Professional Documents
Culture Documents
Introduction: differently. One of the main features verified and options available for
of IEC 61439-1 is that the verification.
IEC 60439, the standard for low-voltage discrimination between Type Tested
switchgear and controlgear assemblies, Assemblies (TTA) and Partially Type Salient features of IEC 61439
was under restructuring from the last Tested Assemblies (PTTA) has been
decade. The new series of IEC 61439 1. Verification of temperature rise
eliminated by the verification approach.
standards were published in January For multiple compartment
2009. This standard has brought The three different but equivalent types assembly, verification by
considerable clarity in technical of verification methods are introduced calculation can be done up to
interpretation. and these are; rated current of 1600 A only.
The new standard follows the a) Verification by Testing. Assemblies, verified by design
philosophy of IEC 60947 series i.e. IEC b) Verification by Calculation/ rule from a similar tested
61439-1 is ‘General Rules’ standard to Measurement. assembly, should comply with
be referred to by subsidiary product parts c) Verification by Design rules. the following:
of IEC 61439 series. (Refer Table 1) The requirements regarding short circuit Functional units shall
The IEC 60439 standards were performance, temperature rise, dielectric belong to the same group
ambiguous about how to assess properties and rated diversity factor as functional unit selected
compliance of partially type tested have been covered in more detail. for test.
assemblies. As a result manufacturers Same type of construction.
and testing bodies often treated Verification of Requirements:
Same or increased overall
partially type-tested assemblies Table 2 gives the characteristics to be
dimensions.
Same or reduced internal
Table 1: Parts of IEC 61439 series separation.
IEC 61439-1 General rules Same or reduced power
losses in the same section
IEC 61439-2 Power switchgear and control gear ASSEMBLIES of assembly.
(Replacing IEC 60439-1) Same or reduced number
IEC 61439-3 Distribution boards (to supersede IEC 60439-3) of outgoing circuit for every
section.
IEC 61439-4 ASSEMBLIES for construction sites Rated diversity factor (RDF) is
(to supersede IEC 60439-4) elaborated in more details with
IEC 61439-5 ASSEMBLIES for power distribution incoming and outgoing circuit
(to supersede IEC 60439-5) diagrams.
The average ambient tempe-
IEC 61439-6 Busbar trunking systems rature for the duration of test
(to supersede IEC 60439-2) shall not exceed 35 C.
o
2. Short circuit withstand test Length of unprotected live are reduced corresponding to rated
Verification of assembly by design conductors of each non- insulation voltage (Refer Table 3)
rules is permitted, if; protected circuit 4. Impulse voltage withstand test
Following requirements are same Verification is mandatory either
Following requirements are greater
as that of reference design
than or equal to reference design by test or by design rules.
Conductor material and its
Cross-sectional dimensions of properties Test is not required when
the busbars and connections clearances in the assembly are
Enclosure design, type and 1.5 times the specified value
Spacing of the busbars and dimensions
connections in Table - 4.
Compartment mechanical 5. Degree of protection
SCPDs are equivalent, i.e. of design and dimensions
the same make with the same The IPX1 to IPX6 tests on an
If all the above requirements are
or better I 2 t based on the satisfied, then further verification by assembly are deemed to be
device manufacturer’s data calculation or actual testing is not failure if water comes into
contact with electrical
Following requirements are less required.
equipment housed within the
than or equal to reference design 3. Power frequency withstand enclosure.
Short circuit rating of each circuit voltage
Requirements for ‘empty
Busbar supports spacing The values of dielectric test voltage enclosures for assemblies (IEC
62208)’ have been incorporated
Table-2 in the standard.
No. Characteristic Verification options 6. Mechanical operation
Rated numbers of operating
Testing Calculation Design
cycles have been increased
rules
from 50 to 200.
1 Degree of protection of enclosures 7. Protection provided by barriers
2 Clearance and creepage distances The protection provided by horizontal
3 Effectiveness of assembly top surfaces of easily accessible
(protective circuit) for external faults barriers is changed from IPXXB (the
protection of person against access to
4 Incorporation of switching hazardous parts with finger) to IPXXD
devices and components (the protection of person against
5 Internal electrical circuits access to hazardous parts with wire).
and connections 8. Cross-section area of neutral
6 Terminals for external conductors 100% - for phase cross section
area upto 16 mm2
7 Impulse withstand voltage
50 % - for phase cross section
8 Temperature rise limits area above 16 mm2, with a
minimum of 16 mm2
9 Short-circuit withstand strength
For conductor other than
10 Electromagnetic compatibility (EMC) copper, the cross section
11 Effective continuity between the should be greater than
exposed conductive parts of the equivalent copper conductor
assembly and the protective circuit 9. Additional Tests in IEC 61439
12 Power frequency withstand voltage Resistance to corrosion Test
13 Mechanical operation Purpose:
To ensure that deterioration of
The following characteristics are newly introduced in IEC 61439 metallic component caused by
14 Resistance to corrosion corrosion shall not impair the
mechanical strength of
15 Thermal stability of enclosure switchboard.
16 Resistance of insulating material Procedure:
to heat
The test is carried out on a typical
17 Glow wire test switchboard enclosure or on a
18 Resistance to UV radiation representative sample showing the
same constructional details.
19 Lifting 6 cycles of 24 hr each to Damp
20 Mechanical impact test (IK) Heat Cycling Test according to
o
IEC 60068-2-30 at (40±3) C &
21 Marking relative humidity of 95%.
Table - 3 Table - 4
Rated insulation voltage (Ui) Dielectric test Dielectric test Rated impulse Minimum
(line to line a.c or d.c) voltage (a.c) r.m.s voltage (d.c) withstand voltage clearance
V V V Uimp (kV) mm
Ui ≤ 60 1000 (1000) 1415
≤ 2.5 1.5
60 < Ui ≤ 300 1500 (2000) 2120
4.0 3.0
300 < Ui ≤ 690 1890 (2500) 2670
6.0 5.5
690 < Ui ≤ 800 2000 (3000) 2830
800 < Ui ≤ 1000 2200 (3500) 3110 8.0 8.0
Printed by Printania Offset Pvt. Ltd.,D 20/21, Shalimar Industrial Estate, Matunga (East), Mumbai 400 019.
Tel: 2407 7996/ 8866/4540 Fax : 2402 4703 Email: pds6@rediffmail.com The views expressed in this magazine are
ABCI not necessarily those of the management of Larsen & Toubro Limited. The contents of this magazine should not be
reproducted without the written permission of the Editor. Not for sale-only for circulation among the customers.
Member Editorial Coordinators : Mahendra Gehlot, Swathi Rangarajan, Hamid Shah