External feedback signal is routed to the PID control output (output tracking) when the switch is turned on. When the function is reset, the output transitions smoothly to that by PID control.
• External feedback connection terminal (ITEM 56)
Used to specify Group and Terminal No. of the external feedback signal.
• Output hold SW (Terminal 10, ITEM 58)
The control output tracks the external feedback signal when the switch is turned on. Use the terminal 10 to control it from a sequential control block.
4.2.11 AUTO/MAN SW
• A/M SW (Terminal 11, ITEM 59)
Automatic or manual control is selected by the switch. Use the terminal 11 to control it from a sequential control block.
SC100/200 Series Function Block Application Manual EM-6460-C 20