You are on page 1of 4

NOVEMBER 2008 - MARCH 2009

Introduction to IEC 61439: A new standard on


Switchgear & Controlgear Assemblies
- Mr. A P Rao; Mr. D A Chavan; Mr. P Patel; Mr. T N Shah
Switchgear Design & Development Center

Introduction: differently. One of the main features verified and options available for
of IEC 61439-1 is that the verification.
IEC 60439, the standard for low-voltage discrimination between Type Tested
switchgear and controlgear assemblies, Assemblies (TTA) and Partially Type Salient features of IEC 61439
was under restructuring from the last Tested Assemblies (PTTA) has been
decade. The new series of IEC 61439 1. Verification of temperature rise
eliminated by the verification approach.
standards were published in January  For multiple compartment
2009. This standard has brought The three different but equivalent types assembly, verification by
considerable clarity in technical of verification methods are introduced calculation can be done up to
interpretation. and these are; rated current of 1600 A only.
The new standard follows the a) Verification by Testing.  Assemblies, verified by design
philosophy of IEC 60947 series i.e. IEC b) Verification by Calculation/ rule from a similar tested
61439-1 is ‘General Rules’ standard to Measurement. assembly, should comply with
be referred to by subsidiary product parts c) Verification by Design rules. the following:
of IEC 61439 series. (Refer Table 1) The requirements regarding short circuit  Functional units shall
The IEC 60439 standards were performance, temperature rise, dielectric belong to the same group
ambiguous about how to assess properties and rated diversity factor as functional unit selected
compliance of partially type tested have been covered in more detail. for test.
assemblies. As a result manufacturers  Same type of construction.
and testing bodies often treated Verification of Requirements:
 Same or increased overall
partially type-tested assemblies Table 2 gives the characteristics to be
dimensions.
 Same or reduced internal
Table 1: Parts of IEC 61439 series separation.
IEC 61439-1 General rules  Same or reduced power
losses in the same section
IEC 61439-2 Power switchgear and control gear ASSEMBLIES of assembly.
(Replacing IEC 60439-1)  Same or reduced number
IEC 61439-3 Distribution boards (to supersede IEC 60439-3) of outgoing circuit for every
section.
IEC 61439-4 ASSEMBLIES for construction sites  Rated diversity factor (RDF) is
(to supersede IEC 60439-4) elaborated in more details with
IEC 61439-5 ASSEMBLIES for power distribution incoming and outgoing circuit
(to supersede IEC 60439-5) diagrams.
 The average ambient tempe-
IEC 61439-6 Busbar trunking systems rature for the duration of test
(to supersede IEC 60439-2) shall not exceed 35 C.
o
2. Short circuit withstand test  Length of unprotected live are reduced corresponding to rated
Verification of assembly by design conductors of each non- insulation voltage (Refer Table 3)
rules is permitted, if; protected circuit 4. Impulse voltage withstand test
 Following requirements are same  Verification is mandatory either
 Following requirements are greater
as that of reference design
than or equal to reference design by test or by design rules.
 Conductor material and its
 Cross-sectional dimensions of properties  Test is not required when
the busbars and connections clearances in the assembly are
 Enclosure design, type and 1.5 times the specified value
 Spacing of the busbars and dimensions
connections in Table - 4.
 Compartment mechanical 5. Degree of protection
 SCPDs are equivalent, i.e. of design and dimensions
the same make with the same  The IPX1 to IPX6 tests on an
If all the above requirements are
or better I 2 t based on the satisfied, then further verification by assembly are deemed to be
device manufacturer’s data calculation or actual testing is not failure if water comes into
contact with electrical
 Following requirements are less required.
equipment housed within the
than or equal to reference design 3. Power frequency withstand enclosure.
 Short circuit rating of each circuit voltage
 Requirements for ‘empty
 Busbar supports spacing The values of dielectric test voltage enclosures for assemblies (IEC
62208)’ have been incorporated
Table-2 in the standard.
No. Characteristic Verification options 6. Mechanical operation
 Rated numbers of operating
Testing Calculation Design
cycles have been increased
rules
from 50 to 200.
1 Degree of protection of enclosures    7. Protection provided by barriers
2 Clearance and creepage distances    The protection provided by horizontal
3 Effectiveness of assembly    top surfaces of easily accessible
(protective circuit) for external faults barriers is changed from IPXXB (the
protection of person against access to
4 Incorporation of switching    hazardous parts with finger) to IPXXD
devices and components (the protection of person against
5 Internal electrical circuits    access to hazardous parts with wire).
and connections 8. Cross-section area of neutral
6 Terminals for external conductors     100% - for phase cross section
area upto 16 mm2
7 Impulse withstand voltage   
 50 % - for phase cross section
8 Temperature rise limits    area above 16 mm2, with a
minimum of 16 mm2
9 Short-circuit withstand strength   
 For conductor other than
10 Electromagnetic compatibility (EMC)    copper, the cross section
11 Effective continuity between the    should be greater than
exposed conductive parts of the equivalent copper conductor
assembly and the protective circuit 9. Additional Tests in IEC 61439
12 Power frequency withstand voltage     Resistance to corrosion Test
13 Mechanical operation    Purpose:
To ensure that deterioration of
The following characteristics are newly introduced in IEC 61439 metallic component caused by
14 Resistance to corrosion    corrosion shall not impair the
mechanical strength of
15 Thermal stability of enclosure    switchboard.
16 Resistance of insulating material    Procedure:
to heat
The test is carried out on a typical
17 Glow wire test    switchboard enclosure or on a
18 Resistance to UV radiation    representative sample showing the
same constructional details.
19 Lifting     6 cycles of 24 hr each to Damp
20 Mechanical impact test (IK)    Heat Cycling Test according to
o
IEC 60068-2-30 at (40±3) C &
21 Marking    relative humidity of 95%.
Table - 3 Table - 4
Rated insulation voltage (Ui) Dielectric test Dielectric test Rated impulse Minimum
(line to line a.c or d.c) voltage (a.c) r.m.s voltage (d.c) withstand voltage clearance
V V V Uimp (kV) mm
Ui ≤ 60 1000 (1000) 1415
≤ 2.5 1.5
60 < Ui ≤ 300 1500 (2000) 2120
4.0 3.0
300 < Ui ≤ 690 1890 (2500) 2670
6.0 5.5
690 < Ui ≤ 800 2000 (3000) 2830
800 < Ui ≤ 1000 2200 (3500) 3110 8.0 8.0

1000 < Ui ≤ 1500* — 3820 12.0 14.0


Note 1: * For d.c only. Based on inhomogeneous field condition and
Note 2: the values in parentheses are according to IEC 60439-1. pollution degree 3.
 2 cycles of 24 hr each to Salt Procedure: Assessment criteria:
Mist test according to IEC  A ball pressure test apparatus  There is no flame and glowing
60068-2-11 at temperature of is used to verify the suitability
o on the sample or flames/
(35±2) C. of insulating materials. glowing of the sample
Assessment Criteria:  The test shall be carried out extinguish within 30 s.
 The mechanical integrity shall on an insulating material of  The cotton or the paper
not be impaired. minimum 2 mm thickness. underlay doesn’t ignite or burn.
 Doors, hinges, locks, etc. shall  The test shall be made in a  Resistance to UV radiation
work without abnormal effects. heating cabinet at a
temperature as stated below: Purpose:
 Seals shall not damage.
v parts supporting live The UV radiation causes
 There shall be no iron-oxide, o
components – 125 C deterioration of synthetic material
cracking or other deterioration o use for enclosures.
more than that allowed by ISO v other parts – 70 C
4628-3 for degree of rusting  After 1 hr, the sample is Procedure:
Ri1. removed and cooled within 10  UV Test according to ISO
 Verification of Thermal stability s to approx. room temperature 4892 – 2 method A; 1000
by immersion in cold water. cycles of 5 min of watering and
Purpose:
Assessment criteria: 25 min. of dry period with
To check the thermal properties of xenon lamp providing a total
the enclosure  The diameter of the impression
test period of 500 hrs.
caused by the ball shall be
Procedure: measured and shall not exceed  The value of temperature and
 The specimen is kept in a 2 mm. humidity for the test are
o
o
heating chamber at 70 C for 7  Resistance to abnormal heat & (65±3) C and (65±5) %.
days. fire (Glow Wire Test) Assessment criteria:
 After that the sample is kept Purpose:  Adherence of synthetic
at ambient temperature for 4 Glow wire test checks the material (according to ISO
days. capability of insulation material to 2409) shall have minimum 50%
Assessment criteria: handle thermal stresses produced retention.
by sources of heat or ignition.  Sample shall not show cracks
 The sample shall show no
cracks nor shall the material Procedure: or deterioration visible to
become sticky or greasy  Sample: Thinnest wall normal or corrected vision
thickness of the completed without any additional
 Sample is pressed with the
application. magnification.
forefinger wrapped in a dry cloth
with a force of 5 N; no traces 
o
Pre-treatment: 24 hours at 23 C  This test is not required if
of cloth shall remain on the at 50% RH. synthetic material supplier
sample. demonstrates that materials of
 Temperatures of glow wire: same thickness or thinner
 Verification of resistance of 550, 650, 750, 850 or 960 comply with this requirement.
insulating materials to heat degrees C (depending on the
Purpose: relevant specification). NOTE: This test is applicable only for
enclosures and external parts of
To ensure the properties of  Force: 1 N ASSEMBLIES intended to be installed
insulating material to normal heat  Contact time: 30 s outdoors.
 Lifting:
Relation between IK code & Impact energy.
Purpose:
IK IK IK IK IK IK IK IK IK IK IK IK
To ensure that there should be no
code 00 01 02 03 04 05 06 07 08 09 10
damage to the panel during
transportation & installation. Impact * 0.14 0.2 0.35 0.5 0.7 1 2 5 10 20
Procedure: Energy
J
 The test is carried out on a
sample having weight 1.25 The degree of protection provided  The test is made by rubbing
times its maximum shipping by an enclosure against impacts the marking by hand for 15 s
weight. is indicated by the letters IK with a piece of cloth soaked in
followed by two digits depending water and then for 15 s with a
 From a standstill position, the on its ability to withstand the piece of cloth soaked with
ASSEMBLY shall be raised impact (as per IEC 62262). petroleum spirit.
smoothly without jerking in a
vertical plane to a height of Procedure: Assessment criteria:
(1±0.1) m and lowered in the  Number of impacts on each  After the test the marking shall
same manner to a standstill exposed face shall be five be legible to normal or
position. This test is repeated unless otherwise specified in corrected vision without
a further two times. relevant product standard. additional magnification.
 After this the ASSEMBLY is
 The impacts shall be evenly Validity of certificates as per
raised up and suspended for
distributed on the faces of the
30 min at a height of (1±0.1) IEC 60439:
enclosure under test.
m without any movement.
 Following this test the  At the surrounding of any point Where tests on the ASSEMBLY have
ASSEMBLY shall be raised of enclosure, not more than been conducted in accordance with the
smoothly without jerking from three impacts shall be applied. IEC 60439 series, prior to the
a standstill position to a height publication of relevant product standard
Assessment Criteria:
of (1±0.1) m and moved in the IEC 61439 series, and the test
(10±0.5) m horizontally, then  Structural integrity shall be results fulfill the requirements of the
lowered to a standstill position. maintained. relevant part of IEC 61439, the
verification of these requirements need
 This sequence shall be carried  Degree of protection (IP) shall not be repeated.
out three times at uniform be unaffected.
speed, each sequence being  Functionality of electrical Conclusion:
carried out within 1 min. products shall not be
hampered. The 4th edition of IEC 60439-1 was
Assessment criteria:
published in 1999 with a subsequent
 During the test, with the test NOTE: Mechanical Impact test is not amendment in 2004. This standard did
weights in place, the applicable to low voltage power not mandate compliance to stringent
ASSEMBLY shall show no switchgear and controlgear (PSC) safety requirements (such as impulse
deflections and after the test assemblies. withstand and resistance to abnormal
show no cracks or permanent heat and fire i.e. glow wire) which are
distortions visible to normal or  Marking: present in other LV product standards.
corrected vision without
additional magnification, which Purpose: In the new standard (IEC 61439-1)
could impair any of its To ensure that the markings are these safety requirements have been
characteristics. legible. included in addition to others pertaining
to satisfactory performance under
 Mechanical Impact Test Procedure: applicable environmental conditions.
Purpose:  Marking made by moulding, Hence, with these additions IEC 61439
This test measures resistance of pressing, engraving or similar series becomes the most updated
an enclosure towards external shall not be submitted to the document from a technological
Mechanical Impact. following test. perspective.

For further details on this subject, please contact:


Electrical & Automation Operating Company, Larsen & Toubro Limited, Saki-Vihar Road, P.O. Box 8901, Powai, Mumbai 400 072
Tel: +91-22-6705 1748/2857  Fax: 022-6705 1024  E-mail: ese-cmt@lntebg.com

Printed by Printania Offset Pvt. Ltd.,D 20/21, Shalimar Industrial Estate, Matunga (East), Mumbai 400 019.
Tel: 2407 7996/ 8866/4540 Fax : 2402 4703 Email: pds6@rediffmail.com The views expressed in this magazine are
ABCI not necessarily those of the management of Larsen & Toubro Limited. The contents of this magazine should not be
reproducted without the written permission of the Editor. Not for sale-only for circulation among the customers.
Member Editorial Coordinators : Mahendra Gehlot, Swathi Rangarajan, Hamid Shah

You might also like