24 inch wide acoustical ceiling grids. Though slightly taller
than the DID600BU, their construction allows easy modification to
specific customer requirements.

DID300 series beams have a nominal face width of 12 inches and


utilize two vertical chilled water coils. As such they can be furnished
with condensate trays to catch any moisture that might have unex-
pectedly formed on the coil surfaces during periods of unusual opera-
tion.

Figure 8: TROX Ceiling Mounted Active Chilled Beams

6
Active Chilled Beams

DID-E series beams are designed for high sidewall mounting in ho-
tels and other domiciliary applications.

BID series beams condition perimeter areas in UFAD applications.


Conditioned air is delivered by a dedicated perimeter area air han-
dling unit. This relieves the UFAD system of the responsibility of pro-
viding sensible cooling to the perimeter, resulting in substantially
reduced building airflow requirements.

QLCI series beams are integrated into low sidewall mounted cabinets
and to discharge conditioned air to the space in a displacement
fashion. They are most commonly used for classroom HVAC as they
offer significant air quality and acoustical advantages. In fact, they are
the only available terminal capable of maintaining classroom sound
pressure levels compliant with ANSI Standard S12.60.

Figure 9: Other TROX Air-Water Products

7
Benefits of Chilled Beams

CHILLED BEAM SYSTEM APPLICATION • Higher chilled water temperatures used by


chilled beams may allow chiller efficiencies to
GUIDELINES be increased by as much as 35%.
Chilled beams (both passive and active) posses certain
• Chilled beam systems offer attractive water
inherent advantages over all-air systems. These
side economizer. Unlike the case with air side
benefits can be divided into the three categories as
economizers, these free cooling opportuni-
follows:
ties are not as restrictive in climates that are
also humid.
First cost benefits of chilled beam systems
• Maintenance costs are considerably lower
Chilled beams afford the designer an opportunity to
than all-air systems. Chilled beams do not
replace large supply and return air ductwork with small
incorporate any moving parts (fans, motors,
chilled water pipes. This results in significant savings in
damper actuators, etc.) or complicated control
terms of plenum space and increases usable floor
devices. Most chilled beams do not require
space.
filters (and thus regular filter changes) or
condensate trays. As their coils operate „dry‟,
• Chilled beams can be mounted in ceiling
regular cleaning and disinfection of
spaces as small as 8 to 10 (vertical) inches
condensate trays is not necessary. Normal
while all-air systems typically require to 2 to
maintenance history suggests that the coils be
2.5 times that. This vertical space savings can
vacuumed every five years (more frequently in
be used to either increase the space ceiling
applications such as hospital patient rooms
height or reduce the slab spacing and thus the
where linens are regularly changed). Figure
overall building height requirements.
10 compares the lifetime maintenance and
replacement costs for active chilled beams to
• The low plenum requirements of chilled beam
fan coil units (FCU), based on an expected
systems make them ideal choices for retrofit of
FCU lifetime of 20 years. It assumes that
buildings that have previously used sidewall
each beam or FCU serves a perimeter floor
mounted equipment such as induction units,
area of 150 square feet.
fan coils and other unitary terminals.

• Chilled beams contribute to horizontal space


savings as their significantly lower supply Active Chilled
Fan Coil Unit
airflow rates result in smaller supply and re- Beam
turn/exhaust air risers. The capacity of the air Filter Changes:
Frequency: Twice Yearly NA
handling units providing conditioned air to the
Cost per Change: $30.00
chilled beam system is also reduced, resulting
Cost over Lifetime (20 Years): $1,200.00 $0.00
in considerably smaller equipment room foot
prints. Clean Coil and Condensate System:
Frequency: Twice Yearly Every four Years
TM
• LEED also requires that certified buildings Cost per Event: $30.00 $30.00
be purged for a period of time before Cost Over Lifetime: $1,200.00 $150.00
occupancy in order to remove airborne
Fan Motor Replacement:
contaminants related to the construction proc-
Frequency: Once during life NA
ess. The significantly reduced airflow require-
Cost per Event: $400.00
ment of chilled beam systems reduces the fan
Cost Over Lifetime: $400.00 $0.00
energy required to accomplish this task.
Life Cycle (20 years) maintenance cost: $2,800.00 $150.00
Operational cost benefits of chilled beam systems
Source: REHVA Chilled Beam Application Guidebook (2004)
The energy costs of operating chilled beam systems are
considerably lower than that of all-air systems. This is Figure 10: Life Cycle Maintenance Costs
largely due to the following:
Active Chilled Beams versus Fan Coils
Reduced supply air flow rates result in lower
fan energy consumption.

• Operational efficiencies of pumps are


intrinsically higher than fans, leading to much
lower cooling and heating energy transport
costs.

8
Applications

Comfort and IAQ benefits of chilled beam systems 1) Brokerage trading areas

Properly designed chilled beam systems generally Trading areas consists of desks where a
result in enhanced thermal comfort and indoor air single trader typically has access to multiple
quality compared to all-air systems. computer terminals and monitors. This high
equipment density results in space sensible
Active chilled beams generally deliver a cooling requirements considerably higher than
constant air volume flow rate to the room. As conventional interior spaces while the ventila-
such, variations in room air motion and cold air tion and latent cooling requirements are es-
dumping that are inherent to variable volume sentially the same. Active chilled beams re-
all-air systems are minimized. move 60 to 70% of the sensible heat by
means of their water circuit, reducing the
• The constant air volume delivery of primary air ducted airflow requirement proportionally.
to the active chilled beam helps assure that
the design space ventilation rates and relative 2) Broadcast and recording studios
humidity levels are closely maintained.
Broadcast and recording studios typically
Chilled beam application criteria have high sensible heat ratios due to their
large electronic equipment and lighting loads.
Although the advantages of using chilled beams are In addition, space acoustics and room air
numerous, there are restrictions and qualifications that velocity control are critical in these spaces.
should be considered when determining their suitability Passive chilled beams are silent and capable
to a specific application. Chilled beams are suitable for of removing large amounts of sensible heat,
use where the following conditions exist: enabling the use of a low velocity supply air
discharge.
• Mounting less than 20 feet. Ceiling heights
may be greater, but the beam should generally 3) Heat driven laboratory spaces
not be mounted more than 20 feet above the
floor. Designers often classify laboratories according
to their required supply airflow rate. In
• The tightness of the building envelope is laboratories that are densely populated by
adequate to prevent excessive moisture fume hoods, the make up air requirement is
transfer. Space moisture gains due to typically 12 air changes per hour or more.
occupancy and/or processes are moderate. These laboratory spaces are classified as air
driven. Laboratories whose make up air
• Space humidity levels can be consistently requirement is less than that are typically
maintained such that the space dew point considered heat driven. This category includes
temperature remains below the temperature of most biological, pharmaceutical, electronic
the chilled water supply. and forensic laboratories. The ventilation re-
quirement in these laboratories is commonly 6
• Passive beams should not be used in areas to 8 air changes per hour, however, the proc-
where considerable or widely variable air esses and equipment in the laboratory can
velocities are expected. often result in sensible heat gains that require
18 to 22 air changes with an all-air system. To
• Passive beams should only be considered make matters worse, recirculation of air
when an adequate entry and discharge area exhausted from these laboratories is not
can be assured. allowed if their activities involve the use of
gases or chemicals.
• Passive Chilled beams can not be used to
heat. Active chilled beams remove the majority (60
to 70%) of the sensible heat by means of their
Applications best served by chilled beams chilled water coil, enabling ducted airflow rates
to be reduced accordingly. Not only is the
Chilled beams are ideal for applications with high space space more efficiently conditioned, but the
sensible cooling loads, relative to the space ventilation ventilation (cooing and heating) load at the air
and latent cooling requirements. These applications handler is substantially reduced as far less
include, but are not limited to: outdoor air is required.

9
Applications

4) High outdoor air percentage applications


Blind Box
Applications such as patient rooms in hospitals
typically demand higher ventilation rates as
well as accurate control of those rates. Chilled
beam systems are ideal for these applications
Passive Return Air
as their hydronic sensible cooling regulates the
Chilled Beam Grille
space temperature while allowing a constant
volume delivery of supply and ventilation air to
the space. Displacement chilled beams such
as the „TROX QLCI‟ also offer opportunities for
improved contaminant removal efficiencies,
reducing the likelihood of communicable
diseases spreading to health care staff
members.

5) Perimeter treatment for UFAD systems

As conditioned air passes through the open


floor plenum in UFAD systems, it picks up heat
transferred through the structural slab from the
return plenum of the floor below. The amount Finned Tube Swirl Type
of heat transfer that is likely to occur is very Heating Coil Floor Diffuser
hard to predict as many factors influence it.
However, the resultant temperature rise in the
conditioned air can often lead to discharge
temperatures 4 to 5˚F higher than those
encountered in interior zones nearer the point
of entry into the supply air plenum. Such Figure 11: Passive Chilled Beams for
higher temperatures contribute to perimeter Perimeter Treatment in a UFAD System
zone airflow requirements that are typically 35
to 40% higher than that of conventional
(ducted) all-air systems. Chilled beams are also an excellent choice w h e r e
the vertical height of the ceiling cavity is limited. These
Passive chilled beams such as the TROX TCB include applications involving:
series provide effective and reliable cooling of
perimeter spaces in UFAD applications. Figure 1) Building height restrictions
11 illustrates such an application where the
passive beam is mounted above the acoustical Building codes may restrict the overall height
ceiling and adjacent to the blind box above an of buildings in certain locales. This commonly
exterior window. Floor diffusers fed directly promotes the use of tighter slab spacing which
from the pressurized supply plenum continue reduces the depth of the ceiling cavity. Passive
to provide space ventilation and humidity chilled beams can often be fit between
control. Heating cannot be effectively structural beams in these applications. Active
accomplished by passive beams, so an chilled beam systems can easily be designed
underfloor finned tube heating system or to require 10 inches or less clearance when
radiant panel heating system typically integrated into the ceiling grid system.
compliments the chilled beams.
2) Retrofits involving reduced slab spacing
Use of passive beams for perimeter area
sensible cooling can reduce overall supply Many buildings that are candidates for HVAC
airflow rates in UFAD systems by as much as system retrofits utilize packaged terminal units
50%. This also results in a) smaller air (induction units, vertical fan coil units, etc.)
handling units and ductwork, smaller supply that are installed below the ceiling level. As
and return air risers, c) reduced maintenance such, many of these structures have ceiling
requirements and occupier disruption, d) cavities with limited depth. Chilled beams are
improved space acoustics and air quality. ideal for such retrofits.

10
Multi-Service Chilled Beams

Multi-service (or integrated) chilled beams incorporate In addition, the outer frame is often customized to pro-
other space services into the linear enclosures associ- vide a visual appeal that is consistent with the architec-
ated with the chilled beams. This allows fitting of the ture of the space in which it is mounted.
selected services to the beams within the factory and
delivery of elements that house all of these services to Multiservice chilled beams can be provided as either
the job site in a “just-in-time” fashion. Upon arrival, active or passive versions. In cases where passive
these devices are hung, attached in a linear fashion and beams are used, a separate air distribution system must
modular connections facilitate the installation of the be provided. Oftentimes this air supply utilizes the cavity
various service systems. beneath a raised access flooring system as a supply
plenum and is referred to as Underfloor Air Distribution.
Figure 12 below illustrates an active multi-service beam
and the services that can be easily integrated with it. The service fixtures provided with multiservice beams
The core of this device is a DID302 active chilled beam are usually provided by others and issued tom the fac-
which incorporates a primary air duct (and plenum) a tory for mounting and connection where possible. Upon
chilled water coil as well as inlet (perforated face) and completion, the beams are shipped to the job site for
discharge (linear slot) air passages. The outer frame of mounting and final connection.
the device is designed to provide mounting surfaces
and provisions for other services which are installed at Lighting provided with these beams may be direct, indi-
the factory prior to shipment to the job site. Some of the rect or both. In all cases, the lighting system designer
services that can be integrated include: should be consulted to assure that the beam design and
placement also provides sufficient space lighting. Fire
1. Lighting fixtures and controls protection designers should also be consulted in order
2. Speakers to assure that the placement of the beams does not
3. Occupancy sensors conflict with that of the fire sprinklers.
4. Smoke detectors

Figure 12: Multiservice Chilled Beams

11
Multi-Service Chilled Beams

Multiservice Chilled Beam Designs The Case for Multiservice Beams

Figures 13 and 14 below illustrate passive and active Multiservice chilled beams offer numerous advantages
(respectively multiservice beam installations. over conventional service delivery systems, notably:

Note that the photograph in figure 13 includes a swirl 1. As the services are integrated into the beams in the
type diffuser mounted in the floor near the window. This factory, quality control can be much better main-
diffuser supplies conditioned air for the ventilation and tained than with field mounted services. Factory
dehumidification of the space. The beams include a mounting involves the provision of proper fixtures
linear bar grille for the room air discharge and are to do the work and facilitates difficult piping and
curved to conform to the curvature of the ceiling. Both valve connection. This also allows the final piping
direct and indirect lighting is provided. to be leak tested after the components are assem-
bled.
Figure 14 illustrates an active beam version where the 2. Factory mounting of the space services reduces
facial slots have been relocated such that they are not the amount of required trade coordination on the
visible and are integrated into the top of the beam, dis- job site.
charging supply air across the surface of the exposed 3. All of the space services mounted in the common
slab. Again lighting is both direct and indirect in the housing can be easily accessed for final connection
case of these beams. and commissioning as well as future maintenance.
4. The design of the housing involves the project ar-
The photographs in these figures do not show a ser- chitects as well as the engineering consultants and
vices corridor that runs perpendicular to the beams to- drives early coordination efforts as opposed to last
ward the interior of the space. This corridor is approxi- minute panics.
mately the depth of the beams themselves and houses 5. The above advantages can result in significant
the main ductwork, piping and other services that feed reductions in the time required to construct the
the beams. These corridors may also house the return building.
air passage in case where the slab is exposed. As a
rule of thumb, about thirty (30) linear feet of beams may The construction time reduction has made multiservice
be connected to each run leaving the service corridor. beams very popular in the Europe, especially the United
Kingdom. Cases where the building construction time
Most multiservice beams are provided for exposed slab has been reduced by 25 to 30 percent have been well
applications but other versions can be provided to inte- documented in a number of publications. Construction
grate with acoustical ceiling grids. schedule reductions of ten to fifteen percent result in

Figure 13: Passive Multiservice Beams Figure 14: Active Multiservice Beams

12
Multi-Service Chilled Beams

significant cost savings. In particular, fixed site costs Building Height Requirements
can be retired much earlier. These fixed site costs
include but are not limited to: Multiservice beams may also afford opportunities for
reduced building height and/or facilitate the retrofit of
1. Communication and utilities services buildings with limited slab spacing. The integration of
2. Sanitation services space services in the beam often eliminates the need
3. Equipment rentals for an acoustical ceiling and allows the beams to be
4. Insurance costs pendant mounted directly to the structural slab.

On a job with a two year construction schedule, these Figure 15 below illustrates the slab spacing require-
fixed costs (which contribute nothing to the value of ments of a VAV system with fan powered terminals
the project) typically amount to 12 to 14% of the value versus an exposed mounted multiservice active
of the construction itself. Terminating the project chilled beam. The ductwork in the VAV system is
sooner allows these costs to be cut proportionally. must be located such it remains below the horizontal
structural supports. It also must be supported several
The use of multiservice beams can also allow the inches above the ceiling grid to allow the installation
elimination of the acoustical ceiling system and, on of light fixtures and sprinkler systems. In order to pro-
new construction projects, may afford the use of vide a floor to ceiling height of nine (9) feet, the slab
lesser slab spacing. This may reduce the structure spacing is typically thirteen (13) feet.
costs as well or may allow more floors to be housed
within in a similar structure height (see next section). Multiservice beams which are mounted to the slab
allow the provision of a ten (10) foot distance from the
Finally, earlier completion allows the building owner to floor to the overhead slab while maintaining an 8.5
begin realizing revenue faster. The combination of foot clearance under the beams when used with a
these financial impacts typically offsets the cost differ- 10.5 foot slab spacing. This savings essentially allows
ence between the multiservice approach and that of the addition twenty percent more floors in a building
conventional HVAC and space services delivery. when multiservice beams are used instead of a VAV
system.

Light fixture Suspended ceiling


M ultiservice Chilled Beams
VAV with Fan Terminals
10'-6" 10'-0" 8'-6"
13'-0"
9'-0"

Figure 15: Slab Spacing Reduction with Multiservice Beams

13
Comfort Considerations

CHILLED BEAM SYSTEM DESIGN Designing for acceptable space acoustical levels
GUIDELINES The space acoustical requirements are usually dictated
by its intended use. The 2007 ASHRAE Handbook
The HVAC system is responsible for three important
(Applications)3 prescribes design guidance (including
tasks that help assure occupant comfort and a healthy
recommended space acoustical levels) for various types
indoor environment:
of facilities and their use.
1) Removal of the space sensible heat gains.
2) Delivery of a prescribed volume flow rate of AIR SIDE DESIGN CONSIDERATIONS
outdoor air to properly ventilate the space.
3) Sufficient dehumidification to offset the space Room and primary air design considerations
latent heat gains.
When chilled beam systems are being contemplated,
As the water circuit in chilled beams is designed only to the relationship between the room design conditions
assist in achieving the sensible cooling objective, the air and the primary air requirements should be closely
supply to the space must be properly maintained to evaluated.
accomplish the ventilation and dehumidification goals.
As previously stated, the chilled water circuit within
In order to achieve efficient chilled beam system chilled beams is capable of considerably higher
operation, certain considerations should be factored into sensible heat removal efficiencies than does
the development of the system design and operational conditioned air supplied to the space. As such, it is
objectives. The following sections identify and briefly advantageous to remove as much sensible heat as
discuss such considerations that apply to the design, possible by means of the chilled water circuit. In theory,
selection and specification of the equipment that this practice would allow the supply airflow rate to the
supplies and controls the chilled beams. space to be reduced proportionally and result in both
energy savings and reduced HVAC services space
• General design objectives. requirements. However, the airflow supply to the space
• Air-side design goals and considerations. is also the sole source of space ventilation and dehu-
• Water-side design goals and considerations. midification so consideration of these functions is im-
• Control and operational considerations. perative in the design of chilled beam systems. The
primary (conditioned) airflow rate to the beam must be
The following sections discuss design decisions that sufficient to provide space humidity control, ventilation
affect the sizing and selection of the air and water and supplement the chilled water circuit in satisfying the
system equipment and accessories. space sensible heat gains. The space primary airflow
rate must be the maximum of that needed to adequately
Designing for occupant thermal comfort accomplish all of those individual tasks.

The maintenance of a high level of occupant thermal Space ventilation requirements are usually based on
comfort is the primary objective of most chilled beam the number of space occupants and the floor area in
applications. ANSI/ASHRAE Standard 55-2004 Thermal which they reside. ASHRAE Standard 62-2004
Environmental Conditions for Human Occupancy 2 provides guidance in the calculation of these
identifies key factors that contribute to thermal comfort requirements. Some spaces (laboratories, healthcare
and defines environmental conditions that are likely to facilities, etc.) may require higher ventilation rates due
produce such. The Standard generally states that dur- to processes they support. Identification of the re-
ing cooling operation, the space (operative) dry bulb quired space ventilation rate should be the first step in
temperature should be maintained between 68 and the design process.
77˚F and the space dew point temperature should not
exceed 60.5˚F. If the space operative temperature is a
75˚F, this maximum dew point temperature corresponds
to a relative humidity of 60%.

The Standard also defines the occupied zone as the


portion of the bounded by the floor and the head level of
the predominant stationary space occupants (42 inches
if seated, 72” if standing) and no closer than 3 feet from
outside walls/windows or 1 foot from internal walls. It is
generally accepted that velocities within the occupied
zone should not exceed 50 to 60 feet per minute.

14
Airside Design Consideration

In order to maintain specified room humidity levels, the 4.5


primary airflow must remove moisture (latent) heat at
the rate at which it is generated. The supply airflow rate A 4.0
required to do this is determined by the equation:

Latent Airflow Factor, FLATENT


3.5 Space Relative
CFMLATENT = qLATENT / 4840 x (W ROOM - W SUPPLY) 50%
Humidity
51%
where, qLATENT is the space latent heat gain and W ROOM 3.0
52%
and W SUPPLY is the humidity ratio (LBS H2O per LB Dry
Air) of the room and supply air, respectively. 53%
2.5
54%
When chilled beam systems are used, the chilled water 55%
2.0 Optimized Design
sensible heat extraction rate allows reduction of design Range
56%
supply airflow rates by 50 to 60% over conventional all- 57%
air systems. Reductions of this magnitude may, how- 1.5
ever, compromise space ventilation and dehumidifica-
tion. When chilled beams are used in applications
1.0
where a) the design outdoor dew point temperature is 48 49 50 51 52 53 54 55 56
above 50˚F and b) preconditioning outdoor air to a dew
point temperature below that (50˚F) is not feasible, Primary Air Dewpoint Termperature, ˚F
careful consideration should be given to the determina-
tion of design room air humidity levels. Figure 12: Pschrometric relationship
Between Space and Primary Airflow
Figure 11 illustrates relationships between the primary
air supply and the space design conditions for a typical
interior space. This figure uses the specified room rela-
tive humidity and the primary air dew point tempera-
ture to establish a factor (FLATENT) that relates the pri-
mary airflow requirement to maintain the desired room
relative humidity as a ratio of the space ventilation re-
quirement. It assumes a ventilation rate of 20 CFM per
person.

The primary airflow rate required to accomplish the


desired space ventilation and dehumidification can be
calculated as:

CFMLATENT = FLATENT x CFMVENT

Note that maintenance of 50% relative humidity with


primary air supplied at a 52˚F dew point temperature
will require that the primary airflow rate for the required
space dehumidification be some 2.3 times the space
ventilation rate. If the design relative humidity of the
space were 55% (well within ASHRAE recommenda-
tions), the primary airflow requirement could be halved.
Alternatively, the primary air could be conditioned to a
48˚F dew point in order to maintain 50% relative humid-
ity with a similar primary airflow rate. As the beams are
generally operated at a constant volume flow rate, the
room relative humidity levels will remain constant during
occupied periods.

Perimeter airflow requirements in chilled beam systems


are generally driven by space sensible heat gains,
therefore, space relative humidity levels in those areas
will typically remain lower than in interior spaces.

In summary, designing for slightly higher relative


humidity levels can result in significant reductions
in space primary airflow requirements!

15
Airside Design Considerations

Room air distribution in passive beam applications When passive beams are mounted adjacent to an
outside window (and the room is thermally stratified),
As passive beams rely only upon natural forces to the momentum of the warm air rising along the
recirculate the air to and from the space, it is critical that perimeter surface will likely result in entering air
excessive restrictions in the air passages to and from temperatures 4 to 6˚F warmer than the room control
the beams be avoided. As such, passive beams utilize temperature, dependent on the surface temperature of
very wide fin spacing (typically 3 to 4 fins per inch) as the façade.
opposed to conventional cooling coils. Research
indicates that the performance of these beams can also Ceiling or high sidewall outlets can be used (with a
be significantly compromised if an adequate entry and lesser heat transfer efficiency) provided their horizontal
discharge path is not maintained. throw to 50 FPM does not extend to within four feet of
the passive beam.
It is generally recommended that the return and dis-
charge passage of air through the ceiling perforated tile In order to maintain a high level of thermal comfort,
be equal to 2 times the width of the coil, normally split passive beams should be located such that the veloci-
50-50, down the long sides of the beam. Figure 13 illus- ties of the falling cool air do not cause discomfort. As a
trates the recommended entry and discharge area rela- general rule, the velocity at the head level of a station-
tionships for recessed passive beams mounted above a ary occupant should not exceed 50 FPM. Figure 14
ceiling tile with a 50% free area. The free area of the illustrates typical velocities directly below passive
perforated ceiling has a direct result on performance of beams as a function of the sensible cooling they
the beam., as the free are decreases, the output also provide.
decreases. The free area of the tile should not be lower
than 28%, however, no increase in output is gained
beyond 50% free area. When passive beams are
mounted very near a perimeter wall or window, the re-
quired return air passage may be reduced as the warm
air entering the beam has more momentum (contact
TROX USA for further application assistance). Exposed
beams must also be located such that the entering air
passage requirements are observed.

Min. 0.33 x B

Minimum
20% Free
Area Panel Separation Skirt

W = 2.0 x B Figure 14: Velocities Below Passive Beams

Figure 13: Entry Area Requirements for


Passive Chilled Beams
Passive chilled beams operate most efficiently in a
stratified or partially stratified room environment. As
such, displacement ventilation or underfloor air
distribution (UFAD) outlets with limited vertical
projection (throw to a terminal velocity of 50 FPM is no
more than 40% of the mounting height of the beams).
For design purposes, the beam entering air temperature
should be assumed 2˚F warmer than that at the control
level of the room under the described installation and
operating conditions.

16
Airside Design Considerations

Space temperature control in passive beam systems is Active beams can be for heat in moderate climates. Hot
accomplished by varying the amount of sensible heat water can either be delivered to each perimeter area
removed by the chilled water. The chilled water supply beam or to a hot water heating coil in the duct supply-
to several beams within a single zone is generally ing a number of beams within the same thermal control
controlled by a single chilled water valve. Although the zone. The use of a zone hot water heating coil feeing
zone may consist of multiple spaces, a certain degree multiple chilled beams is a generally more economic
of temperature compensation for each space will be option than piping each chilled beam for heating as it
affected by the passive beam itself. As the cooling may save considerable labor and piping material costs.
requirement of the space is reduced, the temperature of If active chilled beams are used for heating, the follow-
the air entering the beam will also be reduced. This will ing recommendations should be observed:
result in less heat transfer to the water circuit and a
lower return water temperature. • Chilled beam discharge temperatures should
be maintained within 15˚F of the room
Passive chilled beams cannot be used for heating as its temperature.
airflow would be reversed. They are typically applied • Velocities at the mid-level of outside walls and
with some type of separate heating system such as low windows should be maintained within the
level finned tube heaters. Radiant (ceiling or wall region indicated in figure 15.
mounted) heating panels can also be used depending
on the façade heat losses expected. Unoccupied periods demanding heating via the chilled
beams or primary air system will require that the AHU
Thermal comfort considerations with active beams remain operational.

While the primary (conditioned) airflow rate for active Variable air volume operation using active beams
chilled beams can be greatly reduced, their induction
ratios (2 to 6 CFM of room air per CFM primary air) Although normally operated as constant air volume
result in discharge airflow rates that are slightly higher delivery devices, active chilled beams can also be used
than those of conventional all-air systems. As such, as variable air volume (VAV) devices. VAV operation
attention should be exercised in the beam placement to may be advantageous when space occupancy and/or
avoid drafty conditions and maximize occupant thermal ventilation demands vary widely. Recommendations for
comfort. Figure 15 predicts maximum occupied zone the control of chilled beams in VAV applications can be
velocities for various combinations of primary airflow found in the control section of this document.
rates and active beam spacing. This nomograph
suggests local velocities which will maintain acceptable
levels of occupant comfort per ASHRAE.

As the room air distribution provided by active


beams is identical to that provided by ceiling slot
diffusers, their selection for (total) discharge airflow
rates greater than 40 CFM per linear foot of slot is
not recommended when high levels of occupant
thermal comfort are required!

The vL velocities shown in figure 15 are those predicted


within 2 inches of the window or wall surface during
cooling operation. It is recommended that beams which
are configured for both heating and cooling of perimeter
spaces be selected such that vL (selected for cooling
operation) is between 120 and 150 FPM in order to
assure that the warm air is adequately projected down
the perimeter surface. Velocities taken 6 inches away
from the surface can be expected to be about half those
values.

Heating in chilled beam applications

Ceiling or high sidewall mounted passive chilled beams


exert no motive force on their discharge airflow, and
cannot be used for overhead heating. Heating must be
provided by a separate source, either the primary air
supply or a separate heating system (finned tube,
radiant panel, etc.).

17
Airside Design Considerations

Velocity exceeds that recommended for high


occupant comfort levels.
H - H1 (feet) Ceiling Height (H), ft.
ASHRAE recommended selection for perimeter
3 4 5 6 beams doing both heating and cooling. 9 10 11 12

Velocities VH1 and VL are based on a 15˚F


(cooling) temperature differential
100 FPM between the room and the supply Local
airstream. Velocity VL ,
Type C Nozzle: QTOTAL = 3.2 x QPRIMARY FPM
BEAM
90 FPM TOTAL Type B Nozzle: QTOTAL = 4.2 x QPRIMARY
AIRFLOW Type A Nozzle: QTOTAL = 5.3 x QPRIMARY
RATE Type G Nozzle: QTOTAL = 5.3 x QPRIMARY
Type M Nozzle: QTOTAL = 6.1 x QPRIMARY 150 FPM
Local Velocity V H1 , FPM

80 FPM

80 CFM/LF

70 FPM
140 FPM

60 FPM 70 CFM/LF

130 FPM

50 FPM
60 CFM/LF
120 FPM
40 FPM

50 CFM/LF 110 FPM

30 FPM 100 FPM


40 CFM/LF
90 FPM

4 6 8 10 12 14

Distance A/2 or L (feet)

L A

0.5 QSUPPLY 0.5 QSUPPLY 0.5 QSUPPLY

40 mm
0.5 H H - H1

VL VH1

NOTES:
1) V L values in chart are measured 6" from wall. Velocites 12" from wall will be 40% lower.
2) Selection and velocity recommendations are per 2007 ASHRAE Handbook (HVAC Applications) .

Figure 15: Local Velocity Predictions for TROX Series 300U, 600U, 300BU and 600BU
Active Chilled Beams

18
Water Side Design Considerations

WATER SIDE DESIGN CONSIDERATIONS TROX USA recommends that the chilled water sup-
ply temperature for passive chilled beams is at least
Once the room air conditions have been established, 1˚F above the maximum room dew point that can be
the water side design objectives and requirements can controlled to whilst active beams are kept at or
be identified. Certain factors must be considered in above the room dew point as an operational safety
arriving at the chilled water system design. The margin. In general, most beams installed to date have
following sections discuss these. a supply temperature 1.5˚F or more above room dew
point.
Chilled water supply source
The return water temperature leaving chilled beams is
There are several possible sources of adequately at least 3˚F higher than the chilled water supply. As
conditioned chilled water for the supply of chilled beam such, the chilled water return piping does not normally
systems. Among these are several sources discussed need to be insulated.
below:
Primary Chilled
Primary Chilled Water Return
• Return water from AHU chilled water coil Water Supply

• Dedicated chilled water supply system HEAT EXCHANGER


• District chilled water supply
• Geothermal wells
3-way
Moduating Supply Temperature
When air handling units associated with chilled beam Valve Controller T
systems utilize chilled water evaporator coils, their
return water can often be used to remove heat from the
Chilled Water
chilled beam circuit. Figure 16 illustrates a chilled water Pump
Return Water Bypass
loop whose heat is extracted through a heat exchanger
to the AHU return water loop. The chilled water supply Secondary
Secondary
is a closed loop which includes a bypass by which Chilled Water
(Tempered) Chilled
Water Supply to
return water can be bypassed around the heat Return
Beams
exchanger to maintain the desired chilled water supply
temperature to the beams. Figure 17 illustrates a chilled
beam system where the beams are supplied by a dedi-
Figure 15: Shared or Tempered Chilled
cated chiller. The chilled water loop allows the chiller to Water Supply Circuit
operate at a higher efficiency due to the higher return
water temperatures associated with the chilled beam
system. The chiller‟s COP can often be increased by 25 Dedicated
to 30% by doing so. Chiller

In some cases, water from district chilled water supplies


or geothermal wells may replace the return water from 3-way
Moduating Supply Temperature
the AHU and serve as the primary loop in the heat Valve Controller
Storage T
exchanger shown in figure 16. Vessel

Chilled water supply and return temperatures Chilled Water


Return Water Bypass Pump

The most important decision regarding the chilled water Secondary


system involves the specification of a chilled water Secondary (Tempered) Chilled
Chilled Water Water Supply to
supply temperature. In order to prevent condensation Return Beams
from forming on the beams, the chilled water supply
temperature must be sufficiently maintained. The
REHVA Chilled Beam Applications Guidebook1 Figure 16: Dedicated Chilled Water Circuit
suggests that condensation will first occur on the supply
piping entering the beam. As such, it is very important
to insulate the chilled water supply piping to the beams.
Reference 4 suggests that condensation will not likely
form when the active chilled water supply temperature
is maintained no lower than 3˚F below the room air dew
point and at least 1˚F above the space dew point
temperature in the case of passive beams.

19
Water Side Design Considerations

Hot water supply and return temperatures

Active chilled beams can be used for perimeter heating


and cooling in mild climates. It is recommended that the
hot water supply be maintained at a temperature that
will result in a beam discharge temperature no more
than15˚F warmer than the ambient room temperature.

Water flow rates

There are factors that affect the minimum and maximum


water flow rates within the chilled beam system.
Maximum flow rates are limited by the pressure loss
within the beam. Minimum flow rates are based on the
maintenance of turbulent flow to assure proper heat
transfer. The following recommendations apply to the
chilled water system design:

Water head loss through the beams should be


limited to 10 feet H2O or less.
Pressures exceeding 10 feet H2O at the water con-
trol valve may cause noise when the valve begins
opening.
The 2005 ASHRAE Handbook (Fundamentals)5
limits water flow rates in pipes that are two (2)
inches in diameter or less to that which results in
maximum velocities of 4 FPS.
Chilled beam water flow rates below 0.15 GPM
may result in non-turbulent flow. Selection below
this flow rate should not be made as the coil per-
formance cannot be assured.

Water treatment recommendations

As most of the elements within the chilled (and hot)


water piping systems are typically copper or brass, it is
important that the water circuit is treated to assure that
there are no corrosive elements in the water. The water
circuits feeding the chilled beams should also be treated
with a sodium nitrite and biocide solutions to prevent
bacterial growth. Glycol should not be added except
where absolutely necessary as it changes the specific
capacity of the chilled water and its effect on the chilled
beam performance must be estimated and accounted
for. Prior to start up and commissioning, all chilled and
hot water piping should be flushed for contaminants.

20
Control Strategies

CHILLED BEAM CONTROL CONSIDERATIONS

This section discusses the control of both the air and


the water supply in chilled beam systems. It also
presents and discusses strategies for condensation
prevention.

Temperature control and zoning with chilled beams

Room temperature control is primarily accomplished by


varying the water flow rate or its supply temperature to
the chilled beam coils in response to a zone thermostat
signal. Modulation of the chilled water flow rate typically
produces a 7 to 8˚F swing in the beam‟s supply air
temperature, which affects a 50 - 60% turndown in the
beam‟s sensible cooling rate. This is usually suffi- Figure 18: TROX VFL Flow Controller
cient for the control of interior spaces (except confer-
ence areas) where sensible loads do not tend to vary
significantly. If additional reduction of the space cooling Chilled (and hot) water flow control strategies
is required, the primary air supply to the beam can be
reduced. In any case, modulation of the chilled water The most economical way to control the output of the
flow rate or temperature should be the primary means chilled beam is to modulate the water flow rate through
for controlling room temperature as it has little or no the coil. This may be accomplished in either of two
effect on space ventilation and/or dehumidification. Only ways. Figure 19 illustrates a typical piping and hydronic
after the chilled water flow has been discontinued control schematic for a single thermal zone utilizing
should the primary airflow rate be reduced. chilled beams. There are isolation valves within each
zone which allow the chilled beam coils within the zone
Thermal control zones for chilled beam applications to be isolated from the chilled water system. This
should be establish in precisely the same manner they enables beams to be relocated or removed without
are defined for all air systems. These zones should disturbing the water flow in other zones. The coils‟ water
consist of adjacent spaces whose sensible cooling flow rate is throttled by a 2-way chilled water valve
requirements are similar, and several beams should be actuated by the zone thermostat. Most chilled beam
controlled from a single space thermostat. For example, systems utilize floating point valve actuators that
the beams serving several perimeter spaces with the provide on-off control of the beam water flow. Throttling
same solar exposure can be controlled by a single the water flow rate results in variable volume flow
thermostat to create a zone of similar size to that which through the main water loop while its supply and return
might be served by a single fan terminal in an all air water temperatures tend to remain relatively constant.
system. Conference rooms and other areas with widely
varying occupancy should be controlled separately.
Figure 20 shows a zone within a chilled beam system
Control of the primary airflow rate that is controlled by a 3-way valve. Such a schematic
will allow modulation of the chilled water flow to the
Figure 17 illustrates a TROX model VFL flow limiter beams within the zone while maintaining a constant
which can be fitted directly to the inlet side of the active volume flow rate within the main distribution system.
beam. This limiter is fully self-contained and requires no Such control may be advantageous in cases where a
power or control connections. It may be field set to dedicated chiller is used and significant variations in the
maintain a volume flow rate to the beam. VFL limiters water flow rate can result in danger of freezing within
are recommended for use on beams fed by the same the chiller itself. Three way valves are also frequently
air handling unit supplying VAV terminals. The VFL used when condensation prevention controls are
compensates for system pressure changes to maintain employed.
the beam‟s design airflow rate. Figure 18 illustrates this
application. The piping illustrated in figure 19 is reverse-return. The
first unit supplied with chilled water is the farthest from
VFL flow limiters require a minimum of 0.15 inches H2O the main chilled water return. Using reverse-return
differential static pressure to operate. This must be
added to the catalogued pressure loss of the beam to
arrive at an appropriate inlet static pressure require-
ment. For acoustical reasons, the inlet static pressure
should not exceed 1.0 inches H2O. More information on
VFL flow limiters may be found in TROX leaflet 5/9.2/
EN/3.

21
Control Strategies

Chilled Chilled
water water
supply return

Isolation
Isolation
valve valve

2 way
on-off
control
valve

T Zone thermostat

Chilled beams within a single thermal zone

Figure 19: Chilled Beam Zone Control by Means of a Throttling (On/Off) 2 Way Valve

Chilled Chilled
water water
supply return

Isolation
valves (2)
Flow
Measurement
and Balancing
Valves 3 way
proportional
control
valve

T Zone thermostat

Chilled beams within a single thermal zone

Figure 20: Chilled Beam Zone Control by Means of a Diverting 3 Way Valve

Chilled Chilled
Zone thermostat T water water
supply return
3 way proportional
control valve

Isolation
Pump valves (2)

Chilled beams within a single thermal zone

Figure 21: Chilled Beam Zone Control by Water Temperature Modulation

22
Control Strategies

Outdoor Air
piping tends to adequately balance the water flow to Dew Point
multiple beams within a single zone. Sensor

The chilled beam output may also be controlled by


HEAT
maintaining the water flow rate constant and modulating EXCHANGER
its temperature. In these cases, the water flow rate Supply Water
throughout both the main and zone circuits remains Temperature
constant. This is a more expensive alternative which is Controller

generally only used where space humidity levels are


unpredictable yet condensation must be prevented T
without compromising the space thermal conditions.
Figure 21 illustrates such a zone using a mixing Chilled
Return Water Bypass
strategy where return water is recirculated to raise the Water
Pump
chilled water supply temperature to the beams. A pump
must be supplied within the zone piping circuit to
Secondary Chilled Secondary (Tempered) Chilled
produce a sufficient head to pump the Water Return Water Supply to Beams
supply/recirculated water mixture to the beams.
Pressure
R
Regulator
Condensation prevention strategies
2-way Chilled
Water Valve
As long as the space dew point temperature can be (one per zone)
maintained within a reasonable (+/- 2˚F) range and the To Chilled Beam
chilled water supply temperature is at (or above) the Zones
design value, there should be no chance of condensa-
tion on the surfaces of the chilled beams. The beam Figure 22: Chilled Water Temperature
surfaces will never be as cold as the entering chilled
water temperature. In the case of active beams, the
Reset Based on Outdoor Dew Point
constant room airflow across the coil surface will also
provide a drying effect.
Chilled Chilled
Some applications may, however, be subject to periods water
supply T Zone thermostat
water
return
where room humidity conditions drift or rise due to
infiltration or other processes that may add significant Moisture Sensor

unaccounted for moisture to the space. In these cases, Isolation


Isolation
valve
the employment of some type of condensation control valve

strategy may be warranted. There are several methods 2 way


on-off
of condensation prevention control that include the control
following (and combinations of such): valve

• Central monitoring and control


• Zonal monitoring with on/off control
• Zonal monitoring with modulating control Chilled beams within a single thermal zone

Central dew point monitoring and control involves the


measurement of the outdoor dew point temperature and Figure 23: Throttling Chilled Water Control
control of the chilled water supply temperature in with Moisture Sensor Override
relation to that. This is an effective method of control for
relatively mild climate applications where operable
windows and/or other sources contribute to excessive
infiltration of outdoor air. The central supply water evaporated. Conditioning of the space will be limited to
temperature can be modulated to remain at (or some that provided by the primary airflow until acceptable
amount above) the outdoor air dew point. Figure 22 humidity conditions allow the chilled water flow to be
illustrates such a method of condensation control. resumed. This is an economic and effective method of
condensation control in spaces where such conditions
An alternative method of condensation prevention is the are not expected to occur frequently. The sensor may
use of zonal on/off control signaled by moisture sensors also be used as a signal to increase the flow of primary
on the zone chilled water connection (see figure 23) . air to further dehumidify the space, reducing the time
When moisture forms on the supply water pipe next to that the chilled water flow is shut off.
the zone water valve, the zone water flow is shut off
and will not be restored until the moisture has been

23
Installation and Commissioning

If the maintenance of local thermal conditions is critical,


a zone humidistat may be used to modulate the zone
chilled water supply temperature as shown in figure 24.
This requires that each zone fitted for such control be Uni-strut Channels
fitted with a pump capable of recirculating return water bolted to structure
above allows
into the supply circuit of the chilled beam. adjustment along
beam width
Temperature T Chilled Chilled
Sensor
water water
Beam suspended
supply return
Dew Point Zone Temperature 3 way from channels by
Sensor and Humidity proportional threaded rods
Controller control valve
Factory furnished
Isolation mounting brackets
Pump valves allow adjustment
(2) along beam length

Figure 25: Installation of an Active Beam

Chilled beams within a single thermal zone Integration with


standard 1" wide
Figure 24: Condensation Protection Using (inverted) tee bar grid
Temperature/Humidity Sensing to Modulate 1"
the Zone Chilled Water Temperature

Integration with narrow


INSTALLATION AND COMMISSIONING 9/16" wide (inverted)
tee bar grid
Mounting considerations
9/16"
The weight of chilled beams requires that they be
separately supported, independent of any integrated
ceiling grid or drywall surface. They are usually
suspended from the structure above by means of Integration with narrow
threaded rods or other sufficiently strong support means 9/16" wide tubular type
5/16"
that allow the beam‟s position to be vertically adjusted.
grid
The beams are usually mounted and connected prior to
the installation of the ceiling grid or drywall. TROX
chilled beams are furnished with a minimum of four (4) 9/16"
attachment angles whose position can be adjusted
along the beam length to allow the beam to be
“dropped” into the suspended ceiling grid with which it is
integrated. When integrated with a ceiling grid system Integration into dry wall
or drywall, it is recommended that the beams be ceiling using plaster
suspended from linear channels (such as uni-strut) that frame
run perpendicular to the beam‟s length, so there is
some adjustability in every direction. Figure 25 1"
illustrates the mounting of active and passive beams.

TROX offers various borders to coordinate DID series Figure 26: Integration of Active Beams into
beams with three types of acoustical ceiling grids Common Ceiling System Applications
(illustrated in figure 26):

24
Installation and Commissioning

When active beams are to be used without an adjacent connect the beam to the supply air duct and this flexible
ceiling surface, TROX recommends that an extended duct should not have any excess bends or radius.
outer surface be furnished which allows formation of a
Coanda effect that helps direct the discharge air Water treatment
horizontally and prevent dumping.
It is imperative that there are no corrosive elements in
Recessed passive chilled beams may also be the secondary water supply to the beams as there are
integrated with suspension grid systems, but they are brass fittings on the coils and/or connection hoses.
usually mounted above the grid and have no direct Periodic testing of the secondary water circuit on each
interaction with it. It is recommended that a separation floor should be performed to assure that none of these
skirt (see figure 13) be used to separate the two air corrosive elements are present.
streams (warm entering air from cool discharge air) of
the beam. Exposed passive beams are almost always Prior to connection to the beams and the chiller plant,
pendant mounted to the structural slab above and used the water pipes should be thoroughly flushed to remove
without a false ceiling system. any impurities that may reside within them. Only after
this purging has occurred should the connections to the
Air and water connections coils and the chiller plant be performed. Additional
information regarding system cleaning may be found in
Connection of the chilled water (and hot water where reference 6.
applicable) supplies to chilled beams are the
responsibility of the installing contractor. Chilled beams Once filled by the mechanical contractor, the system
may be furnished with either NPT (threaded) male con- should be dosed with chemicals that prevent bacterial
nections or with straight pipe ends appropriate for field growth. Typical additives would be a sodium nitrate
soldering. While each coil is factory tested for leakage, inhibitor solution of 1000 parts per million (e.g. Nalcol
it is important that the beams are at no time subjected 90) and a biocide solution of 200 parts per million (e.g.
to installation or handling that might result in bending or Nalcol). Reference 6 provides additional information
otherwise damaging the pipe connections in any way. regarding water treatment.
All control, balancing and shut –off valves that may be
necessary are also to be provided and installed by System Commissioning
others. Do not over tighten any threaded connections to
the beams. TROX provides each beam with vents that are used to
purge air from the water circuit. These vents are located
All chilled water supply piping should be adequately on the coil‟s intended return header. Prior to
insulated. Return water piping may be left un-insulated commissioning any air trapped in the pipe work should
provided the return water temperature remains above be purged from the water circuit through these vents.
the dew point of the spaces over which it passes.
A flow measuring device and suitable balancing valve
Flexible hoses may be used for chilled beam water should be provided for each beam which will enable
connections. These hoses may employ either threaded adjustment of the chilled water flow rate to each beam
or snap lock connectors. TROX USA offers such within the thermal zone to its design value. This is
threaded connectors as an option. These connectors illustrated in figure 20. Where five to six beams are
are 100% tested and marked with individual installed in a reverse-return piping circuit (per figure 19),
identification numbers. In the event of a failure, the there will likely be no need for such measuring devices
batch within which they were manufactured can be and balancing valves.
readily identified and preemptive remediation can be
performed without concern that all hoses on the job are The primary airflow rate to an active chilled beam can
subject to failure soon. The normal life of flexible hoses best be determined by measuring the static pressure
exceeds fifteen year but can be affected by (among within the pressurized entry plenum and referring to the
other things) swings in their operational temperature calibration chart provided with the beam. TROX
and lack of sufficient water treatment. provides an integral pressure tap (accessible through
the face of the beam) to which a measuring gauge can
The connection of the primary air supply duct to active be connected. Do not attempt to read the total dis-
chilled beams is also the responsibility of the installing charge airflow rate using a hood or any other device
contractor. This connection should include the provision that adds downstream pressure to the beam as it will
of at least eight (8) inches of straight sheet metal duct reduce the amount of induction and as such give false
connected directly to the beam‟s primary air inlet. No readings.
more than five (5) feet of flexible duct should be used to
a

25
Maintenance

SYSTEM OPERATION AND MAINTENANCE REFERENCES

There are certain operational requirements that must 1. REHVA. 2004. Chilled Beam Application
observed when chilled beam systems are employed in Guidebook.
humid climates. In the event the HVAC system is 2. ASHRAE. 2004 Thermal environmental
disabled on nights and/or weekends, the chilled water con di tio ns for h u man oc cu pa nc y.
supply must remain suspended until the primary air ANSI/ASHRAE Standard 55-2004.
supply has properly dehumidified the space. It is 3. ASHRAE. 2007. ASHRAE Handbook-
recommended that some type of space humidity Applications.
sensing be used to assure that a proper space dew 4. Energie. 2001. Climatic ceilings technical note:
point temperature has been established prior to starting design calculations.
the delivery of chilled water to the space. 5. ASHRAE. 2005. ASHRAE Handbook-
Fundamentals.
If chilled beams are to be used in traffic or lobby areas, 6. BSRIA. 1991. Pre-commission cleaning of
it is important that the space be maintained at a positive water systems. BSRIA Application Guide 8/91.
pressure in order to minimize the infiltration of outdoor 7. ASHRAE. 2004 Ventilation for acceptable
air. In the case of lobby areas, the use of revolving indoor air quality. ANSI/ASHRAE Standard
doors may be warranted. It is also recommended that 62.1-2004.
the beams not be located near any opening doors or
windows in these areas.

Maintenance requirements

Due to their simplicity and lack of moving parts, chilled


beams require little maintenance. In fact, the only
scheduled maintenance with chilled beams involves the
periodic vacuuming of their coil surfaces. Passive
beams generally require that this be done every four to
five years. In the case of active beams, such cleaning is
only required when the face of the unit return section
shows visible dirt. At this time, the primary air nozzles
should be visually inspected and any debris or lint
removed. In all cases, it is recommended that good
filtration be maintained within the air handling unit.

26
Passive Beam Selection

CHILLED BEAM SELECTION


1. Estimate the beam entering air temperature
PASSIVE BEAM SELECTION AND LOCATION • If a fully mixed room air distribution
system is being used, the entering air
Selection and location of passive chilled beams is pri- temperature will equal the room control
marily affected by the following parameters: temperature.
• If a stratified system is being used, the
• Required sensible heat removal entering air temperature may be assumed
• Allowable chilled water supply temperature to be 2˚F warmer than the room control
• Horizontal and vertical space restrictions temperature.
• Occupant thermal comfort considerations • When mounted directly above a perimeter
• Architectural considerations window, the entering air temperature can
be assumed to be 6˚F warmer than the
Chilled water supply and return temperatures room temperature.

Before a passive beam selection can be made, it is 2. Specify the chilled water supply temperature.
necessary that an appropriate chilled water supply
temperature be identified. TROX USA recommends that 3. Using the temperature difference between the
the chilled water supply temperature to passive beams entering air and chilled water, select a beam
be maintained at least 1˚F above the space dew point whose width and length will remove the
temperature in order to assure that condensation does required amount of sensible heat.
not occur.
4. Identify the required water flow rate and
Return water temperatures will generally be 3 to 6˚F pressure loss for the selected beam.
higher than the supply water temperature.
Passive chilled beam selection examples
Water flow rate and pressure loss considerations
EXAMPLE 1:
Water flow velocities in excess of 4 feet per second
should be avoided in order to prevent unwanted noise. TCB-1 series passive (recessed type) chilled beams are
Design water flow rates below 0.25 gallons per minute being used to condition an interior office space that is
are not recommended as laminar flow begins to occur 120 feet long by 60 feet wide with a sensible heat gain
below this flow rate and coil performance may be 12 BTUH per square foot. The space is controlled by a
reduced. Passive chilled beams should also be selected thermostat (at the mid-level of the room) for a dry bulb
such that their water side head loss does not exceed 10 temperature of 76˚F and space RH of 50%. A thermal
feet of water. displacement ventilation system supplies 0.2 CFM per
square foot of pretreated ventilation air at 65˚F.
Passive chilled beam performance data
SOLUTION:
The amount of sensible cooling that can be provided by
an active chilled beam is dependent on all of the factors The total sensible heat gain of the space is 8,640
listed above. Tables 2 and 3 illustrate the performance BTUH. The room dew point temperature is 57˚F
of TROX TCB-1 and TCB-2 series passive chilled therefore a chilled water supply temperature of 58˚F will
beams. The available beam widths are listed in the be used.
table. The water side pressure loss is illustrated for 4, 6,
8 and 10 foot versions of each beam. The sensible As the displacement ventilation system being used in
cooling capacity of each beam is expressed in BTUH conjunction with the beams will crate a stratified room
per linear foot of length for various temperature environment, the beam entering air temperature (and
differentials between entering air and the entering the return air temperature leaving the space) may be
chilled water supply. This capacity is based on a 6 foot assumed to be 2˚F warmer than the room control
beam length, a discharge free area of 50% and an temperature, or in this case 78˚F.
equal inlet free area. It also assumes that the distance a
between the beam and any obstacle above it is at least
40% the width of the beam. Table 4 presents correction
factors for other beam lengths and inlet/discharge
conditions.

Passive beam selection procedures

Selection of passive chilled beams should be performed


as follows:

27
Passive Beam Performance

ΔPWATER, ft. H2O Sensible Cooling Capacity, (BTUH/LF)


Beam Width (B) Water Flow Rate
Chilled Beam Length, Ft. TROOM - TCWS
(inches) (GPM)
4 5 6 8 10 15 16 17 18 19 20 21 22
0.75 0.6 0.6 0.7 0.9 1.1 216 236 257 278 299 319 340 361
1.00 1.0 1.1 1.3 1.6 1.9 243 264 285 305 326 347 367 388
1.25 1.6 1.8 2.0 2.5 2.9 259 280 301 321 342 363 383 404
1.50 2.3 2.5 2.9 3.6 4.2 270 291 301 332 353 374 394 415
1.75 0.4 0.4 0.5 0.6 0.7 278 299 319 340 361 381 402 423
24
2.00 0.5 0.6 0.6 0.8 1.0 284 304 325 346 366 387 408 428
2.25 0.6 0.7 0.8 1.0 1.2 288 309 329 350 371 391 412 433
2.50 0.8 0.9 1.0 1.2 1.5 292 312 333 354 374 395 416 437
2.75 0.9 1.1 1.2 1.5 1.8 295 315 336 357 377 398 419 439
3.00 1.1 1.3 1.4 1.8 2.1 297 318 338 359 380 400 421 442
0.75 0.4 0.5 0.6 0.7 0.9 211 229 247 264 278 296 315 334
1.00 0.8 0.9 1.0 1.3 1.6 232 249 267 284 299 318 337 355
1.25 1.2 1.4 1.6 2.0 2.4 244 262 279 297 312 331 350 368
1.50 1.7 2.1 2.3 2.8 3.5 252 270 287 305 321 346 359 377
1.75 0.3 0.4 0.4 0.5 0.6 270 276 293 311 327 216 365 383
20
2.00 0.4 0.5 0.5 0.7 0.8 262 280 298 315 332 351 369 388
2.25 0.5 0.6 0.7 0.8 1.0 266 284 301 319 336 354 373 392
2.50 0.7 0.7 0.8 1.0 1.2 269 286 304 321 339 357 376 395
2.75 0.8 0.9 1.0 1.2 1.5 271 288 306 324 341 360 378 397
3.00 0.9 1.1 1.2 1.5 1.8 273 290 308 325 343 362 380 399
0.75 0.5 0.5 0.6 0.7 0.9 183 197 212 227 241 256 270 285
1.00 0.8 1.0 1.1 1.3 1.6 197 211 226 240 255 270 284 299
1.25 1.3 1.5 1.7 2.1 2.5 205 220 234 249 263 278 293 307
1.50 1.9 2.2 2.4 3.0 3.6 210 225 240 254 269 283 298 313
1.75 0.3 0.3 0.3 0.4 0.5 214 229 244 258 273 287 302 317
16
2.00 0.3 0.4 0.4 0.5 0.6 217 232 247 261 276 290 305 320
2.25 0.4 0.5 0.5 0.7 0.8 220 234 249 264 278 293 307 322
2.50 0.5 0.6 0.7 0.8 1.0 222 236 251 265 280 295 309 324
2.75 0.6 0.7 0.8 1.0 1.2 223 238 252 267 281 296 311 325
3.00 0.8 0.9 1.0 1.2 1.4 224 239 254 268 283 297 312 327
0.75 0.3 0.3 0.4 0.4 0.5 164 174 185 195 206 217 227 238
1.00 0.5 0.6 0.6 0.8 0.9 172 182 193 204 214 225 235 246
1.25 0.8 0.9 1.0 1.2 1.5 177 187 198 208 219 230 240 251
1.50 1.1 1.3 1.4 1.8 2.1 180 191 201 212 222 233 244 254
1.75 0.2 0.2 0.2 0.3 0.4 182 193 203 214 225 235 246 256
12
2.00 0.3 0.3 0.3 0.4 0.5 184 195 205 216 226 237 248 258
2.25 0.3 0.4 0.4 0.5 0.6 185 196 207 217 228 238 249 260
2.50 0.4 0.4 0.5 0.6 0.7 186 197 208 218 229 239 250 261
2.75 0.5 0.5 0.6 0.8 0.9 187 198 209 219 230 240 251 262
3.00 0.6 0.6 0.7 0.9 1.1 188 199 209 220 230 241 252 262

NOTES REGARDING PERFORMANCE DATA:


1. Sensible cooling data is based on a six (6) foot long uncapped beam with a 12" stack height (H), a ceiling free area of 50%
and an air passage width (W) twice the beam width (B) per figure 13.
2. For other beam lengths, ceiling free areas and/or air passage widths see table 3 for correction factors.

Table 1: TCB-1 Passive Beam (One Row Coil) Cooling Performance Data

28
Passive Beam Performance

ΔPWATER, ft. H2O Sensible Cooling Capacity, (BTUH/LF)


Beam Width (B) Water Flow Rate
Chilled Beam Length, Ft. TROOM - TCWS
(inches) (GPM)
4 5 6 8 10 15 16 17 18 19 20 21 22
0.75 1.8 1.3 1.5 1.7 2.1 153 194 236 277 318 360 401 442
1.00 3.2 2.3 2.6 3.1 3.7 242 283 324 366 407 448 490 531
1.25 5.0 3.6 4.1 4.8 5.8 295 336 377 418 460 501 542 584
1.50 7.2 5.2 5.9 6.9 8.3 330 371 412 454 495 536 577 619
1.75 0.8 0.9 1.0 1.2 1.4 354 396 437 478 520 561 602 643
24
2.00 1.0 1.1 1.3 1.6 1.9 373 415 456 497 539 580 621 662
2.25 1.3 1.4 1.6 2.0 2.4 387 429 470 511 553 594 635 677
2.50 1.6 1.8 2.0 2.5 2.9 399 440 482 523 564 606 647 688
2.75 1.9 2.2 2.4 3.0 3.5 409 450 491 533 574 615 656 698
3.00 2.3 2.6 2.9 3.6 4.2 417 458 499 541 582 623 665 706
0.75 0.9 1.1 1.2 1.5 1.7 169 204 239 273 308 343 378 413
1.00 1.7 1.9 2.2 2.7 3.1 232 266 301 336 371 406 440 475
1.25 2.6 3.0 3.4 4.2 4.8 267 302 337 372 407 441 476 511
1.50 3.8 4.3 4.9 6.0 6.9 292 326 361 396 431 466 500 535
1.75 0.6 0.7 0.8 1.0 1.1 309 343 378 413 448 483 517 552
20
2.00 0.8 1.0 1.1 1.3 1.4 322 356 391 426 461 496 530 565
2.25 1.0 1.2 1.4 1.7 1.8 332 366 401 436 471 506 540 575
2.50 1.3 1.5 1.7 2.0 2.2 340 375 409 444 479 514 549 583
2.75 1.6 1.8 2.0 2.5 2.7 346 381 416 451 486 520 555 590
3.00 1.9 2.2 2.4 2.9 3.2 352 387 422 456 491 526 561 596
0.75 0.8 0.9 1.0 1.2 1.4 168 195 221 247 274 300 326 352
1.00 1.4 1.5 1.7 2.2 2.5 202 228 254 281 307 333 360 386
1.25 2.1 2.4 2.7 3.4 3.9 222 249 275 301 327 354 380 406
1.50 3.0 3.4 3.9 4.9 5.7 235 262 288 314 341 367 393 419
1.75 0.5 0.6 0.6 0.8 1.0 245 272 298 324 350 377 403 429
16
2.00 0.7 0.8 0.8 1.1 1.2 252 279 305 331 358 384 410 437
2.25 0.8 1.0 1.1 1.3 1.6 258 284 311 337 363 389 416 442
2.50 1.0 1.2 1.3 1.6 2.0 262 289 315 341 368 394 420 447
2.75 1.2 1.4 1.6 2.0 2.4 266 292 319 345 371 398 424 450
3.00 1.5 1.7 1.9 2.4 2.8 269 296 322 348 375 401 427 453
0.75 0.6 0.7 0.8 1.1 1.3 153 176 198 221 244 266 289 311
1.00 1.1 1.3 1.5 1.9 2.2 177 199 222 245 267 290 312 335
1.25 1.8 2.0 2.3 3.0 3.5 191 214 237 259 282 304 327 350
1.50 2.5 2.9 3.3 4.3 5.0 201 224 246 269 291 314 337 359
1.75 0.4 0.5 0.6 0.7 0.8 208 231 253 276 298 321 344 366
14
2.00 0.6 0.7 0.7 0.9 1.1 213 236 258 281 303 326 349 371
2.25 0.7 0.8 0.9 1.2 1.3 217 240 262 285 308 330 353 375
2.50 0.9 1.0 1.2 1.4 1.7 220 243 265 288 311 333 356 378
2.75 1.1 1.2 1.4 1.7 2.0 223 245 268 291 313 336 358 381
3.00 1.3 1.5 1.7 2.1 2.4 225 248 270 293 315 338 361 383

NOTES REGARDING PERFORMANCE DATA:


1. Sensible cooling data is based on a six (6) foot long uncapped beam with a 12" stack height (H), a ceiling free area of 50%
and an air passage width (W) twice the beam width (B) per figure 13.
2. For other beam lengths, ceiling free areas and/or air passage widths see table 3 for correction factors.

Table 2: TCB-2 Passive Beam (Two Row Coil) Cooling Performance Data

29
Passive Beam Performance

Cooling Performance Factor (FC)


Beam Length Stack Height Ceiling Panel Free Area Beam Width (Inches)
(linear ft.) (inches) (%) 12 * 14 * 16 20 24
W = 2.0 x B W = 2.0 x B W = 2.0 x B W = 2.0 x B W = 2.0 x B
30.0% 0.81 0.81 0.81 0.81 0.81
8 40.0% 0.91 0.91 0.91 0.91 0.91
50% or more 0.95 0.95 0.95 0.95 0.95
30.0% 0.86 0.86 0.86 0.86 0.86
4 10 40.0% 0.96 0.96 0.96 0.96 0.96
50% or more 1.01 1.01 1.01 1.01 1.01
30.0% 0.90 0.90 0.90 0.90 0.90
12 40.0% 1.01 1.01 1.01 1.01 1.01
50% or more 1.06 1.06 1.06 1.06 1.06
30.0% 0.77 0.77 0.77 0.77 0.77
8 40.0% 0.86 0.86 0.86 0.86 0.86
50% or more 0.90 0.90 0.90 0.90 0.90
30.0% 0.81 0.81 0.81 0.81 0.81
6 10 40.0% 0.90 0.90 0.90 0.90 0.90
50% or more 0.95 0.95 0.95 0.95 0.95
30.0% 0.85 0.85 0.85 0.85 0.85
12 40.0% 0.95 0.95 0.95 0.95 0.95
50% or more 1.00 1.00 1.00 1.00 1.00
30.0% 0.73 0.73 0.73 0.73 0.73
8 40.0% 0.82 0.82 0.82 0.82 0.82
50.0% 0.86 0.86 0.86 0.86 0.86
30.0% 0.78 0.78 0.78 0.78 0.78
8 10 40.0% 0.87 0.87 0.87 0.87 0.87
50% or more 0.91 0.91 0.91 0.91 0.91
30.0% 0.82 0.82 0.82 0.82 0.82
12 40.0% 0.91 0.91 0.91 0.91 0.91
50.0% 0.96 0.96 0.96 0.96 0.96
30.0% 0.71 0.71 0.71 0.71 0.71
8 40.0% 0.80 0.80 0.80 0.80 0.80
50% or more 0.84 0.84 0.84 0.84 0.84
30.0% 0.75 0.75 0.75 0.75 0.75
10 10 40.0% 0.84 0.84 0.84 0.84 0.84
50% or more 0.88 0.88 0.88 0.88 0.88
30.0% 0.79 0.79 0.79 0.79 0.79
12 40.0% 0.88 0.88 0.88 0.88 0.88
50% or more 0.93 0.93 0.93 0.93 0.93

* TCB-1 (1 row) beams are available in 12 inch width, but not 14 inches. TCB-2 (2 row) beams are available in 14 inch width, but not 12".

NOTES:
1. Cooling performance in tables 1 and 2 are based on 6 foot long beams with a 12" stack height (and W = 2.0 x B).
They also assume a 50% (or more free area for both the intake and discharge section (see table 13).
2. To determine the performance of a beam with a different length, stack height or facial (free) area, multiply the
appropriate cooling factor (FC) from the table of above by the sensible cooling value from table 1 or 2.
3. To determine the performance of a beam with a different length, stack height or facial (free) area, multiply the
appropriate cooling factor (FC) from the table of above by the sensible cooling value from table 1 or 2.

Table 3: Correction Factors for Other Beam Configurations

30
Passive Beam Selection

The sensible heat removal of the ventilation air can then


be calculated as follows:

qVENT = 1.09 x CFMVENT x (TRETURN – TSUPPLY)


Blind Box
= 1.09 x (0.2 x 720) x (78 – 65)
= 2,040 BTUH 0.5 x B
The required sensible heat removal of the beams is the H
total sensible heat gain of the space (8,640 BTUH) less
that removed by the air supply (2,040 BTUH) or 6,600
BTUH.
0.3 x B B
In order to contain the beam and its required inlet area
within a single 2 foot wide ceiling module, it is desired
that 12” wide beams be used. Table 1 indicates four 8
foot long beams with chilled water flow rates of 0.75
GPM (and a 20˚F temperature differential between the
entering air and chilled water) could remove the re-
quired sensible heat. These would be located uniformly
within the space.
Figure 27: Passive Beams for Perimeter
Passive Beams in Perimeter Applications Cooling Applications

When passive beams are used for perimeter applica- ACTIVE BEAM SELECTION AND LOCATION
tions, it is not necessary that the inlet area to the beam
be as wide as with interior applications. The momentum In addition to sensible heat removal and water side
of the warm air moving up the façade assists in the de- pressure loss effects, active chilled beam selection and
livery to the beam. Figure 27 illustrates such an applica- location should also consider acoustical and air side
tion and suggests that the width of the gap between the pressure effects as well as room air distribution per-
beam and the façade can be as little as 33 percent of formance and its effect on occupant thermal comfort.
the beam width, but must be maintained throughout the
entire entry passage. For such cases, the performance TROX DID active chilled beams offer a range of air noz-
data shown in tables 1 and 2 may be used. In addition, zles that afford the designer to tailor the beam selection
the beam entering air temperature can be assumed to to the space cooling and air distribution requirements.
be 6 to 8°F warmer during design operation. DID300 and DID600U series beams offer three different
nozzle sizes (A, B or C) . Type A nozzles are the small-
EXAMPLE 2: est in diameter, create the highest induction ratios and
thus provide the greatest sensible cooling per CFM of
A TCB-2 (recessed type) passive beam is to be used for primary air. Their small diameter however also results in
conditioning a 120 square foot perimeter space served higher air side pressure losses which limit the primary
by a UFAD system. The space design conditions are airflow rates through the beam. These beams are com-
74˚F/55% RH. The space sensible heat gain is 45 monly used for interior spaces where ventilation rates
BTUH per square foot, 10 BTUH per square foot of are very low compared to the sensible load.
which will be removed by the pretreated air in the UFAD
system. The perimeter exposure is 10 feet long. Type C nozzles are the largest in diameter and allow
considerably higher primary airflow rates. Use of type C
SOLUTION: nozzles will allow the most sensible cooling per linear
foot of beam of all the nozzles. These beams are most
The beam entering air temperature can be assumed to often used when reasonably high primary airflow rates
be 81˚F. A chilled water supply temperature of 59˚F are necessary.
(1˚F above the space dew point) has been chosen,
therefore the temperature difference between the enter- Type B nozzles are considerably larger than type A but
ing air and entering water is 22˚F. The passive beam still smaller than type C nozzles. Their performance is
selected must be capable of removing 4,200 BTUH (35 thus a compromise between the other two nozzle types.
BTUH per square foot) of sensible heat. If an 8 foot long
beam is to be used, it must remove 525 BTUH per lin- DID620 series beams offer four nozzle sizes (G, M, Z
ear foot. According to table 2, a 20 inch wide beam at and K), but the most predominantly used are the G and
1.5 GPM could be used.

31
Active Beam Selection and Location

M types. The type G nozzle produces induction ratios Chilled water supply and return temperatures
similar to the type C nozzles previously discussed but
with slightly higher pressure drops and noise levels. Before an active chilled beam selection can be made, it
is necessary that an appropriate chilled water supply
Type M nozzles produce induction ratios that are some temperature be identified. TROX USA recommends that
15% higher, but at an additional pressure drop and the chilled water supply temperature to active beams be
noise level. selected and maintained at or above the space dew
point temperature in order to assure that condensation
For information on nozzle types Z and K contact TROX does not occur. Return water temperatures will gener-
USA. Table 4 below presents a brief performance com- ally be 3 to 6˚F higher than the supply water tempera-
parison of the various nozzle types. ture.

Maximum Chilled Secondary Cooling 2 Total Cooling 3


Active Beam Nozzle Induction Primary Airflow ΔPAIR
Water Flow Rate NC
Series Type Ratio 1 CFM/LF inches H2O BTUH/LF BTUH/CFM BTUH/LF BTUH/CFM
(GPM)
5.0 0.19 <15 247 49.4 356 71.2
A 5.3 8.0 0.48 23 360 45.0 534 66.8
11.0 0.91 32 433 39.3 672 61.1
8.0 0.18 <13 316 39.5 490 61.3
DID-302-US B 4.2 13.0 0.47 1.5 26 419 32.2 702 54.0
18.0 0.91 35 504 28.0 896 49.8
13.0 0.22 18 347 26.7 630 48.5
C 3.2 19.0 0.47 28 432 22.7 846 44.5
25.0 0.81 36 505 20.2 1050 42.0
6.0 0.32 <15 454 75.7 585 97.5
A 5.3 8.0 0.57 20 549 68.6 723 90.4
10.0 0.89 25 634 63.4 852 85.2
10.0 0.29 18 543 54.3 761 76.1
DID-602-US B 4.2 14.0 0.58 1.5 27 673 48.1 979 69.9
18.0 0.96 33 787 43.7 1179 65.5
15.0 0.28 22 561 37.4 888 59.2
C 3.3 21.0 0.55 31 695 33.1 1153 54.9
27.0 0.91 38 812 30.1 1400 51.9
6.0 0.32 <15 523 87.1 653 108.9
A 5.3 8.0 0.57 20 638 79.7 812 101.5
10.0 0.89 25 743 74.3 961 96.1
10.0 0.29 18 630 63.0 848 84.8
DID-602-HC B 4.2 14.0 0.58 3.0 27 793 56.6 1098 78.4
18.0 0.96 33 938 52.1 1330 73.9
15.0 0.28 22 653 43.5 980 65.3
C 3.3 21.0 0.55 31 821 39.1 1278 60.9
27.0 0.91 38 970 35.9 1559 57.7
5.0 0.17 <15 292 58.4 401 80.2
M 4.8 8.0 0.45 17 460 57.5 634 79.3
11.0 0.85 25 566 51.4 806 73.2
DID-622-US 1.5
10.0 0.19 <15 417 41.7 635 63.5
G 3.7 16.0 0.49 27 592 37.0 941 58.8
22.0 0.92 36 702 31.9 1182 53.7
4.0 0.17 <15 319 79.7 406 101.5
M 4.8 8.0 0.45 17 511 63.9 685 85.7
12.0 0.85 25 636 53.0 898 74.8
DID-622-HC 3.0
10.0 0.19 <15 461 46.1 679 67.9
G 3.7 16.0 0.49 27 667 41.7 1016 63.5
22.0 0.92 36 802 36.4 1281 58.2

NOTES:
1. Induction ratio is volumetric measure of total supply airflow rate divided by the ducted (primary) airflow rate.
2. Secondary (sensible) cooling is based on a 18˚F temperature differential between the room and the entering chilled water.
3. Total (sensible) cooling is the sum of the secondary cooling (defined in note 2) and the primary air contribution (based on a 20˚F temperature
differential between the room and the entering primary air).
4. Values shown above are based on six (6) foot active beams with two slot (two way) discharge.

Table 4: Nozzle Types and Performance for TROX (2 Slot) Active Chilled Beams

32
Active Beam Selection and Location

Water flow rate and pressure loss considerations Active beams used for both heating and cooling

Water flow velocities in excess of 4 feet per second Active chilled beams can be used for heating as well as
should be avoided in order to prevent unwanted noise. cooling. This is commonly done in climates where over-
Design water flow rates below 0.25 gallons per minute head heating with all air systems is popular.
are not recommended as laminar flow begins to occur
below this flow rate and coil performance may be re- Heating can be accomplished in either of two ways:
duced.
Beams can be fitted to a four pipe system (using the
Chilled beams should also be selected such that their four pipe performance data) that enables the beam to
water side head loss does not exceed 10 feet of water. access either chilled or hot water according to the
space demand.
Air side design considerations A zone heating coil can be provided in the primary air
duct that will add the required zone heating to the pri-
Although active chilled beams remove large amounts mary air prior to its entry into the beam. A two pipe sys-
sensible heat from the room air that is circulated tem (delivering chilled water only) will then be sufficient
through them, it is very important that the designer does as the zone chilled water valve will remain closed during
not treat them as purely an air conditioning device. They periods demanding space heating.
are also an air distribution device and their proper se-
lection and placement is paramount to the maintenance The latter practice is often employed as it results in far
of thermal comfort within the space. The design of ac- less piping. With either approach, the discharge air tem-
tive chilled beam systems must not only consider the perature should not be more than 15°F above that of
sensible cooling (and or heating) capacities of the the room (per ASHRAE recommendations) if adequate
beams but also their resultant room air distribution. overhead heating performance is to be achieved. This
same recommendation is valid for all air heating as well.
Figure 18 can be used to predict local velocities for ac-
tive chilled beams. In order to prevent excessive veloci- Selecting active beams to do both heating and cooling
ties in the occupied zone, it is recommended that the of perimeter areas requires a close examination of the
beam discharge airflow rate (primary plus induced room resultant room air velocities. Figure 18 introduces two
air) not be greater than 40 CFM per linear foot of slot, velocities (VL2 and VL6) that aid the designer in select-
therefore 2 slot beams should not be sized for primary ing beams for this application.
airflow rates in excess of 80 CFM per linear foot of
beam. VL2 represents the velocity measured two (2) inches
from the outside window at the mid-level of the space.
The primary airflow rate to active chilled beams must be For good heating performance this value should be at
sufficient to maintain proper ventilation of the space7. least 50 FPM during the heating mode.
The preconditioning of the primary air delivery must also
enable the primary air supply to provide adequate VL6 represents the velocity six (6) inches form the sur-
space dehumidification without assistance from the face, and is used to assess the draft risk during cooling
cooling coil within the beam. When active beams are operation. For minimal draft risk, the VL6 value should
applied in humid climates, designing for a space relative not exceed about 75 FPM.
humidity level near 55% will often result in a more effec-
tive application of the chilled beam system. This is par- A good beam selection will conform to both of the rec-
ticularly true when the dew point temperature of the ommendations cited.
primary air cannot be suppressed below about 53˚F
(see further discussion see page 13). Active beams operated in a VAV mode

Oftentimes, the cooling, ventilation and/or demands for Although they primarily deliver constant air volume (at a
areas fed by the same air handling unit vary. In such variable temperature) active beams may be operated in
cases, the designer should attempt to match the inlet a VAV mode when space cooling requirements vary
pressure requirements of those beams as closely as greatly (conference rooms, etc.). In such cases there is
possible in order to reduce the noise that can be gener- little concern over “dumping” at low discharge velocities
ated by pressure regulating dampers in the ductwork. as the cooling coil is off and the discharge air tempera-
This can often be accomplished by selecting nozzle ture is only a few degrees below that of the room being
types that will match the pressure drop to the beam served.
primary airflow rate.

33
Active Beam Performance Data

Active beam performance data Use of these nomographs will facilitate the selection of
a nozzle type as well as identify the cooling capacities
Performance data for DID600 series, DID620 series, of the beam for various differentials between the room
and DID300 series active chilled beams are presented and entering chilled water temperatures.
in figures 30 through 55. Table 5 may be used as a
reference to that data. Note that this performance data Similar nomographs are provided for heating applica-
pertains only to those beams manufactured by TROX tions which assume a primary air delivery temperature
USA and is intended for the sole purpose of selecting that is 20˚F below that of the room and a hot water sup-
those products. These data may not be applicable to ply that is 50°F warmer than the induced room air.
versions offered by other TROX companies. Again the primary air ranges for the various nozzles are
limited by the air side pressure loss (less than 1” H2O.)
TROX USA also offers electronic selection pro- and space NC (40) level. In the case of the heating no-
grams for all of these chilled beams. Contact TROX mographs, shaded areas are labeled “Primary Air Cool-
USA or your local representative for details. ing” represents the cooling effect of the primary air. The
net sensible heating values shown reflect this primary
The cooling capacity nomographs are based on beams air cooling effect.
of six (6) foot length supplied by primary air whose dry
bulb temperature is 20˚F cooler than the room being Both the cooling and heating nomographs include cor-
supplies. The chilled water is supplied at a temperature rection factors for other beam lengths. Corrections
which is 18°F above the room air being induced into the should also be made if the room to primary air tempera-
beam. Cooling performance for each nozzle type is ture differential varies from that assumed by the nomo-
presented. The primary airflow range for each nozzle is graphs.
limited to that which results in primary air side pressure
losses below one (1) inch of water and NC levels below Finally, figure 18 is used to estimate local velocities
40 (based on 10dB per octave band room attenuation. associated with the chilled beam selection and place-
The minimum cooling capacities shown are with no ment.
chilled water contribution and represent the sensible
cooling provided by the preconditioned primary air sup- The use of these tables is illustrated in the selection
ply. examples that follow.

Active Beam Type and Discharge Configuration


Performance Parameter DID601 DID602 DID621 DID622 DID301 DID302
(1 Slot) (2 Slot) (1 Slot) (2 Slot) (1 Slot) (2 Slot)

Cooling Performance (2 Pipe Variants)


- Sensible cooling capacities
- Chilled water flow rates Figure 40 Figure 41 Figure 46 Figure 47 Figure 52 Figure 53
- Airside pressure loss data
- Acoustical (NC) data
Cooling Performance (4 Pipe Variants)
- Sensible cooling capacities
- Chilled water flow rates Figure 42 Figure 43 Figure 48 Figure 49 Figure 54 Figure 55
- Airside pressure loss data
- Acoustical (NC) data

Heating Performance (2 Pipe Variants)


- Sensible heating capacities
- Hot water flow rates Figure 44 Figure 45 Figure 50 Figure 51 Figure 56 Figure 57
- Airside pressure loss data
- Acoustical (NC) data

Figures 32 Figures 32 Figures 32 Figures 32


Chilled Water Pressure Loss (2 Pipe Coils) Figure 37 Figure 37
and 34 and 34 and 34 and 34
Figures 33 Figures 33 Figures 33 Figures 33
Chilled Water Pressure Loss (4 Pipe Coils) Figure 38 Figure 38
and 35 and 35 and 35 and 35

Hot Water Pressure Loss (4 Pipe Coils) Figure 36 Figure 36 Figure 36 Figure 36 Figure 39 Figure 39

Table 5: Reference to Active Beam Performance Data


34
Active Beam Selection Examples

Active beam selection examples In order to satisfy the space latent gain, the required
primary airflow rate would be calculated as:
The following examples detail the selection of active
chilled beams for a call center, brokerage trading area CFMLATENT = qLATENT / 4840 x (W ROOM – W PRIMARY)
(high sensible load) and a laboratory (high primary air = 4,400 / 4840 x (0.0098 – 0.0079)
change rates). = 478 CFM

EXAMPLE 3: The ratio of the sensible heat gain to the primary airflow
rate is therefore 52.7 (25,200 BTUH/478 CFM). The
Select and locate DID302 series active chilled beams to chilled water supply temperature will be specified at
condition a large open office area in a call center. The 57˚F (18˚F below room temperature) in order to main-
area considered is 60 feet by 30 feet and houses 22 tain it above the space dew point temperature. Refer-
occupants. The space sensible load (14 BTUH/ft² or a ring to table 4, it would appear that a DID302-US beam
total of 25,200 BTUH) is comprised as follows: with type B nozzles delivering primary air at 13 CFM per
linear foot of beam would be appropriate. Table 4 also
Occupants: 4.0 BTUH/ ft² predicts that this selection would provide 702 BTUH of
Lighting: 1.5 W/ft² (5 BTUH/ ft²) sensible cooling per linear foot of beam, so the applica-
Equipment: 1.5 W/ft² (5 BTUH/ft²) tion would require 36 linear feet of beam, or six (4) six
(8) foot long beams.
The space should be designed for a 75˚F dry bulb tem-
perature and a maximum relative humidity of 53% Figure 28 illustrates the desired mounting layout for the
(corresponding to a dew point temperature of 56.8˚Fand beams. Figure 18 indicates that beams with an oppos-
a humidity ratio (W ROOM) of 0.0098 Lbs H2O per Lb DA). ing blow will provide very low VH1 velocities when a
The primary air will be conditioned to a dew point tem- spacing of 30 feet is maintained. The air side pressure
perature of 51˚F (corresponding to a humidity ratio W PRI- loss will be 0.47 inches of H2O and an NC value of 28
MARY of 0.0079 Lbs H2O per Lb DA) and delivered at are indicated by table 4. Figure 37 predicts a water side
55˚F. The ceilings are ten (10) feet high. The space NC pressure loss of 8.25 feet for a chilled water flow rate of
shall not exceed 35. 1.5 GPM.

SOLUTION: EXAMPLE 4:

As there are 22 occupants, the chilled beams must not Select and locate DID622 series active chilled beams to
only remove the space sensible gain, but must also condition a brokerage trading area. The area consid-
treat the space latent gain (200 BTUH per person or a ered is 40 feet by 40 feet and houses 16 traders. The
total of 5,000 BTUH) and provide proper space ventila- space sensible load (44 BTUH/ft² or a total of 81,600
tion. If a ventilation rate of 15 CFM per person is to be BTUH) is comprised as follows:
maintained this amounts to a space ventilation rate of
330 CFM. Occupants: 5.0 BTUH/ ft²
Lighting: 1.5 W/ft² (5 BTUH/ ft²)
Equipment: 12 W/ft² (41 BTUH/ft²)

The space should be designed for a 75˚F dry bulb tem-


perature and a maximum relative humidity of 53%
DID302-US Active Chilled (corresponding to a dew point temperature of 56.8˚F
Beams, 6 foot Nominal and a humidity ratio (W ROOM) of 0.0098 Lbs H2O per Lb
Length (typical of 6) DA). The primary air will be conditioned to a dew point
temperature of 51˚F (corresponding to a humidity ratio
W PRIMARY of 0.0079 Lbs H2O per Lb DA) and delivered
at 55˚F. The ceilings are ten (10) feet high. The space
10 feet
NC shall not exceed 40.

30 feet

Figure 28: Beam Layout for Example 3

35
Active Beam Selection Examples

SOLUTION: If, in order to minimize the primary airflow requirement,


the latter selection were preferred, the beam layout
The beams must be selected to remove 70,400 BTUH might be as shown in figure 29 below.
(44 BTUH/FT²) of sensible heat from the space.

The beams‟ primary airflow rate must also be sufficient


to handle the latent gain from the 16 occupants (200
BTUH per person or a total of 3,200 BTUH) and provide
proper ventilation (176 CFM per ASHRAE Standard
62.1-2004) to the space occupants. In order to satisfy
the space latent gain, the required primary airflow rate
would be calculated as:

CFMLATENT = qLATENT / 4840 x (W ROOM – W PRIMARY)


= 3,200 / 4840 x (0.0098 – 0.0079)
= 348 CFM

The ideal ratio of the sensible heat gain to the primary


airflow rate would be 202 BTUH/CFM of primary air, but
this is not achievable for any of the beam/nozzle ar-
rangements listed in table 4. The sensible cooling re-
quirement will therefore determine the primary airflow 12 feet 12 feet
rate.

The chilled water supply temperature will be specified at 40 feet


57˚F (18˚F below room temperature) in order to main-
tain it above the space dew point temperature. In order
Figure 29: Chilled Beam Layout for
to minimize the number of beams, DID622-HC beams
(and two pipe –HC coils) will be considered. Figure 47 Selection Example 4
summarizes the performance of a six (6) foot beam of
this type. If “G” nozzles are to be used, an airflow rate
of 23 BTUH/LF can be employed within the acoustical Referring to figure 18, the total discharge airflow rate
constraints defined. This will result in a beam sensible (CFM/LF of beam) of the selection using “M” nozzles is:
cooling capacity of about 1,275 BTUH/LF (with its maxi-
mum chilled water flow rate of 2.25 GPM). In this case, CFMSUPPLY = CFMPRIMARY x Induction Ratio
we would require 64 linear feet of beams. If twelve (12) = 11.5 CFM/LF x 4.8 = 55 CFM/LF
six foot units were provided, the necessary cooling
(1,133 BTUH/LF) could be accomplished with a primary As the beam has 2 slots, this equates to 27.5 CFM per
airflow rate of 20 CFM/LF and a chilled water flow rate linear foot of slot. The beam spacing (A) is twelve feet
of 2.25 GPM. This results in a space primary airflow so A/2 is six feet. Figure 18 indicates that, the velocities
requirement of 1,440 CFM. VH1 and VL6 six feet below the ceiling velocity will be
approximately 30 and 58 FPM, respectively. These are
Alternatively, type “M” nozzles could be employed. Fig- well within the values recommended.
ure 45 indicates that these nozzles (in a six foot beam)
can provide up to 900 BTUH/LF of sensible cooling with The airside pressure loss is about 0.93 inches H2O and
a chilled water flow rate of 2.25 GPM and a primary the NC level (27) is well within the range specified.
airflow rate of 12 CFM/LF and. If these nozzles are cho-
sen, we need 78 linear feet of beams. If twelve (12) EXAMPLE 5:
eight foot units (at their maximum chilled water flow rate
of 2.0 GPM) are employed, the cooling requirement DID602 series beams are to be used for a biological
could be satisfied at a primary airflow rate of 11.5 CFM / laboratory module. The laboratory module is 30 by 20
LF, or a total primary airflow rate of 1,104 CFM. feet (600 ft²) with ten (10) foot ceilings. The space sen-
sible cooling load is 70 BTUH/ft² while the total space
In either case the NC level would be within specified latent load is 2,000 BTUH. A minimum air change rate
levels, while the air side pressure drop would be ap- of 8 ACH-1 will be required. The velocity at the six foot
proximately 1.0 inches H2O. level of the occupied space should not exceed 60 FPM
while that along the wall cannot exceed 100 FPM. The
design conditions within the laboratory are 75˚F/50%
RH (W = 0.0092 LBM H2O per pound dry air, dew point
temperature of 55.2˚F). The NC shall not

36
Active Beam Selection Examples

exceed 40 nor shall the primary air pressure drop ex- This relates to a chilled water flow rate of 1.0 GPM.
ceed 1.0 inches H2O.
Figure 31 illustrates the proposed beam placement.
The primary air supply is to be delivered at 55˚F with a Referring to figure 18, the total air supply from each
dew point temperature of 52˚F (W = 0.0082 LBM H2O beam will be 666 CFM or 40 CFM per linear foot of slot.
per pound dry air). The beams are to be located directly As A/2 is 8 feet and X is 7 feet, the value of VH1 and
above the work benches in order to capture the most VL6 at the six foot (H - H1 = 4 feet) level will be 56 and
sensible heat. Figure 30 illustrates the bench layout for 86 FPM, respectively.
the lab.
The water side pressure drop for DID602-US and
SOLUTION: DID602-HC can be found in figures 32 and 34, respec-
tively.
As the space dew point temperature is 55.2˚F, a 56˚F
chilled water supply temperature will be used. As the
beams are to be located directly above the benches
where most of the space heat sources reside, the in-
duced air entering the beams will be assumed to be 2°F 8 feet
(typical)
warmer than the room air resulting in a 21˚F tempera-
ture differential between the room air and the entering
chilled water.

The minimum primary air delivery to the space for venti-


lation purposes is 8 ACH-1, or 800 CFM. The amount of Lab
Benches
primary air required to satisfy the space latent load may
be calculated as:

CFMLATENT = qLATENT / 4840 x (W ROOM – W PRIMARY)


= 2,000 / 4840 x (0.0092 – 0.0082)
= 413 CFM

As this is less than the ventilation requirement, the mini-


mum primary airflow delivery will be 800 CFM. Figure 30: Lab Bench Arrangement
for Example 5
The total space sensible load is 42,000 BTUH. Ideally,
the beam selected should provide 52.5 (42,000 / 800)
BTUH of sensible cooling per CFM of primary air. Table
4 indicates that DID602 beams with “C” nozzles can
provide such a ratio. 16 feet
(typical)

The layout of the laboratory would favor the placement


of one or two beams over each bench, so we will con-
DID602-US Active
sider the use of four (8) eight foot beams. Applying the Chilled Beam
correction factors from figure 41 we see that an eight (8 ft. Long, "C" Nozzles)
(typical of 4)
foot beam can provide 25 CFM/LF of primary air while
keeping the air side pressure drop of inches H 2O. The
NC level (39) would also be acceptable. In order to sup-
ply the required air changes (800 CFM), we would need
32 feet of these beams or four (4) eight foot lengths.

As figure 41 is based on an 18°F temperature difference


between the air and chilled water entering the beam, we
must correct the water side sensible cooling according
to the correction factor (1.16) shown in table 6 (page Figure 31: Chilled Beam Arrangement
38) while the primary air contribution (567 BTUH/LF or
17,400 BTUH total) remains the same. The sensible for Example 5
cooling provided the chilled water coil must thus be
24,600 BTUH or 769 BTUH/LF. Applying the correction
factor (1.16) from table 6, we enter figure 41 to deter-
mine the chilled water flow rate that will provide 663
(769/1.16) BTUH/LF of water side sensible cooling or
1,230 (663 + 567) BTUH/LF of total sensible cooling.

37
Nomenclature and Performance Notes

L (X + H1) Beam Spacing (A)

X A/2

ΔT Z
TSUPPLY

H - H1
VH1
VL
ΔT H1
ΔT L
H

6" for Cooling


1 ft.
2" for Heating OCCUPIED ZONE
(as defined by ASHRAE Std. 55-2004)
Occupied Zone Height (H1)

3.3 ft.

Nomenclature
VH1: Local velocity at the top of the occupied zone directly below the point of collision of opposing air streams

TH1: Local temperature at the top of the occupied zone directly below the point of collision of opposing air streams

VL2: Local velocity at the top of the occupied zone measured two (2) inches from an outside wall

TL2: Local temperature at the top of the occupied zone measured two (2) inches from an outside wall

VL6: Local velocity at the top of the occupied zone measured six (6) inches from an outside wall

TL6: Local temperature at the top of the occupied zone measured six (6) inches from an outside wall

A: Centerline distance between two active beams with opposing blows

X: Distance between active beam centerline and an adjacent wall

H: Mounting height of active chilled beam

H1: Height of occupied zone (usually considered 42” for seated occupants, 66 inches for standing occupants)

TINDUCED AIR: Dry bulb temperature of room air entering the chilled beam cooling coil

TCWS: Temperature of the chilled water entering the chilled beam transfer coil (cooling mode)

THWS: Temperature of the hot water entering the chilled beam heat transfer coil (heating mode)

Induction ratio: Ratio of discharge airflow rate (to the room) to primary (ducted) airflow rate

Net sensible heating: Beam water side heating less the cooling effect of the (cooler) primary air

tINDUCED AIR - tCWS 12°F 14°F 16°F 18°F 20°F 22°F tIHWS - tINDUCED AIR 20°F 30°F 40°F 50°F 60°F 70°F
Water Side Sensible
Water Side Heating
Cooling Correction 0.67 0.78 0.89 1.0 1.11 1.22 0.4 0.6 0.8 1.0 1.2 1.4
Factor Correction Factor

Table 6: Water Side Correction Factors for Table 7: Water Side Correction Factors for
Various Entering Air to Entering Chilled Water Various Entering Air to Entering Hot Water
Temperature Differentials Temperature Differentials

38
Water Side Pressure Loss

9.0
10 Foot Nominal Length

Selection for Design Water Flow Rates Less than


Max. GPM = 0.90
Chilled Water Pressure Drop (FT H2O)

8.0

8 Foot Nominal Length

0.25 GPM is Not Recommended


Max. GPM = 1.0
7.0

6.0

5.0
6 Foot Nominal Length
Max. GPM = 1.15
4.0

3.0 4 Foot Nominal Length


Max. GPM = 1.35

2.0

1.0

0.25 0.50 0.75 1.00 1.25 1.50

Water Flow Rate (GPM)


Figure 32: 2 Pipe Standard Capacity Coil Chilled Water Pressure Loss
Models DID601-US-2, DID602-US-2, DID621-US-2 and DID622-US-2

9.0
Selection for Design Water Flow Rates Less than
Chilled Water Pressure Drop (FT H2O)

10 Foot Nominal Length


8.0 Max. GPM = 1.1
0.25 GPM is Not Recommended

7.0
8 Foot Nominal Length
Max. GPM = 1.2

6.0

5.0
6 Foot Nominal Length
Max. GPM = 1.35
4.0

3.0 4 Foot Nominal Length


Max. GPM = 1.5

2.0

1.0

0.25 0.50 0.75 1.00 1.25 1.50

Water Flow Rate (GPM)


Figure 33: 4 Pipe Standard Capacity Coil Chilled Water Pressure Loss
Models DID601-US-4, DID602-US-4, DID621-US-4 and DID622-US-4

39
Water Side Pressure Loss

10.0

9.0
10 Foot Nominal Length

Selection for Design Water Flow Rates Less than


Chilled Water Pressure Drop (FT H2O)

Max. GPM = 1.85

8.0

8 Foot Nominal Length


0.5 GPM is Not Recommended
Max. GPM = 2.05
7.0

6.0

5.0
6 Foot Nominal Length
Max. GPM = 2.35
4.0

3.0 4 Foot Nominal Length


Max. GPM = 2.75

2.0

1.0

0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75 3.00

Figure 34: 2 Pipe High Capacity Coil Chilled Water Pressure Loss
Models DID601-HC-2, DID602-HC-2, DID621-HC-2 and DID622-HC-2

9.0
Selection for Design Water Flow Rates Less than
Chilled Water Pressure Drop (FT H2O)

10 Foot Nominal Length


8.0 Max. GPM = 2.1
0.5 GPM is Not Recommended

7.0
8 Foot Nominal Length
Max. GPM = 2.3

6.0

5.0

6 Foot Nominal Length


Max. GPM = 2.7
4.0

3.0 4 Foot Nominal Length


Max. GPM = 3.0

2.0

1.0

0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75 3.00

Figure 35: 4 Pipe High Capacity Coil Chilled Water Pressure Loss
Models DID601-HC-4, DID602-HC-4, DID621-HC-4 and DID622-HC-4

40
Water Side Pressure Loss

6.0

5.5

5.0

Selection for Design Water Flow Rates Less than


4.5
Hot Water Pressure Drop (FT H2O)

0.25 GPM is Not Recommended


4.0

10 Foot Nominal Length


3.5

3.0

8 Foot Nominal Length


2.5

2.0

1.5
6 Foot Nominal Length

1.0

4 Foot Nominal Length


0.5

0.25 0.50 0.75 1.00 1.25 1.50

Water Flow Rate (GPM)

Figure 36: 4 Pipe (Std. or High Capacity) Hot Water Coils Pressure Loss
Models DID601-US-4, DID602-US-4, DID621-US-4 and DID622-US-4,
DID601-HC-4, DID602-HC-4, DID621-HC-4 and DID622-HC-4

41
Water Side Pressure Loss

9.0

Selection for Design Water Flow Rates Less than


Chilled Water Pressure Drop (FT H2O)

10 Foot Nominal Length


8.0 Max. GPM = 1.3

0.25 GPM is Not Recommended


7.0

8 Foot Nominal Length


Max. GPM = 1.45
6.0

5.0

4.0

3.0
4 Foot Nominal Length
Max. GPM = 1.5

2.0

6 Foot Nominal Length


1.0 Max. GPM = 1.5

0.25 0.50 0.75 1.00 1.25 1.50

Figure 37: 2 Pipe Standard Capacity Coil Chilled Water Pressure Loss
Models DID301-US-2 and DID302-US-2

9.0
10 Foot Nominal Length
Selection for Design Water Flow Rates Less than
Chilled Water Pressure Drop (FT H2O)

Max. GPM = 1.5

8.0
0.25 GPM is Not Recommended

7.0 8 Foot Nominal Length


Max. GPM = 1.5

6.0

5.0

4.0

3.0

6 Foot Nominal Length


2.0 Max. GPM = 1.35

1.0
4 Foot Nominal Length
Max. GPM = 1.5

0.25 0.50 0.75 1.00 1.25 1.50

Water Flow Rate (GPM)

Figure 38: 4 Pipe Standard Capacity Coil Chilled Water Pressure Loss
Models DID301-US-4 and DID302-US-4

42
Water Side Pressure Loss

6.0

5.5

5.0

Selection for Design Water Flow Rates Less than


4.5
Hot Water Pressure Drop (FT H2O)

0.25 GPM is Not Recommended


4.0

3.5

3.0

2.5
10 Foot Nominal Length

2.0
8 Foot Nominal Length

1.5

1.0

4 Foot Nominal Length

0.5
6 Foot Nominal Length

0.25 0.50 0.75 1.00 1.25 1.50

Water Flow Rate (GPM)

Figure 39: 4 Pipe Hot Water Coil Pressure Loss


Models DID301-US-4 and DID3022-US-4

43
Cooling Performance (2-Pipe) DID601

1200
Chart is based on 6 ft. DID601-HC-2 (2
pipe) cooling with a 20˚F temperature
differential between room and primary air
1120
and an 18˚F temperature differential
between room and entering chilled water.
For other beam lengths, see the
1040 correction factors table below.
GPMCWS
Performance at water flow rates > 1.5
GPM is only achievable with DID601-HC
960 models.

3.0
880
2.5
2.0
GPMCWS

SECONDARY (WATER) COOLING


800
Sensible Cooling Capacity, BTUH/LF

GPMCWS 1.5

3.0 1.0
720
2.5 0.8
2.0
0.6
640 3.0
1.5
2.5

TOTAL SENSIBLE COOLING


1.0 0.4
2.0
560 0.8
0.3
1.5 0.6
480 1.0
0.4 0.2
0.8
0.6 0.3
400
0.4
0.2
0.3
320
0.2

240

PRIMARY AIR COOLING


"C" NOZZLES
160
NC 22 25 30 35 39

0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9" 1.0"


80
NC 20 25 30 34
"B" NOZZLES
0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9"1.0"
0
NC 15 20 25
"A" NOZZLES
0.3" 0.4" 0.6" 0.8" 1.0"

2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 14.0 15.0

Primary Airflow Rate, CFM/LF

Corrections for Other DID601-US-2 or DID601-HC-2 Lengths & T INDUCED AIR - TENTERING WATER
Beam Length (Nominal Length in Feet)
Performance Parameter
4 Feet 6 Feet 8 Feet 10 Feet

Sensible Cooling (BTUH/LF) Multiply by 1.03 No Correction Multiply by 0.91 Multiply by 0.90

Max. Recommended GPM (DID601-US-2 models) 1.35 1.15 1.0 0.9

Max. Recommended GPM (DID601-HC-2 models) 2.65 2.25 2.0 1.8

Noise Level (NC) -5 No Correction +3 +4

Primary Air Pressure Drop Multiply by 0.85 No Correction Multiply by 1.03 Multiply by 1.15

Chilled Water Pressure Loss See Figure 32 (DID601-US-2) or Figure 34 (DID601-HC-2)

TINDUCED AIR - TENTERING CHILLED WATER See Table 6 (page 38)

Figure 40: Cooling (2 Pipe) Performance, DID601-US-2 and DID601-HC-2


44
Cooling Performance (2-Pipe) DID602

1600
Chart is based on 6 ft. DID602-HC-2 (2
pipe) cooling with a 20˚F temperature
differential between room and primary air GPMCWS
1500
and an 18˚F temperature differential
between room and entering chilled water.
For other beam lengths, see the
1400 correction factors table below.

Performance at water flow rates > 1.5 3.0


GPM is only achievable with DID602-HC
1300 models. 2.5

SECONDARY (WATER) COOLING


2.0

1200 1.5
GPMCWS
1.0

1100 0.8
Sensible Cooling Capacity, BTUH/LF

GPMCWS 3.0
2.5 0.6
1000
2.0

TOTAL SENSIBLE COOLING


0.4
1.5
900 3.0
1.0
0.3
2.5
0.8
2.0
800
1.5 0.6 0.2
1.0
0.4
700

0.8 0.3

600 0.6
0.2
0.4

500 0.3

0.2

PRIMARY AIR COOLING


400

"C" NOZZLES
300
NC 22 25 30 35 39

0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9" 1.0"


200
NC 20 25 30 34
"B" NOZZLES
0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9"1.0"
100
NC 15 20 25
"A" NOZZLES
0.3" 0.4" 0.6" 0.8" 1.0"
0
4.0 6.0 8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0 28.0 30.0

Primary Airflow Rate, CFM/LF

Corrections for Other DID602-US-2 or DID602-HC-2 Lengths & T INDUCED AIR - TENTERING WATER
Beam Length (Nominal Length in Feet)
Performance Parameter
4 Feet 6 Feet 8 Feet 10 Feet

Sensible Cooling (BTUH/LF) Multiply by 1.03 No Correction Multiply by 0.91 Multiply by 0.90

Max. Recommended GPM (DID602-US-2 models) 1.35 1.15 1.0 0.9

Max. Recommended GPM (DID602-HC-2 models) 2.65 2.25 2.0 1.8

Noise Level (NC) -5 No Correction +3 +4

Primary Air Pressure Drop Multiply by 0.85 No Correction Multiply by 1.03 Multiply by 1.15

Chilled Water Pressure Loss See Figure 32 (DID602-US-2) or Figure 34 (DID602-HC-2)

TINDUCED AIR - TENTERING CHILLED WATER See Table 6 (page 38)

Figure 41: Cooling (2 Pipe) Performance, DID602-US-2 and DID602-HC-2

45
Cooling Performance (4-Pipe) DID601

1200
Chart is based on 6 ft. DID601-HC-4 (4
pipe) cooling with a 20˚F temperature
differential between room and primary air
1120
and an 18˚F temperature differential
between room and entering chilled water.
For other beam lengths, see the
1040 correction factors table below.
GPMCWS
Performance at water flow rates > 1.5
GPM is only achievable with DID601-HC
960 models.

3.0
880
2.5
GPMCWS
2.0
800
Sensible Cooling Capacity, BTUH/LF

GPMCWS

SECONDARY (WATER) COOLING


3.0
1.5
720 2.5
1.0
2.0
1.5 0.8
640
1.0 0.6
3.0
2.5 0.4

TOTAL SENSIBLE COOLING


560
2.0
0.8 0.3
1.5
480 0.6
1.0
0.2
0.4
0.8
400 0.6 0.3

0.4
0.2
320 0.3

0.2
240

PRIMARY AIR COOLING


"C" NOZZLES
160
NC 22 25 30 35 39

0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9" 1.0"


80
NC 20 25 30 34
"B" NOZZLES
0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9"1.0"
0
NC 15 20 25
"A" NOZZLES
0.3" 0.4" 0.6" 0.8" 1.0"

2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 14.0 15.0

Primary Airflow Rate, CFM/LF

Corrections for Other DID601-US-4 or DID601-HC-4 Lengths & T INDUCED AIR - TENTERING WATER
Beam Length (Nominal Length in Feet)
Performance Parameter
4 Feet 6 Feet 8 Feet 10 Feet

Sensible Cooling (BTUH/LF) Multiply by 1.03 No Correction Multiply by 0.91 Multiply by 0.90

Max. Recommended GPM (DID601-US-4 models) 1.5 1.35 1.2 1.1

Max. Recommended GPM (DID601-HC-4 models) 3.0 2.65 2.35 2.1

Noise Level (NC) -5 No Correction +3 +4

Primary Air Pressure Drop Multiply by 0.85 No Correction Multiply by 1.03 Multiply by 1.15

Chilled Water Pressure Loss See Figure 33 (DID601-US-4) or Figure 35 (DID601-HC-4)

TINDUCED AIR - TENTERING CHILLED WATER See Table 6 (page 38)

Figure 42: Cooling (4 Pipe) Performance, DID601-US-4 and DID601-HC-4

46
Cooling Performance (4-Pipe) DID602

1600
Chart is based on 6 ft. DID602-HC-4 (4
pipe) cooling with a 20˚F temperature
differential between room and primary air
1500
and an 18˚F temperature differential
GPMCWS
between room and entering chilled water.
For other beam lengths, see the
1400 correction factors table below.

Performance at water flow rates > 1.5


GPM is only achievable with DID602-HC
1300 3.0
models.
2.5
2.0

SECONDARY (WATER) COOLING


1200
GPMCWS
1.5
1100 1.0
Sensible Cooling Capacity, BTUH/LF

3.0
GPMCWS 0.8
2.5
1000 0.6
2.0
1.5
900 0.4

TOTAL SENSIBLE COOLING


3.0
0.3
2.5 1.0
800
2.0 0.8 0.2
1.5 0.6
700 1.0
0.4
0.8
0.3
600
0.6
0.2
0.4
500
0.3

PRIMARY AIR COOLING


0.2
400

"C" NOZZLES
300
NC 22 25 30 35 39

0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9" 1.0"


200
NC 20 25 30 34
"B" NOZZLES
0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9"1.0"
100
NC 15 20 25
"A" NOZZLES
0.3" 0.4" 0.6" 0.8" 1.0"
0
4.0 6.0 8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0 28.0 30.0

Primary Airflow Rate, CFM/LF

Corrections for Other DID602-US-4 or DID602-HC-4 Lengths & T INDUCED AIR - TENTERING WATER
Beam Length (Nominal Length in Feet)
Performance Parameter
4 Feet 6 Feet 8 Feet 10 Feet

Sensible Cooling (BTUH/LF) Multiply by 1.03 No Correction Multiply by 0.91 Multiply by 0.90

Max. Recommended GPM (DID602-US-4 models) 1.5 1.35 1.2 1.1

Max. Recommended GPM (DID602-HC-4 models) 3.0 2.65 2.35 2.1

Noise Level (NC) -5 No Correction +3 +4

Primary Air Pressure Drop Multiply by 0.85 No Correction Multiply by 1.03 Multiply by 1.15

Chilled Water Pressure Loss See Figure 33 (DID602-US-4) or Figure 35 (DID602-HC-4)

TINDUCED AIR - TENTERING CHILLED WATER See Table 6 (page 38)

Figure 43: Cooling (4 Pipe) Performance, DID602-US-4 and DID602-HC-4

47
Heating Performance (4-Pipe) DID601

1200 Chart is based on 6 ft. DID601-HC-4 (4 pipe) heating


with a 20˚F temperature differential between room and
primary air and a 50˚F temperature differential
between room and entering hot water. For other beam
1100 lengths, see the correction factors table below.

1000

GPMHWS
900
GPMHWS

GPMHWS
1.5
800
1.5
1.0 1.0
1.5
700 0.8 0.8
1.0
Net Sensible Heating Capacity, BTUH/LF

0.8 0.6 0.6


600 0.6

NET SENSIBLE HEATING


0.4
0.4 0.4
500
0.3
0.3
0.3

WATER SIDE HEATING


400
0.2 0.2

0.2
300

200

100

PRIMARY AIR COOLING


-100

"A" NOZZLES

-200 25
NC 15 20

0.3" 0.4" 0.6" 0.8" 1.0"


-300
NC 20 25 30 34
"B" NOZZLES
0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9"1.0"
-400

NC 22 25 30 35 39
-500 "C" NOZZLES
0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9" 1.0"

2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 14.0 15.0

Primary Airflow Rate, CFM/LF

Corrections for Other DID601-US-4 or DID601-HC-4 Lengths & T ENTERING WATER - TINDUCED AIR
Beam Length (Nominal Length in Feet)
Performance Parameter
4 Feet 6 Feet 8 Feet 10 Feet

Water Side Heating (BTUH/LF) Multiply by 1.04 No Correction Multiply by 0.88 Multiply by 0.85

Max. Recommended GPM (DID601-US-4 models) 1.5 1.5 1.5 1.5

Max. Recommended GPM (DID601-HC-4 models) 1.5 1.5 1.5 1.5

Noise Level (NC) -5 No Correction +3 +4

Primary Air Pressure Drop Multiply by 0.85 No Correction Multiply by 1.03 Multiply by 1.15

Hot Water Pressure Loss See Figure 36

TENTERING HOT WATER - TINDUCED AIR See Table 7 (page 38)

Figure 44: Heating (4 Pipe) Performance, DID601-US-4 and DID601-HC-4

48
Heating Performance (4-Pipe) DID602

1000 Chart is based on 6 ft. DID602-HC-4 (4


pipe) heating with a 20˚F temperature
differential between room and primary air
900 and a 50˚F temperature differential
between room and entering hot water.
For other beam lengths, see the
correction factors table below.
800
GPMHWS
GPMHWS
GPMHWS
700
1.5
1.5
1.0 1.0 1.5
600
0.8 0.8
1.0
0.6 0.6
500 0.8
Net Sensible Heating Capacity, BTUH/LF

NET SENSIBLE HEATING


0.4
0.6
0.4
400
0.3

0.3 0.4
300 0.2

0.2 0.3
200

WATER SIDE HEATING


100 0.2

-100

PRIMARY AIR COOLING


-200

"A" NOZZLES
-300
NC 15 20 25

0.3" 0.4" 0.6" 0.8" 1.0"


-400

-500
NC 20 25 30 34
"B" NOZZLES
0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9"1.0"
-600

NC 22 25 30 35 39
-700 "C" NOZZLES
0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9" 1.0"

4.0 6.0 8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0 28.0 30.0

Primary Airflow Rate, CFM/LF

Corrections for Other DID602-US-4 or DID602-HC-4 Lengths & T ENTERING WATER - TINDUCED AIR
Beam Length (Nominal Length in Feet)
Performance Parameter
4 Feet 6 Feet 8 Feet 10 Feet

Water Side Heating (BTUH/LF) Multiply by 1.04 No Correction Multiply by 0.88 Multiply by 0.85

Max. Recommended GPM (DID602-US-4 models) 1.5 1.5 1.5 1.5

Max. Recommended GPM (DID602-HC-4 models) 1.5 1.5 1.5 1.5

Noise Level (NC) -5 No Correction +3 +4

Primary Air Pressure Drop Multiply by 0.85 No Correction Multiply by 1.03 Multiply by 1.15

Hot Water Pressure Loss See Figure 36

TENTERING HOT WATER - TINDUCED AIR See Table 7 (page 38)

Figure 45: Heating (4 Pipe) Performance, DID602-US-4 and DID602-HC-4

49
Cooling Performance (2-Pipe) DID621

1120
Chart is based on 6 ft. DID621-HC-2 (2
pipe) cooling with a 20˚F temperature
differential between room and primary air
1040
and an 18˚F temperature differential
between room and entering chilled water.
For other beam lengths, see the
960 correction factors table below.

Performance at water flow rates > 1.5 GPMCWS


GPM is only achievable with DID621-HC
880 models.

800
Sensible Cooling Capacity, BTUH/LF

3.0
2.5

SECONDARY (WATER) COOLING


720 2.0

640 GPMCWS 1.5

1.0

560
0.6

TOTAL SENSIBLE COOLING


3.0
2.0
480 0.4
1.5
0.3
1.0
400 0.6
0.2
0.4
0.3
320
0.2

240

PRIMARY AIR COOLING


160

"G" NOZZLES

80
NC 15 20 25 30 35 37

0.2" 0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9" 1.0"


0
NC 15 20 25 27
"M" NOZZLES
0.2" 0.3" 0.4" 0.6" 0.8" 1.0"

1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0

Primary Airflow Rate, CFM/LF

Corrections for Other DID621-US-2 or DID621-HC-2 Lengths & T INDUCED AIR - TENTERING WATER
Beam Length (Nominal Length in Feet)
Performance Parameter
4 feet 6 feet 8 feet 10 feet

Sensible Cooling (BTUH/LF) Multiply by 1.02 No Correction Multiply by 0.98 Multiply by 0.90

Max. Recommended GPM (DID621-US-2 models) 1.35 1.15 1.0 0.9

Max. Recommended GPM (DID621-HC-2 models) 2.65 2.25 2.0 1.8

Noise Level (NC) -5 No Correction +3 +6

Primary Air Pressure Drop Multiply by 1.03 No Correction Multiply by .98 Multiply by .97

Chilled Water Pressure Loss See Figure 32 (DID621-US-2) or 34 (DID621-HC-2)

TINDUCED AIR - TENTERING WATER See Table 6 (page38)

Figure 46: Cooling (2 Pipe) Performance, DID621-US-2 and DID621-HC-2

50
Cooling Performance (2-Pipe) DID622

1500
Chart is based on 6 ft. DID622-HC-2 (2
pipe) cooling with a 20˚F temperature
differential between room and primary air
1400
and an 18˚F temperature differential
between room and entering chilled water.
For other beam lengths, see the
1300 correction factors table below.

Performance at water flow rates > 1.5


GPMCWS
GPM is only achievable with DID622-HC
1200 models.

1100
Sensible Cooling Capacity, BTUH/LF

3.0

SECONDARY (WATER) COOLING


2.5
1000 2.0
1.5

900 1.0

GPMCWS
0.6

TOTAL SENSIBLE COOLING


800
0.4

700 3.0
0.3
2.0
1.5 0.2
600
1.0
0.6
500 0.4
0.3

400 0.2

PRIMARY AIR COOLING


300

"G" NOZZLES

200
NC 15 20 25 30 35 37

0.2" 0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9" 1.0"


100
NC 15 20 25 27
"M" NOZZLES
0.2" 0.3" 0.4" 0.6" 0.8" 1.0"

2.0 4.0 6.0 8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0

Primary Airflow Rate, CFM/LF

Corrections for Other DID622-US-2 or DID622-HC-2 Lengths & T INDUCED AIR - TENTERING
WATER Beam Length (Nominal Length in Feet)
Performance Parameter
4 feet 6 feet 8 feet 10 feet

Sensible Cooling (BTUH/LF) Multiply by 1.02 No Correction Multiply by 0.98 Multiply by 0.90

Max. Recommended GPM (DID622-US-2 models) 1.35 1.15 1.0 0.9

Max. Recommended GPM (DID622-HC-2models) 2.65 2.25 2.0 1.8

Noise Level (NC) -5 No Correction +3 +6

Primary Air Pressure Drop Multiply by 1.02 No Correction Multiply by .98 Multiply by .97

Chilled Water Pressure Loss See Figure 32 (DID622-US-2) or Figure 34 (DID622-HC-2)

TINDUCED AIR - TENTERING CHILLED WATER See table 6 (page38)

Figure 47: Cooling (2 Pipe) Performance, DID622-US-2 and DID622-HC-2

51
Cooling Performance (4-Pipe) DID621

1120
Chart is based on 6 ft. DID621-HC-4 (4
pipe) cooling with a 20˚F temperature
differential between room and primary air
1040
and an 18˚F temperature differential
between room and entering chilled water.
For other beam lengths, see the
960 correction factors table below.

Performance at water flow rates > 1.5


GPM is only achievable with DID621-HC
880 models. GPMCWS

800
Sensible Cooling Capacity, BTUH/LF

3.0

SECONDARY (WATER) COOLING


720
2.5

2.0
640
GPMCWS
1.5
560 1.0

0.6

TOTAL SENSIBLE COOLING


480 3.0
0.4
2.0
1.5 0.3
400
1.0
0.2
0.6
320 0.4
0.3
0.2
240

PRIMARY AIR COOLING


160

"G" NOZZLES

80
NC 15 20 25 30 35 37

0.2" 0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9" 1.0"


0
NC 15 20 25 27
"M" NOZZLES
0.2" 0.3" 0.4" 0.6" 0.8" 1.0"

1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0

Primary Airflow Rate, CFM/LF

Corrections for Other DID621-US-4 or DID621-HC-4 Lengths & T INDUCED AIR - TENTERING
WATER Beam Length (Nominal Length in Feet)
Performance Parameter
4 feet 6 feet 8 feet 10 feet

Sensible Cooling (BTUH/LF) Multiply by 1.02 No Correction Multiply by 0.98 Multiply by 0.90

Max. Recommended GPM (DID621-US-4 models) 1.5 1.35 1.2 1.1

Max. Recommended GPM (DID621-HC-4 models) 3.0 2.65 2.35 2.1

Noise Level (NC) -5 No Correction +3 +6

Primary Air Pressure Drop Multiply by 1.03 No Correction Multiply by .98 Multiply by .97

Chilled Water Pressure Loss See Figure 33 (DID621-US-4) or Figure 35 (DID621-HC-4)

TINDUCED AIR - TENTERING CHILLED WATER See Table 6 (page 38)

Figure 48: Cooling (4 Pipe) Performance, DID621-US-4 and DID621-HC-4

52
Cooling Performance (4-Pipe) DID622

1500
Chart is based on 6 ft. DID622-HC-4 (4
pipe) cooling with a 20˚F temperature
differential between room and primary air
1400
and an 18˚F temperature differential
between room and entering chilled water.
For other beam lengths, see the
1300 correction factors table below.

Performance at water flow rates > 1.5


GPM is only achievable with DID622-HC
1200 models.
GPMCWS

1100
Sensible Cooling Capacity, BTUH/LF

SECONDARY (WATER) COOLING


3.0
1000
2.5
2.0
900 1.5
1.0
GPMCWS

800 0.6

TOTAL SENSIBLE COOLING


0.4
700 3.0
0.3
2.5

1.5
600 0.2
1.0

500 0.6

400

PRIMARY AIR COOLING


0.4
300
0.2
"G" NOZZLES

200
NC 15 20 25 30 35 37

0.2" 0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9" 1.0"


100
NC 15 20 25 27
"M" NOZZLES
0.2" 0.3" 0.4" 0.6" 0.8" 1.0"

2.0 4.0 6.0 8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0

Primary Airflow Rate, CFM/LF

Corrections for Other DID622-US-4 or DID622-HC-4 Lengths & T INDUCED AIR - TENTERING WATER
Beam Length (Nominal Length in Feet)
Performance Parameter
4 feet 6 feet 8 feet 10 feet

Sensible Cooling (BTUH/LF) Multiply by 1.02 No Correction Multiply by 0.98 Multiply by 0.90

Max. Recommended GPM (DID622-US-4 models) 1.5 1.35 1.2 1.05

Max. Recommended GPM (DID622-HC-4 models) 3.0 2.65 2.3 2.1

Noise Level (NC) -5 No Correction +3 +6

Primary Air Pressure Drop Multiply by 1.03 No Correction Multiply by .98 Multiply by .97

Chilled Water Pressure Loss See Figure 33 (DID622-US-4) or Figure 35 (DID622-HC-4)

TINDUCED AIR - TENTERING HOT WATER See Table 7 (page 38)

Figure 49: Cooling (4 Pipe) Performance, DID622-US-4 and DID622-HC-4

53
Heating Performance (4-Pipe) DID621

1050 Chart is based on 6 ft. DID621-US-4 or


DID621-HC-4 (4 pipe) heating with a 20˚F
temperature differential between room
and primary air and an 50˚F temperature
950 differential between room and entering
hot water. For other beam lengths, see
the correction factors table below.
850

GPMHWS

750
Net Sensible Heating Capacity, BTUH/LF

GPMHWS
650 1.5

1.0
550

NET SENSIBLE HEATING


1.5
0.6
1.0
450
0.6
0.4

WATERSIDE HEATING
350

0.4 0.3

250 0.3

0.2
0.2
150

50

-50

PRIMARY AIR
COOLING
-150 NC 15 20 25 27

0.2" 0.3" 0.4" 0.6" 0.8" 1.0"


-250
"M" NOZZLES
"G" NOZZLES

NC 15 20 25 30 35 37

0.2" 0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9" 1.0"

1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0

Primary Airflow Rate, CFM/LF

Corrections for Other DID621-US-4 or DID621-HC-4 Lengths & T ENTERING WATER - TINDUCED AIR
Beam Length (Nominal Length in Feet)
Performance Parameter
4 Feet 6 Feet 8 Feet 10 Feet

Water Side Heating (BTUH/LF) Multiply by 1.03 No Correction Multiply by 0.96 Multiply by 0.92

Max. Recommended GPM (DID621-US-4 models) 1.5 1.5 1.5 1.5

Max. Recommended GPM (DID621-HC-4 models) 1.5 1.5 1.5 1.5

Noise Level (NC) -5 No Correction +3 +6

Primary Air Pressure Drop Multiply by 1.03 No Correction Multiply by 0.98 Multiply by 0.97

Hot Water Pressure Loss See Figure 36

TENTERING HOT WATER - TINDUCED AIR See table 7 (page 38)

Figure 50: Heating (4 Pipe) Performance, DID621-US-4 and DID621-HC-4

54
Heating Performance (4-Pipe) DID622

Chart is based on 6 ft. DID622-US-4 or


1000 DID622-HC-4 (4 pipe) heating with a 20˚F
temperature differential between room
and primary air and an 50˚F temperature
900 differential between room and entering GPMHWS
hot water. For other beam lengths, see
the correction factors table below.

800

GPMHWS
1.5
700
1.0
Net Sensible Heating Capacity, BTUH/LF

0.8
600
1.5

NET SENSIBLE HEATING


0.6
500 1.0
0.8

0.6 0.4
400

0.4

WATER SIDE HEATING


300
0.3
0.3

200 0.2

0.2
100

-100

PRIMARY AIR COOLING


-200

-300 NC 15 20 25 27

0.2" 0.3" 0.4" 0.6" 0.8" 1.0"


-400
"M" NOZZLES

-500
NC 15 20 25 30 35 37
"G" NOZZLES
0.2" 0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9" 1.0"

2.0 4.0 6.0 8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0

Primary Airflow Rate, CFM/LF

Corrections for Other DID622-US-4 or DID622-HC-4 Lengths & T ENTERING WATER - TINDUCED AIR
Beam Length (Nominal Length in Feet)
Performance Parameter
4 Feet 6 Feet 8 Feet 10 Feet

Water Side Heating (BTUH/LF) Multiply by 1.03 No Correction Multiply by 0.96 Multiply by 0.92

Max. Recommended GPM (DID622-US-4 models) 1.5 1.5 1.5 1.5

Max. Recommended GPM (DID622-HC-4 models) 1.5 1.5 1.5 1.5

Noise Level (NC) -5 No Correction +3 +6

Primary Air Pressure Drop Multiply by 1.02 No Correction Multiply by 0.98 Multiply by 0.97

Hot Water Pressure Loss See Figure 36

TENTERING HOT WATER - TINDUCED AIR See Table 7 (page 38)

Figure 51: Heating (4 Pipe) Performance, DID622-US-4 and DID622-HC-4

55
Cooling Performance (2-Pipe) DID301

750
Chart is based on 6 ft. DID301-US-2 (2
pipe) cooling with a 20˚F temperature
differential between room and primary air
700
and an 18˚F temperature differential
between room and entering chilled water.
For other beam lengths, see the
650 correction factors table below.

600

GPMCWS

550

SECONDARY (WATER) COOLING


500 1.5
Sensible Cooling Capacity, BTUH/LF

GPMCWS
1.0

450
0.8
0.6
400 1.5
0.4
1.0
GPMCWS 0.3

TOTAL SENSIBLE COOLING


0.8
350 0.2

300
1.5 0.6
1.0 0.4
250 0.8 0.3

0.6 0.2

PRIMARY AIR COOLING


200
0.4
0.3
150 0.2
"C" NOZZLES

NC 20 25 30 35 39
100
0.2" 0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9" 1.0"

50 NC 15 20 25 30 35 37
"B" NOZZLES
0.2" 0.3" 0.4" 0.5" 0.6" 0.8" 1.0"

NC 15 20 25 30 33
0
"A" NOZZLES
0.3" 0.3" 0.4" 0.6" 0.8" 1.0"

2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 14.0 150.0

Primary Airflow Rate, CFM/LF

Corrections for Other DID301-US-2 Lengths & T INDUCED AIR - TENTERING WATER
Beam Length (Nominal Length in Feet)
Performance Parameter
4 Feet 6 Feet 8 Feet 10 Feet

Sensible Cooling (BTUH/LF) Multiply by 1.02 No Correction Multiply by 0.97 Multiply by 0.95

Max. Recommended GPM (DID301-US-2 models) 1.5 1.5 1.45 1.35

Noise Level (NC) -1 No Correction +1 +2

Primary Air Pressure Drop Multiply by 0.74 No Correction Multiply by 1.03 Multiply by 1.07

Chilled Water Pressure Loss See Figure 37

TINDUCED AIR - TENTERING CHILLED WATER See Table 6 (page 38)

Figure 52: Cooling (2 Pipe) Performance, DID301-US-2

56
Cooling Performance (2-Pipe) DID302

1500
Chart is based on 6 ft. DID302-US-2 (2
pipe) cooling with a 20˚F temperature
differential between room and primary air
1400
and an 18˚F temperature differential
between room and entering chilled water.
For other beam lengths, see the
1300 correction factors table below.
GPMCWS

1200

1.5

SECONDARY (WATER) COOLING


1100
1.0

1000 0.8
Sensible Cooling Capacity, BTUH/LF

0.6
GPMCWS
900 0.4

0.3
1.5
800 1.0 0.2

TOTAL SENSIBLE COOLING


GPMCWS

700
0.8
0.6
600 1.5 0.4
1.0 0.3

0.8 0.2
500
0.6
0.4

PRIMARY AIR COOLING


400 0.3
0.2

300 "C" NOZZLES

NC 20 25 30 35 39
200
0.2" 0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9" 1.0"

100 NC 15 20 25 30 35 37
"B" NOZZLES
0.2" 0.3" 0.4" 0.5" 0.6" 0.8" 1.0"

NC 15 20 25 30 33
0
"A" NOZZLES
0.3" 0.3" 0.4" 0.6" 0.8" 1.0"

4.0 6.0 8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0 28.0 30.0

Primary Airflow Rate, CFM/LF

Corrections for Other DID302-US-2 Lengths & T INDUCED AIR - TENTERING WATER
Beam Length (Nominal Length in Feet)
Performance Parameter
4 Feet 6 Feet 8 Feet 10 Feet

Sensible Cooling (BTUH/LF) Multiply by 1.02 No Correction Multiply by 0.97 Multiply by 0.95

Max. Recommended GPM (DID302-US-2 models) 1.35 1.15 1.0 0.9

Noise Level (NC) -1 No Correction +1 +2

Primary Air Pressure Drop Multiply by 0.74 No Correction Multiply by 1.03 Multiply by 1.07

Chilled Water Pressure Loss See Figure 37

TINDUCED AIR - TENTERING CHILLED WATER See table 6 (page 38)

Figure 53: Cooling (2 Pipe) Performance, DID302-US-2

57
Cooling Performance (4-Pipe) DID301

750
Chart is based on 6 ft. DID301-US-4 (4
pipe) cooling with a 20˚F temperature
differential between room and primary air
700
and an 18˚F temperature differential
between room and entering chilled water.
For other beam lengths, see the
650 correction factors table below.

600

550

GPMCWS

SECONDARY (WATER) COOLING


500
Sensible Cooling Capacity, BTUH/LF

450

GPMCWS 1.5
400 1.0

0.5
350 0.3

TOTAL SENSIBLE COOLING


1.5
GPMCWS
300
1.0

0.5
250 0.3
1.5
1.0

PRIMARY AIR COOLING


200
0.5
0.3
150 "C" NOZZLES

NC 20 25 30 35 39
100
0.2" 0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9" 1.0"

50 NC 15 20 25 30 35 37
"B" NOZZLES
0.2" 0.3" 0.4" 0.5" 0.6" 0.8" 1.0"

NC 15 20 25 30 33
0
"A" NOZZLES
0.3" 0.3" 0.4" 0.6" 0.8" 1.0"

2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 14.0 15.0

Primary Airflow Rate, CFM/LF

Corrections for Other DID301-US-4 Lengths & T INDUCED AIR - TENTERING WATER
Beam Length (Nominal Length in Feet)
Performance Parameter
4 Feet 6 Feet 8 Feet 10 Feet

Sensible Cooling (BTUH/LF) Multiply by 1.02 No Correction Multiply by 0.97 Multiply by 0.95

Max. Recommended GPM (DID301-US-4 models) 1.5 1.5 1.5 1.5

Noise Level (NC) -1 No Correction +1 +2

Primary Air Pressure Drop Multiply by 0.74 No Correction Multiply by 1.03 Multiply by 1.07

Chilled Water Pressure Loss See Figure 38

TINDUCED AIR - TENTERING CHILLED WATER See Table 6 (page 38)

Figure 54: Cooling (4 Pipe) Performance, DID301-US-4

58
Cooling Performance (4-Pipe) DID302

1500
Chart is based on 6 ft. DID302-US-4 (4
pipe) cooling with a 20˚F temperature
differential between room and primary air
1400
and an 18˚F temperature differential
between room and entering chilled water.
For other beam lengths, see the
1300 correction factors table below.

1200

GPMCWS
1100

SECONDARY (WATER) COOLING


1000
Sensible Cooling Capacity, BTUH/LF

1.5
1.0
900
GPMCWS
0.8
0.6
800
1.5 0.4
1.0 0.3

700 GPMCWS 0.8 0.2

TOTAL SENSIBLE COOLING


600
0.6
1.5
0.4
500 1.0
0.3
0.8
0.2

PRIMARY AIR COOLING


400 0.6
0.4

300 0.2
"C" NOZZLES

NC 20 25 30 35 39
200
0.2" 0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9" 1.0"

100 NC 15 20 25 30 35 37
"B" NOZZLES
0.2" 0.3" 0.4" 0.5" 0.6" 0.8" 1.0"

NC 15 20 25 30 33
0
"A" NOZZLES
0.3" 0.3" 0.4" 0.6" 0.8" 1.0"

4.0 6.0 8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0 28.0 30.0

Primary Airflow Rate, CFM/LF

Corrections for Other DID302-US-2 Lengths & T INDUCED AIR - TENTERING WATER
Beam Length (Nominal Length in Feet)
Performance Parameter
4 Feet 6 Feet 8 Feet 10 Feet

Sensible Cooling (BTUH/LF) Multiply by 1.02 No Correction Multiply by 0.97 Multiply by 0.95

Max. Recommended GPM (DID302-US-2 models) 1.5 1.5 1.45 1.3

Noise Level (NC) -1 No Correction +1 +2

Primary Air Pressure Drop Multiply by 0.74 No Correction Multiply by 1.03 Multiply by 1.07

Chilled Water Pressure Loss See Figure 38

TINDUCED AIR - TENTERING CHILLED WATER See Table 6 (page 38)

Figure 55: Cooling (4 Pipe) Performance, DID302-US-4

59
Heating Performance (4-Pipe) DID301

450 Chart is based on 6 ft. DID301-US-4 (4


pipe) heating with a 20˚F temperature
differential between room and primary air
and an 50˚F temperature differential
400 between room and entering hot water.
For other beam lengths, see the GPMHWS
correction factors table below.
350

GPMHWS

300 1.5
GPMHWS
1.0
Net Sensible Heating Capacity, BTUH/LF

250
1.5
1.0
0.8 1.5
200 0.8
1.0

NET SENSIBLE HEATING


0.5
0.8
0.5
150
0.5
0.3 0.3

100

WATERSIDE HEATING
0.3

50

PRIMARY AIR COOLING


-50

-150

-200 NC 15 20 25 30 33
"A" NOZZLES
0.3" 0.3" 0.4" 0.6" 0.8" 1.0"

-250
NC 15 20 25 30 35 37
"B" NOZZLES
0.2" 0.3" 0.4" 0.5" 0.6" 0.8" 1.0"

NC 25 30 35 39
"C" NOZZLES
0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9" 1.0"

2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 14.0

Primary Airflow Rate, CFM/LF

Corrections for Other DID301-US-4 Lengths & T ENTERING WATER - TINDUCED AIR
Beam Length (Nominal Length in Feet)
Performance Parameter
4 Feet 6 Feet 8 Feet 10 Feet

Water Side Heating (BTUH/LF) Multiply by 1.03 No Correction Multiply by 0.96 Multiply by 0.92

Max. Recommended GPM (DID301-US-4 models) 1.5 1.5 1.5 1.5

Noise Level (NC) -1 No Correction +1 +2

Primary Air Pressure Drop Multiply by 1.02 No Correction Multiply by 0.98 Multiply by 0.97

Hot Water Pressure Loss See Figure 39

TENTERING HOT WATER - TINDUCED AIR See table 7 (page 38)

Figure 56: Heating (4 Pipe) Performance, DID301-US-4

60
Heating Performance (4-Pipe) DID302

700 Chart is based on 6 ft. DID302-US-4 (4 pipe) heating with


a 20˚F temperature differential between room and primary
air and an 50˚F temperature differential between room and
entering hot water. For other beam lengths, see the
600 correction factors table below.

GPMHWS GPMHWS
500 GPMHWS

1.5 1.5
400 1.0
1.0
0.8
0.8
0.6
Net Sensible Heating Capacity, BTUH/LF

0.6 1.5

NET SENSIBLE HEATING


300 0.4 1.0
0.4
0.8
200 0.6

0.4
100

WATERSIDE HEATING
-100

PRIMARY AIR COOLING


-200

-300

-400

-500 NC 15 20 25 30 33
"A" NOZZLES
0.3" 0.3" 0.4" 0.6" 0.8" 1.0"

-600
NC 15 20 25 30 35 37
"B" NOZZLES
0.2" 0.3" 0.4" 0.5" 0.6" 0.8" 1.0"

NC 25 30 35 39
"C" NOZZLES
0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9" 1.0"

4.0 6.0 8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0 28.0

Primary Airflow Rate, CFM/LF

Corrections for Other DID302-US-4 Lengths & T ENTERING WATER - TINDUCED AIR
Beam Length (Nominal Length in Feet)
Performance Parameter
4 Feet 6 Feet 8 Feet 10 Feet

Water Side Heating (BTUH/LF) Multiply by 1.03 No Correction Multiply by 0.96 Multiply by 0.92

Max. Recommended GPM (DID302-US-4 models) 1.5 1.5 1.5 1.5

Noise Level (NC) -1 No Correction +1 +2

Primary Air Pressure Drop Multiply by 1.02 No Correction Multiply by 0.98 Multiply by 0.97

Hot Water Pressure Loss See Figure 39

TENTERING HOT WATER - TINDUCED AIR See Table 7 (page 38)

Figure 57: Heating (4 Pipe) Performance, DID302-US-4

61
Specification DID600

steel flanked by two linear supply slots. The


DID600 Series Active Chilled Beams entire visible face section shall be finished in
white powder coat paint or as specified by the
PART 1- GENERAL architect. All visible internal surfaces shall be flat
black. The face of the beam shall be hinged for
1.01 Summary easy access to internal components.
3. Beams shall be provided with side and end
This section describes the active chilled details which will allow its integration into the
beams. applicable (nominal 24 inch wide) acoustical
ceiling grid as specified by the architect. Beams
1.02 Submittals used for exposed mounting applications shall
include factory mounted Coanda plates to assure
Submit product data for all items complete with the a horizontal discharge of the supply air.
following information: 4. The beams shall consist of a minimum 20 gauge
galvanized steel housing encasing the integral
1. Operating weights and dimensions of all unit sensible cooling coil and a plenum feeding a
assemblies. series of induction nozzles. A side or end
2. Performance data, including sensible and latent mounted connection spigot shall afford the
cooling capacities, nozzle types, primary and total connection of a primary air supply duct (4”
supply (primary plus induced) airflow rates, nominal diameter for all one way beams and 2
chilled (and where applicable hot) water flow way beams through six feet in length, 5” nominal
rates, noise levels in octave bands, air and water diameter for 2 way beams longer than six feet)
side pressure losses and maximum discharge air The overall height of the beams shall not exceed
throw values. 9¾ inches.
3. Construction details including manufacturers 5. Beams shall incorporate provisions for
recommendations for installation, mounting and measurement of their primary airflow rate. The
connection. measurement location must be accessible from
the face of the beam and require a single
PART 2- PRODUCTS pressure differential measurement. Airflow
calibration charts that relate the measurement to
2.01 General the primary airflow rate shall be furnished with the
beams.
Materials and products required for the work of this 6. (OPTIONAL) Each beam shall be furnished with
section shall not contain asbestos, polychlorinated a separate volume flow limiter for mounting in the
biphenyls (PCB) or other hazardous materials primary air duct by the installing contractor. This
identified by the engineer or owner. device shall allow field adjustment of a maximum
primary air flow rate that is maintained
Approved Manufacturers: independent of any static pressure changes in
the inlet ductwork. The volume flow limiter shall
These specifications set forth the minimum add no more than 0.20 inches H2O pressure drop
requirements for the active chilled beams to be to the primary air delivery system and shall not
accepted for this project. Products provided by the require any control or power connections.
following manufacturers will be deemed acceptable 7. Beams shall be provided with connections for
provided they meet all of the construction and either 2 or 4 pipe operation as indicated on plans
performance requirements of this specification: and schedules. Four pipe configurations shall
require separate supply and return connections
1. TROX for chilled and hot water. The coils shall be
mounted horizontally and shall be manufactured
2.02 Design with seamless copper tubing (½” outside
diameter) with minimum .025 inch wall thickness
1. Furnish and install TROX DID601 and/or DID602 mechanically fixed to aluminum fins. The
series active chilled beams of sizes and aluminum fins shall be limited to no more than ten
capacities as indicated on the drawings and (10) fins per inch. The beam shall have a working
within the mechanical equipment schedules. The pressure of at least 300 PSI, be factory tested for
quantity and length of the beams shall be as leakage at a minimum pressure of 360 PSI. Each
shown on the drawings, without EXCEPTION. chilled beam shall be provided with factory
The beams shall be constructed and delivered to integrated drain fittings. Each chilled beam shall
the job site as single units. be provided with factory integrated
2. The face of the beam shall consist of a room air
induction section of 50% free area perforated

62
Specification DID600

vent and drain fittings. Unless otherwise lowered into the grid module by adjusting the nuts
specified, coil connections shall be bare copper connecting the threaded rods to the beam.
for field sweating to the water supply circuit. 3. Before connecting the supply water system(s) to
Connections shall face upwards, be located near the beams, contractor shall flush the piping
the left end of the beam (when viewing into the system(s) to assure that all debris and other
primary air connection matter have been removed.
8. (OPTIONAL) The chilled water coil shall be 4. Contractor shall perform connection of beams to
provided with NPT male threaded fittings where the chilled water circuit by method specified (hard
specified. These fittings must be suitable for field connection using sweated connection or
connection to a similar NPT female flexible hose connection using flexible hoses.
spigot and shall be at least 1½” long to facilitate 5. Flexible connector hoses shall be furnished by
field connection (by others). others (optionally by the manufacturer). Hoses
9. Beams shall be delivered clean, flushed and shall be twenty four (24) inches in length and
capped to prevent ingress of dirt. suitable for operation with a bend radius as small
as five (5) inches. Such hoses shall be 100%
2.03 Performance tested and certified for no leakage at 500 PSI.
Connector hoses shall consist of a PFTE lined
1. All performance shall be in compliance with that hose with a wire braided jacket. The hoses shall
shown on the equipment schedule. Acoustical be suitable for operation in an environment
testing shall have been performed in accordance between -40 and 200˚F, rated for a least 300 PSI
with ISO 3741. and tested for leakage at a minimum pressure of
2. Coils shall be rated in accordance with ARI 360 PSI. Contractor shall assure that the chilled
Standard 410, but their cooling and heating water supplying the beams has been properly
capacities shall be established in accordance to treated in accordance to BSRIA publication AG
European Standard EN15116 for the specific 2/93.
application on the inlet side of the submitted 6. No power or direct control connections shall be
chilled beam. Evidence of this testing must be required for the operation of the chilled beam.
included in the submittal.
3. Primary airflow rates shall not result in supply 3.03 Cleaning and Protection
(primary plus induced) airflow rates in excess of
80 CFM per linear foot of (two slot) beam. 1. Protect units before, during and after installation.
4. Chilled water flow rates to the beams shall be Damaged material due to improper site protection
limited to that which results in a maximum ten shall be cause for rejection.
(10) foot head loss. Water flow velocities through 2. Clean equipment, repair damaged finishes as
the beam shall not exceed 4 FPS. required to restore beams to as-new appearance.

PART 3- EXECUTION

3.02 Installation

1. Coordinate the size, tagging and capacity of the


beams to their proper location.
2. (RECOMMENDED INSTALLATION
PROCEDURE) Chilled beams up to six feet in
length shall be independently suspended from
the structure above by a four (4) threaded rods of
⅜” diameter (provided by the installing
contractor). For beams beyond six feet in length,
six (6) threaded rods of ⅜” diameter. The upper
end of the rods shall be suspended from strut
channels that are a) mounted perpendicular to
the beam length and b) at least four inches wider
than the beam to facilitate relocation of the
threaded rods along their length. The rods shall
be fixed to factory mounting brackets on the
beam that allow repositioning (at least four
inches) along its length. The beam shall then be
positioned above the acoustical ceiling grid and

63
Specification DID620

DID620 Series Active Chilled Beams entire visible face section shall be finished in
white powder coat paint or as specified by the
PART 1- GENERAL architect. All visible internal surfaces shall be flat
black.
1.01 Summary 3. Beams shall be provided with side and end
details which will allow its integration into the
This section describes the active chilled applicable (nominal 24 inch wide) acoustical
beams. ceiling grid as specified by the architect. Beams
used for exposed mounting applications shall
1.02 Submittals include factory mounted Coanda plates to assure
a horizontal discharge of the supply air.
Submit product data for all items complete with the 4. The beams shall consist of a minimum 20 gauge
following information: galvanized steel housing encasing the integral
sensible cooling coil and a plenum feeing a series
1. Operating weights and dimensions of all unit of induction nozzles. A side (model 622-US-H) or
assemblies. top (model 622-US-V) mounted connection spigot
2. Performance data, including sensible and latent shall afford the connection of a six (6) inch
cooling capacities, nozzle types, primary and total diameter supply air. The overall height of beams
supply (primary plus induced) airflow rates, shall not exceed 8⅞ inches.
chilled (and where applicable hot) water flow 5. Each beam shall be provided with a pressure tap
rates, noise levels in octave bands, air and water that may be used to measure the pressure
side pressure losses and maximum discharge air differential between the primary air plenum and
throw values. the room. Airflow calibration charts that relate this
3. Construction details including manufacturers pressure differential reading with the primary and
recommendations for installation, mounting and beam supply airflow rates shall be furnished with
connection. the beams.
6. (OPTIONAL) Each beam shall be furnished with
PART 2- PRODUCTS a separate volume flow limiter for mounting in the
primary air duct by the installing contractor. This
2.01 General device shall allow field adjustment of a maximum
primary air flow rate that is maintained
Materials and products required for the work of this independent of any static pressure changes in
section shall not contain asbestos, polychlorinated the inlet ductwork. The volume flow limiter shall
biphenyls (PCB) or other hazardous materials add no more than 0.20 inches H2O pressure drop
identified by the engineer or owner. to the primary air delivery system and shall not
require any control or power connections.
Approved Manufacturers: 7. Beams shall be provided with connections for
either 2 or 4 pipe operation as indicated on plans
These specifications set forth the minimum and schedules. Four pipe configurations shall
requirements for the active chilled beams to be require separate supply and return connections
accepted for this project. Products provided by the for chilled and hot water. The coils shall be
following manufacturers will be deemed acceptable mounted horizontally and shall be manufactured
provided they meet all of the construction and with seamless copper tubing (½” outside
performance requirements of this specification: diameter) with minimum .025 inch wall thickness
mechanically fixed to aluminum fins. The
1. TROX aluminum fins shall be limited to no more than ten
(10) fins per inch. The beam shall have a working
2.02 Design pressure of at least 300 PSI, be factory tested for
leakage at a minimum pressure of 360 PSI. Each
1. Furnish and install TROX DID621 (1 slot) and/or chilled beam shall be provided with factory
DID622 (2 slot) series single slot active chilled integrated vent and drain fittings. Unless
beams of sizes and capacities as indicated on the otherwise specified, coil connections shall be
drawings and within the mechanical equipment bare copper for field sweating to the water supply
schedules. The quantity and length of the beams circuit. Connections shall face upwards, be
shall be as shown on the drawings, without located near the left end of the beam (when
EXCEPTION. The beams shall be constructed viewing into the primary air connection
and delivered to the job site as single units.
2. The face of the beam shall consist of a room air
induction section of 50% free area perforated
steel flanked by two linear supply slots. The

64
Specification DID620

8. (OPTIONAL) The chilled water coil shall be 4. Contractor shall perform connection of beams to
provided with NPT male threaded fittings where the chilled water circuit by method specified (hard
specified. These fittings must be suitable for field connection using sweated connection or
connection to a similar NPT female flexible hose connection using flexible hoses.
spigot and shall be at least 1½” long to facilitate 5. Flexible connector hoses shall be furnished by
field connection (by others). others (optionally by the manufacturer). Hoses
9. Beams shall be delivered clean, flushed and shall be twenty four (24) inches in length and
capped to prevent ingress of dirt suitable for operation with a bend radius as small
as five (5) inches. Such hoses shall be 100%
2.03 Performance tested and certified for no leakage at 500 PSI.
Connector hoses shall consist of a PFTE lined
1. All performance shall be in compliance with that hose with a wire braided jacket. The hoses shall
shown on the equipment schedule. Acoustical be suitable for operation in an environment
testing shall have been performed in accordance between -40 and 200˚F, rated for a least 300 PSI
with ISO 3741. and tested for leakage at a minimum pressure of
2. Coils shall be rated in accordance with ARI 360 PSI. Contractor shall assure that the chilled
Standard 410, but their cooling and heating water supplying the beams has been properly
capacities shall be established in accordance to treated in accordance to BSRIA publication AG
European Standard EN15116 for the specific 2/93.
application on the inlet side of the submitted 6. No power or direct control connections shall be
chilled beam. Evidence of this testing must be required for the operation of the chilled beam.
included in the submittal.
3. 3.03 Cleaning and Protection
4. Primary airflow rates shall not result in supply
(primary plus induced) airflow rates in excess of 1. Protect units before, during and after installation.
80 CFM per linear foot of beam. Damaged material due to improper site protection
5. Chilled water flow rates to the beams shall be shall be cause for rejection.
limited to that which results in a maximum ten 2. Clean equipment, repair damaged finishes as
(10) foot head loss. Water flow velocities through required to restore beams to as-new appearance.
the beam shall not exceed 4 FPS.

PART 3- EXECUTION

3.02 Installation

1. Coordinate the size, tagging and capacity of the


beams to their proper location.
2. (RECOMMENDED INSTALLATION
PROCEDURE) Chilled beams up to six feet in
length shall be independently suspended from
the structure above by a four (4) threaded rods of
⅜” diameter (provided by the installing
contractor). For beams beyond six feet in length,
six (6) threaded rods of ⅜” diameter. The upper
end of the rods shall be suspended from strut
channels that are a) mounted perpendicular to
the beam length and b) at least four inches wider
than the beam to facilitate relocation of the
threaded rods along their length. The rods shall
be fixed to factory mounting slots on the beam
that allow repositioning (at least four inches)
along its length. The beam shall then be
positioned above the acoustical ceiling grid and
lowered into the grid module by adjusting the nuts
connecting the threaded rods to the beam.
3. Before connecting the supply water system(s) to
the beams, contractor shall flush the piping
system(s) to assure that all debris and other
matter have been removed.

65
Specification DID300

DID300 Series Active Chilled Beams steel flanked by two linear supply slots (or an
OPTIONAL linear bar grille with a 70% free area
PART 1- GENERAL face). The entire visible face section shall be
finished in white powder coat paint or as specified
1.01 Summary by the architect. All visible internal surfaces shall
be flat black.
This section describes the active chilled beams. 3. Beams shall be provided with side and end
details which will allow its integration into the
1.02 Submittals applicable (nominal 12 inch wide) acoustical
ceiling grid as specified by the architect. Beams
Submit product data for all items complete with the used for exposed mounting applications shall
following information: include factory mounted “Coanda” plates to
assure a horizontal discharge of the supply air.
1. Operating weights and dimensions of all unit 4. The beams shall consist of a minimum 20 gauge
assemblies. galvanized steel housing encasing the integral
2. Performance data, including sensible and latent sensible cooling coil and a plenum feeing a series
cooling capacities, nozzle types, primary and total of induction nozzles. A side entry primary air duct
supply (primary plus induced) airflow rates, connection shall be provided with a nominal five
chilled (and where applicable hot) water flow (5) or six (6) inch round spigot. The overall height
rates, noise levels in octave bands, air and water of the beams shall not exceed 9½”
side pressure losses and maximum discharge air 5. Beams shall incorporate provisions for
throw values. measurement of their primary airflow rate. The
3. Construction details including manufacturers measurement location must be accessible from
recommendations for installation, mounting and the face of the beam and require a single
connection. pressure differential measurement. Airflow
calibration charts that relate the measurement to
PART 2- PRODUCTS the primary airflow rate shall be furnished with the
beams.
2.01 General 6. (OPTIONAL) Each beam shall be furnished with
a separate volume flow limiter for mounting in the
Materials and products required for the work of this primary air duct by the installing contractor. This
section shall not contain asbestos, polychlorinated device shall allow field adjustment of a maximum
biphenyls (PCB) or other hazardous materials primary air flow rate that is maintained
identified by the engineer or owner. independent of any static pressure changes in
the inlet ductwork. The volume flow limiter shall
Approved Manufacturers: add no more than 0.20 inches H2O pressure drop
to the primary air delivery system and shall not
These specifications set forth the minimum require any control or power connections.
requirements for the active chilled beams to be 7. When furnished in a 2 pipe configuration, the
accepted for this project. Products provided by the assembly shall contain two (2) separate chilled
following manufacturers will be deemed acceptable water coils with single supply and return
provided they meet all of the construction and connections. Four pipe connections shall require
performance requirements of this specification: separate connections for their chilled and hot
water supply. The coils shall be mounted
1. TROX vertically and (non-piped) condensate trays shall
be furnished directly beneath them. The coils
2.02 Design shall be manufactured with seamless copper
tubing (½” outside diameter) with minimum .025
1. Furnish and install TROX DID301 (single slot) inch wall thickness mechanically fixed to
and/or DID302 (two slot) series active chilled aluminum fins. The aluminum fins shall be limited
beams of sizes and capacities as indicated on the to no more than ten (10) fins per inch. The beam
drawings and within the mechanical equipment shall have a working pressure of at least 300 PSI,
schedules. The quantity and length of the beams be factory tested for leakage at a minimum
shall be as shown on the drawings, without pressure of 360 PSI. Each chilled beam shall be
EXCEPTION. The beams shall be constructed provided with factory integrated vent and drain
and delivered to the job site as single units. fittings. Unless otherwise specified, coil
2. The face of the beam shall consist of a room air connections shall be ½” O.D. bare
induction section of 50% free area perforated

66
Specification DID300

copper for field sweating to the water supply circuit. 3. Before connecting the supply water system(s) to
Connections to 2 pipe coils shall extend from left end the beams, contractor shall flush the piping sys-
of the beam (when viewing into the primary air con- tem(s) to assure that all debris and other matter
nection spigot) and shall be at least 1½” long to facili- have been removed.
tate field connection (by others). 4. Contractor shall perform connection of beams to
the chilled water circuit by method specified (hard
8. (OPTIONAL) The chilled water coil shall be pro- connection using sweated connection or connec-
vided with NPT male threaded fittings where tion using flexible hoses.
specified. These fittings must be suitable for field 5. Flexible connector hoses shall be furnished by
connection to a similar NPT female flexible hose. others (optionally by the manufacturer). Hoses
9. Beams shall be delivered clean, flushed and shall be twenty four (24) inches in length and
capped to prevent ingress of dirt. suitable for operation with a bend radius as small
as five (5) inches. Such hoses shall be 100%
2.03 Performance tested and certified for no leakage at 500 PSI.
Connector hoses shall consist of a PFTE lined
All performance shall be in compliance with that hose with a wire braided jacket. The hoses shall
shown on the equipment schedule. Acoustical testing be suitable for operation in an environment be-
shall have been performed in accordance with ISO tween -40 and 200˚F, rated for a least 300 PSI
3741. and tested for leakage at a minimum pressure of
Coils shall be rated in accordance with ARI Standard 360 PSI. Contractor shall assure that the chilled
410, but their cooling and heating capacities shall be water supplying the beams has been properly
established in accordance to European Standard treated in accordance to BSRIA publication AG
EN15116 for the specific application on the inlet side 2/93.
of the submitted chilled beam. Evidence of this testing 6. No power or direct control connections shall be
must be included in the submittal. required for the operation of the chilled beam.

Primary airflow rates shall not result in supply (primary 3.03 Cleaning and Protection
plus induced) airflow rates in excess of 40 CFM per
linear foot of beam. Protect units before, during and after installation.
Chilled water flow rates to the beams shall be limited Damaged material due to improper site protection
to that which results in a maximum ten (10) foot head shall be cause for rejection.
loss. Water flow velocities through the beam shall not Clean equipment, repair damaged finishes as re-
exceed 4 FPS. quired to restore beams to as-new appearance.

PART 3- EXECUTION

3.02 Installation

1. Coordinate the size, tagging and capacity of the


beams to their proper location.
2. (RECOMMENDED INSTALLATION PROCE-
DURE) Chilled beams up to six feet in length
shall be independently suspended from the struc-
ture above by a four (4) threaded rods of ⅜” di-
ameter (provided by the installing contractor). For
beams beyond six feet in length, six (6) threaded
rods of ⅜” diameter. The upper end of the rods
shall be suspended from strut channels that are
a) mounted perpendicular to the beam length and
b) at least four inches wider than the beam to
facilitate relocation of the threaded rods along
their length. The rods shall be fixed to factory
mounting brackets on the beam that allow reposi-
tioning (at least four inches) along its length. The
beam shall then be positioned above the acousti-
cal ceiling grid and lowered into the grid module
by adjusting the nuts connecting the threaded
rods to the beam.

67
In North America Head Office & Research Centers
Trox USA, Inc. Gebrüder Trox GmbH
4305 Settingdown Circle Postfach 10 12 63
Cumming D-47504 Neukirchen-Vluyn
Georgia Telephone 49 28 45/2 02-0
Telefax 49 28 45/2 02-2 65
USA 30028 www.troxtechnik.com
E-mail: trox@troxtechnik.de
Telephone: (770) 569-1433
Telefax: (770) 569-1435
e-mail: sales@troxusa.com
www.troxusa.com

Australia Czech Republic Hong Kong South Africa


Trox (Australia) Pty Ltd. Trox Austria GmbH Trox Hong Kong Ltd. Trox (South Africa)
Austria Denmark Hungary (Pty) Ltd.
Trox Austria GmbH Trox Danmark A/S Trox Austria GmbH Spain
Belgium Dubai Italy Trox Española, S.A.
S.A. Trox Belgium N.V. Trox (U.K.) Ltd. Trox Italiana S.p.A. Switzerland
Brazil France Malaysia Trox Hesco
Trox do Brasil Ltda. Trox France Sarl Trox (Malaysia) Sdn. Bhd. (Schweiz) AG
China Germany Norway Yugoslavia
Trox Air Conditioning Hesco Deutschland GmbH Auranor Group AS Trox Austria GmbH
Components (Suzhou) FSL FassadenSystemLüftung Poland
Co., Ltd. GmbH & Co. KG Trox Austria GmbH
Croatia Great Britain
Trox Austria GmbH Trox (U.K.) Ltd.

68
Design changes reserved · All rights reserved © Gebrüder Trox GmbH (01/2009)

You might also like