2 FLOW BATCH CONTROL

■ LOOP CONFIGURATION EXAMPLE: FIXED QUANTITY PREPARATION

flow

LCQ
preparation batch start PBS
valve

batch reset PBS

blowdown
tank
valve

■ BLOCK DIAGRAM

Accumulator
QNT
G31

S1 Y1

Sequence
SEQ
G81
DI 1 DI 2
AI DO

batch start batch reset


PBS PBS
flow
preparation valve

DI 1 and DI 2 are assigned to G30 Internal SW block as an example.

■ OPERATION
• Feeding starts when the start PBS is pressed.
• When the feeding reaches the preset value, the valve is closed and the feed value is reset.
• When the reset PBS is pressed during feeding, the valve is closed and the feed value is reset.

■ CODING LIST ESSENTIALS

GROUP ITEM DATA FUNCTION


81 10 95 Sequential control block
11 130000 ST STEP 00
12 013001 IN DI 1 Start PBS pressed
13 050501 OR DO Hold by feed output
14 043002 NA DI 2 Valve close command when reset command PBS is pressed
15 043111 NA G31 - 11 Valve close command when preset value is reached
16 070501 OT DO Feed output
17 083102 NO G31 - 02 Feed value reset when the valve is closed

Holding DO by DI 1
DI 1 DI 2 G31 - 11 DO

Cancelling holding DO and resetting


DO G31 - 02 accumulated value by DI 2

SC100/200 Series Function Block Application Manual EM-6460-C 84