Louvre systems are popular with Aesthetically pleasing. Colt louvre Besides aluminium and stainless steel
designers for many applications in systems have a distinctive sharp louvre profiles, there are all manner of glass,
industrial and commercial buildings. profile. textile, wood, terracotta clay and
Their purpose can be to control light translucent acrylic louvres available
entry, to provide ventilation whilst Reduced energy costs. Colt louvre depending upon aesthetic and
maintaining rain defence, to provide systems are highly aerodynamically energetic requirements.
screening, or a combination of these. efficient. This reduced air resistance
They can also be provided simply for allows the plant and the aperture to be There are also a wide range of
aesthetic impact. smaller thereby saving running costs. accessories, including single skin or
insulated blanking panels, acoustic
This brochure describes Colt’s range of Enhanced performance. Colt louvre modules, guards and meshes, doors
screening, ventilation and rain defence systems are both aerodynamically and turrets.
louvre systems, as well as acoustic efficient and have a remarkably high
louvres. resistance to weather. Upgradeable louvre. Colt can upgrade
“live” areas to double or triple bank
Proven performance. All Colt louvre configurations at a later stage than the
systems have been tested to installation. Please see page 7
EN 13030:2001. for more details.
2
COLT LOUVRE SYSTEMS
3
Technical Standards
Specifying louvre is always a There has been a problem for many years Site location and exposure
compromise, and requires some in quantifying the performance of louvre Severity of local (site) weather conditions
judgement to take into account the systems due to the competing test Location and exposure of louvres on
particular needs of each application. At standards and lack of application guidance building
one end of the scale for example a car for designers. Airflow rate and direction through louvre
park may require maximum ventilation Maximum acceptable pressure drop
but little protection from rain penetration. The European Standard EN 13030:2001 Degree and depth of water penetration
Alternatively, a plant room containing “Ventilation for buildings – Terminals – acceptable
special machinery or electrical equipment Performance testing of louvres subjected Special solutions for sloping applications
may still need high levels of ventilation to simulated rain” helps by providing a
but with maximum protection from water useful classification method. However, EN 13030:2001 AND EQUIVALENT
entry. the responsibility for recommending STANDARDS
classifications for particular applications
The ideal design solution is to produce a still remains with the designer or specifier. British manufacturers of louvre systems in
louvre system that offers the best RAIN conjunction with HEVAC and BSRIA
DEFENCE and AERODYNAMIC This guide is therefore intended to assist developed a test and classification method
PERFORMANCE. Unfortunately this designers and specifiers to select the most to help designers differentiate between
seems to be unachievable. But nothing appropriate louvre performance alternative louvre systems to suit specific
matches the overall performance classification to suit each specific applications. The HEVAC standard formed
standards set by the Colt Universal application. the basis for the European standard EN
Louvre range. 13030, which is technically identical.
To help put the performance classifications into perspective the table above shows how “effectiveness” relates to actual A high coefficient means low resistance and high airflow
rain entry under standard test conditions, which are representative of bad Northern European weather.The effectiveness performance.
classification should be specified for the design air inlet velocity through the louvre since it is velocity dependent.
4
APPLICATIONS
The test environment in the standard, at Recommendations for the selection of rain defence louvres, based on actual design inlet
13m/s (30mph) wind speed and 75mm/h air velocities (for exhaust louvres take a velocity of 0 m/s, representing the worst case
(3 inches/h) for a period of 30 to 60 with the exhaust system switched off):
minutes, is intended to represent bad
Northern European weather conditions. Class A Where excellent rain defence is required and core velocities are above 1m/s and up to 3.5m/s.
Two performance classifications are Solution 3 UL No appreciable water penetration
provided, one for rain defence and one for Class A Where excellent rain defence is required and core velocities are up to 1m/s.
The principles of EN 13030 are replicated 2 UL (Double Bank) Class A2 up to 1.0 m/s
in the USA under the AMCA Standard Class B2 from 1.0m/s to 2.2 m/s
500-L, “Laboratory Methods of Testing Class C2 from 2.2m/s to 3.5 m/s
Louvers for Rating”, and in Australia / ERD (Single Bank) Class A2 at 0m/s
New Zealand in AS/NZS 4740:2000: Class B2 up to 1.5 m/s
“Natural ventilators - Classification and Class C2 from 1.5m/s to 2.3 m/s
performance”. Class D2 from 2.3m/s to 3.5 m/s
Performance specifications should always include the design air inlet (core) velocity.
5
Screening Louvre
The principal objective of screening louvre What building elements do I want to Colt offers two choices of screening
is to obstruct line of sight from normal hide? louvre: a single bank 50mm or 100mm
vantage points by virtue of its design or pitch roll-formed Universal Louvre 1UL,
orientation. Generally each run of louvre Do I want the louvre to blend with the and a single bank 50mm pitch extruded
will have a continuous appearance surrounding building structure? “E” Series ESC Louvre.
unbroken by framing so as to blend in
with the building, but it also can be made Do I want the louvre to be a feature on Universal Louvre - 1UL
to provide contrast so as to provide an my building?
architectural feature.
What effect do I want to create?
Whilst the screening application is
certainly the simplest from a performance What material and finish do I need?
perspective, it is arguably the most
demanding from the viewpoint of Do I need to maximise the light entry
aesthetics and configuration. through the louvre system?
‘E’ Series ESC
Colt Universal Louvre 1UL and “E” Series Should louvre blades be inverted?
ESC Louvre allow maximum airflow with
minimum resistance and are ideal for
screening areas such as plant rooms and
car parks.
6
Experian, Nottingham.
UPGRADEABLE LOUVRE
Establishing the louvre material, colour Alternatively, if the need for high installation, but with the capability to be
and louvre blade arrangement is performance ‘rain defence’ louvre is ‘upgraded’ at any later date, to suit either
relatively straightforward. However accepted, often requiring double or triple final design requirements or later
when it comes to rain defence bank configurations, it may be difficult to modifications and use requirements.
performance this can present problems determine the location and areas of
relating to an appropriate specification, ‘functional’ louvre required at an early This solution allows complete design
particularly at the stage in a project enough stage. This can result in large flexibility at optimum cost.
before full ventilation design areas of double or triple bank louvre
requirements have been established. being installed but subsequently blanked
off. Clearly this can add unnecessary
If a basic louvre is specified, there is a cost.
risk that water penetration may occur
resulting in later problems on a Colt has developed a design solution for
completed project, often with only Universal Louvre. This allows a basic Project Orange/Gerber, Bridgewater.
limited and / or expensive solutions being installation of single bank louvres, which 1UL & 2UL louvre panels for screening
available. can be blanked off as part of an initial and ventilation.
7
Screening Louvre - 1UL
Its consistent appearance and installation There are three standard material options There are a large selection of optional
flexibility makes the Single Bank for the principal components: accessories such as:
Universal Louvre ideal for screening and
cladding applications. Single Bank Aluminium Mitred Corners
Universal Louvre, 1UL (one louvre deep) Mild Steel Blanking Panels (Single Skin or Insulated)
is an aerodynamically shaped louvre and Stainless Steel (50mm pitch only) Special Shapes
has two standard louvre profiles: Acoustic Modules
There are many decorative finish options, Guards (Bird / Insect* / Security)
Shallow (50mm pitch) and including: Doors
Deep (100mm pitch) Turrets
Mill Finish
1UL also has two arrangements: Stoved Polyester Powder Paint * Insect mesh will result in reduced
Anodised airflow and additional resistance.
Horizontal
Vertical Perforated, Stucco and Pre-Coated
Louvres are also available on request for
Both arrangements can be inverted for larger applications.
roof screens, which is important when
wishing to hide items which are high up, The applied finishes can be supplied in
such as the lift plant on high rise two coverage levels:
apartments.
Total (all principal components)
Partial (louvres and frames only)
8
William Harvey Hospital, Ashford.
1UL/SH inverted louvre panels.
A multi purpose louvre system shall be Colt Single Bank Universal Louvre type High airflow properties
provided to achieve minimum resistance 1UL having louvre blades at 50mm pitch
to airflow, with louvre blades to be (shallow section) or 100mm pitch (deep Moderate rain defence properties
aerodynamically shaped with no sharp section). (subject to location and exposure)
edges or protrusions, to ensure the highest
efficiency airflow performance. Construction throughout shall be from Equally suited to applications requiring
high quality corrosion resistant aluminium architectural screening or cladding, Colt
Airflow alloy type 3005 (Colterra) or 3105 to BS Single Bank Louvre is ideal where a high
1470. airflow is required and where rain defence
The following minimum aerodynamic is not of primary importance.
coefficients shall be achieved when the Louvre blades shall not be drilled but shall
louvre panel is tested to EN 13030: be clipped and not rivetted or screwed to
structural supporting mullions. Thus
Air Inlet - 0.43 allowing for expansion and contraction
along their length without distortion and to
Air Extract - 0.38 provide a continuous external appearance
if required.
The above aerodynamic coefficients shall
be established as a result of full scale wind Mullions shall be concealed at 1250mm
tunnel tests. maximum centres and their points of
support along their length shall be in
Rain Defence accordance with prevailing site wind
pressures (as calculated and specified by a
Single bank louvres are ideally applied in structural engineer) in accordance with BS
sheltered locations or where rain 6399 part 2. Manufactured from 2mm
penetration may be acceptable. sheet so that associated support steelwork
is reduced to a minimum.
The louvre system will achieve Class D1
when tested at all velocities to Cill and frames shall contain all peripheral
EN 13030:2001. fixings and be manufactured from 1.6mm
sheet.
9
Screening Louvre - 1UL Performance Data
167
22
88.5
112
22
88.5
100 Pitch
50 Pitch
88.5
12
25
88.5
20
25
95
137 149
192
1.25
1.0
1.1
0.9
0.5
0.6
0.7
0.8
30
Maximum Unsupported MullionLength
1.4
Pressure Drop (pa)
1.3
20
INLET
1.2
10
1.1
1.0 0
3800 3400 3000 2600 2200 1800 1400 1000 600 0 0.5 1.0 1.5 2.0 2.5
3600 3200 2800 2400 2000 1600 1200 800 400
2
Wind Load (N/m ) Face Velocity (m/s)
10
Assembly
Side Frame
Top Frame
Cill
Louvre Blade
(Shallow)
Intermediate
supporting
Mullion
steelwork
External
Corner Internal Corner
0.8
Effectiveness
0.6
0.6
0.2
1 2 3
Inlet Ventilation (m/s)
11
Screening Louvre - ‘E’ Series ESC
The E Series is the latest addition to the Standard material options for the principal There are a large selection of optional
Colt Universal Louvre range. It is an components: accessories such as:
extruded aluminium, Single Bank Louvre
System available in a 75mm pitch Aluminium Mitred Corners
configuration. Blanking Panels (Single Skin or Insulated)
There are many decorative finish options, Special Shapes
‘E’ Series type ESC offers an alternative including: Acoustic Modules
solution to screening and cladding Guards (Bird / Insect* / Security)
applications. Mill Finish Doors
Stoved Polyester Powder Paint Turrets
It is recommended that ‘E’ Series type Anodised
ESC should not be installed in exposed * Insect mesh will result in reduced
locations where rain penetration may not Perforated, Stucco and Pre-Coated airflow and additional resistance.
be acceptable. Louvres are not available, please see
Universal Louvre.
12
PERFORMANCE SPECIFICATION PRODUCT SPECIFICATION
A simple, clean extruded louvre with Colt Single Bank ‘E’ Series Louvre type
sharp, crisp edges to give a continuous ESC having louvre blades at 75mm pitch.
appearance.
Construction throughout shall be from
Airflow high quality corrosion resistant aluminium
alloy.
The following minimum aerodynamic
coefficients shall be achieved when the Louvre blades shall not be drilled but
louvre panels is tested to EN 13030:2001: clipped and not rivetted or screwed to
structural supporting mullions. Thus
Air Inlet - 0.27 allowing for expansion and contraction
along their length without distortion and
Air Extract - 0.26 to provide a continuous external
appearance if required.
The above aerodynamic coefficients shall
be established as a result of full scale Mullions shall be concealed at 1250mm
wind tunnel tests. maximum centres and their points of
support along their length shall be in
Rain Defence accordance with prevailing site wind
pressures (as calculated and specified by a C-Plex,West Bromich.
Single bank louvres should only be structural engineer) in accordance with Trapezoidal 2UL louvre panels.
applied in sheltered locations or where BS 6399 part 2. Manufactured from 2mm
rain penetration may be acceptable. sheet so that associated support steelwork
is reduced to a minimum.
The louvre system will achieve Class D1
when tested at all velocities to Cill and frames shall contain all
EN 13030:2001. peripheral fixings and be manufactured
from 1.6mm sheet.
13
Screening Louvre - ‘E’ Series ESC
95 97
22
45
45
100
45
15
25
75
45
15
140
1.1
0.9
0.7
0.5
1.25
0.8
0.6
1.0
60
Maximum Unsupported MullionLength
1.4
50
Pressure Drop (pa)
1.3 40
INLET
30
1.2
20
1.1
10
1.0 00
3800 3400 3000 2600 2200 1800 1400 1000 600 0.5 1.0 1.5 2.0 2.5
3600 3200 2800 2400 2000 1600 1200 800 400
2
Wind Load (N/m ) Face Velocity (m/s)
14
Assembly
Half Mullion
Internal
Mitre
15
Ventilation & Rain Defence Louvre
The principal objective of ventilation and How much air needs to flow through Colt offer three choices of performance
rain defence louvre is to allow the passage the louvre louvre, a double bank roll formed louvre:
of air, whilst providing a measure of
protection against the rain. It is worth considering that the actual area Universal Louvre - 2UL
of louvre system being installed to meet
If your louvre has a functional role to play, the performance requirements, might result
your selection will need further in more ventilation than is actually needed.
consideration. Some areas may even need to be blanked
off. However, this should not stop you
Specifying performance has not been from clearly specifying your ventilation
helped by conflicting technical requirements.
information given by louvre manufacturers a triple bank roll formed louvre:
which quotes percentage free areas Whether you are specifying a louvre
measured in different ways, namely as system for natural or forced ventilation, Universal Louvre - 3UL
resistance to airflow and aerodynamic you need to know the resistance to airflow
coefficients alternatively. caused by the louvre system for a given
flowrate.
For a true comparison of performance the
aerodynamic coefficient and the degree of How much rain defence is required
rain defence effectiveness are the only
sensible measures. These have been UPGRADEABLE LOUVRE
included as part of the EN 13030 test Please see page 7. and an extruded, 75mm pitch single
standard, which includes a simple bank louvre:
classification system.
‘E’ Series ERD
16
Mass Transit Railway Corporation (MTRC), Hong Kong.
Side vents fitted externally with Colt Universal Louvre
in line with surrounding Colt Louvre panels.
RAIN DISPERSION
AIR FLOW
17
Ventilation & Rain Defence Louvre - 2UL
Double Bank Universal Louvre is ideal for There are three standard material options There are a large selection of optional
applications requiring ventilation with a for the principal components: accessories such as:
good degree of rain defence. Double Bank
Universal Louvre, 2UL (two louvres deep) Aluminium Mitred Corners
and has two front louvre profiles: Mild Steel Blanking Panels (Single Skin or Insulated)
Stainless Steel (50mm pitch only) Special Shapes
Shallow (50mm pitch) Acoustic Modules
Deep (100mm pitch) There are many decorative finish options, Guards (Bird / Insect* / Security)
including: Doors
2UL also has two arrangements: Turrets
Mill Finish
Horizontal and Vertical Stoved Polyester Powder Paint * Insect mesh will result in reduced
Anodised airflow and additional resistance.
Both arrangements can be inverted.
Perforated, Stucco and Pre-Coated louvres
(normally applied to front louvres blades
and frames only) are also available on
request.
18
Piccadilly Station, Manchester.
A combination of single and double bank louvres,
depending on the specific airflow and rain
defence requirements.
A multi purpose louvre system shall be Colt Double Bank Universal Louvre type Good airflow properties
provided to achieve minimum resistance 2UL having louvre blades at 50mm pitch
to airflow, with louvre blades to be (shallow section) or 100mm pitch (deep Good rain defence properties
aerodynamically shaped with no sharp section, front louvre only).
edges or protrusions, to ensure the highest Equally suited to applications requiring
efficiency airflow performance. Construction throughout shall be from architectural screening or cladding with
high quality corrosion resistant aluminium ventilation and a good degree of rain
Airflow alloy type 3005 (Colterra) or 3105 to BS defence.
1470.
The following minimum aerodynamic
coefficients shall be achieved when the Front louvre blades shall not be drilled but
louvre panel is tested to EN 13030:2001: clipped and not rivetted or screwed to
structural supporting mullions allowing
Air Inlet - 0.308 for expansion and contraction along their
Air Extract - 0.25
length without distortion and to provide
a continuous external appearance if
Rain defence
required.
The louvre system will achieve the
Mullions shall be concealed at 1250mm
following weathering classification when
maximum centres and their points of
the louvre panel is tested to EN
13030:2001: support along their length shall be in
accordance with prevailing site wind
Class A2 - up to 1m/s suction velocity pressures (as calculated and specified by a
Class B2 - up to 2.2m/s suction velocity structural engineer) in accordance with BS
Class C2 - up to 3.0m/s suction velocity 6399 part 2. Manufactured from 2mm
Class D2 - up to 3.5m/s suction velocity sheet so that associated support steelwork
is reduced to a minimum.
Piccadilly Station, Manchester.
The louvre system shall be drained
internally through hollow section Cill and frames shall contain all peripheral
vertical mullions which shall discharge fixings and be manufactured from 1.6mm
water onto the cill. sheet.
140
22
88.5
22
88.5
100 Pitch
50 Pitch
88.5
88.5
12
20
25
25
119 175
165 220
1.25
1.0
1.1
0.9
0.5
0.6
0.7
0.8
60
Maximum Unsupported MullionLength
2.2
50
Pressure Drop (pa)
2.1
40
2.0 INLET
30
1.9
20
1.8 10
1.7 0
3800 3400 3000 2600 2200 1800 1400 1000 600 0 0.5 1.0 1.5 2.0 2.5
3600 3200 2800 2400 2000 1600 1200 800 400
Wind Load (N/m 2 ) Face Velocity (m/s)
20
Assembly
Top Frame
Secondary
Steel
Support
Cill
External
Corner
Front Louvre Internal Corner
Mullion
Blade (Shallow)
0.8
Effectiveness
0.6
0.6
0.2
1 2 3
Inlet Ventilation (m/s)
21
Ventilation & Rain Defence Louvre - 3UL
Its consistent appearance and installation There are three standard material options There are a large selection of optional
flexibility makes the Triple Bank for the principal components: accessories such as:
Universal Louvre ideal for screening and
cladding applications requiring ventilation Aluminium Mitred Corners
with maximum rain defence. Triple Bank Mild Steel and Blanking Panels (Single Skin or Insulated)
Universal Louvre, 3UL (three louvres Stainless Steel (50mm pitch only) Special Shapes
deep) has two front louvre profiles: Acoustic Modules
There are many decorative finish options, Guards (Bird / Insect* / Security)
Shallow (50mm pitch) and including: Doors
Deep (100mm pitch) Front louvre only Turrets
Mill Finish
3UL also has two arrangements: Stoved Polyester Powder Paint and * Insect mesh will result in reduced
Anodised airflow and additional resistance.
Horizontal andVertical
Perforated, Stucco and Pre-Coated louvres
(normally applied to front louvres blades
and frames only) are also available on
request.
Western Harbour Tunnel, Hong Kong. Indoor Recreation Centre, Ma On Shan, Hong Kong.
Triple bank facetted circular louvre installed Universal Louvre for plant room ventilation and
to handle the high air volumes required and to for controllable air inlet for the smoke
provide maximum rain protection even in typhoon extraction system.
conditions.
22
The Light, Leeds.
Single bank 1UL louvre upgraded to 3UL for “live” areas.
A multi purpose louvre system shall be Colt Triple Bank Universal Louvre type Good airflow properties
provided to achieve minimum resistance 3UL having louvre blades at 50mm pitch
to airflow, with louvre blades to be (shallow section) or 100mm pitch (deep Excellent rain defence properties
aerodynamically shaped with no sharp section, front louvres only).
edges or protrusions, to ensure the highest Suited to applications requiring
efficiency airflow performance. Construction throughout shall be from architectural screening or cladding with
high quality corrosion resistant aluminium excellent rain defence protection even
Airflow alloy type 3005 (Colterra) or 3105 to BS with high air intake velocities.
1470.
The following minimum aerodynamic
coefficients shall be achieved when the Front louvre blades shall not be drilled
louvre panel is tested to EN 13030:2001: but clipped and not rivetted or screwed to
structural supporting mullions allowing for
Air Inlet - 0.277 expansion and contraction along their
Air Extract - 0.22 length without distortion and to provide
a continuous external appearance if
Rain defence required.
The louvre system will achieve the Mullions shall be concealed at 1250mm
following weathering classification when maximum centres and their points of
the louvre panel is tested to EN support along their length shall be in
13030:2001: accordance with prevailing site wind
pressures (as calculated and specified by a
Class A3 - up to 3.5m/s suction velocity structural engineer) in accordance with BS
6399 part 2. Manufactured from 2mm
The louvre system shall be drained sheet such that associated support
internally through hollow section steelwork is reduced to a minimum.
vertical mullions which shall discharge
water onto the cill. Cill and frames shall contain all peripheral
fixings and be manufactured from 1.6mm
The louvre system shall be capable of Turbine Surface Technologies, Nottingham, UK.
sheet. Customer comment:
combining both double bank functional
“Colt was the only company capable of
louvre and single bank aesthetic louvre handling a combined package of natural extract
with rear blanking panels on the same ventilation, solar shading louvre and screening
elevation without variation in external & ventilation louvre”.
profile.
23
Ventilation & Rain Defence Louvre - 3UL
88.5
22
195
88.5
22
100 Pitch
50 Pitch
88.5
88.5
20
12
25
25
181 234
220 272
1.1
0.9
MAX
1.25
1.0
0.5
0.6
0.7
0.8
4.2
90
Maximum Unsupported MullionLength
80
3.8
Pressure Drop (pa)
70
60
3.4 INLET
50
40
3.0
30
2.6 20
10
3800 3400 3000 2600 2200 1800 1400 1000 600
2.2 3600 3200 2800 2400 2000 1600 1200 800 400 00 0.5 1.0 1.5 2.0 2.5 3.0 3.5
Wind Load (N/m 2 ) Face Velocity (m/s)
24
Assembly
Frame
Mullion
External Inner Louvre
Corner
Mullion Drain Outlet
0.6
0.6
0.2
1 2 3
Inlet Ventilation (m/s)
25
Ventilation & Rain Defence Louvre - ‘E’ Series ERD
SINGLE BANK ‘E’ SERIES ERD LOUVRE FINISHING OPTIONS OPTIONAL EXTRAS
‘E’ Series type ERD is an extruded Standard material for all principal There are a large selection of optional
aluminium, single bank louvre system components: accessories such as:
available in a 75mm pitch configuration.
Aluminium Mitred Corners
‘E’ Series type ERD offers a competitive Blanking Panels (Single Skin or Insulated)
solution to screening and cladding There are many decorative finish options, Special Shapes
applications which require a good degree including: Acoustic Modules
of rain defence. Guards (Bird / Insect* / Security)
Mill Finish Doors
Stoved Polyester Powder Paint Turrets
Anodised
* Insect mesh will result in reduced
Perforated, Stucco and Pre-Coated louvres airflow and additional resistance.
are not available, please see Universal
Louvre.
26
National Physical Laboratory,Teddington.
1UL/SH panels with upgradeable
2UL/SH panel sections.
A simple, clean extruded louvre with Colt Single Bank ‘E’ Series Louvre type
sharp, crisp edges to give a continuous ERD having louvre blades at 75mm pitch,
appearance. shallow section only.
The louvre system will achieve the Mullions shall be concealed at 1250mm
following weathering classification when maximum centres and their points of
the louvre panel is tested to EN support along their length shall be in
13030:2001: accordance with prevailing site wind
pressures (as calculated and specified by a
Class A2 - up to 0m/s suction velocity structural engineer) in accordance with BS
Class B2 - up to 1.5m/s suction velocity 6399 part 2. Manufactured from 2mm
Class C2 - up to 2.0m/s suction velocity sheet such that associated support
Class D2 - up to 3.5m/s suction velocity steelwork is reduced to a minimum.
27
Ventilation & Rain Defence - ‘E’ Series ERD
124
153
123
45
45
45
15
75
45
15
178
1.1
0.9
0.7
0.5
1.25
0.8
0.6
1.0
60
Maximum Unsupported MullionLength
1.4
50
Pressure Drop (pa)
1.3 40
INLET
1.2 30
20
1.1
10
1.0
3800 3400 3000 2600 2200 1800 1400 1000 600 00 0.5 1.0 1.5 2.0 2.5
3600 3200 2800 2400 2000 1600 1200 800 400
Wind Load (N/m 2 ) Face Velocity (m/s)
28
Wales Millenium Centre, Cardiff. Eastbourne Terrace, London. Burj Al Arab, Jumeirah Beach, Dubai.
Addenbrookes Car Park , Cambridge. Evelina’s Childrens’ Hospital, London.
Bexley Business Academy, Bexley. Crawley College, Crawley.
29
Acoustic Louvre
As part of the Colt Universal Louvre There are two acoustic louvre models: Type R
range, Colt can provide acoustic louvre
panels for mounting behind the louvre. Type R
Infill
Dimension ‘X’*
Acoustic Performance Aerodynamic Performance
15
Type R Static Pressure Drop (Pa) 300 Type R
Transmission Loss dB
200
10
Type LP
Type LP
100
5
ACOUSTIC PERFORMANCE
Octave Band Centre 1 2 3 4 5 6 7 8
Frequency, Hz 63 125 250 500 1k 2k 4k 8k
Model R 5 7 11 12 13 14 12 9
Model LP 4 5 8 9 12 9 7 8
AERODYNAMIC PERFORMANCE
Aerodynamic Coefficient
Acoustic Louvre Model Pressure Loss ( )
(cv)
DIMENSIONS
Vertical section through Colt ‘E’ Series ESC 75
Acoustic Louvre Model Module Width (mm) Module Height (mm)
pitch louvre panel with acoustic module into
brickwork opening.
Model R 610, 914 or 1219 305 to 3653 in 305mm increments
* Dimension ‘X’ is a minimum of 300mm or Model LP 610, 914 or 1219 356 to 3556 in 356mm increments
greater depending on the acoustic
performance requirements.
31
TERMINOLOGY COLT SERVICE
Weather Louvre Measured Free Area Part of the Colt Group of companies, Colt
Service offers a comprehensive range of
A device intended to allow the passage A term used to indicate the open area maintenance packages incorporating
of inlet or exhaust air while minimising between frame members with the the maintenance and repair of all building
the ingress of rain (HEVAC). louvre blades removed and used with services equipment including non Colt
the aerodynamic co-efficient (Cv) to products.
Acoustic Louvre calculate the aerodynamic free area and
thus the pressure drop through a louvre. Colt Service provide a 24 hour, 365 day
Specially designed louvres to reduce This is now sometimes referred to as emergency cover as standard.
the transmission of noise to or from a the “core area”.
building or enclosure and may be used MAINTENANCE
in conjunction with other weather Aerodynamic Area
louvres (HEVAC). Colt Louvre Systems are designed to be
The product of measured free area and virtually maintenance free, although
Free Area the aerodynamic coefficient. Equal to regular cleaning of the louvres with a mild
the total area of a theoretically perfect detergent is recommended. For obvious
The minimum area through which air can opening. This value is used for the reasons, abrasive cleaning agents and wire
pass. Determined by multiplying the sum calculation of the pressure drop. brushes must not be used.
of the minimum distance between
“Colt” and the Colt logo are registered trademarks of Colt International
“People feel better in Colt conditions” Architectural Solutions Colt International Limited
New Lane Havant
terna
In t Climate Control Hampshire PO9 2LY
io
nal
3
0
9