2 PID CONTROL Refer to Basic PID and Advanced PID blocks in the SC100/SC200 Series Function Block List (EM-6460-B) for the following ITEM numbers and explanations.
4.2.1 PROCESS VALUE PV
• Engineering unit range (ITEM 82 thr. 85)
In order to set temperature range to 0.0-1200.0°C for example, set ITEM 82 (upper range) to ‘12000,’ ITEM 83 (lower range) to ‘0,’ ITEM 84 (decimal point position) to ‘1,’ and ITEM 85 (engineering unit) to ‘C.’
• PV connection terminal (ITEM 15)
Used to specify Group and Terminal No. of measured input signal terminal.
4.2.2 SETPOINT VALUE SP
• CAS connection terminal (ITEM 24)
Used to specify Group and Terminal No. of the analog input used for cascade control. If ‘Local’ setting mode (ITEM 29) is specified, the terminal is not needed.
• Setting mode (ITEM 29)
Used to specify whether the setpoint value is controlled only locally (Loc mode) or its setting should be able to be switched between cascade and local control (Cas/Loc mode). When Cas/Loc mode is specified, a sequence control command is used to remotely select between modes.
• C/L switch (Terminal 03, ITEM 30)
Used to switch cascade or local setpoint control. The command is invalid when ITEM 29 is set to the local setting mode. A sequence control command (1: Cascade, 0: Local) can switch it.