You are on page 1of 2

VOLTAGE DROP OF LIGHTING SYSTEM-FUTABA VN PHASE-3 PROJECT

QUATITY LIGHT VOLTAGE


NO. CIRCUIT NO. AREA LENGTH (m) CURENT(A) CABLE SIZE STANDARD REMARK
FL20Wx2 FL20Wx1 DROP e(V)

LIGHTING IN FACTORY

1 FDB-1/1 OFFICE 38 7 20 9.545 3.5 1.94 e<4.4 (2%) OK

2 FDB-1/2 OFFICE 32 8 11 8.28 3.5 0.93 e<4.4 (2%) OK

3 FDB-1/3 PRODUCTION 27 0 44 6.21 3.5 2.78 e<4.4 (2%) OK

4 FDB-1/4 PRODUCTION 23 0 56 5.29 3.5 3.01 e<4.4 (2%) OK

5 FDB-1/5 PRODUCTION 28 0 56 6.44 3.5 3.67 e<4.4 (2%) OK

6 FDB-1/6 PRODUCTION 24 0 68 5.52 3.5 3.82 e<4.4 (2%) OK

7 FDB-1/7 PRODUCTION 27 0 68 6.21 3.5 4.30 e<4.4 (2%) OK

8 FDB-1/8 PRODUCTION 23 0 80 5.29 3.5 4.30 e<4.4 (2%) OK

9 FDB-1/9 PRODUCTION 27 0 80 6.21 5.5 3.22 e<4.4 (2%) OK

10 FDB-1/10 PRODUCTION 23 0 92 5.29 5.5 3.15 e<4.4 (2%) OK

11 FDB-1/11 PRODUCTION 20 0 92 4.6 3.5 4.30 e<4.4 (2%) OK

12 FDB-1/12 PRODUCTION 17 0 104 3.91 3.5 4.14 e<4.4 (2%) OK

13 FDB-1/13 PRODUCTION 14 0 104 3.22 3.5 3.41 e<4.4 (2%) OK

14 FDB-1/14 PRODUCTION 12 0 116 2.76 3.5 3.26 e<4.4 (2%) OK

15 FDB-1/15 PRODUCTION 9 0 15 2.07 3.5 0.32 e<4.4 (2%) OK

16 FDB-1/16 OFFICE 2 0 28 0.46 3.5 0.13 e<4.4 (2%) OK


EXTERIOR LIGHTING

17 LG-2/1 152 7.95 5.5 7.82 e<8.8 (4%) OK

18 LG-2/2 165 7.95 5.5 8.49 e<8.8 (4%) OK

LOAD 3 PHASE

19 LG-2/3 165 3.42 3.5 2.87 e<8.8 (4%) OK