GREE ELECTRIC APPLIANCES,INC.OF ZHUHAI


Service Manual

Table of Contents
Part Ⅰ : Technical Information .......................................................................1
1. Summary ......................................................................................................................1
2. Specifications ..........................................................................................................5
2.1 Specification Sheet...........................................................................................................5
2.2 Capacity Curve in Different Outdoor Temperature .........................................................21
2.3 Cooling and Heating Data Sheet in Rated Frequency ...................................................21
3. Outline Dimension Diagram ......................................................................22
3.1 Indoor Unit ......................................................................................................................22
3.2 Outdoor Unit ...................................................................................................................23
4. Refrigerant System Diagram ....................................................................26
5. Electrical Part.........................................................................................................28
5.1 Wiring Diagram...............................................................................................................28
5.2 PCB Printed Diagram .....................................................................................................37
6. Function and Control ......................................................................................38
6.1 Remote Controller Introduction of YAN1F1 ...................................................................38
6.2 Remote Controller Introduction of YB1FA(MOTO) .........................................................42
6.3 Brief Description of Modes and Functions......................................................................46

Part Ⅱ : Installation and Maintenance .................................................51


7. Notes for Installation and Maintenance..........................................51
8. Installation ................................................................................................................53
8.1 Installation Dimension Diagram......................................................................................53
8.2 Installation Parts-Checking ............................................................................................55
8.3 Selection of Installation Location ....................................................................................55
8.4 Electric Connection Requirement ...................................................................................55
8.5 Installation of Indoor Unit................................................................................................55
8.6 Installation of Outdoor Unit .............................................................................................58
8.7 Vacuum Pumping and Leak Detection ...........................................................................59
8.8 Check after Installation and Test Operation ...................................................................59
9. Maintenance ............................................................................................................61
9.1 Error Code ......................................................................................................................61
9.2 Procedure of Troubleshooting ........................................................................................63
9.3 Maintenance Method for Normal Malfunction.................................................................70

Table of Contents
Service Manual

10. Exploded View and Parts List ..............................................................72


10.1 Indoor Unit ....................................................................................................................72
10.2 Outdoor Unit .................................................................................................................90
11. Removal Procedure ..................................................................................... 111
11.1 Removal Procedure of Indoor Unit ............................................................................. 111
11.2 Removal Procedure of Outdoor Unit ..........................................................................121

Appendix: ......................................................................................................................139
Appendix 1: Reference Sheet of Celsius and Fahrenheit ..................................................139
Appendix 2: Configuration of Connection Pipe...................................................................139
Appendix 3: Pipe Expanding Method .................................................................................140
Appendix 4: List of Resistance for Temperature Sensor ....................................................141

Table of Contents
Service Manual

Part Ⅰ : Technical Information


1. Summary
Indoor Unit:

A1 Panel

A6 Panel

B6 Panel

C2 Panel

B4 Panel

C6 Panel

Technical Information 1
Service Manual

Outdoor Unit:

GWC09QB-K3NNA1B/O
GWC09QB-K3NNA1J/O

GWH09QB-K3NNA1B/O
GWH09QB-K3NNA1J/O
GWC12QC-K3NNA1B/O
GWC12QC-K3NNA1G/O
GWH12QC-K3NNA1B/O
GWH12QC-K3NNA1D/O

GWC18QD-K3NNA1B/O
GWC18QD-K3NNA1F/O

GWH18QD-K3NNA1B/O
GWC24QE-K3NNA1B/O
GWH24QE-K3NNA1B/O

2 Technical Information
Service Manual

GWH18QD-K3NNA1D/O

GWH24QE-K3NNA1E/O
GWC24QE-K3NNA1E/O

Remote Controller:

YAN1F1

YB1FA(MOTO)

X-FAN I

Technical Information 3
Service Manual

Model List:

Indoor product Outdoor Remote


No Model Product code Indoor model Outdoor model
code product code Controller
1 GWC09QB-K3NNA1B CA419006000 GWC09QB-K3NNA1B/I CA419N06000 GWC09QB-K3NNA1B/O CA419W06000
2 GWH09QB-K3NNA1B CA419006100 GWH09QB-K3NNA1B/I CA419N06100
3 GWH09QB-K3NNB6B CA435001400 GWH09QB-K3NNB6B/I CA435N01400 GWH09QB-K3NNA1B/O CA419W06100
4 GWH09QB-K3NNC6B CA443001000 GWH09QB-K3NNC6B/I CA443N01000
5 GWC09QB-K3NNA1J CA419015100 GWC09QB-K3NNA1J/I CA419N15100 GWC09QB-K3NNA1J/O CA419W15100
6 GWH09QB-K3NNA1J CA419015000 GWH09QB-K3NNA1J/I CA419N15000 GWH09QB-K3NNA1J/O CA419W15000
YAN1F1
7 GWC12QC-K3NNA1B CA419006400 GWC12QC-K3NNA1B/I CA419N06400
8 GWC12QC-K3NNA6B CA427005600 GWC12QC-K3NNA6B/I CA427N05600 GWC12QC-K3NNA1B/O CA419W06400
9 GWC12QC-K3NNC2B CA439003000 GWC12QC-K3NNC2B/I CA439N03000
10 GWH12QC-K3NNA1B CA419006500 GWH12QC-K3NNA1B/I CA419N06500
11 GWH12QC-K3NNB6B CA435001300 GWH12QC-K3NNB6B/I CA435N01300 GWH12QC-K3NNA1B/O CA419W06500
12 GWH12QC-K3NNC6B CA443001300 GWH12QC-K3NNC6B/I CA443N01300
13 GWC12QC-K3NNA1G CA419015300 GWC12QC-K3NNA1G/I CA419N15300 GWC12QC-K3NNA1G/O CA419W15300 YB1FA
14 GWH12QC-K3NNA1D CA419015200 GWH12QC-K3NNA1D/I CA419N15200 GWH12QC-K3NNA1D/O CA419W15200 (MOTO)
15 GWC18QD-K3NNA1B CA419006600 GWC18QD-K3NNA1B/I CA419N06600 GWC18QD-K3NNA1B/O CA419W06600
16 GWH18QD-K3NNA1B CA419006700 GWH18QD-K3NNA1B/I CA419N06700
17 GWH18QD-K3NNB6B CA435001200 GWH18QD-K3NNB6B/I CA435N01200 GWH18QD-K3NNA1B/O CA419W06700
18 GWH18QD-K3NNC6B CA443001200 GWH18QD-K3NNC6B/I CA443N01200
19 GWC18QD-K3NNA1F CA419014000 GWC18QD-K3NNA1F/I CA419N14000 GWC18QD-K3NNA1F/O CA419W14000
20 GWH18QD-K3NNA1D CA419013900 GWH18QD-K3NNA1D/I CA419N13900 GWH18QD-K3NNA1D/O CA419W13900
21 GWC24QE-K3NNA1B CA419005600 GWC24QE-K3NNA1B/I CA419N05600
YAN1F1
22 GWC24QE-K3NNA1B CA419005601 GWC24QE-K3NNA1B/I CA419N05601
23 GWC24QE-K3NNA6B CA427006100 GWC24QE-K3NNA6B/I CA427N06100 GWC24QE-K3NNA1B/O CA419W05600
24 GWC24QE-K3NNB4B CA434007000 GWC24QE-K3NNB4B/I CA434N07000
25 GWC24QE-K3NNC2B CA439002500 GWC24QE-K3NNC2B/I CA439N02500
26 GWH24QE-K3NNA1B CA419005500 GWH24QE-K3NNA1B/I CA419N05500
27 GWH24QE-K3NNB6B CA435001500 GWH24QE-K3NNB6B/I CA435N01500 GWH24QE-K3NNA1B/O CA419W05500
28 GWH24QE-K3NNC6C CA443001100 GWH24QE-K3NNC6C/I CA443N01100
YB1FA
29 GWC24QE-K3NNA1E CA419015600 GWC24QE-K3NNA1E/I CA419N15600 GWC24QE-K3NNA1E/O CA419W15600
(MOTO)
30 GWH24QE-K3NNA1E CA419015400 GWH24QE-K3NNA1E/I CA419N15400 GWH24QE-K3NNA1E/O CA419W15400 YAN1F1

4 Technical Information
Service Manual

2. Specifications
2.1 Specification Sheet
1.GWH09QB-K3NNA1B
Model GWC09QB-K3NNA1B 2.GWH09QB-K3NNB6B
3.GWH09QB-K3NNC6B
1.CA419006100 2.CA435001400
Product Code CA419006000
3.CA443001000
Rated Voltage V~ 220-240 220-240
Power
Rated Frequency Hz 50 50
Supply
Phases 1 1
Power Supply Mode Indoor Indoor
Cooling Capacity W 2638 2638
Heating Capacity W / 2800
Cooling Power Input W 865 865
Heating Power Input W / 800
Cooling Power Current A 4.18 4.01
Heating Power Current A / 3.71
Rated Input W 1250 1250
Rated Current A 6.0 6.0
3
Air Flow Volume(SH/H/M/L/SL) m /h 550/490/430/330/- 550/500/445/340/-
Dehumidifying Volume L/h 0.8 0.8
EER W/W 3.05 3.05
COP W/W / 3.5
SEER W/W / /
HSPF W/W / /
2
Application Area m 12-18 12-18
1.GWH09QB-K3NNA1B/I
Model of indoor unit GWC09QB-K3NNA1B/I 2.GWH09QB-K3NNB6B/I
3.GWH09QB-K3NNC6B/I
1.CA419N06100 2.CA435N01400
Indoor Unit Product Code CA419N06000
3.CA443N01000
Fan Type Cross-flow Cross-flow
Diameter Length(DXL) mm Ф98X580 Ф98X580
Fan Motor Cooling Speed(SH/H/M/L/SL) r/min 1300/1200/1050/800/- 1300/1200/1050/800/-
Fan Motor Heating Speed(SH/H/M/L/SL) r/min / 1300/1200/1050/900/-
Output of Fan Motor W 20 20
Fan Motor RLA A 0.15 0.2
Fan Motor Capacitor μF 1 1
Evaporator Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Indoor Unit Pipe Diameter mm Ф5 Ф5
Row-fin Gap mm 2-1.4 2-1.4
Coil Length (LXDXW) mm 578X22.8X266.7 584X22.8X266.7
Swing Motor Model MP24AA MP24AA
Output of Swing Motor W 1.5 1.5
Fuse A 3.15 3.15
Sound Pressure Level (SH/H/M/L/SL) dB (A) 40/37/33/26/- 40/37/33/26/-
Sound Power Level (SH/H/M/L/SL) dB (A) 50/47/43/36/- 50/47/43/36/-
Dimension (WXHXD) mm 790X275X200 790X275X200
Dimension of Carton Box (LXWXH) mm 863X268X352 863X268X352
Dimension of Package (LXWXH) mm 866X271X367 866X271X367
Net Weight kg 8.5 8.5
Gross Weight kg 10.5 10.5

Technical Information 5
Service Manual

Model of Outdoor Unit GWC09QB-K3NNA1B/O GWH09QB-K3NNA1B/O


Outdoor Unit Product Code CA419W06000 CA419W06100
ZHUHAI LANDA ZHUHAI LANDA
Compressor Manufacturer/Trademark
COMPRESSOR CO.,LTD. COMPRESSOR CO.,LTD.
Compressor Model QXA-B102C130 QXA-B102C150
Compressor Oil LB68EP POE(Ze-GLES RB68EP)
Compressor Type Rotary Rotary
L.R.A. A 17 15
Compressor RLA A 3.9 3.9
Compressor Power Input W 850 850
Overload Protector Internal Internal
Throttling Method Capillary Capillary
o
Operation Temp C 16~30 16~30
o
Ambient Temp (Cooling) C 18~43 18~43
o
Ambient Temp (Heating) C / -7~24
Condenser Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Pipe Diameter mm Ф7.94 Ф7
Rows-fin Gap mm 1-1.4 1-1.4
Coil Length (LXDXW) mm 655X19.05X396 730X12.7X495
Fan Motor Speed rpm 950 850
Output of Fan Motor W 20 35
Outdoor Unit Fan Motor RLA A 0.3 0.37
Fan Motor Capacitor μF 1.5 2.5
Air Flow Volume of Outdoor Unit m3/h 1200 1600
Fan Type Axial-flow Axial-flow
Fan Diameter mm Ф320 Ф394.5
Defrosting Method / Automatic Defrosting
Climate Type T1 T1
Isolation I I
Moisture Protection IP24 IP24
Permissible Excessive Operating Pressure for
MPa 4.3 4.3
the Discharge Side
Permissible Excessive Operating Pressure for
MPa 2.5 2.5
the Suction Side
Sound Pressure Level (H/M/L) dB (A) 48/-/- 48/-/-
Sound Power Level (H/M/L) dB (A) 58/-/- 58/-/-
Dimension (WXHXD) mm 720X428X310 776X540X320
Dimension of Carton Box (LXWXH) mm 765X350X475 820X355X580
Dimension of Package (LXWXH) mm 768X353X490 823X358X595
Net Weight kg 26 30
Gross Weight kg 28 32.5
Refrigerant R410A R410A
Refrigerant Charge kg 0.56 0.72
Length m 5 5
Gas Additional Charge g/m 15 20
Outer Diameter Liquid Pipe mm Ф6 Ф6
Connection
Pipe Outer Diameter Gas Pipe mm Ф9.52 Ф9.52
Max Distance Height m 10 10
Max Distance Length m 15 15
Note: The connection pipe applies metric diameter.

The above data is subject to change without notice; please refer to the nameplate of the unit.

6 Technical Information
Service Manual

Model GWC09QB-K3NNA1J GWH09QB-K3NNA1J


Product Code CA419015100 CA419015000
Rated Voltage V~ 220-240 220-240
Power
Rated Frequency Hz 50 50
Supply
Phases 1 1
Power Supply Mode Indoor Indoor
Cooling Capacity W 2650 2650
Heating Capacity W / 2785
Cooling Power Input W 820 820
Heating Power Input W / 763
Cooling Power Current A 3.73 3.73
Heating Power Current A / 3.47
Rated Input W 1250 1250
Rated Current A 5.33 5.23
3
Air Flow Volume(SH/H/M/L/SL) m /h 550/500/450/400/- 550/500/445/340/-
Dehumidifying Volume L/h 0.8 0.8
EER W/W 3.23 3.23
COP W/W / 3.65
SEER W/W / /
HSPF W/W / /
Application Area m2 12-18 12-18
Model of indoor unit GWC09QB-K3NNA1J/I GWH09QB-K3NNA1J/I
Indoor Unit Product Code CA419N15100 CA419N15000
Fan Type Cross-flow Cross-flow
Diameter Length(DXL) mm Ф98X580 Ф98X580
Fan Motor Cooling Speed(SH/H/M/L/SL) r/min 1300/1200/1050/800/- 1300/1200/1050/800/-
Fan Motor Heating Speed(SH/H/M/L/SL) r/min / 1300/1200/1050/900/-
Output of Fan Motor W 20 20
Fan Motor RLA A 0.09 0.09
Fan Motor Capacitor μF 1 1
Evaporator Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Pipe Diameter mm Ф5 Ф5
Indoor Unit Row-fin Gap mm 2-1.4 2-1.4
Coil Length (LXDXW) mm 578X22.8X266.7 578X22.8X266.7
Swing Motor Model MP24AA MP24AA
Output of Swing Motor W 1.5 1.5
Fuse A 3.15 3.15
Sound Pressure Level (SH/H/M/L/SL) dB (A) 39/35/32/25/- 39/35/32/25/-
Sound Power Level (SH/H/M/L/SL) dB (A) 49/45/42/35/- 49/45/42/35/-
Dimension (WXHXD) mm 790X275X200 790X275X200
Dimension of Carton Box (LXWXH) mm 863X268X352 863X268X352
Dimension of Package (LXWXH) mm 866X271X367 866X271X367
Net Weight kg 9 9
Gross Weight kg 11 11

Technical Information 7
Service Manual

Model of Outdoor Unit GWC09QB-K3NNA1J/O GWH09QB-K3NNA1J/O


Outdoor Unit Product Code CA419W15100 CA419W15000
ZHUHAI LANDA ZHUHAI LANDA
Compressor Manufacturer/Trademark
COMPRESSOR CO.,LTD. COMPRESSOR CO.,LTD.
Compressor Model QXA-B098E030 QXA-B098E050
Compressor Oil RB68EP,FCV68D RB68EP,FCV68D
Compressor Type Rotary Rotary
L.R.A. A 18.5 18.5
Compressor RLA A 3.6 3.6
Compressor Power Input W 800 795
Overload Protector Internal Internal
Throttling Method Throttle Throttle
o
Operation Temp C 16~30 16~30
o
Ambient Temp (Cooling) C 18~43 18~43
o
Ambient Temp (Heating) C / -7~24
Condenser Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Pipe Diameter mm Ф7.94 Ф7
Rows-fin Gap mm 1-1.4 1-1.4
Coil Length (LXDXW) mm 655X19.05X396 730X12.7X495
Fan Motor Speed rpm 950 850
Output of Fan Motor W 20 35
Outdoor Unit Fan Motor RLA A 0.25 0.37
Fan Motor Capacitor μF 1.5 2.5
Air Flow Volume of Outdoor Unit m3/h 1200 1600
Fan Type Axial-flow Axial-flow
Fan Diameter mm Ф320 Ф394.5
Defrosting Method / /
Climate Type T1 T1
Isolation I I
Moisture Protection IP24 IP24
Permissible Excessive Operating Pressure for
MPa 4.3 4.3
the Discharge Side
Permissible Excessive Operating Pressure for
MPa 2.5 2.5
the Suction Side
Sound Pressure Level (H/M/L) dB (A) 48/-/- 48/-/-
Sound Power Level (H/M/L) dB (A) 58/-/- 58/-/-
Dimension (WXHXD) mm 720X428X310 776X540X320
Dimension of Carton Box (LXWXH) mm 765X350X475 820X355X580
Dimension of Package (LXWXH) mm 768X353X490 823X358X595
Net Weight kg 25.5 29
Gross Weight kg 27.5 31.5
Refrigerant R410A R410A
Refrigerant Charge kg 0.66 0.76
Length m 5 5
Gas Additional Charge g/m 20 20
Outer Diameter Liquid Pipe mm Ф6 Ф6
Connection
Pipe Outer Diameter Gas Pipe mm Ф9.52 Ф9.52
Max Distance Height m 10 10
Max Distance Length m 15 15
Note: The connection pipe applies metric diameter.

The above data is subject to change without notice; please refer to the nameplate of the unit.

8 Technical Information
Service Manual

1.GWC12QC-K3NNA1B 1.GWH12QC-K3NNA1B
Model 2.GWC12QC-K3NNA6B 2.GWH12QC-K3NNB6B
3.GWC12QC-K3NNC2B 3.GWH12QC-K3NNC6B
1.CA419006400 2.CA427005600 1.CA419006500 2.CA435001300
Product Code
3.CA439003000 3.CA443001300
Rated Voltage V~ 220-240 220-240
Power
Rated Frequency Hz 50 50
Supply
Phases 1 1
Power Supply Mode Indoor Indoor
Cooling Capacity W 3223 3223
Heating Capacity W / 3400
Cooling Power Input W 1070 1057
Heating Power Input W / 958
Cooling Power Current A 5.0 4.9
Heating Power Current A / 4.4
Rated Input W 1500 1500
Rated Current A 8 8
3
Air Flow Volume(SH/H/M/L/SL) m /h 650/540/460/330/- 650/540/460/330/-
Dehumidifying Volume L/h 1.2 1.2
EER W/W 3.01 3.05
COP W/W / 3.55
SEER W/W / /
HSPF W/W / /
2
Application Area m 15-22 15-22
1.GWC12QC-K3NNA1B/I 1.GWH12QC-K3NNA1B/I
Model of indoor unit 2.GWC12QC-K3NNA6B/I 2.GWH12QC-K3NNB6B/I
3.GWC12QC-K3NNC2B/I 3.GWH12QC-K3NNC6B/I
1.CA419N06400 2.CA427N05600 1.CA419N06500 2.CA435N01300
Indoor Unit Product Code
3.CA439N03000 3.CA443N01300
Fan Type Cross-flow Cross-flow
Diameter Length(DXL) mm Ф98X633.5 Ф98X633.5
Fan Motor Cooling Speed(SH/H/M/L/SL) r/min 1300/1100/1000/800/- 1300/1100/1000/800/-
Fan Motor Heating Speed(SH/H/M/L/SL) r/min / 1200/1100/1000/900/-
Output of Fan Motor W 20 20
Fan Motor RLA A 0.32 0.32
Fan Motor Capacitor μF 1.5 1.5
Evaporator Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Indoor Unit Pipe Diameter mm Ф5 Ф5
Row-fin Gap mm 2-1.4 2-1.4
Coil Length (LXDXW) mm 635X22.8X306.3 635X22.8X306.3
Swing Motor Model MP24BA MP24BA
Output of Swing Motor W 1.5 1.5
Fuse A 3.15 3.15
Sound Pressure Level (SH/H/M/L/SL) dB (A) 41/37/34/29/- 41/37/34/29/-
Sound Power Level (SH/H/M/L/SL) dB (A) 50/47/44/39/- 50/47/44/39/-
Dimension (WXHXD) mm 845X289X209 845X289X209
Dimension of Carton Box (LXWXH) mm 918X278X364 918X278X364
Dimension of Package (LXWXH) mm 921X281X379 921X281X379
Net Weight kg 10 10
Gross Weight kg 12 12

Technical Information 9
Service Manual

Model of Outdoor Unit GWC12QC-K3NNA1B/O GWH12QC-K3NNA1B/O


Outdoor Unit Product Code CA419W06400 CA419W06500
ZHUHAI LANDA ZHUHAI LANDA
Compressor Manufacturer/Trademark
COMPRESSOR CO., LTD COMPRESSOR CO., LTD
Compressor Model QXA-B120C150 QXA-B120C150
Compressor Oil RB68EP RB68EP
Compressor Type Rotary Rotary
L.R.A. A 22 22
Compressor RLA A 4.7 4.7
Compressor Power Input W 1020 1020
Overload Protector Internal Internal
Throttling Method Capillary Capillary
o
Operation Temp C 16~30 16~30
o
Ambient Temp (Cooling) C 18~43 18~43
o
Ambient Temp (Heating) C / -7~24
Condenser Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Pipe Diameter mm Ф5 Ф7.94
Rows-fin Gap mm 1-1.3 1-1.4
Coil Length (LXDXW) mm 710X11.4X495 697X19.05X506
Fan Motor Speed rpm 850 850
Output of Fan Motor W 35 35
Outdoor Unit Fan Motor RLA A 0.33 0.33
Fan Motor Capacitor μF 2.5 2.5
Air Flow Volume of Outdoor Unit m3/h 1600 1600
Fan Type Axial-flow Axial-flow
Fan Diameter mm Ф394.5 Ф394.5
Defrosting Method / Automatic Defrosting
Climate Type T1 T1
Isolation I I
Moisture Protection IP24 IP24
Permissible Excessive Operating Pressure for
MPa 4.3 4.3
the Discharge Side
Permissible Excessive Operating Pressure for
MPa 2.5 2.5
the Suction Side
Sound Pressure Level (H/M/L) dB (A) 49/-/- 49/-/-
Sound Power Level (H/M/L) dB (A) 59/-/- 59/-/-
Dimension (WXHXD) mm 776X540X320 776X540X320
Dimension of Carton Box (LXWXH) mm 820X355X580 820X355X580
Dimension of Package (LXWXH) mm 823X358X595 823X358X595
Net Weight kg 27 29.5
Gross Weight kg 29.5 32
Refrigerant R410A R410A
Refrigerant Charge kg 0.6 0.75
Length m 5 5
Gas Additional Charge g/m 15 20
Outer Diameter Liquid Pipe mm Ф6 Ф6
Connection
Pipe Outer Diameter Gas Pipe mm Ф12 Ф12
Max Distance Height m 10 10
Max Distance Length m 20 20
Note: The connection pipe applies metric diameter.

The above data is subject to change without notice; please refer to the nameplate of the unit.

10 Technical Information
Service Manual

Model GWC12QC-K3NNA1G GWH12QC-K3NNA1D


Product Code CA419015300 CA419015200
Rated Voltage V~ 220-240 220-240
Power
Rated Frequency Hz 50 50
Supply
Phases 1 1
Power Supply Mode Indoor Indoor
Cooling Capacity W 3223 3223
Heating Capacity W / 3250
Cooling Power Input W 1001 1001
Heating Power Input W / 867
Cooling Power Current A 4.63 4.64
Heating Power Current A / 4.02
Rated Input W 1500 1500
Rated Current A 8.0 8.0
3
Air Flow Volume(SH/H/M/L/SL) m /h 650/540/460/330/- 650/540/460/330/-
Dehumidifying Volume L/h 1.2 1.2
EER W/W 3.22 3.22
COP W/W / 3.75
SEER W/W / /
HSPF W/W / /
Application Area m2 15-22 15-22
Model of indoor unit GWC12QC-K3NNA1G/I GWH12QC-K3NNA1D/I
Indoor Unit Product Code CA419N15300 CA419N15200
Fan Type Cross-flow Cross-flow
Diameter Length(DXL) mm Ф98X633.5 Ф98X633.5
Fan Motor Cooling Speed(SH/H/M/L/SL) r/min 1300/1100/1000/800/- 1350/1100/1000/800/-
Fan Motor Heating Speed(SH/H/M/L/SL) r/min / 1350/1200/1050/950/-
Output of Fan Motor W 20 20
Fan Motor RLA A 0.32 0.32
Fan Motor Capacitor μF 1.5 1.5
Evaporator Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Pipe Diameter mm Ф5 Ф5
Indoor Unit Row-fin Gap mm 2-1.4 2-1.4
Coil Length (LXDXW) mm 635X22.8X306.3 635X22.8X306.3
Swing Motor Model MP24BA MP24BA
Output of Swing Motor W 1.5 1.5
Fuse A 3.15 3.15
Sound Pressure Level (SH/H/M/L/SL) dB (A) 41/38/34/29/- 41/38/33/29/-
Sound Power Level (SH/H/M/L/SL) dB (A) 51/48/44/39/- 51/45/42/39/-
Dimension (WXHXD) mm 845X289X209 845X289X209
Dimension of Carton Box (LXWXH) mm 918X278X364 918X278X364
Dimension of Package (LXWXH) mm 921X281X379 921X281X379
Net Weight kg 10.5 10.5
Gross Weight kg 12.5 12.5

Technical Information 11
Service Manual

Model of Outdoor Unit GWC12QC-K3NNA1G/O GWH12QC-K3NNA1D/O


Outdoor Unit Product Code CA419W15300 CA419W15200
ZHUHAI LANDA ZHUHAI LANDA
Compressor Manufacturer/Trademark
COMPRESSOR CO., LTD COMPRESSOR CO., LTD
Compressor Model QXA-B117C050 QXA-B117C050
Compressor Oil RB68EP RB68EP
Compressor Type Rotary Rotary
L.R.A. A 21.3 21.3
Compressor RLA A 4.4 4.4
Compressor Power Input W 960 960
Overload Protector Internal Internal
Throttling Method Throttle Throttle
o
Operation Temp C 16~30 16~30
o
Ambient Temp (Cooling) C 18~43 18~43
o
Ambient Temp (Heating) C / -7~24
Condenser Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Pipe Diameter mm Ф5 Ф7.94
Rows-fin Gap mm 1-1.3 1-1.4
Coil Length (LXDXW) mm 710X11.4X495 697X19.05X506
Fan Motor Speed rpm 850 850
Output of Fan Motor W 35 35
Outdoor Unit Fan Motor RLA A 0.33 0.33
Fan Motor Capacitor μF 2.5 2.5
Air Flow Volume of Outdoor Unit m3/h 1600 1600
Fan Type Axial-flow Axial-flow
Fan Diameter mm Ф394.5 Ф394.5
Defrosting Method Automatic Defrosting Automatic Defrosting
Climate Type T1 T1
Isolation I I
Moisture Protection IP24 IP24
Permissible Excessive Operating Pressure for
MPa 4.3 4.3
the Discharge Side
Permissible Excessive Operating Pressure for
MPa 2.5 2.5
the Suction Side
Sound Pressure Level (H/M/L) dB (A) 51/-/- 51/-/-
Sound Power Level (H/M/L) dB (A) 61/-/- 61/-/-
Dimension (WXHXD) mm 776X540X320 776X540X320
Dimension of Carton Box (LXWXH) mm 820X355X580 820X355X580
Dimension of Package (LXWXH) mm 823X358X595 823X358X595
Net Weight kg 27.5 29
Gross Weight kg 30 31.5
Refrigerant R410A R410A
Refrigerant Charge kg 0.54 0.77
Length m 5 5
Gas Additional Charge g/m 15 20
Outer Diameter Liquid Pipe mm Ф6 Ф6
Connection
Pipe Outer Diameter Gas Pipe mm Ф12 Ф12
Max Distance Height m 10 10
Max Distance Length m 20 20
Note: The connection pipe applies metric diameter.

The above data is subject to change without notice; please refer to the nameplate of the unit.

12 Technical Information
Service Manual

1.GWH18QD-K3NNA1B
Model GWC18QD-K3NNA1B 2.GWH18QD-K3NNB6B
3.GWH18QD-K3NNC6B
1.CA419006700 2.CA435001200
Product Code CA419006600
3.CA443001200
Rated Voltage V~ 220-240 220-240
Power
Rated Frequency Hz 50 50
Supply
Phases 1 1
Power Supply Mode Indoor Indoor
Cooling Capacity Btu/h 17400 17500
Heating Capacity Btu/h / 19200
Cooling Power Input W 1670 1698
Heating Power Input W / 1631
Cooling Power Current A 7.75 7.88
Heating Power Current A / 7.56
Rated Input W 2150 2150
Rated Current A 9.97 11.09
Air Flow Volume(SH/H/M/L/SL) m3/h 900/855/825/765/- 850/820/790/730/-
Dehumidifying Volume L/h 1.8 1.8
EER Btu/h.W 10.42 10.31
COP Btu/h.W / 11.77
SEER W/W / /
HSPF W/W / /
2
Application Area m 23-34 23-34
1.GWH18QD-K3NNA1B/I
Model of indoor unit GWC18QD-K3NNA1B/I 2.GWH18QD-K3NNB6B/I
3.GWH18QD-K3NNC6B/I
1.CA419N06700 2.CA435N01200
Indoor Unit Product Code CA419N06600
3.CA443N01200
Fan Type Cross-flow Cross-flow
Diameter Length(DXL) mm Ф106X706 Ф106X706
Fan Motor Cooling Speed(SH/H/M/L/SL) r/min 1350/1200/1100/900/- 1300/1150/1000/850/-
Fan Motor Heating Speed(SH/H/M/L/SL) r/min / 1250/1150/1050/900/-
Output of Fan Motor W 35 35
Fan Motor RLA A 0.35 0.15
Fan Motor Capacitor μF 2.5 2.5
Evaporator Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Indoor Unit Pipe Diameter mm Ф7 Ф7
Row-fin Gap mm 2-1.4 2-1.4
Coil Length (LXDXW) mm 715X25.4X304.8 715X25.4X304.8
Swing Motor Model MP35CJ MP35CJ
Output of Swing Motor W 2.5 2.5
Fuse A 3.15 3.15
Sound Pressure Level (SH/H/M/L/SL) dB (A) 47/43/41/36/- 46/44/41/35/-
Sound Power Level (SH/H/M/L/SL) dB (A) 57/53/51/46/- 56/54/51/45/-
Dimension (WXHXD) mm 970X300X224 970X300X224
Dimension of Carton Box (LXWXH) mm 1038X380X305 1038X380X305
Dimension of Package (LXWXH) mm 1041X383X320 1041X383X320
Net Weight kg 13.5 13.5
Gross Weight kg 16.5 16.5

Technical Information 13
Service Manual

Model of Outdoor Unit GWC18QD-K3NNA1B/O GWH18QD-K3NNA1B/O


Outdoor Unit Product Code CA419W06600 CA419W06700
ZHUHAI LANDA ZHUHAI LANDA
Compressor Manufacturer/Trademark
COMPRESSOR CO.,LTD. COMPRESSOR CO., LTD.
Compressor Model QXA-F20F050 QXA-F20F050
Compressor Oil RB 68EP RB 68EP
Compressor Type Rotary Rotary
L.R.A. A 42 42
Compressor RLA A 7.7 7.7
Compressor Power Input W 1650 1650
Overload Protector Internal(UP3-A6) Internal(UP3-A6)
Throttling Method Capillary Capillary
o
Operation Temp C 16~30 16~30
o
Ambient Temp (Cooling) C 18~43 18~43
o
Ambient Temp (Heating) C / -7~24
Condenser Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Pipe Diameter mm Ф7 Ф7.94
Rows-fin Gap mm 2-1.4 2-1.4
Coil Length (LXDXW) mm 712X38.1X506 809X19X660
Fan Motor Speed rpm 900 780
Output of Fan Motor W 45 68
Outdoor Unit Fan Motor RLA A 0.48 0.75
Fan Motor Capacitor μF 2.5 2.5
3
Air Flow Volume of Outdoor Unit m /h 1800 2800
Fan Type Axial-flow Axial-flow
Fan Diameter mm Ф394.5 Ф460
Defrosting Method / /
Climate Type T1 T1
Isolation I I
Moisture Protection IP24 IP24
Permissible Excessive Operating Pressure for
MPa 4.3 4.3
the Discharge Side
Permissible Excessive Operating Pressure for
MPa 2.5 2.5
the Suction Side
Sound Pressure Level (H/M/L) dB (A) 52/-/- 54/-/-
Sound Power Level (H/M/L) dB (A) 62/-/- 64/-/-
Dimension (WXHXD) mm 848X540X320 913X680X378
Dimension of Carton Box (LXWXH) mm 878X360X580 994X428X725
Dimension of Package (LXWXH) mm 881X363X595 997X431X740
Net Weight kg 42.5 47
Gross Weight kg 45 51
Refrigerant R410A R410A
Refrigerant Charge kg 1.05 1.20
Length m 5 5
Gas Additional Charge g/m 15 15
Outer Diameter Liquid Pipe mm Ф6 Ф6
Connection
Pipe Outer Diameter Gas Pipe mm Ф12 Ф12
Max Distance Height m 10 10
Max Distance Length m 25 25
Note: The connection pipe applies metric diameter.

The above data is subject to change without notice; please refer to the nameplate of the unit.

14 Technical Information
Service Manual

Model GWC18QD-K3NNA1F GWH18QD-K3NNA1D


Product Code CA419014000 CA419013900
Rated Voltage V~ 220-240 220-240
Power
Rated Frequency Hz 50 50
Supply
Phases 1 1
Power Supply Mode Indoor Indoor
Cooling Capacity W 5000 17100
Heating Capacity W / 17500
Cooling Power Input W 1538 1540
Heating Power Input W / 1445
Cooling Power Current A 7.13 7.12
Heating Power Current A / 6.7
Rated Input W 2000 2000
Rated Current A 11.5 11.03
3
Air Flow Volume(SH/H/M/L/SL) m /h 850/780/650/550/- 850/820/790/730/-
Dehumidifying Volume L/h 1.8 1.8
EER W/W 3.25 11.1
COP W/W / 12.11
SEER W/W / /
HSPF W/W / /
Application Area m2 23-34 23-34
Model of indoor unit GWC18QD-K3NNA1F/I GWH18QD-K3NNA1D/I
Indoor Unit Product Code CA419N14000 CA419N13900
Fan Type Cross-flow Cross-flow
Diameter Length(DXL) mm Ф106X706 Ф106X706
Fan Motor Cooling Speed(SH/H/M/L/SL) r/min 1350/1200/1050/900/- 1300/1200/1100/900/-
Fan Motor Heating Speed(SH/H/M/L/SL) r/min / /
Output of Fan Motor W 35 35
Fan Motor RLA A 0.35 0.35
Fan Motor Capacitor μF 2.5 2.5
Evaporator Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Pipe Diameter mm Ф7 Ф7
Indoor Unit Row-fin Gap mm 2-1.4 2-1.4
Coil Length (LXDXW) mm 715X25.4X304.8 715×25.4×304.8
Swing Motor Model MP35CJ MP35CJ
Output of Swing Motor W 2.5 2.5
Fuse A 3.15 3.15
Sound Pressure Level (SH/H/M/L/SL) dB (A) 46/42/38/34/- 45/43/38/34/-
Sound Power Level (SH/H/M/L/SL) dB (A) 56/52/48/44/- 55/53/48/44/-
Dimension (WXHXD) mm 970X300X224 970X300X224
Dimension of Carton Box (LXWXH) mm 1038X380X305 1038X380X305
Dimension of Package (LXWXH) mm 1041X383X320 1041X383X320
Net Weight kg 13.5 13.5
Gross Weight kg 16.5 16.5

Technical Information 15
Service Manual

Model of Outdoor Unit GWC18QD-K3NNA1F/O GWH18QD-K3NNA1D/O


Outdoor Unit Product Code CA419W14000 CA419W13900
ZHUHAI LANDA ZHUHAI LANDA
Compressor Manufacturer/Trademark
COMPRESSOR CO. LTD. COMPRESSOR CO., LTD.
Compressor Model QXA-F184F050 QXA-F184F050
Compressor Oil RB 68EP RB 68EP
Compressor Type Rotary Rotary
L.R.A. A 28 32
Compressor RLA A 6.5 6.5
Compressor Power Input W 1490 1490
Overload Protector Internal(UP3-06C) UP3-06C
Throttling Method Capillary Throttle
o
Operation Temp C 16~30 16~30
o
Ambient Temp (Cooling) C 18~43 18~43
o
Ambient Temp (Heating) C / -7~24
Condenser Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Pipe Diameter mm Ф5 Ф7.94
Rows-fin Gap mm 2-1.4 1-1.4
Coil Length (LXDXW) mm 763X22.8X495.3 809X19X660
Fan Motor Speed rpm 900 780
Output of Fan Motor W 45 68
Outdoor Unit Fan Motor RLA A 0.48 0.75
Fan Motor Capacitor μF 2.5 3
3
Air Flow Volume of Outdoor Unit m /h 1800 2800
Fan Type Axial-flow Axial-flow
Fan Diameter mm Ф394.5 Ф460
Defrosting Method Automatic Defrosting /
Climate Type T1 T1
Isolation I I
Moisture Protection IP24 IP24
Permissible Excessive Operating Pressure for
MPa 4.3 4.3
the Discharge Side
Permissible Excessive Operating Pressure for
MPa 2.5 2.5
the Suction Side
Sound Pressure Level (H/M/L) dB (A) 52/-/- 54/-/-
Sound Power Level (H/M/L) dB (A) 62/-/- 64/-/-
Dimension (WXHXD) mm 848X540X320 913X680X378
Dimension of Carton Box (LXWXH) mm 878X360X580 994X428X725
Dimension of Package (LXWXH) mm 881X363X595 997X431X740
Net Weight kg 39 46.5
Gross Weight kg 41.5 50.5
Refrigerant R410A R410A
Refrigerant Charge kg 0.98 1.2
Length m 5 5
Gas Additional Charge g/m 15 15
Outer Diameter Liquid Pipe mm Ф6 Ф6
Connection
Pipe Outer Diameter Gas Pipe mm Ф12 Ф12
Max Distance Height m 10 10
Max Distance Length m 25 25
Note: The connection pipe applies metric diameter.

The above data is subject to change without notice; please refer to the nameplate of the unit.

16 Technical Information
Service Manual

Model GWH24QE-K3NNA1E GWC24QE-K3NNA1E


Product Code CA419015400 CA419015600
Rated Voltage V~ 220-240 220
Power
Rated Frequency Hz 50 50
Supply
Phases 1 1
Power Supply Mode Indoor Indoor
Cooling Capacity Btu/h 22001 22001
Heating Capacity Btu/h 22690 /
Cooling Power Input W 1885 1950
Heating Power Input W 1750 /
Cooling Power Current A 8.1 8.8
Heating Power Current A 7.5 /
Rated Input W 2400 2300
Rated Current A 12 13
3
Air Flow Volume(SH/H/M/L/SL) m /h 1150/1000/850/750/- 1150/1020/880/750/-
Dehumidifying Volume L/h 2 2
EER W/W 3.42 3.41
COP W/W 3.8 /
SEER W/W / /
HSPF W/W / /
Application Area m2 27-42 27-42
Model of indoor unit GWH24QE-K3NNA1E/I GWC24QE-K3NNA1E/I
Indoor Unit Product Code CA419N15400 CA419N15600
Fan Type Cross-flow Cross-flow
Diameter Length(DXL) mm Ф108X830 Ф108X830
Fan Motor Cooling Speed(SH/H/M/L/SL) r/min 1200/1100/900/800/- 1350/1150/1000/850/-
Fan Motor Heating Speed(SH/H/M/L/SL) r/min 1150/1000/900/850/- /
Output of Fan Motor W 35 35
Fan Motor RLA A 0.35 0.35
Fan Motor Capacitor μF 3 3
Evaporator Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Pipe Diameter mm Ф7 Ф7
Indoor Unit Row-fin Gap mm 2-1.4 2-1.4
Coil Length (LXDXW) mm 845X25.4X342.9 845X25.4X342.9
Swing Motor Model MP35CJ MP35CJ
Output of Swing Motor W 2.5 3
Fuse A 3.15 3.15
Sound Pressure Level (SH/H/M/L/SL) dB (A) 48/45/38/36/- 48/45/38/36/-
Sound Power Level (SH/H/M/L/SL) dB (A) 58/55/48/46/- 58/55/48/46/-
Dimension (WXHXD) mm 1078X325X246 1078X325X246
Dimension of Carton Box (LXWXH) mm 1145X410X335 1145X410X335
Dimension of Package (LXWXH) mm 1148X413X350 1148X413X350
Net Weight kg 17 17
Gross Weight kg 20.5 20.5

Technical Information 17
Service Manual

Model of Outdoor Unit GWH24QE-K3NNA1E/O GWC24QE-K3NNA1E/O


Outdoor Unit Product Code CA419W15400 CA419W15600
ZHUHAI LANDA ZHUHAI LANDA
Compressor Manufacturer/Trademark
COMPRESSOR CO., LTD. COMPRESSOR CO., LTD.
Compressor Model QXA-F232F050 QXA-F232F050
Compressor Oil RB68EP RB68EP
Compressor Type Rotary Rotary
L.R.A. A 44 44
Compressor RLA A 8.4 8
Compressor Power Input W 1930 1930
Overload Protector Internal(UP3-27) UP3-27
Throttling Method Throttle /
o
Operation Temp C 16~30 16~30
o
Ambient Temp (Cooling) C 18~43 18~43
o
Ambient Temp (Heating) C / -7~24
Condenser Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Pipe Diameter mm Ф7 Ф9.52
Rows-fin Gap mm 2-1.4 1-1.4
Coil Length (LXDXW) mm 823X25.4X660 837X22X660
Fan Motor Speed rpm 690 690
Output of Fan Motor W 60 60
Outdoor Unit Fan Motor RLA A 0.58 0.58
Fan Motor Capacitor μF 3.5 3.5
3
Air Flow Volume of Outdoor Unit m /h 3200 3200
Fan Type Axial-flow Axial-flow
Fan Diameter mm Ф520 Ф520
Defrosting Method Automatic Defrosting /
Climate Type T1 T1
Isolation I I
Moisture Protection IP24 IP24
Permissible Excessive Operating Pressure for
MPa 4.3 4.3
the Discharge Side
Permissible Excessive Operating Pressure for
MPa 2.5 2.5
the Suction Side
Sound Pressure Level (H/M/L) dB (A) 55/-/- 55/-/-
Sound Power Level (H/M/L) dB (A) 65/-/- 65/-/-
Dimension (WXHXD) mm 955X700X396 955X700X396
Dimension of Carton Box (LXWXH) mm 1026X455X735 1026X455X735
Dimension of Package (LXWXH) mm 1029X458X750 1029X458X750
Net Weight kg 53.5 49
Gross Weight kg 58 53.5
Refrigerant R410A R410A
Refrigerant Charge kg 1.40 1.40
Length m 5 5
Gas Additional Charge g/m 15 15
Outer Diameter Liquid Pipe mm Ф6 Ф6
Connection
Outer Diameter Gas Pipe mm Ф16 Ф16
Pipe
Max Distance Height m 10 10
Max Distance Length m 25 25
Note: The connection pipe applies metric diameter.

The above data is subject to change without notice; please refer to the nameplate of the unit.

18 Technical Information
Service Manual

1.GWC24QE-K3NNA1B
1.GWH24QE-K3NNA1B
2.GWC24QE-K3NNA6B
Model 2.GWH24QE-K3NNB6B
3.GWC24QE-K3NNB4B
3.GWH24QE-K3NNC6C
4.GWC24QE-K3NNC2B
1.CA419005600 CA419005601
1.CA419005500 2.CA435001500
Product Code 2.CA427006100 3.CA434007000
3.CA443001100
4.CA439002500
Rated Voltage V~ 220-240 220-240
Power
Rated Frequency Hz 50 50
Supply
Phases 1 1
Power Supply Mode Indoor Indoor
Cooling Capacity W 6448 6448
Heating Capacity W / 6500
Cooling Power Input W 2140 2140
Heating Power Input W / 1805
Cooling Power Current A 9.93 9.93
Heating Power Current A / 8.37
Rated Input W 3300 3300
Rated Current A 15.31 15.31
Air Flow Volume(SH/H/M/L/SL) m3/h 1250/1100/960/820/- 1150/1050/860/760/-
Dehumidifying Volume L/h 2 2
EER W/W 3.01 3.01
COP W/W / 3.60
SEER W/W / /
HSPF W/W / /
Application Area m2 27-42 27-42
1.GWC24QE-K3NNA1B/I
1.GWH24QE-K3NNA1B/I
2.GWC24QE-K3NNA6B/I
Model of indoor unit 2.GWH24QE-K3NNB6B/I
3.GWC24QE-K3NNB4B/I
3.GWH24QE-K3NNC6C/I
4.GWC24QE-K3NNC2B/I
1.CA419N05600 CA419N05601 1.CA419N05500
Indoor Unit Product Code 2.CA427N06100 3.CA434N07000 2.CA435N01500
4.CA439N02500 3.CA443N01100
Fan Type Cross-flow Cross-flow
Diameter Length(DXL) mm Φ108X830 Φ108X830
Fan Motor Cooling Speed(SH/H/M/L/SL) r/min 1300/1150/1000/850/- 1200/1100/900/800/-
Fan Motor Heating Speed(SH/H/M/L/SL) r/min / 1150/1100/900/850/-
Output of Fan Motor W 35 35
Fan Motor RLA A 0.35 0.35
Fan Motor Capacitor μF 3 3
Indoor Unit Evaporator Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Pipe Diameter mm Ф7 Φ7
Row-fin Gap mm 2-1.4 2-1.4
Coil Length (LXDXW) mm 850X25.4X381 850X25.4X381
Swing Motor Model MP35CJ MP35CJ
Output of Swing Motor W 2.5 2.5
Fuse A 3.15 3.15
Sound Pressure Level (SH/H/M/L/SL) dB (A) 50/46/42/38/- 50/46/42/38/-
Sound Power Level (SH/H/M/L/SL) dB (A) 60/56/52/48/- 60/56/52/48/-
Dimension (WXHXD) mm 1078X325X246 1078X325X246
Dimension of Carton Box (LXWXH) mm 1145X410X335 1145X410X335
Dimension of Package (LXWXH) mm 1148X413X350 1148X413X350
Net Weight kg 17 17
Gross Weight kg 20.5 20.5

Technical Information 19
Service Manual

Model of Outdoor Unit GWC24QE-K3NNA1B/O GWH24QE-K3NNA1B/O


Outdoor Unit Product Code CA419W05600 CA419W05500
ZHUHAI LANDA COMPRESSOR ZHUHAI LANDA COMPRESSOR
Compressor Manufacturer/Trademark
CO.,LTD CO.,LTD
Compressor Model QXA-F232F050 QXA-F232F050
Compressor Oil RB68EP RB68EP
Compressor Type Rotary Rotary
L.R.A. A 44 44
Compressor RLA A 8.4 8.4
Compressor Power Input W 1930 1930
Overload Protector Internal Internal
Throttling Method Capillary Capillary
o
Operation Temp C 16~30 16~30
o
Ambient Temp (Cooling) C 18~43 18~43
o
Ambient Temp (Heating) C / -7~24
Condenser Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Pipe Diameter mm Ф7.94 Ф7
Rows-fin Gap mm 1-1.4 2-1.4
Coil Length (LXDXW) mm 810X19.05X660 613X38.1X660
Fan Motor Speed rpm 780 780
Output of Fan Motor W 68 68
Outdoor Unit Fan Motor RLA A 0.75 0.75
Fan Motor Capacitor μF 3 3
3
Air Flow Volume of Outdoor Unit m /h 2800 2800
Fan Type Axial-flow Axial-flow
Fan Diameter mm Ф460 Ф460
Defrosting Method / Automatic Defrosting
Climate Type T1 T1
Isolation I I
Moisture Protection IP24 IP24
Permissible Excessive Operating Pressure for
MPa 4.3 4.3
the Discharge Side
Permissible Excessive Operating Pressure for
MPa 2.5 2.5
the Suction Side
Sound Pressure Level (H/M/L) dB (A) 54/-/- 54/-/-
Sound Power Level (H/M/L) dB (A) 64/-/- 64/-/-
Dimension (WXHXD) mm 913X680X378 913X680X378
Dimension of Carton Box (LXWXH) mm 994X428X725 994X428X725
Dimension of Package (LXWXH) mm 997X431X740 997X431X740
Net Weight kg 49 52
Gross Weight kg 53 56
Refrigerant R410A R410A
Refrigerant Charge kg 1.4 1.65
Length m 5 5
Gas Additional Charge g/m 15 50
Outer Diameter Liquid Pipe mm Ф6 Ф6
Connection
Outer Diameter Gas Pipe mm Ф16 Ф16
Pipe
Max Distance Height m 10 10
Max Distance Length m 25 25
Note: The connection pipe applies metric diameter.

The above data is subject to change without notice; please refer to the nameplate of the unit.

20 Technical Information
Service Manual

2.2 Capacity Curve in Different Outdoor Temperature


Cooling: Heating:

110
120
100
100

90
80
Capacity ratio(%)

80
60

Capacity ratio (%)


70
40

60 Condition Condition Heating


20
Indoor:DB27°C WB19°C Indoor:DB20°C
50 Indoor air flow: Super High Indoor air flow: Super High
Pipe length: 5m 0
Pipe length: 5m
40
32 33 34 35 36 37 38 39 40 41 42 43 44 45 -10 -7 -5 0 2 5 7 10 15 24
Outdoor temp.(°C) Outdoor Temp.(°C)

2.3 Cooling and Heating Data Sheet in Rated Frequency


Cooling:

Pressure of gas pipe


Rated cooling condition(°C) Inlet and outlet pipe Fan speed
connecting indoor and Fan speed of
(DB/WB) Model temperature of heat exchanger of outdoor
outdoor unit indoor unit
unit
Indoor Outdoor P (MPa) T1 (°C) T2 (°C)
in:10~14 in:72~83
27/19 35/24 09K 0.9~1.1 Super High High
out:11~14 out:35~40
in:10~14 in:69~74
27/19 35/24 12K 0.8~1.1 Super High High
out:11~14 out:38~45
in:8~11 in:75~85
27/19 35/24 18/24K 0.8~1.0 Super High High
out:11~14 out:37~43

Heating:
Pressure of gas pipe
Rated heating condition(°C) Inlet and outlet pipe Fan speed
connecting indoor and Fan speed of
(DB/WB) Model temperature of heat exchanger of outdoor
outdoor unit indoor unit
unit
Indoor Outdoor P (MPa) T1 (°C) T2 (°C)
in:61~65 in:1~2
20/- 7/6 09K 2.3~2.5 Super High High
out:30~37 out:2~4
in:55~65 in:1~3
20/- 7/6 12K 2.8~3.2 Super High High
out:25~32 out:2~5
in:75~85 in:1~3
20/- 7/6 18/24K 1.8~2.1 Super High High
out:37~43 out:2~5

Instruction:
T1: Inlet and outlet pipe temperature of evaporator
T2: Inlet and outlet pipe temperature of condenser
P: Pressure at the side of big valve
Connection pipe length: 5 m.

Technical Information 21
Service Manual

3. Outline Dimension Diagram


3.1 Indoor Unit

W D

09K 12K
168.5 462 159.5
131 542 172

Φ55 Φ55
Ф55 Ф55

54 43 43
54
143 80
150 90

18K 24K

104 685 181 206 685 187

Ф55 Φ70 Φ70


Ф55

38 38
190 43 43
181
154 79

Unit:mm

Model W H D
09K 790 275 200
12K 845 289 209
18K 970 300 224
24K 1078 325 246

22 Technical Information
Service Manual

3.2 Outdoor Unit


GWC09QB-K3NNA1B/O GWC09QB-K3NNA1J/O

660 255

428
720 310

440

286

Unit:mm

GWH09QB-K3NNA1B/O GWH09QB-K3NNA1J/O GWC12QC-K3NNA1B/O GWH12QC-K3NNA1B/O


GWC12QC-K3NNA1G/O GWH12QC-K3NNA1D/O

712 257
540

776 320

510
286

Unit:mm

Technical Information 23
Service Manual

GWC18QD-K3NNA1B/O GWC18QD-K3NNA1F/O

763 257

540
848 320

540

286
Unit:mm

GWH18QD-K3NNA1B/O GWC24QE-K3NNA1B/O GWH24QE-K3NNA1B/O

846 300

680

913 378
345

Unit:mm
550

24 Technical Information
Service Manual

GWH18QD-K3NNA1D/O

847 300

680
931 378

549

348

Unit: mm

GWC24QE-K3NNA1E/O GWH24QE-K3NNA1E/O
955

340
700

890 396

860
364

Unit: mm

Technical Information 25
Service Manual

4. Refrigerant System Diagram


Cooling models excep: GWC09QB-K3NNA1J GWC12QC-K3NNA1G GWC18QD-K3NNA1F

Indoor unit Outdoor unit

Gas pipe
side
Valve

Discharge
Heat
exchanger
(evaporator) Suction Accumlator Heat
Compressor exchanger
(condenser)

Liquid pipe
side
Valve
Capillary Strainer

COOLING

Cooling and heating models excep: GWH09QB-K3NNA1J GWH12QC-K3NNA1D GWH18QD-K3NNA1D


GWH24QE-K3NNA1E

Indoor unit Outdoor unit

Gas pipe
side
Valve
4-Way valve

Discharge

Heat Suction Accumlator


exchanger
Compressor
(evaporator)
Heat
exchanger
Liquid pipe (condenser)
side
Valve
Strainer Capillary Strainer

COOLING
HEATING

26 Technical Information
Service Manual

GWC09QB-K3NNA1J GWC12QC-K3NNA1G GWC18QD-K3NNA1F GWC24QE-K3NNA1E

Indoor unit Outdoor unit

Gas pipe
side
Valve

Discharge
Heat
exchanger
(evaporator) Suction Accumlator
Compressor

Liquid pipe
side
Valve
Throttle Valve Strainer

COOLING

GWH09QB-K3NNA1J GWH12QC-K3NNA1D GWH18QD-K3NNA1D GWH24QE-K3NNA1E

Indoor unit Outdoor unit

Gas pipe
side
Valve
4-Way valve

Discharge

Heat Suction Accumlator


exchanger Compressor
(evaporator) Heat
exchanger
Liquid pipe
(condenser)
side
Valve Strainer
Strainer Throttle Valve
Capillary

COOLING
HEATING

Connection pipe specification:


Liquid pipe:1/4" (6mm)
Gas pipe:3/8" (9.52mm)(09K)
Gas pipe:1/2" (12mm)(12/18K)
Gas pipe:5/8" (16mm)(24K)

Technical Information 27
Service Manual

5. Electrical Part
5.1 Wiring Diagram

●Instruction

Symbol Symbol Color Symbol Symbol Color Symbol Name


WH White GN Green CAP Jumper cap
YE Yellow BN Brown COMP Compressor
RD Red BU Blue Grounding wire
YEGN Yellow/Green BK Black / /
VT Violet OG Orange / /

Note: Jumper cap is used to determine fan speed and the swing angle of horizontal lover for this model.

● Indoor Unit

(1) GWC09QB-K3NNA1B/I GWC09QB-K3NNA1J/I GWC12QC-K3NNA1B/I GWC12QC-K3NNA6B/I GWC12QC-K3NNA1G/I


GWC12QC-K3NNC2B/I

TUBE TEMP. ROOM TEMP. RECEIVER AND BU(WH)


SENSOR SENSOR DISPLAY BOARD N
BN(BK)
AP1 DISPLAY L
θ θ YEGN(GN)
RT1 RT2 POWER

T-SENSOR DISP1 DISP2 TERMINAL


BLOCK
CAP N1 BU BU
OUTDOOR UNIT

N(1)
AP2 AC-L
K1(K3) COMP BK 2 BK
JUMP
PRINTED CIRCUIT BOARD YEGN
CONNECTING
SWING-UD PG PGF YEGN XT CABLE
PE
EVAPORATOR
M2
M1
STEPPING 6363244401
MOTOR FAN MOTOR

28 Technical Information
Service Manual

(2) GWH09QB-K3NNA1B/I GWH09QB-K3NNA1J/I GWH12QC-K3NNA1B/I GWH12QC-K3NNA1D/I GWH09QB-K3NNB6B/I


GWH12QC-K3NNB6B/I GWH09QB-K3NNC6B/I GWH12QC-K3NNC6B/I

BU(WH) POWER
TUBE TEMP. ROOM TEMP. RECEIVER AND N
SENSOR SENSOR DISPLAY BOARD BN(BK)
L
AP1 DISPLAY YEGN(GN)
0 0

RT1 PE
RT2
EARTH-PLATE
YEGN
DISP1 DISP2 PE YEGN
T-SENSOR
EVAPORATOR
CAP AP2 N1 BU
XT
BU
PRINTED CIRCUIT BOARD N(1)
JUMP

OUTDOOR UNIT
AC-L BK BK
K1(K3) 2
COMP
VT 4 VT
4WAY
SWING-UD OG OG
PG PGF OFAN 5
C0NNECTING
TERMINAL CABLE
BLOCK
M2
M1
STEPPING
MOTOR FAN MOTOR 6363220101

(3) GWC18QD-K3NNA1B/I GWC18QD-K3NNA1F/I

TUBE ROOM
TEMP. TEMP. RECEIVER AND
SENSOR SENSOR DISPLAY BOARD BN(BK)
L
AP1 DISPLAY BU(WH)
θ θ N
YEGN(GN)
RT1 RT2
POWER

T-SENSOR DISP1 DISP2 L101 TERMINAL


BLOCK
CAP N1 BU BU
OUTDOOR UNIT

N(1)

JUMP AP2 K1 L(AC-L) BK 2


BK
COMP
PRINTED CIRCUIT BOARD
YEGN
(SWING) CONNECTING
SWING-UD YEGN XT CABLE
PG PGF
PE
EVAPORATOR
M2
M1
STEPPING 6363244702
MOTOR FAN MOTOR

Technical Information 29
Service Manual

(4) GWH18QD-K3NNA1B/I GWH18QD-K3NNA1D/I GWH18QD-K3NNB6B/I GWH18QD-K3NNC6B/I

BN(BK)
L
ROOM
BU(WH)
TUBE N
TEMP. TEMP. RECEIVER AND YEGN(GN)
SENSOR SENSOR DISPLAY BOARD
AP1 DISPLAY POWER
0 0
PE
RT2 EARTH-PLATE
RT1
YEGN YEGN
PE
T-SENSOR DISP1 DISP2 EVAPORATOR
L101

OUTDOOR UNIT
CAP XT
N1 BU BU
N(1)
JUMP AP2 K1 L(AC-L) BK 2 BK
PRINTED CIRCUIT BOARD COMP
VT 4 VT
4WAY
(SWING) OG 5 OG
SWING-UD OFAN
PG PGF CONNECTING
TERMINAL CABLE
BLOCK

M2
M1
STEPPING
MOTOR FAN MOTOR 6363243802

(5) GWC24QE-K3NNA1B/I(CA419N05600) GWC24QE-K3NNA6B/I GWC24QE-K3NNA1E/I GWC24QE-K3NNC2B/I

TUBE ROOM
TEMP. TEMP. RECEIVER AND
SENSOR SENSOR DISPLAY BOARD BN(BK)
L
AP1 DISPLAY BU(WH)
θ θ N
YEGN(GN)
RT1 RT2
POWER

T-SENSOR DISP1 DISP2 L101 TERMINAL


BLOCK
CAP N1 BU N(1)
BU
OUTDOOR UNIT

BK BK
AP2 COMP 2
JUMP
PRINTED CIRCUIT BOARD L(AC-L) BN 3 BN
YEGN
(SWING) CONNECTING
SWING-UD YEGN XT CABLE
PG PGF
PE
EVAPORATOR
M2
M1
STEPPING
MOTOR FAN MOTOR 6363244802

30 Technical Information
Service Manual

(6) GWC24QE-K3NNA1B/I(CA419N05601) GWC24QE-K3NNB4B/I

TUBE ROOM
TEMP. TEMP. RECEIVER AND
SENSOR SENSOR DISPLAY BOARD BN(BK)
L
AP1 DISPLAY BU(WH)
θ θ N
YEGN(GN)
RT1 RT2
POWER

T-SENSOR DISP1 DISP2 L101 TERMINAL


BLOCK
CAP N1 BU N(1)
BU

OUTDOOR UNIT
BK BK
AP2 COMP 2
JUMP
PRINTED CIRCUIT BOARD L(AC-L) BN 3 BN
YEGN
(SWING) CONNECTING
SWING-UD YEGN XT CABLE
PG PGF
HEALTH-L HEALTH-N PE
EVAPORATOR
M2
M1 RD BU
COLD PLASMA
STEPPING GENERATOR 63632448
MOTOR FAN MOTOR

(7) GWH24QE-K3NNA1B/I GWH24QE-K3NNA1E/I GWH24QE-K3NNB6B/I GWH24QE-K3NNC6C/I

BN(BK)
L
TUBE ROOM RECEIVER AND BU(WH)
TEMP. TEMP. DISPLAY BOARD N
SENSOR SENSOR YEGN(GN)
AP2 DISPLAY
POWER
0 0
PE
RT1 RT2 EARTH-PLATE
YEGN
PE
YEGN
T-SENSOR DISP1 DISP2 L101 EVAPORATOR
XT
CAP N1 BU N(1) BU
OUTDOOR UNIT

BK BK
JUMP AP1 COMP 2
BN 3 BN
PRINTED CIRCUIT BOARD L(AC-L)
VT VT
(SWING) 4WAY 4
SWING-UD OG OG
PG PGF OFAN 5
CONNECTING
TERMINAL CABLE
BLOCK
M2
M1
STEPPING
MOTOR FAN MOTOR 6363243702

Technical Information 31
Service Manual

● Outdoor Unit

(1) GWC09QB-K3NNA1B/O GWC09QB-K3NNA1J/O GWC12QC-K3NNA1B/O GWC18QD-K3NNA1B/O GWC18QD-K3NNA1F/O

C(U)
M1 M2
BK E YEGN E YEGN
COMP FAN
S(X) MOTOR R(M,V) MOTOR
E E
YE C1 BU RD

(BK) BU BN C2

XT1
BU
BU
N(1)
INDOOR UNIT

BK (BN)
2 BK

YEGN
E
63613294

(2) GWH09QB-K3NNA1B/O GWH09QB-K3NNA1J/O GWH12QC-K3NNA1B/O

61413297
C(T,U)
M1
E YEGN
S(W,X) COMP
MOTOR R(M,V)
E
BK YE BU
C1

YEGN M2
BU E YEGN
E FAN
MOTOR
E
INDOOR UNIT

XT1 BU
BU BN
N(1) BU
BK C2
2 RD
VT 4
OG XT2
5

YV

OG

32 Technical Information
Service Manual

(3) GWC12QC-K3NNA1G/O

NOTE:
Motor ground
C COMP. FAN only applies
MOTOR to the iron
shell motor.
COMP PE YEGN M
BK PE YEGN
S R(M) PE
PE
YE C1 BU RD
BN
TERMINAL BU C2
BLOCK
BU N(1)
INDOOR UNIT

BU(BK)
BK BK
2
YEGN XT
PE 6363357901

(4) GWH12QC-K3NNA1D/O

NOTE:
Motor ground
C COMP. only applies
to the iron
COMP PE YEGN FAN shell motor.
BK MOTOR
S R(M) PE
M PE YEGN
YE C1 BU PE
CAP. BN
YEGN RD C2
BU(BK)
PE CAP.
INDOOR UNIT

XT1
BU
BU XT2
N(1) BU TERMINAL
BLOCK VT
BK
2 4-WAY
VT VT VALVE
4 4YV
OG OG
5
TERMINAL 6363361501
BLOCK

Technical Information 33
Service Manual

(5) GWH18QD-K3NNA1B/O GWH18QD-K3NNA1D/O

C(T,U) COMP.
COMP YEGN
PE
S(W,X) R(M,V) PE
BK
YE BU FAN MOTOR
C1
YEGN M YEGN
PE
PE
INDOOR UNIT

CAP. PE
XT BU
BU
N(1) RD BN
BK
2
BK(BU) (BN)
VT C2
4 VT 4YV
VT
OG 5 4-WAY VALVE CAP.
TERMINAL WH
BOARD (OG)
6363302101

(6) GWC24QE-K3NNA1B/O

5BK

C COMP.
COMP. PE 6YEGN
S R(M) FAN MOTOR
3BU PE M2 PE
YEGN
4YE
1BU
C1 PE

RD BN
(BN)

XT1 C2
BU 2BU
N(1) BK (BU)
BK 9BU
INDOOR UNIT

2
7BK 6 1
BN 3
8BN
KM CONTACTOR
YEGN 4 0
PE
WH (OG)

63613899

34 Technical Information
Service Manual

(7) GWC24QE-K3NNA1E/O

%.
& 7
&203
&203 3( <(*1
3(
6 ; 5 0
%8
<(
& )$102725
%8

&$3
-
0 3(
<(*1

3(
;7 %8 %. 5' %1
%8
1  %8 %8
&
,1'22581,7

%. %. 


%1 &$3
%1
 .0 $&&217$&725
<(*1 7(50,1$/ 
%2$5' 
%.
3(


(8) GWH24QE-K3NNA1B/O

C COMP. FAN MOTOR


YEGN
COMP YEGN M
PE
S R(M) PE
C1 BU BK RD C2 BN
BK YE BU
J (BU) (BN)

CAP. CAP.
AC CONTACTOR

YEGN BU 6 1
BU
INDOOR UNIT

PEXT
KM
BU N(1) HP 4 0
BK 1 P 2 BK
BK
2 HIGH PRESSURE
BN BN SWITCH
3
VT VT 4YV VT
4
OG WH(OG) 4-WAY VALVE
5
TERMINAL
BLOCK 6361000001201

Technical Information 35
Service Manual

(9) GWH24QE-K3NNA1E/O

C COMP. FAN MOTOR


COMP YEGN M YEGN
S R(M) PE PE
C1 BU BK RD C2 BN
BK YE BU
J (BU)

CAP. CAP.
YEGN BU

AC CONTACTOR
6 1
BU
INDOOR UNIT

PEXT
KM
BU N(1) HP 4 0
BK 1 P 2 BK
BK
2 HIGHPRESSURE
BN BN SWITCH
3
VT VT 4YV VT
4
OG OG 4-WAY VALVE
5
TERMINAL
BLOCK 63610000012

These wiring diagrams are subject to change without notice; please refer to the one supplied with the unit.

36 Technical Information
Service Manual

5.2 PCB Printed Diagram

4 5 6 7 8 9 10

3 11

2
12
13
1
14

Technical Information 37
Service Manual

6. Function and Control


6.1 Remote Controller Introduction of YAN1F1

1 ON/OFF button

2 MODE button
WIFI

3 FAN button

4 SWING button
1
3 5 TURBO button
2
5
6 ▲/ button

4
6
7 7 SLEEP button
8
9
8 TEMP button
11 10
9 I FEEL button

12 10 LIGHT button

11 CLOCK button

TIMER ON / TIMER OFF


12
button

Introduction for icons on display screen

I feel Set fan speed


Operation mode Send signal
Turbo mode
Auto mode
8℃ heating function
Cool mode
WIFI(This unit without WiFi fuction)
Dry mode WIFI
Fan mode Set temperature

Heat mode Set time


TIMER ON / TIMER OFF
Clock
Sleep mode Child lock
Light Up & down swing
Temp. display type
:Set temp. :Indoor ambient temp.
:Outdoor ambient temp.

Introduction for buttons on remote controller


Note:
● After putting through the power, the air conditioner will give out a sound. Operation indictor " " is ON (red indicator). After that,
you can operate the air conditioner by using remote controller.
● Under on status, pressing the button on the remote controller, the signal icon " "on the display of remote controller will blink once
and the air conditioner will give out a “de” sound, which means the signal has been sent to the air conditioner.
● Under off status, set temperature and clock icon will be displayed on the display
of remote controller (If timer on, timer off and light functions are set, the corre- sponding icons will be displayed on the display of
remote controller at the same time); Under on status, the display will show the corresponding set function icons.

38 Technical Information
Service Manual

1. ON/OFF button
Press this button can turn on or turn off the air conditioner. After turning on the air conditioner, operation indicator " "on indoor unit’s
display is ON (green indicator. The colour is different for different models), and indoor unit will give out a sound.

2. MODE button
Press this button to select your required operation mode.

AUTO COOL DRY FAN HEAT

● When selecting auto mode, air conditioner will operate automatically according to ex-factory setting. Set temperature can’t be adjusted and
will not be displayed as well. Press "FAN" button can adjust fan speed. Press "SWING" button can adjust fan blowing angle.
● After selecting cool mode, air conditioner will operate under cool mode. Cool indicator " "on indoor unit is ON. Press "▲" or " " button

to adjust set temperature. Press "FAN" button to adjust fan speed. Press "SWING" button to adjust fan blowing angle.
● When selecting dry mode, the air conditioner operates at low speed under dry mode. Dry indicator " " on indoor unit is ON. Under dry
mode, fan speed can’t be adjusted. Press "SWING" button to adjust fan blowing angle.
● When selecting fan mode, the air conditioner will only blow fan, no cooling and no heating. All indicators are OFF. Press "FAN" button to
adjust fan speed. Press "SWING" button to adjust fan blowing angle.
● When selecting heating mode, the air conditioner operates under heat mode. Heat indicator " " on indoor unit is ON. Press "▲" or " "

button to adjust set temperature. Press "FAN" button to adjust fan speed. Press "SWING" button to adjust fan blowing angle. (Cooling only
unit won’t receive heating mode signal. If setting heat mode with remote controller, press ON/OFF button can’t start up the unit).
Note:
● For preventing cold air, after starting up heating mode, indoor unit will delay 1~5 minutes to blow air (actual delay time is depend on indoor
ambient temperature).
● Set temperature range from remote controller: 16~30℃ ; Fan speed: auto, low speed, medium speed, high speed.

3. FAN button
Pressing this button can set fan speed circularly as: auto (AUTO), low( ) ,medium( ), high( ).

Auto

Caution:
● Under AUTO speed, air conditioner will select proper fan speed automatically according to ex-factory setting.
● Fan speed under dry mode is low speed.
4. SWING button
Press this button can select up&down swing angle. Fan blow angle can be selected circularly as below:

no display
(horizontal louvers stops at current position)

● When selecting " ", air conditioner is blowing fan automatically. Horizontal louver will automatically swing up & down at maximum angle.
● When selecting " 、 、 、 、 ", air conditioner is blowing fan at fixed position. Horizontal louver will stop at the fixed position.
● When selecting " 、 、 " , air conditioner is blowing fan at fixed angle. Horizontal louver will send air at the fixed angle.
● Hold " "button above 2s to set your required swing angle. When reaching your required angle, release the button.
Note:
● " 、 、 " may not be available. When air conditioner receives this signal, the air conditioner will blow fan automatically.

5. TURBO button
Under COOL or HEAT mode, press this button to turn to quick COOL or quick HEAT mode. " " icon is displayed on remote controller.
Press this button again to exit turbo function and " " icon will disappear.

6. ▲/

button
● Press "▲" or " " button once increase or decrease set temperature 1℃ . Holding "▲" or " " button, 2s later, set temperature on remote
▲ ▲
controller will change quickly. On releasing button after setting is finished, temperature indicator on indoor unit will change accordingly.
(Temperature can’t be adjusted under auto mode)
● When setting TIMER ON, TIMER OFF or CLOCK, press "▲" or "▲" button to adjust time. (Refer to CLOCK, TIMER ON, TIMER OFF
buttons) When setting TIMER ON, TIMER OFF or CLOCK, press "▲" or "▲" button to adjust time. (Refer to CLOCK, TIMER ON, TIMER
OFF buttons)

Technical Information 39
Service Manual

7. SLEEP button
Under COOL, HEAT or DRY mode, press this button to start up sleep function. " " icon is displayed on remote controller. Press this button
again to cancel sleep function and " " icon will disappear.

8. TEMP button
By pressing this button, you can see indoor set temperature, indoor ambient temperature or outdoor ambient temperature on indoor unit’s
display. The setting on remote controlleris selected circularly as below:

no display

● When selecting " " or no display with remote controller, temperature indicator on indoor unit displays set temperature.
● When selecting " " with remote controller, temperature indicator on indoor unit displays indoor ambient temperature.
● When selecting " " with remote controller, temperature indicator on indoor unit displays outdoor ambient temperature.
Note:
● Outdoor temperature display is not available for some models. At that time, indoor unit receives " "signal, while it displays indoor set
temperature.
● It’s defaulted to display set temperature when turning on the unit.There is no display in the remote controller.
● Only for the models whose indoor unit has dual-8 display.
● When selecting displaying of indoor or outdoor ambient temperature, indoor temperature indicator displays corresponding temperature and
automatically turn to display set temperature after three or five seconds.

9. I FEEL button
Press this button to start I FEEL function and " " will be displayed on the remote controller. After this function is set, the remote controller
will send the detected ambient temperature to the controller and the unit will automatically adjust the indoor temperature according to the
detected temperature. Press this button again to close I FEEL function and " " will disappear.
● Please put the remote controller near user when this function is set. Do not put the remote controller near the object of high temperature
or low temperature in order to avoid detecting inaccurate ambient temperature.
10. LIGHT button
Press this button to turn off display light on indoor unit. " " icon on remote controller disappears. Press this button again to turn on
display light. " " icon is displayed.

11. CLOCK button


Press this button to set clock time. " " icon on remote controller will blink. Press "▲" or " " button within 5s to set clock time. Each

pressing of "▲" or " " button, clock time will increase or decrease 1 minute. If hold "▲" or " " button, 2s later, time will change quickly.
▲ ▲

Release this button when reaching your required time. Press "CLOCK" button to confirm the time. " " icon stops blinking.
Note:
● Clock time adopts 24-hour mode.
● The interval between two operation can’t exceeds 5s. Otherwise, remote controller will quit setting status. Operation for TIMER ON/TIMER
OFF is the same.

12. TIMER ON / TIMER OFF button


● TIMER ON button
"TIMER ON" button can set the time for timer on. After pressing this button, " " icon disappears and the word "ON" on remote controller
blinks. Press "▲" or " "button to adjust TIMER ON setting. After each pressing "▲" or " " button, TIMER ON setting will increase or
▲ ▲
decrease 1min. Hold "▲" or " " button, 2s later, the time will change quickly until reaching your required time. Press "TIMER ON" to

confirm it. The word "ON" will stop blinking. " " icon resumes displaying. Cancel TIMER ON: Under the condition that TIMER ON is
started up, press "TIMER ON" button to cancel it.
● TIMER OFF button
"TIMER OFF" button can set the time for timer off. After pressing this button," " icon disappears and the word "OFF" on remote
controller blinks. Press "▲" or " " button to adjust TIMER OFF setting. After each pressing "▲" or " " button,
▲ ▲
TIMER OFF setting will increase or decrease 1min. Hold "▲" or " " button, 2s later, the time will change quickly until reaching your

required time. Press "TIMER OFF" word "OFF" will stop blinking. " " icon resumes displaying. Cancel TIMER OFF. Under the condition
that TIMER OFF is started up, press "TIMER OFF" button to cancel it.
Note:
● Under on and off status, you can set TIMER OFF or TIMER ON simultaneously.
● Before setting TIMER ON or TIMER OFF, please adjust the clock time.
● After starting up TIMER ON or TIMER OFF, set the constant circulating valid. After that, air conditioner will be turned on or turned off
according to setting time. ON/OFF button has no effect on setting. If you don’t need this function, please use remote controller to cancel it.

40 Technical Information
Service Manual

Function introduction for combination buttons


1. Energy-saving function
Under cooling mode, press "TEMP" and " CLOCK" buttons simultaneously to start up or turn off energy-saving function. When energy-saving
function is started up, "SE" will be shown on remote controller, and air conditioner will adjust the set temperature automatically according to
ex-factory setting to reach to the best energy-saving effect. Press "TEMP" and "CLOCK"buttons simultaneously again to exit energy-saving
function.
Note:
● Under energy-saving function, fan speed is defaulted at auto speed and it can’t be adjusted.
● Under energy-saving function, set temperature can’t be adjusted. Press "TURBO" button and the remote controller won’t send signal.
● Sleep function and energy-saving function can’t operate at the same time. If energy-saving function has been set under cooling mode,
press sleep button will cancel energy-saving function. If sleep function has been set under cooling mode, start up the energy-saving
function will cancel sleep function.

2. 8 ℃ heating function
Under heating mode, press "TEMP" and "CLOCK" buttons simultaneously to start up or turn off 8℃ heating function. When this function is
started up, " " and "8℃ " will be shown on remote controller, and the air conditioner keep the heating status at 8℃ . Press "TEMP" and
"CLOCK" buttons simultaneously again to exit 8℃ heating function.
Note:
● Under 8℃ heating function, fan speed is defaulted at auto speed and it can’t be adjusted.
● Under 8℃ heating function, set temperature can’t be adjusted. Press "TURBO" button and the remote controller won’t send signal.
● Sleep function and 8℃ heating function can’t operate at the same time. If 8℃ heating function has been set under cooling mode, press
sleep button will cancel 8℃ heating function. If sleep function has been set under cooling mode, start up the 8℃ heating function will
cancel sleep function.
● Under ℉ temperature display, the remote controller will display 46 ℉ heating.

3. Child lock function


Press "▲" and " " simultaneously to turn on or turn off child lock function. When child lock function is on, " " icon is displayed on remote

controller. If you operate the remote controller, the " " icon will blink three times without sending signal to the unit.

4. Temperature display switchover function


Under OFF status, press " " and "MODE" buttons simultaneously to switch temperature display between ℃ and ℉ .

5. WIFI fuction (This unit is without WiFi fuction)


Under ON status, press "Mode" and "Turbo" button simultaneously,the "WiFi" icon will be displayed on remote controller .
press "Mode"and"Turbo" button simultaneously,the "WiFi" icon will disppear.

Operation guide
1. After putting through the power, press "ON/OFF" button on remote controller to turn on the air conditioner.
2. Press "MODE" button to select your required mode: AUTO, COOL, DRY, FAN, HEAT.
3. Press "▲" or " " button to set your required temperature. (Temperature can’t be adjusted under auto mode).

4. Press "FAN" button to set your required fan speed: auto, low, medium and high speed.
5. Press "SWING" button to select fan blowing angle.

Replacement of batteries in remote controller

1. Press the back side of remote controller marked with " ", as shown in the fig, and then push signal sender battery
out the cover of battery box along the arrow direction.
2. Replace two 7# (AAA 1.5V) dry batteries, and make sure the position of "+" polar and "-" polar reinstall
are correct.
3. Reinstall the cover of battery box. remove

Note:
Cover of battery box
● During operation, point the remote control signal sender at the receiving window on indoor unit.
● The distance between signal sender and receiving window should be no more than 8m, and there should be no obstacles between them.
● Signal may be interfered easily in the room where there is fluorescent lamp or wireless telephone; remote controller should be close to
indoor unit during operation.
● Replace new batteries of the same model when replacement is required.
● When you don’t use remote controller for a long time, please take out the batteries.
● If the display on remote controller is fuzzy or there’s no display, please replace batteries.

Technical Information 41
Service Manual

6.2 Remote Controller Introduction of YB1FA(MOTO)


Buttons on Remote Controller
1 ON/OFF Button

2 MODE Button

3 +/- Button

4 FAN Button

5 Button
1 2
6 CLOCK Button
3
7 TIMER ON/TIMER-OFF Button
4
5
6 8 X-FAN Button

8 7 9 TEMP Button
10 9 10 TURBO Button
12 11
11 LIGHT Button

12 SLEEP Button

Introduction for Icons on Display Screen


Operation mode
mode Set fan speed
Auto mode Send signal
Cool mode X-fan mode
Dry mode
Fan mode Set temperature
Heat mode
Turbo mode
Set time
Clock
TIMER ON/TIMER OFF
Sleep mode
Child lock
display type
Temp. display type Light
:Set temp. :Indoor ambient temp.
:Outdoor ambient temp.

Up&down swing

Introduction for Buttons on Remote Controller


Note:After putting through the power, the air conditioner will give out a sound. Operation indictor " " is ON (red indicator). After that,
you can operate the air conditioner by using remote controller.
1. ON/OFF Button
Press this button can turn on or turn off the air conditioner. After turning on the air conditioner, operation indicator " " on indoor
unit’s display is ON (green indicator. The colour is different for different models), and indoor unit will give out a sound.

2. MODE Button
Press this button to select your required operation mode.
AUTO COOL DRY FAN HEAT

42 Technical Information
Service Manual

● When selecting auto mode, Air conditioner will start auto operation according to indoor ambient temperature.Set temperature can’t be
adjusted and will not be displayed as well. Press "FAN" button can adjust fan speed. Press " " button can adjust fan blowing angle.
● After selecting cool mode, air conditioner will operate under cool mode. Cool indicator " " on indoor unit is ON. Press "+" or "-" button
to adjust set temperature. Press "FAN" button to adjust fan speed. Press " " button to adjust fan blowing angle.
● When selecting dry mode, the air conditioner operates at low speed under dry mode. Dry indicator " " on indoor unit is ON. Under dry
mode, fan speed can’t be adjusted. Press " " button to adjust fan blowing angle.
● When selecting fan mode, the air conditioner will only blow fan, no cooling and no heating.All indicators are OFF.Operation indicator is
ON.Press "FAN" button to adjust fan speed. Press " " button to adjust fan blowing angle.
● When selecting heating mode, the air conditioner operates under heat mode. Heat indicator " " on indoor unit is ON. Press “+” or “-“
button to adjust set temperature Press “FAN” button to adjust fan speed. Press " " button to adjust fan blowing angle.(Cooling only unit
won’t receive heating mode signal. If setting heat mode with remote controller, press ON/OFF button can’t start up the unit).
Note:
● For preventing cold air, after starting up heating mode, indoor unit will delay 1~5minutes to blow air (actual delay time is depend on
indoor ambient temperature).
● Set temperature range from remote controller: 16~30 ; Fan speed: auto, low speed,medium speed, high speed.

3. “+” or“-” Button


● Press “+” or “-“ button once increase or decrease set temperature 1 .Holding "+" or "-" button, 2s later, set temperature on remote
controller will change quickly. On releasing button after setting is finished, temperature indicator on indoor unit will change accordingly.
(Temperature can’t be adjusted under auto mode)
● When setting TIMER ON, TIMER OFF or CLOCK, press “+” or “-“ button to adjust time.(Refer to CLOCK, TIMER ON, TIMER OFF
buttons)

4. FAN Button
Pressing this button can set fan speed circularly as: auto (AUTO), low( ) ,medium( ),high( ).
Auto

Note:
● Under AUTO speed, the IDU fan motor will adjust the fan speed (high, medium or low speed) according to ambient temperature.
● Fan speed under dry mode is low speed.
5. Button
Pressing this button can select up&down swing angle. Fan blow angle can be selected circularly as below:

no display
(horizontal louvers
stops at current position)
● When selecting " " , air conditioner is blowing fan automatically. Horizontal louver will automatically swing up & down at
maximum angle.
● When selecting " ", air conditioner is blowing fan at fixed position. Horizontal louver will stop at the fixed
position.
● When selecting " ”, air conditioner is blowing fan at fixed angle. Horizontal louver will send air at the fixed angle.
● Hold " " button above 2s to set your required swing angle. When reaching your required angle, release the button.

Note:
" " may not be available. When air conditioner receives this signal, the air conditioner will blow fan automatically.

6. CLOCK Button
Press this button to set clock time. " " icon on remote controller will blink. Pess "+" or "-" button within 5s to set clock time. Each
pressing of "+" or "-" button, clock time will increase or decrease 1 minute. Hold "+" or "-" button, 2s later, time will change quickly.
Release this button when reaching your required time. Press “CLOCK" button to confirm the time. " " icon stops blinking.
Note:
● Clock time adopts 24-hour mode.
● The interval between two operation can’t exceeds 5s. Otherwise, remote controller will quit setting status. Operation for TIMER
ON/TIMER OFF is the same.

7. TIMER-ON/TIMER-OFF Button
● TIMER ON button
TIMER ON button
“TIMER ON” button can set the time for timer on. After pressing this button, " " icon disappears and the word “ON" on remote

Technical Information 43
Service Manual

controller blinks. Press "+" or "-"button to adjust TIMER ON setting. After each pressing "+" or "-"button, TIMER ON setting will increase
or decrease 1min. Hold "+" or "-"button, 2s later, the time will change quickly
until reaching your required time. Press “ TIMER ON”to confirm it. The word “ON" will stop blinking. " " icon resumes displaying.
Cancel TIMER ON: Under the condition that TIMER ON is started up, press “TIMER ON” button to cancel it.
● TIMER OFF button
"TIMER OFF" button can set the time for timer off. After pressing this button, " " icon disappears and the word "OFF" on remote
controller blinks. Press "+" or "-" button to adjust TIMER OFF setting. After each pressing "+" or "-" button, TIMER OFF setting will
increase or decrease 1min. Hold "+" or "-" button, 2s later, the time will change
quickly until reaching your required time. Press "TIMER OFF" to confirm it .The word "OFF"will stop blinking " " icon resumes
displaying. Cancel TIMER OFF. Under the condition that TIMER OFF is started up, press “TIMER OFF” button to cancel it.
Note:
● Under on and off status, you can set TIMER OFF or TIMER on simultaneously.
● Before setting TIMER ON or TIMER OFF, please adjust the clock time.
● After starting up TIMER ON or TIMER OFF, set the constant circulating valid. After that, air conditioner will be turned on or turned off
according to setting time. ON/OFF button has no effect on setting. If you don’t need this function, please use remote controller to cancel
it.

8. X-FAN Button
Press this button under cool and dry mode to start up x-fan function, and " " icon on remote controller will be displayed. Press this
button again to cancel x-fan function, and " "icon will disappear.
Note:
● When x-fan function is on, if the air conditioner is turned off, indoor fan will still operate at low speed for a while to blow the residual
water inside the air duct.
● During x-fan operation, press X-FAN button to turn off x-fan function. Indoor fan will stop operation immediately.

9. TEMP Button
By pressing this button, you can see indoor set temperature, indoor ambient temperature or outdoor ambient temperature on indoor
unit’s display. The setting on remote controlleris selected circularly as below:
no display

When selecting " " or no display with remote controller, temperature indicator on indoor unit displays set temperature;
When selecting " " with remote controller, temperature indicator on indoor unit displays indoor ambient temperature;
When selecting " " with remote controller, temperature indicator on indoor unit displays outdoor ambient temperature.
Note:
● Outdoor temperature display is not available for some models. At that time, indoor unit receives" " signal, while it displays
indoor set temperature.
● It’s defaulted to display set temperature when turning on the unit.There is no display in the remote controller.
● Only for the models whose indoor unit has dual-8 display

10. TURBO Button


Under COOL or HEAT mode, press this button to turn to quick COOL or quick HEAT mode. " " icon is displayed on remote
controller. Press this button again to exit turbo function and " " icon will disappear.

11. SLEEP Button


Under COOL, HEAT mode, press this button to start up sleep function. " " icon is displayed on remote controller. Press this button
again to cancel sleep function and " " icon will disappear.
12. LIGHT Button
Press this button to turn off display light on indoor unit. " " icon on remote controller disappears. Press this button again to turn
on display light. " " icon is displayed.

Function Introduction for Combination Buttons

Child lock function:


Press "+"and "-" simultaneously to turn on or turn off child lock function. When child lock function is on, " " icon is displayed on
remote controller. If you operate the remote controller, it won’t send signal.
Temperature display switchover function:
Under OFF status, press "-" and "MODE" buttons simultaneously to switch temperature display between and .

44 Technical Information
Service Manual

Operation Guide
1. After putting through the power, press “ON/OFF” button on remote controller to turn on
1 2
the air conditioner.
2. Press "MODE" button to select your required mode:AUTO,COOL,DRY,FAN,HEAT. 3
3. Press “+” or “-“ button to set your required temperature. (Temperature can’t be 4
5
adjusted under auto mode).
4. Press ‘FAN” button to set your required fan speed: auto, low, medium and high speed.
5. Press " " button to select fan blowing angle.

Replacement of Batteries in Remote Controller


1.Press the back side of remote controller marked with“ ”as shown in the fig, and then push out the cover
of battery box along the arrow direction.
2. Replace two 7# (AAA 1.5V) dry batteries, and make sure the position of “+” polar and “-“ polar are correct.
3. Reinstall the cover of battery box.

Note: Signal sender Battery


● During operation, point the remote control signal sender at the receiving window
on indoor unit.
● The distance between signal sender and receiving window should be no more than
8m, and there should be no obstacles between them.
Reinstall
● Signal may be interfered easily in the room where there is fluorescent lamp or
wireless telephone; remote controller should be close to indoor unit during operation. Cover of
battery box Remove
● Replace new batteries of the same model when replacement is required.
● When you don’t use remote controller for a long time, please take out the batteries.
● If the display on remote controller is fuzzy or there’s no display, please replace
batteries.

Technical Information 45
Service Manual

6.3 Brief Description of Modes and Functions


1. Summary
(1) Buzzer
When the controller is energized or receives signal from button (emergency operation switch on air conditioner) or remote controller, the
buzzer will give out a beep.
(2) Display
A1/B6/C2/B4/C6 panel:After energization, all icons will be displayed once. Operation icon is in red under standby status. After turning on the
unit by remote controller, operation icon is bright and corresponding set operation mode icon will be displayed(Mode icon include: cooling,
heating, drying).
A6 panel:After energizing, the unit will display all icons. Understandby status,power indicator is displayed in red. If the unit is started by
remote controller,powerindicator is displayed in green.Meanwhile, the mode indi-cator is displayed in thecolor of corresponding operation
mode(displayed color of mode indicator:whitecooling mode, red-heating mode, orange-dry mode).
A1/B6/C2 display A6 display

(Display content or position may


B4/C6 display
be different from above graphics, Dual-8 nixie Temp.
please refer to actual products) tube display indicator
Power LED color indicator: Heating
Cooling icon Operation icon Receiver receiver Green-status-ON. indicator
window window Red-status-OFF.
Heating icon Dual-8 nixie Drying icon Cooling
tube display Mode LED color indicator:
indicator
(3) Temperature parameter W R O
White-W-Cool Mode-
W
Power Receiver
◆ Indoor set temperature (Tpreset) Red-R-Heat Mode- R
(only for heating model)
indicator window

◆ Indoor ambient temperature (Tamb.) Orange-O-Dry Mode- O drying


indicator
◆ Inner tube temperature of indoor evaporator (Ttube)

2. Introduction of Basic Mode Function


◆ Once the compressor is energized, there should be a minimum interval of 3 mins between two start-ups.
◆ If the unit is with memory function and is off before power failure, the compressor can be restarted without an interval of 3 mins; if the
◆ unit is on before power failure, the compressor will be restarted with an interval of 3 mins.
Once compressor is started, it won’t stop within 6 mins according to the change of room temp.
(1) Auto mode
① Operation condition and process for auto mode
Under auto mode, the system will automatically select operation mode (cooling, heating, and fan) according to indoor ambient temperature.
There swill be 30s delayed for protection between mode switchover.
◆ When Tamb≥26 , unit will be in cooling mode℃ Ex-factory set temperature is 25℃
◆ Cooling and heating unit: When Tamb≤(19℃ +Tcompensation), unit will be in heating mode Tpreset=20℃ .
◆ Cooling only unit: When Tamb≤22℃ (or 72 ℉ ), unit will be in fan mode Tpreset=25℃ .
◆ For cooling and heating unit under condition that (19℃ +Tcompensation) < Tamb < 26℃ (For cooling only unit under condition that 22℃
< Tamb < 26℃ ), when unit is initially turned on in auto mode, it will operate according to auto fan mode. When unit is changed to auto
mode from other modes, it will maintain its previous working status (If auto mode is turned on from
drying mode, unit will operate according to auto fan mode).
② Display: Operation icon, actual operation mode icon, set temperature (that’s the display content of dual-8 nixie tube)
③ Protection function is same as that under each mode.
(2) Cooling mode
① Operation condition and process for cooling mode
◆ When Tamb. ≥Tset+1℃ , the system operates under cooling mode. In this case, the compressor, the ODU fan motor and the IDU fan
motor operates at set speed.
◆ When Tamb. ≤Tset-1℃ , the compressor and the ODU fan motor stop, while the IDU fan motor operates at set speed.
◆ When Tset-1℃ <Tamb. <Tset+1℃ , the system will maintain its previous operation status.

Start cooling
Tpreset +1 ˚C Tamb.
Original operating status
Tpreset –1 ˚C

Stop cooling
Graphic instruction: 6 min. 3 min. 6 min.
(Same as below)
Compressor
Indicates operation
Outdoor fan motor
Indicates stop
Indoor fan motor Set fan speed

In cooling mode, the 4-way valve is de-energized (4-way valve is not available for cooling only unit). Temperature setting range is 16~30℃ .
② Display: Operation icon, cooling icon, set temperature.
③ Protection function
◆ Freeze protection

46 Technical Information
Service Manual

During operation, when controller detected that Ttube≤0℃ for a consecutive period of time, the system enters into freeze protection. In
that case, the compressor and the ODU fan stop operation, while the IDU operates at set fan speed. If freeze protection is released and
the compressor has been out of operation for 3 mins, the unit will resume its previous operation status.
Freeze protection period

Compressor 3 min
Outdoor fan motor
Indoor fan motor Set fan speed

◆ Overcurrent protection ( this protection function is not available for those models whose cooling capacity ≤12000Btu/h)
During operation process, if controller detected that system current exceeds the limit value for 3s consecutively (overcurrent), only the
fan operates. About 3 mins later, if overcurrent is released, the system will resume original operation.
If overcurrent protection occurs for 6 times consecutively, and resume operation time won’t exceed 6min every time, overcurrent protec-
tion information will be displayed. After turning off the unit, display won’t be displayed.
If turn on the unit again, the system will be restated up again. Overcurrent protection information will be eliminated.
Please refer to maintenance part for display information and disposal method for details.

◆ Locked protection to IDU fan motor


During operation of IDU fan motor, if controller detected that the rotation speed of IDU fan motor less than 300/min or stop rotation, the
motor operates abnormally. In order to prevent damage to motor, controller will protect automatically, the system stops operation and
blocked information of IDU fan motor will be displayed. After turning off the unit, display won’t be displayed.
If turn on the unit again, the system will be restated up again. Blocked information of IDU fan motor will be eliminated. (For some models,
they can only be restated up after re-energized)
Please refer to maintenance part for display information and disposal method for details.

(3) Drying mode


① Operation condition and process for drying mode
◆ When Tamb. >Tset+2℃ , the system starts drying and cooling. In this case, the compressor and the ODU fan motor operate, and the
IDU fan motor operates at low speed.
◆ When Tset-2℃ ≤Tamb. ≤Tset+2℃ , the system will start drying. In this case, the IDU fan motor operates at low speed; the compressor
and the ODU fan motor operate for 6 minutes and stop for 4 minutes in cycle.
◆ When Tamb.<Tset-2℃ , the compressor and the ODU fan motor stop, while the IDU fan motor runs at low speed.
In drying mode, the 4-way valve is de-energized (4-way valve is not available for cooling only unit); Temperature setting range is
16~30℃ . Fan speed can’t be adjusted.

Tamb.
Cooling
Tpreset+2
Drying
Tpreset-2
6 min 6min. Stop
4min. 4min.

Compressor
Outdoor fan motor
Indoor fan motor Low speed

② Display: Operation icon, drying icon, set temperature.


③ Protection function
◆ Freeze protection
During dying and cooling operation, when the controller detected that Ttube≤0℃ for a period of time consecutively, the system will enter
into freeze protection. In that case, the compressor and the ODU fan motor stops operation, while the IDU fan motor operates at low
speed. When freeze protection is release and the compressor has stopped for 3min, the system will resume original operation.
During drying operation, when the controller detected that Ttube≤0℃ for a period of time consecutively, the system enters into freeze
protection. In that case, the compressor, the ODU fan motor stops operation, while the IDU fan motor operates at low speed. When
freeze protection is release and the compressor has stopped for 4min, the system will resume original operation.
◆ Other protection is same as that under cooling mode.

Technical Information 47
Service Manual

(4) Fan mode


① Operation condition and process for fan mode
In fan mode, the IDU fan motor operates at set speed, while the compressor and the ODU fan motor stop. 4-way valve is de-energized
(4-way valve is not available for cooling only unit). Temperature setting range is 16~30℃ .
② Display: Operation icon, set temperature.
③ Protection function
In fan mode, there are overcurrent protection and blocked protection of IDU fan motor. Please refer to corresponding protection function
under cooling mode for details.

(5) Heating mode(no heating mode is not available for cooling only unit)
① Operation conditioner and process for heating mode
◆ When Tamb-Tcompensation≤Tpreset-1℃ , unit will operate in heating mode. 4-way valve will be energized while compressor and
outdoor fan starts operation at the same time. Indoor fan will start some time later so that air condition won’t blow out cold air.
◆ When Tamb-Tcompensation≥Tpreset+1℃ , compressor and outdoor fan will stop operation while 4-way valve is still power on. Indoor
fan will continue operation for a while at set fan speed to blow out the residual heat so that temperature within the air conditioner won’t
be too high.
◆ When Tpreset-1℃< Tamb-Tcompensation < Tpreset+1℃ , system will maintain its previous working status.
In heating mode, 4-way valve is energized. Temperature setting range is 16~30℃ .

Stop heating
Tpreset+4
Original operating status
Tpreset+2
Tamb.
min. min. min. Start heating

Compressor

Outdoor unit
Intdoor unit min. Set fan speed min. Set fan speed

Reversing valve

② Display: Operation icon, heating icon, set temperature.


③ Defrosting condition and process
For ensusing heating effect, air conditioner will defrost automatically according to defrosting status on outdoor unit. During defrosting,
heating icon will be on and off.
④ Protection function
◆ Overheating prevention protection
During operation, when controller detects that Ttube≥55℃ ,the ODU fan motor stops operation; When Ttube is resumed normally, the
ODU fan motor resumes operation.
◆ Noise silencing protection
When turning off the unit or during mode switchover, the 4-way valve is closed. In order to decrease noise, the 4-way valve will delay
2mins to be closed.
◆ Overcurrent protection ( this protection function is not available for those models whose cooling capacity ≤12000Btu/h)
During operation process, if controller detected that system current exceeds the limit value for 3s consecutively(overcurrent), the
system stops operation. About 3mins later, if overcurrent is released, the system will resume original operation. If overcurrent protection
occurs for 6 times consecutively, and resume operation time won’t exceed 6min every time, overcurrent protection information will be
displayed. After turning off the unit, display won’t be displayed.
If turn on the unit again, the system will be restated up again. Overcurrent protection information will be eliminated.
Please refer to maintenance part for display information and disposal method for details.
◆ Locked protection to IDU fan motor
During operation of IDU fan motor, if controller detected that the rotation speed of IDU fan motor less than 300/min or stop rotation, the
motor operates abnormally. In order to prevent damage to motor, controller will protect automatically, the system stops operation and
blocked information of IDU fan motor will be displayed. After turning off the unit, display won’t be displayed.
If turn on the unit again, the system will be restated up again. Blocked information of IDU fan motor will be eliminated. (For some mod-
els, they can only be restated up after re-energized)
Please refer to maintenance part for display information and disposal method for details.

3. Other Control Function Introduction


(1) Timer function

48 Technical Information
Service Manual

Controller has general timer function and clock timer function. When you select the remote controller with general timer function, only
the general timer function of controller can be activated; when you select the remote controller with clock timer, only the clock timer
function of controller can be activated.
① General timer: The precision of general timer is 0.5hour. 24hours circulated timer can’t be set.
◆ Timer ON: Timer ON can be set at unit OFF. If selected ON time is reached, the unit will start to operate according to previous
setting status. Time setting range is 0.5~24hr in 30-minute increments.
◆ Timer OFF: Timer OFF can be set at unit ON. If selected OFF time is reached, the unit will stop. Time setting range is 0.5~24hr in
30-minute increments.
② Clock timer: The precision of clock timer is 1minute. 24hours circulated timer can be set.
◆ Timer ON: If timer ON is set during operation of the unit, the unit will continue to operate. If timer ON is set at unit OFF, upon ON
time reaches, the unit will start to run according to previous setting status.
◆ Timer OFF: If timer OFF is set at unit OFF, the system will keep standby status. If timer OFF is set at unit ON, upon OFF time
reaches, the unit will stop operation.
◆ Timer change:
Although timer has been set, the unit still can be turned on/off by pressing ON/OFF button on the remote controller. You can also reset
the timer.
If timer ON and timer OFF are set at the same time during operation of the unit, the unit will keep running at current status till OFF
time reaches. Upon ON time reached, the system will be turned on automatically. The unit will operate circularly like that every
24hours.
If timer ON and timer OFF are set at unit OFF status, the system keep OFF status till ON time reaches. Upon OFF time reaches, the
system will be turned OFF automatically. The unit will operate circularly like that every 24hours.
(2) Emergency operation switch
After pressing this button, the system will operate according under auto mode and the IDU fan motor operates at auto speed. Swing
motor operates when the IDU fan motor operates. Press this button again to turn off the unit.

Emergency
operation switch OFF status Press ON status(Auto mode)

Press

(3) Sleep function


In this mode, the system will select proper sleep curve to operate according to different set temperature.
① If start up sleep function under cooling or drying mode, the system will increase set temperature automatically within a certain
range to operate.
② If start up sleep function under heating mode, the system will decrease set temperature automatically within a certain range to
operate.
(4) Turbo function
Turbo function can be set under cooling and heating modes. During operation of turbo function, the system operates at the maximum
fan speed.
(5) Dry function
Dry function can be set under cooling and drying modes. During operation of drying function, the fan will stop operation after operating
for a period of time when turning off the unit.
(6) Auto fan speed control
Auto fan speed control can be set under cooling, heating and fan mode. During operation of auto fan speed control, the IDU fan motor
will adjust the fan speed (high, medium or low speed) according to ambient temperature.
(7) Up&down swing control
① After energization, up & down swing motor will firstly have the horizontal louver rotate anticlockwise to position O to close air outlet.
If swing function has not been set after start-up of the unit, horizontal louver will turn clockwise to position D in heating mode, or turn
clockwise to level position L in other modes.
② If swing function is set when turning on the unit, the horizontal louver will swing between L and D.
Horizontal louver has 7 swing statuses: O(0°)
◆ Stay at position L: control by remote controller:
◆ Stay at position A: control by remote controller:
◆ Stay at position B: control by remote controller:
◆ Stay at position C: control by remote controller:
◆ Stay at position D: control by remote controller:
◆ Swing between L and D: control by remote controller: , , ,
◆ Stop at any postion between L and D (angles between L and D are equiangular) and no display
on remote controller.
③ When turning off the unit, horizontal louver will close at position O.
④ Swing action is valid only when set swing command and the IDU fan motor is operating.

Technical Information 49
Service Manual

(8) Dual-8 nixie tube display


◆ When the air conditioner is turned on for the first time, dual-8 nixie tube defaulted to display current set temperature.
◆ When controller receives signal of display set temperature, dual-8 nixie tube displays set temperature. When received remote control
signal is switched to indoor ambient temperature display status signal from other display status, dual-8 nixie tube will display indoor
ambient temperature for 3-5s, and then turn back to display set temperature. If remote control to set other status, the display keeps the
same.
◆ When air conditioner has a malfunction,dual-8 nixie tube will show relevant error code.
Indoor ambient temperature sensor is open/
F1
short-circuited
Indoor evaporator temperature sensor is
F2
open/short-circuited
H6 Blocked protection of IDU fan motor
C5 Malfunction protection of jumper cap
E5 Overcurrent protection
Zero-crossing inspection circuit malfunction
U8
of the IDU fan motor
E8 Overload protection
H3 Overload protection compressor

◆ When air conditioner is in auto defrosting, heating icon will be on and off.
◆ If turn off light button, all display will be turned off.

(9) Memory function


① Power failure when turning on the unit
◆ Memory content: ON status, mode, up&down swing, light, set temperature, set fan speed, general timer, Fahrenheit/ Celsius
◆ General timer can be memorized. Time of timer is calculated again from energization.
◆ Clock timer can’t be memorized.
② Power failure when turning off the unit
◆ Memory content: OFF status, mode, up&down swing, light, set temperature, set fan speed, general timer, Fahrenheit/ Celsius
◆ General timer can be memorized. Time of timer is calculated again from energization.
◆ Clock timer can’t be memorized.
4. Special Function
(1) Health function (for the model with health function)
During operation of the IDU fan motor, press health button on the remote controller to start health function (If there is not health button on
the remote controller, the unit defaults health function ON).
(2) I Feel function (for all models, but it needs the remote controller which can set this function)
When I FEEL command is received, the controller will operate according to the ambient temperature sent by the remote controller (For
defrosting and cold air prevention, the unit operates according to the ambient temperature sensed by the air conditioner). The remote
controller will regularly send ambient temperature data to the controller. When the data has not been received for a long time, the unit
will operate according to the temperature sensed by the air conditioner. If I FEEL function is not set, the ambient temperature will be that
sensed by the air conditioner.

50 Technical Information
Service Manual

Part Ⅱ : Installation and Maintenance


7. Notes for Installation and Maintenance
Safety Precautions: 10. If the power cord or connection wire is not long enough,
please get the specialized power cord or connection wire
Important! from the manufacture or distributor. Prohibit prolong the wire
by yourself.
Please read the safety precautions carefully before 11. For the air conditioner without plug, an air switch must
installation and maintenance. be installed in the circuit. The air switch should be all-pole
The following contents are very important for installation parting and the contact parting distance should be more than
and maintenance. 3mm.
12. Make sure all wires and pipes are connected properly and
Please follow the instructions below. the valves are opened before energizing.
13. Check if there is electric leakage on the unit body. If yes,
●The installation or maintenance must accord with the please eliminate the electric leakage.
instructions. 14. Replace the fuse with a new one of the same specification
●Comply with all national electrical codes and local if it is burnt down; don’t replace it with a cooper wire or
electrical codes. conducting wire.
●Pay attention to the warnings and cautions in this 15. If the unit is to be installed in a humid place, the circuit
manual. breaker must be installed.
●All installation and maintenance shall be performed by
distributor or qualified person.
●All electric work must be performed by a licensed Installation Safety Precautions:
technician according to local regulations and the
instructions given in this manual. 1. Select the installation location according to the require-
●Be caution during installation and maintenance. Prohibit ment of this manual.(See the requirements in installation
incorrect operation to prevent electric shock, casualty and part)
other accidents. 2. Handle unit transportation with care; the unit should not
be carried by only one person if it is more than 20kg.
3. When installing the indoor unit and outdoor unit, a suffi-
cient fixing bolt must be installed; make sure the installation
Warnings support is firm.
4. Ware safety belt if the height of working is above 2m.
5. Use equipped components or appointed components dur-
ing installation.
Electrical Safety Precautions: 6. Make sure no foreign objects are left in the unit after fin-
ishing installation.
1. Cut off the power supply of air conditioner before
checking and maintenance. Refrigerant Safety Precautions:
2. The air condition must apply specialized circuit and
prohibit share the same circuit with other appliances. 1. Avoid contact between refrigerant and fire as it generates
3. The air conditioner should be installed in suitable poisonous gas; Prohibit prolong the connection pipe by
location and ensure the power plug is touchable. welding.
4. Make sure each wiring terminal is connected firmly 2. Apply specified refrigerant only. Never have it mixed with
during installation and maintenance. any other refrigerant. Never have air remain in the refrigerant
5. Have the unit adequately grounded. The grounding line as it may lead to rupture or other hazards.
wire can’t be used for other purposes. 3. Make sure no refrigerant gas is leaking out when
6. Must apply protective accessories such as protective installation is completed.
boards, cable-cross loop and wire clip. 4. If there is refrigerant leakage, please take sufficient
7. The live wire, neutral wire and grounding wire of measure to minimize the density of refrigerant.
power supply must be corresponding to the live wire, 5. Never touch the refrigerant piping or compressor without
neutral wire and grounding wire of the air conditioner. wearing glove to avoid scald or frostbite.
8. The power cord and power connection wires can’t be
pressed by hard objects. Improper installation may lead to fire hazard, explosion,
9. If power cord or connection wire is broken, it must be electric shock or injury.
replaced by a qualified person.

Installation and Maintenance 51


Service Manual

Main Tools for Installation and Maintenance


1. Level meter, measuring tape 2. Screw driver 3. Impact drill, drill head, electric drill

4. Electroprobe 5. Universal meter 6. Torque wrench, open-end wrench, inner


hexagon spanner

7. Electronic leakage detector 8. Vacuum pump 9. Pressure meter

10. Pipe pliers, pipe cutter 11. Pipe expander, pipe bender 12. Soldering appliance, refrigerant container

52 Installation and Maintenance


Service Manual

8. Installation
8.1 Installation Dimension Diagram

Space to the ceiling

At least 15cm Space to the wall

At least 15cm
At least 15cm

Space to the wall

cm
00
At least 250cm
3
st
lea tio
n
At
Space to the

tr uc
obs
o the
et
ac
Sp
Space to the obstruction

the
to n
At least 50cm

e
ac tio
Sp truc
s st
ob
t lea
A cm
30

At least 30cm Drainage pipe

Space to th
e wall

n At least 50cm
tio cm
tr uc 0
obs t 20
he le as Space to the ob
struction
ot At
et
ac
Sp

Installation and Maintenance 53


Service Manual

Installation procedures

Start installation

Preparation before installation

Read the requirements select installation Prepare tools


for electric connection location

Select indoor unit Select outdoor unit


installation location installation location

Install wall-mounting Install the support of outdoor unit


frame, drill wall holes (select it according to the actual situation)

Connect pipes of indoor Fix outdoor unit


unit and drainage pipe

Connect wires of indoor unit Install drainage joint of outdoor unit


(only for cooling and heating unit)

Bind up pipes and


hang the indoor unit

Make the bound pipes pass


through the wall hole and then
connect outdoor unit

Connect pipes of outdoor unit

Connect wires of outdoor unit

Neaten the pipes

Vacuum pumping and leakage detection

Check after installation and test operation

Finish installation

Note: this flow is only for reference; please find the more detailed installation steps in this section.

54 Installation and Maintenance


Service Manual

8.2 Installation Parts-Checking 8.4 Electric Connection Requirement


1. Safety Precaution
No. Name No. Name
(1) Must follow the electric safety regulations when installing
1 Indoor unit 8 Sealing gum
the unit.
2 Outdoor unit 9 Wrapping tape
(2) According to the local safety regulations, use qualified
Support of outdoor
3 Connection pipe 10 power supply circuit and air switch.
unit
(3) Make sure the power supply matches with the requirement
4 Drainage pipe 11 Fixing screw
of air conditioner. Unstable power supply or incorrect wiring
Wall-mounting Drainage plug(cooling
5 12 may result in electric shock,fire hazard or malfunction. Please
frame and heating unit)
install proper power supply cables before using the air
Connecting Owner’s manual,
6 13 conditioner.
cable(power cord) remote controller
7 Wall pipe Air-conditioner Air switch capacity
09K 10A
Note:
12K 16A
1. Please contact the local agent for installation.
18/24K 25A
2. Don't use unqualified power cord.
(4) Properly connect the live wire, neutral wire and grounding
wire of power socket.
8.3 Selection of Installation Location (5) Be sure to cut off the power supply before proceeding any
work related to electricity and safety.
1. Basic Requirement:
(6) Do not put through the power before finishing installation.
Installing the unit in the following places may cause
(7) For appliances with type Y attachment,the instructions
malfunction. If it is unavoidable, please consult the local dealer:
shall contain the substance of thefollowing.If the supply cord is
(1) The place with strong heat sources, vapors, flammable or
damaged,it must be replaced by the manufacturer,its service
explosive gas, or volatile objects spread in the air.
agent or similarly qualified persons in order to avoid a hazard.
(2) The place with high-frequency devices (such as welding
(8) The temperature of refrigerant circuit will be high, please
machine, medical equipment).
keep the interconnection cable away from the copper tube.
(3) The place near coast area.
(9) The appliance shall be installed in accordance with national
(4) The place with oil or fumes in the air.
wiring regulations.
(5) The place with sulfureted gas.
(6) Other places with special circumstances. 2. Grounding Requirement:
(7) The appliance shall nost be installed in the laundry. (1) The air conditioner is first class electric appliance. It must
be properly grounding with specialized grounding device
by a professional. Please make sure it is always grounded
2. Indoor Unit:
effectively, otherwise it may cause electric shock.
(1) There should be no obstruction near air inlet and air outlet.
(2) The yellow-green wire in air conditioner is grounding wire,
(2) Select a location where the condensation water can be
which can't be used for other purposes.
dispersed easily andwon't affect other people.
(3) The grounding resistance should comply with national
(3) Select a location which is convenient to connect the
electric safety regulations.
outdoor unit and near the power socket.
(4) The appliance must be positioned so that the plug is
(4) Select a location which is out of reach for children.
accessible.
(5) The location should be able to withstand the weight of
(5) An all-pole disconnection switch having a contact separation
indoor unit and won't increase noise and vibration.
of at least 3mm in all poles should be connected in fixed wiring.
(6) The appliance must be installed 2.5m above floor.
(6) Including an air switch with suitable capacity, please note
(7) Don't install the indoor unit right above the electric
the following table. Air switch should be included magnet
appliance.
buckle and heating buckle function, it can protect the circuit-
(8) Please try your best to keep way from fluorescent lamp.
short and overload. (Caution: please do not use the fuse only
3. Outdoor Unit: for protect the circuit)
(1) Select a location where the noise and outflow air emitted by
the outdoor unit will not affect neighborhood. 8.5 Installation of Indoor Unit
(2) The location should be well ventilated and dry, in which the
1. Choosing Installation Iocation
outdoor unit won't be exposed directly to sunlight or strong
Recommend the installation location to the client and then
wind.
confirm it with the client.
(3) The location should be able to withstand the weight of
outdoor unit. 2. Install Wall-mounting Frame
(4) Make sure that the installation follows the requirement of (1) Hang the wall-mounting frame on the wall; adjust it in
installation dimension diagram. horizontal position with the level meter and then point out the
(5) Select a location which is out of reach for children and far screw fixing holes on the wall.
away from animals or plants.If it is unavoidable, please add (2) Drill the screw fixing holes on the wall with impact drill (the
fence for safety purpose. specification of drill head should be the same as the plastic
expansion particle) and then fill the plastic expansion particles

Installation and Maintenance 55


Service Manual

in the holes. 4. Outlet Pipe


(3) Fix the wall-mounting frame on the wall with tapping screws (1) The pipe can be led out in the direction of right, rear right,
(ST4.2X25TA) and then check if the frame is firmly installed by left or rear left.(As show in Fig.3)
pulling the frame. If the plastic expansion particle is loose, (2) When selecting leading out the pipe from left or right, please
please drill another fixing hole nearby. cut off the corresponding hole on the bottom case.(As show in
3. Install Wall-mounting Frame Fig.4)
(1) Choose the position of piping hole according to the direction
of outlet pipe. The position of piping hole should be a little
lower than the wall-mounted frame.(As show in Fig.1)
Wall Wall
Mark in the middle of it Level meter Left Rear left
Space Space
to the to the Fig.3 Rear right
09K: wall wall Right
above above
150mm 150mm
Left Right
Left Right
Φ55mm Φ55mm
Rear piping hole Rear piping hole

Wall
Mark in the middle of it Level meter
Wall Cut off Fig.4
Space Space the hole
to the to the
12K: wall wall
above above
150mm 150mm 5. Connect the Pipe of Indoor Unit
Left Right (1) Aim the pipe joint at the corresponding bellmouth.(As show
Φ55mm Φ55mm
Rear piping hole Rear piping hole
in Fig.5)
(2) Pretightening the union nut with hand.
Wall Wall (3) Adjust the torque force by referring to the following sheet.
Mark in the middle of it Level meter
Space Space Place the open-end wrench on the pipe joint and place the
to the to the torque wrench on the union nut. Tighten the union nut with
wall wall
18K: above above torque wrench.(As show in Fig.6)
150mm 150mm
(4) Wrap the indoor pipe and joint of connection pipe with
Left Right insulating pipe, and then wrap it with tape.(As show in Fig.7)
Φ55mm Φ55mm
Rear piping hole Rear piping hole

Open-end
Wall Wall
Mark in the middle of it Level meter wrench
Space Space
to the to the Union nut
wall wall Pipe joint Union nut Pipe
24K: above above Torque wrench Pipe
150mm 150mm

Left Right Fig.5 Indoor pipe Fig.6


Φ70mm Φ70mm
Rear piping hole Rear piping hole

Fig.1

(2) Open a piping hole with the diameter of Φ55 or Φ70 mm


Insulating pipe Fig.7
on the selected outlet pipe position.In order to drain smoothly,
slant the piping hole on the wall slightly downward to the
outdoor side with the gradient of 5-10°.(As show in Fig.2) Refer to the following table for wrench moment of force

Indoor Outdoor Hex nut diameter(mm) Tightening torque(N.m)


Φ6 15~20
Φ9.52 30~40
Φ12 45~55
Φ55 or Φ70 mm
Φ16 60~65
Φ19 70~75

Note: Fig.2 6. Install Drain Hose


(1) Connect the drain hose to the outlet pipe of indoor unit.(As
(1) Pay attention to dust prevention and take relevant safety
show in Fig.8)
measures when opening the hole.
(2) Bind the joint with tape.(As show in Fig.9)
(2) The plastic expansion particles are not provided and should
be bought locally.

56 Installation and Maintenance


Service Manual

Grounding Wiring board


wire
N(1) 2 4 5

Drain hose
Outlet pipe

Tape Wire clip


Outlet Drain hose
pipe Fig.9 Note: the wiring board is for reference only,
Fig.8 please refer to the actual one. Fig.13
(4) Put wiring cover back and then tighten the screw.
Note:
(5) Close the panel.
(1) Add insulating pipe in the indoor drain hose in order to
Note:
prevent condensation.
(1) All wires of indoor unit and outdoor unit should be
(2) The plastic expansion particles are not provided.
connected by a professional.
(As show in Fig.10)
(2) If the length of power connection wire is insufficient, please
Drain hose contact the supplier for a new one. Avoid extending the wire by
yourself.
(3) For the air conditioner with plug, the plug should be
Insulating pipe
Fig.10 reachable after finishing installation.
(4) For the air conditioner without plug, an air switch must be
7. Connect Wire of Indoor Unit
installed in the line. The air switch should be all-pole parting
(1) Open the panel, remove the screw on the wiring cover and
and the contact parting distance should be more than 3mm.
then take down the cover.(As show in Fig.11)
8. Bind up Pipe
Panel Screw
(1) Bind up the connection pipe, power cord
and drain hose with the band.(As show in Fig.14)
(2) Reserve a certain length of drain hose and power cord
for installation when binding them. When binding to a certain
degree, separate the indoor power and then separate the drain
Fig.11
Wiring cover hose.(As show in Fig.15)
(3) Bind them evenly.
(2) Make the power connection wire go through the cable-cross (4) The liquid pipe and gas pipe should be bound separately at
hole at the back of indoor unit and then pull it out from the front the end.
side.(As show in Fig.12) Indoor and
outdoor power cord
Indoor unit Gas
pipe

Cable-cross
hole
Liquid
Fig.14 Band pipe
Power connection Fig.12 Drain hose
wire
Connection pipe Drain hose
Band
(3) Remove the wire clip; connect the power connection wire
and signal control wire(Only for cooling and heating unit) to the
wiring terminal according to the color; tighten the screw and
then fix the power connection wire with wire clip.(As show in
Fig.13) Fig.15
Indoor power cord

09/12/18K cooling unit 09/12/18K cooling and heating unit


Note:
N(1) 2 N(1) 2 4 5
yellow-
yellow- (1) The power cord and control wire can't be crossed or
blue black green blue black violet orange
green
winding.
(2) The drain hose should be bound at the bottom.
Outdoor unit connection Outdoor unit connection
9. Hang the Indoor Unit
24K cooling unit 24K cooling and heating unit
(1) Put the bound pipes in the wall pipe and then make them
pass through the wall hole.
N(1) 2 3 N(1) 2 3 4 5

blue black brown yellow- yellow-


green green
blue black brown violet orange (2) Hang the indoor unit on the wall-mounting frame.
(3) Stuff the gap between pipes and wall hole with sealing gum.
Outdoor unit connection
(4) Fix the wall pipe.(As show in Fig.16)
Outdoor unit connection
(5) Check if the indoor unit is installed firmly and closed to the
wall.(As show in Fig.17)

Installation and Maintenance 57


Service Manual

4. Connect Indoor and Outdoor Pipes


Indoor Outdoor
(1) Remove the screw on the right handle of outdoor unit and
Wall pipe Fig.17
Sealing gum then remove the handle.(As show in Fig.21)
Upper hook (2) Remove the screw cap of valve and aim the pipe joint at the
bellmouth of pipe.(As show in Fig.22)

Liquid pipe Pipe joint


Liquid Gas pipe
Fig.16 Lower hook of valve
wall-mounting frame Union nut
Note: Gas valve
Do not bend the drain hose too excessively in order to prevent Fig.22
blocking.
(3) Pretightening the union nut with hand.
8.6 Installation of Outdoor Unit (4) Tighten the union nut with torque wrench .
1. Fix the Support of Outdoor Unit(Select it According to Refer to the following table for wrench moment of force
the Actual Installation Situation)
Hex nut diameter(mm) Tightening torque(N.m)
(1) Select installation location according to the house structure.
Φ6 15~20
(2) Fix the support of outdoor unit on the selected location with
Φ9.52 30~40
expansion screws.
Φ12 45~55
Note: Φ16 60~65
(1) Take sufficient protective measures when installing the Φ19 70~75
outdoor unit.
5. Connect Outdoor Electric Wire
(2) Make sure the support can withstand at least four times the
(1) Remove the wire clip; connect the power connection wire
unit weight.
and signal control wire(Only for cooling and heating unit) to the
(3) The outdoor unit should be installed at least 3cm above the
wiring terminal according to the color; fix them with screws.(As
floor in order to install drain joint.(As show in Fig.18)
show in Fig.23)
(4) For the unit with cooling capacity of 2300W~5000W, 6
expansion screws are needed; for the unit with cooling capacity 09/12/18K cooling unit 09/12/18K cooling and heating unit
of 6000W~8000W, 8 expansion screws are needed; for the 2 N(1) 2 4 5
N(1)
unit with cooling capacity of 10000W~16000W, 10 expansion yellow-
yellow-
screws are needed. blue black
(Brown) green
green blue black violet orange

Indoor unit connection Indoor unit connection

24K cooling unit 24K cooling and heating unit

N(1) 2 3 N(1) 2 3 4 5
Drain vent Chassis
blue black brown yellow- yellow- blue black brown violet orange
Outdoor drain joint green green
Drain hose
At least 3cm above the floor
Fig.18 Fig.19 Indoor unit connection Indoor unit connection
2. Install Drain Joint(Only for cooling and heating unit)
(1) Connect the outdoor drain joint into the hole on the chassis.
(2) Connect the drain hose into the drain vent. Grounding Wiring board
wire
(As show in Fig.19)
N(1) 2 4 5

3. Fix Outdoor Unit


(1) Place the outdoor unit on the support.
(2) Fix the foot holes of outdoor unit with bolts.
(As show in Fig.20) Wire clip
Handle
Note: the wiring board is for reference only, Fig.23
Foot holes please refer to the actual one.

(2) Fix the power connection wire and signal control wire(only
Screw
for cooling and heating unit) with wire clip.
Note:

Foot holes Handle (1) After tightening the screw, pull the power cord slightly to
Fig.21 check if it is firm.
Fig.20
(2) Never cut the power connection wire to prolong or shorten
the distance.
58 Installation and Maintenance
Service Manual

6. Neaten the Pipes


(1) The pipes should be placed along the wall, bent reasonably Liquid valve Piezometer
and hidden possibly. Min. semidiameter of bending the pipe is
Lo Hi

10cm. Gas valve

(2) If the outdoor unit is higher than the wall hole, you must set Refrigerant charging Valve cap
a U-shaped curve in the pipe before pipe goes into the room, vent
in order to prevent rain from getting into the room.(As show in Nut of refrigerant
Fig.24) Charging vent

Vacuum pump
The drain hos
can't raise Inner hexagon
upwards spanner

Wall
Fig.28 Close
Open
Fig.25
U-shaped curve
Fig.24 2. Leakage Detection
Drain hose (1) With leakage detector:
Note: Check if there is leakage with leakage detector.
(1) The through-wall height of drain hose shouldn't be higher (2) With soap water:
than the outlet pipe hole of indoor unit.(As show in Fig.25) If leakage detector is not available, please use soap water for
(2) Slant the drain hose slightly downwards. The drain hose leakage detection. Apply soap water at the suspected position
can't be curved, raised and fluctuant, etc.(As show in Fig.26) and keep the soap water for more than 3min. If there are air
(3) The water outlet can't be placed in water in order to drain bubbles coming out of this position, there's a leakage.
smoothly.(As show in Fig.27)
8.8 Check after Installation and Test
Operation
1. Check after Installation
Check according to the following requirement after finishing
The drain hose can't be fluctuant
installation.
No. Items to be checked Possible malfunction
The water outlet Has the unit been The unit may drop, shake or
can't be placed 1
The drain hose in water installed firmly? emit noise.
can't be fluctuant
The water Have you done the It may cause insufficient cooling
outlet can't be 2
fluctuant Fig.27 refrigerant leakage test? (heating) capacity.
Is heat insulation of It may cause condensation and
3
Fig.26 pipeline sufficient? water dripping.
It may cause condensation and
4 Is water drained well?
water dripping.
Is the voltage of power
8.7 Vacuum Pumping and Leak supply according to the It may cause malfunction or
5
Detection voltage marked on the damage the parts.
nameplate?
Is electric wiring and
1. Use Vacuum Pump It may cause malfunction or
(1) Remove the valve caps on the liquid valve and gas valve 6 pipeline installed
damage the parts.
and the nut of refrigerant charging vent. correctly?
(2) Connect the charging hose of piezometer to the refrigerant Is the unit grounded
7 It may cause electric leakage.
charging vent of gas valve and then connect the other charging securely?
hose to the vacuum pump. Does the power cord It may cause malfunction or
8
(3) Open the piezometer completely and operate for 10-15min follow the specification? damage the parts.
to check if the pressure of piezometer remains in -0.1MPa. Is there any obstruction It may cause insufficient cooling
9
(4) Close the vacuum pump and maintain this status for 1-2min in air inlet and air outlet? (heating).
to check if the pressure of piezometer remains in -0.1MPa. If The dust and
the pressure decreases, there may be leakage. sundries caused It may cause malfunction or
10
(5) Remove the piezometer, open the valve core of liquid valve during installation are damaging the parts.
and gas valve completely with inner hexagon spanner. removed?
(6) Tighten the screw caps of valves and refrigerant charging The gas valve and liquid
It may cause insufficient cooling
vent.(As show in Fig.28) 11 valve of connection pipe
(heating) capacity.
are open completely?

Installation and Maintenance 59


Service Manual

2. Test Operation
(1) Preparation of test operation
● The client approves the air conditioner installation.
● Specify the important notes for air conditioner to the client.
(2) Method of test operation
● Put through the power, press ON/OFF button on the remote
controller to start operation.
● Press MODE button to select AUTO, COOL, DRY, FAN and
HEAT to check whether the operation is normal or not.
● If the ambient temperature is lower than 16℃ , the air
conditioner can’t start cooling.

60 Installation and Maintenance


Service Manual

9. Maintenance
9.1 Error Code
Display Method Possible Causes(For specific maintenance
No. Malfunction
of Indoor Unit A/C Status method, please refer to the following procedure of
Name
(Error Code) troubleshooting)
1. The wiring terminal between indoor ambient temperature
The unit will stop operation as it sensor and main board is loosened or poorly contacted;
Indoor ambient
reaches the temperature point. 2. There’s short circuit due to trip-over of the parts on
temperature
During cooling and drying operation, controller;
1 sensor is F1
except IDU fan motor operates, other 3. Indoor ambient temperature sensor is damaged (Please
open/short-
loads stop operation; During heating check it by referring to the resistance table for temperature
circuited
operation, the system stops operation. sensor)
4. Main board is broken.
1. The wiring terminal between indoor evaporator
The unit will stop operation as it temperature sensor and main board is loosened or poorly
Indoor
reaches the temperature point. contacted;
evaporator
During cooling and drying operation, 2. There’s short circuit due to the trip-over of the parts on
temperature
2 F2 except IDU fan operates, other controller;
sensor is
loads stop operation; During heating 3.Indoor evaporator temperature sensor is damaged
open/short-
operation, the complete unit stops (Please check it by referring to the resistance table for
circuited
operation. temperature sensor)
4. Main board is broken.
1. The feedback terminal of PG motor is not connected
tightly.
IDU fan, ODU fan, compressor and
Blocked 2. The control terminal of PG motor is not connected
electric heat tube stop operation.
3 protection of H6 tightly.
Horizontal louver stops at the current
IDU fan motor 3. Fan blade rotates unsmoothly.
position.
4. Malfunction of motor
5. Main board is broken.
1. There’s not jumper cap on the main board.
Malfunction Operation of remote controller or
2. Jumper cap is not inserted properly and tightly.
4 protection of C5 control panel is available, but the unit
3. Jumper cap is damaged.
jumper cap won’t act.
4. Controller is damaged.
1. Unstable supply voltage. Normal fl uctuation shall be
within 10% of the rated voltage on the nameplate.
2. Supply voltage is too low and load is too high.
Overcurrent 3. Measure the current of live wire on main board. If the
protection(This current isn’t higher than the overcurrent protection value,
protection please check the controller.
During cooling and drying operation,
function is not 4. The indoor and outdoor heat exchangers are too dirty,
except IDU fan motor operates, other
5 available for E5 or the air inlet and air outlet are blocked.
loads stop operation; During heating
those models 5. The fan motor is not running. Abnormal fan speed: fan
operation, the system stops operation.
whose cool- speed is too low or the fan doesn’t run
ing capacity 6. The compressor is not running normally. There is
≤12000Btu/h) abnormal sound, oil leakage or the temperature of the
shell is too high, etc.
7. There’s blockage in the system (filth blockage, ice plug,
greasy blockage, Y-valve hasn’t been opened completely)
1. Outdoor and indoor heat exchangers are too dirty or the
air inlet/outlet is blocked
2. Fan motor is not working. Abnormal fan speed; fan
speed is too low or the fan doesn’t run.
Overload 3. Compressor doesn’t work normally. Strange noise or
6 E8 Unit stops working.
malfunction leakage occurs. Temperature of the shell is too high.
4. System is blocked inside (dirt block, ice block, oil block,
Y-valve not fully open)
5.Temperature sensor of main board doesn’t sense
correctly.

Installation and Maintenance 61


Service Manual

Zero-crossing
1. Quick de-energization and energization. Wrong
inspection
Operation of remote controller or judgement by the controller because the electric-
circuit
7 U8 control panel is available, but the unit discharging of capacitor is slow.
malfunction
won’t act. 2. Zero-crossing inspection circuit of main board for
of the IDU fan
controller is abnormal.
motor
1. Outdoor and indoor heat exchangers are too dirty or the
air inlet/outlet is blocked.
2. Fan motor is not working Abnormal fan speed; fan
speed is too low or the fan doesn't run.
Overload 3. Compressor doesn't work normally.Strange noise or
8 protection for H3 The entire unit stops. leakage occurs.Temperature of the shell is too high.
compressor 4. System is blocked inside(dirt block, ice block, oil block,
Y-valve not fully open).
5. High pressure switch is abnormal.
6. The refrigerant is leaking and cause overheating
protection to compressor.

62 Installation and Maintenance


Service Manual

9.2 Procedure of Troubleshooting


1. Malfunction of Temperature Sensor F1, F2
Main detection points:
● Is the wiring terminal between the temperature sensor and the controller loosened or poorly contacted?
● Is there short circuit due to trip-over of the parts?
● Is the temperature sensor broken?
● Is mainboard broken?
Malfunction diagnosis process:
Start

Is the wiring terminal between the


temperature sensor and the controller Yes
loosened or poorly contacted?

Insert the temperature


sensor tightly

No
No Is malfunction
eliminated

Is there short circuit due to trip- Yes


over of the parts

Make the parts upright

No

No Is malfunction Yes
eliminated

Is the temperature sensor normal No Yes


according to the resistance table?

Replace it with a
temperature sensor with
the same model

Yes

No Is malfunction
eliminated

Replace the mainboard with


the same model.

Yes

End

Installation and Maintenance 63


Service Manual

2. Malfunction of Blocked Protection of IDU Fan Motor H6


Main detection points:
● SmoothlyIs the control terminal of PG motor connected tightly?
● SmoothlyIs the feedback interface of PG motor connected tightly?
● The fan motor can't operate?
● The motor is broken?
● Detectioncircuit of the mainboard is defined abnormal?
Malfunction diagnosis process:
Start

While power is off stir the blade


with a tool to see whether the No
blade rotates smoothly
Tighten the screw; reassemble the blade, motor
and shaft bearing rubber base sub-assy to make
sure there is no foreign object between them
Yes

No Is malfunction Yes
eliminated

Check if the connection of PG No


motor feedback terminal is firm
Insert the control terminal
of PG motor tightly

Yes
No Is malfunction Yes
eliminated

Check if the connection of PG No


motor control terminal is firm

Reinstall the blade


and motor correctly
Yes

No Is malfunction Yes
eliminated

Turn on the unit again; measure


whether the output voltage on Yes
control terminal for PG motor is Yes
more than 50V within 1 min after
the louvers are opened

Yes
Is the motor started up

No
Measure the voltage of this foot to
neutral wire on the mainboard Replace PG motor
No

No Is malfunction Yes
eliminated

Replace the mainboard


with the same model

End

64 Installation and Maintenance


Service Manual

3. Malfunction of Protection of Jumper Cap C5


Main detection points:
● Is there jumper cap on the mainboard?
● Is the jumper cap inserted correctly and tightly?
● The jumper is broken?
● The motor is broken?
● Detection circuit of the mainboard is defined abnormal?
Malfunction diagnosis process:

Start

No Appearance of the
Is there jumper cap on the mainboard?
jumper cap

Assemble the jumper


cap with the same model
Yes

No Is malfunction
eliminated

Is the jumper cap inserted correctly No


and tightly?

Insert the jumper


cap tightly
Yes

No Is malfunction Yes
eliminated

Replace the jumper cap with


the same model

Is malfunction Yes
eliminated

Yes
No

Replace the mainboard


with the same model

End

Installation and Maintenance 65


Service Manual

4. Malfunction of Overcurrent Protection E5


Main detection points:
● Is the supply voltage unstable with big fluctuation?
● Is the supply voltage too low with overload?
● Hardware trouble?
Malfunction diagnosis process:

Start

Yes Normal fluctuation should be within 10 % Is malfunction Yes


Is the supply voltage unstable
with big fluctuation? of the rated voltage on the nameplate eliminated

No No

Is the supply voltage too low Yes Adjust the supply voltage to maintain it Is malfunction Yes
with overload? within normal range eliminated

No No

Is the indoor / outdoor Yes Clean the indoor and outdoor heat Is malfunction Yes
heat exchanger dirty,or are the air inlet exchangers and remove the blockage eliminated
and outlet blocked? of air inlet and outlet

No
No

The fan is abnormal? Fan Yes Check the motor and reinstall the Is malfunction Yes
speed is too low or fan doesn’t rotate motor to have the fan run normally eliminated

No No

Measure the current of live wire on


the main board with a clamp ampere No Replace the mainboard with the same Yes
Is malfunction
meter. Is the current higher than the model eliminated
value of the overcurrent protection?

Yes No

Is there blockage inside the system? Yes


(Filth blockage, ice plug, greasy Flush the heat exchangers with high Is malfunction Yes
blockage, the cut off valve hasn’t been pressure nitrogen eliminated
opened completely)

No No

Is the compressor running abnormally? Yes


Is malfunction Yes
Is there abnormal sound or oil leakage; Replace the compressor
eliminated
Is the temperature of the shell too high,
etc.?

No

Replace the mainboard


with the same model

End

66 Installation and Maintenance


Service Manual

5. High temperature and overload protection (AP1 below means control board of outdoor unit) E8
Main detection points:
● If the outdoor ambient temperature is in normal range;
● If the indoor and outdoor fan are running normally;
● If the radiating environment of indoor and outdoor unit is good.
Malfunction diagnosis process:

Start

Normal protection, please use it


If the outdoor ambient temperature is Yes Unit restarts Yes
after improving the outdoor ambient
higher than 53°C? normally
temperature

No
No

Improve the radiating environment of


If the airflow of indoor and outdoor unit Unit restarts Yes
unit (clean the heat exchanger and
is good? remove surrounding obstacles) normally

No
No

If the indoor and outdoor fan are Yes Adjust the


Connect normally?
running normally? connection

Yes

Yes
Yes Replace fan
Fan capacitor is broken? capacitor
Replace outdoor
mainboard
No

Motor is broken? Yes Replace motor

No

Replace mainboard

End

Installation and Maintenance 67


Service Manual

6. Malfunction of Zero-crossing Inspection Circuit Malfunction of the IDU Fan Motor U8


Main detection points:
● Instant energization afte de-energization while the capacitordischarges slowly?
● The zero-cross detectioncircuit of the mainboard is defined abnormal?
Malfunction diagnosis process:

Start

Turn power off for


1minute,the turn
back on

The unit returns to normal.


U8 is still No Conclusion:U8 is displayed due to
displayed power off/on while the
capacitor discharges slowly.

Yes

The zero-cross detection circuit


of the mainboard is defined
abnormal.Replace the mainboard
with the same model

End

68 Installation and Maintenance


Service Manual

7. Overload Protection Compressor H3


Main detection points:
● Heat exchange of unit is not good? (heat exchanger is dirty and unit radiating environment is bad)
● Fan motor is not working?
● Too much load of the system causes high temperature of compressor after working for a long time?
● Whether high pressure switch is normal?
● If the refrigerant is leaked?
Malfunction diagnosis process:

Start

Outdoor and indoor heat Yes Yes


Clean the outdoor and indoor heat exchangers Malfunction is
exchangers are too dirty or the air
and remove blockage of air inlet/outlet. eliminated.
inlet/outlet is blocked.

No
No

Fan motor is not working.


Yes Check motor and re-install the motor to Malfunction is Yes
Abnormal fan speed; fan speed is too
low or the fan doesn't run. make it run normally. eliminated.

No No

Compressor doesn't work Malfunction is Yes


Yes
normally. Strange noise or leakage occurs. Make compressor run normally. eliminated.
Temperature of the shell is too high.

No
No

System is blocked inside Yes Malfunction is Yes


(dirt block, ice block, oil block, Y-valve not Remove blockage in the system. eliminated.
fully open).

No
No

Check whether high Yes Replace high pressure switch Malfunction is Yes
pressure switch is normal eliminated.

No No

Check whether the


refrigerant is leaking and cause Yes Check the leaking status of refrigerant Malfunction is Yes
overheating protection to compressor and charge refrigerant eliminated.

No
No

Replace a main
board of the
same model.

End

Installation and Maintenance 69


Service Manual

9.3 Maintenance Method for Normal Malfunction


1. Air Conditioner Can't be Started Up
Possible Causes Discriminating Method (Air conditioner Status) Troubleshooting
Confirm whether it's due to power failure. If yes,
No power supply, or poor After energization, operation indicator isn’t bright wait for power recovery. If not, check power
connection for power plug and the buzzer can't give out sound supply circuit and make sure the power plug is
connected well.
Wrong wire connection between
Check the circuit according to circuit diagram
indoor unit and outdoor unit, Under normal power supply circumstances,
and connect wires correctly. Make sure all
or poor connection for wiring operation indicator isn't bright after energization
wiring terminals are connected firmly
terminals
Make sure the air conditioner is grounded
reliably
Make sure wires of air conditioner is connected
After energization, room circuit breaker trips off at
Electric leakage for air conditioner correctly
once
Check the wiring inside air conditioner. Check
whether the insulation layer of power cord is
damaged; if yes, place the power cord.
Model selection for air switch is
After energization, air switch trips off Select proper air switch
improper
After energization, operation indicator is bright,
Replace batteries for remote controller
Malfunction of remote controller while no display on remote controller or buttons
Repair or replace remote controller
have no action.

2. Poor Cooling (Heating) for Air Conditioner

Possible Causes Discriminating Method (Air conditioner Status) Troubleshooting


Set temperature is improper Observe the set temperature on remote controller Adjust the set temperature
Rotation speed of the IDU fan
Small wind blow Set the fan speed at high or medium
motor is set too low
Filter of indoor unit is blocked Check the filter to see it's blocked Clean the filter
Check whether the installation postion is proper
Installation position for indoor unit Adjust the installation position, and install the
according to installation requirement for air
and outdoor unit is improper rainproof and sunproof for outdoor unit
conditioner
Discharged air temperature during cooling is
higher than normal discharged wind temperature;
Discharged air temperature during heating is Find out the leakage causes and deal with it.
Refrigerant is leaking
lower than normal discharged wind temperature; Add refrigerant.
Unit's pressure is much lower than regulated
range
Malfunction of 4-way valve Blow cold wind during heating Replace the 4-way valve
Discharged air temperature during cooling is
higher than normal discharged wind temperature;
Discharged air temperature during heating is
Malfunction of capillary lower than normal discharged wind temperature; Replace the capillary
Unit't pressure is much lower than regulated
range. If refrigerant isn’t leaking, part of capillary
is blocked
Flow volume of valve is The pressure of valves is much lower than that
Open the valve completely
insufficient stated in the specification
Refer to point 3 of maintenance method for
Malfunction of horizontal louver Horizontal louver can’t swing
details
Refer to troubleshooting for H6 for maintenance
Malfunction of the IDU fan motor The IDU fan motor can’t operate
method in details
Refer to point 4 of maintenance method for
Malfunction of the ODU fan motor The ODU fan motor can't operate
details
Refer to point 5 of maintenance method for
Malfunction of compressor Compressor can't operate
details

3. Horizontal Louver Can't Swing


Possible Causes Discriminating Method (Air conditioner Status) Troubleshooting
Connect wires according to wiring diagram to
Wrong wire connection, or poor Check the wiring status according to circuit
make sure all wiring terminals are connected
connection diagram
firmly
Stepping motor is damaged Stepping motor can't operate Repair or replace stepping motor
Others are all normal, while horizontal louver
Main board is damaged Replace the main board with the same model
can't operate

70 Installation and Maintenance


Service Manual

4. ODU Fan Motor Can't Operate


Possible causes Discriminating method (air conditioner status) Troubleshooting
Connect wires according to wiring diagram to
Wrong wire connection, or poor Check the wiring status according to circuit
make sure all wiring terminals are connected
connection diagram
firmly
Measure the capacity of fan capacitor with an
Capacity of the ODU fan motor is universal meter and find that the capacity is out of
Replace the capacity of fan
damaged the deviation range indicated on the nameplate of
fan capacitor.
Power voltage is a little low or Use universal meter to measure the power supply
Suggest to equip with voltage regulator
high voltage. The voltage is a little high or low
When unit is on, cooling/heating performance
Change compressor oil and refrigerant. If no
Motor of outdoor unit is damaged is bad and ODU compressor generates a lot of
better, replace the compressor with a new one
noise and heat.

5. Compressor Can't Operate


Possible causes Discriminating method (air conditioner status) Troubleshooting
Connect wires according to wiring diagram to
Wrong wire connection, or poor Check the wiring status according to circuit
make sure all wiring terminals are connected
connection diagram
firmly
Measure the capacity of fan capacitor with an
Capacity of compressor is universal meter and find that the capacity is out of
Replace the compressor capacitor
damaged the deviation range indicated on the nameplate of
fan capacitor.
Power voltage is a little low or Use universal meter to measure the power supply
Suggest to equip with voltage regulator
high voltage. The voltage is a little high or low
Use universal meter to measure the resistance
Coil of compressor is burnt out Repair or replace compressor
between compressor terminals and it's 0
Cylinder of compressor is blocked Compressor can't operate Repair or replace compressor

6. Air Conditioner is Leaking


Possible causes Discriminating method (air conditioner status) Troubleshooting
Eliminate the foreign objects inside the drain
Drain pipe is blocked Water leaking from indoor unit
pipe
Drain pipe is broken Water leaking from drain pipe Replace drain pipe
Water leaking from the pipe connection place of
Wrapping is not tight Wrap it again and bundle it tightly
indoor unit

7. Abnormal Sound and Vibration

Possible causes Discriminating method (air conditioner status) Troubleshooting


When turn on or turn off the unit,
the panel and other parts will Normal phenomenon. Abnormal sound will
There's the sound of "PAPA"
expand and there's abnormal disappear after a few minutes.
sound
When turn on or turn off the unit,
there's abnormal sound due Normal phenomenon. Abnormal sound will
Water-running sound can be heard
to flow of refrigerant inside air disappear after a few minutes.
conditioner
Foreign objects inside the indoor Remove foreign objects. Adjust all parts'
unit or there're parts touching There's abnormal sound fro indoor unit position of indoor unit, tighten screws and stick
together inside the indoor unit damping plaster between connected parts
Foreign objects inside the outdoor Remove foreign objects. Adjust all parts'
unit or there're parts touching There's abnormal sound fro outdoor unit position of outdoor unit, tighten screws and
together inside the outdoor unit stick damping plaster between connected parts
Short circuit inside the magnetic During heating, the way valve has abnormal
Replace magnetic coil
coil electromagnetic sound
Adjust the support foot mat of compressor,
Abnormal shake of compressor Outdoor unit gives out abnormal sound
tighten the bolts
If add too much refrigerant during maintenance,
Abnormal sound inside the
Abnormal sound inside the compressor please reduce refrigerant properly. Replace
compressor
compressor for other circumstances.

Installation and Maintenance 71


Service Manual

10. Exploded View and Parts List


10.1 Indoor Unit
09/12K

27 28 29 30 10

9 11
8

X-FAN
I

I
12
7

6 13

4
14

3
15

16

2 17
1 18
19
20
A1
/B6
/C2
pan
21
el 22
A6
pan
el
C6
pan
23
el

24

26

25

The component picture is only for reference; please refer to the actual product.

72 Installation and Maintenance


Service Manual

Part Code
Description
No. GWC09QB-K3NNA1B/I GWH09QB-K3NNA1B/I Qty
Product Code CA419N06000 CA419N06100
1 Front Case Assy 20022495 20022495 1
2 Display Board 30565231 30565231 1
3 Front Case Assy 20022495 20022495 1
4 Helicoid Tongue 26112508 26112508 1
5 Left Axile Bush 10512037 10512037 1
6 Rear Case assy 22202560 22202560 1
7 Drainage Hose 0523001408 0523001408 1
8 Ring of Bearing 26152022 26152022 1
9 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
10 Evaporator Support 24212180 24212180 1
11 Evaporator Assy 01002678 01002678 1
12 Wall Mounting Frame 01252043 01252043 1
13 Cross Flow Fan 10352059 10352059 1
14 Fan Motor 150120874 150120874 1
15 Connecting pipe clamp 2611216401 2611216401 1
16 Rubber Plug (Water Tray) 76712012 76712012 1
17 Stepping Motor 1521212901 1521212901 1
18 Crank 73012005 73012005 1
19 Electric Box Assy 20402660 20402679 1
20 Axile Bush 10542036 10542036 1
21 Terminal Board 42010276 42010268 1
22 Jumper 4202300113 4202300113 1
23 Main Board 30135964 30135968 1
24 Electric Box Cover Sub-Assy 02601070 02601070 1
25 Shield Cover of Electric Box Cover 20112207 01592135 1
26 Electric Box Cover 20112207 20112207 1
27 Power Cord 400203495 400203495 1
28 Connecting Cable / 40020536 0
29 Connecting Cable 40020540 40020540 0
30 Remote Controller 30510474 30510474 1

Above data is subject to change without notice.

Installation and Maintenance 73


Service Manual

Part Code
Description
No. GWC09QB-K3NNA1J/I GWH09QB-K3NNA1J/I Qty
Product Code CA419N15100 CA419N15000
1 Front Case Assy 20022495 20022495 1
2 Display Board 30565231 30565231 1
3 Front Case Assy 20022495 20022495 1
4 Helicoid Tongue 26112508 26112508 1
5 Left Axile Bush 10512037 10512037 1
6 Rear Case assy 20162010 20162010 1
7 Drainage Hose 0523001408 0523001408 1
8 Ring of Bearing 26152022 26152022 1
9 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
10 Evaporator Support 24212180 24212180 1
11 Evaporator Assy 01100100095 01100100095 1
12 Wall Mounting Frame 01252043 01252043 1
13 Cross Flow Fan 10352059 10352059 1
14 Fan Motor 150120874 150120874 1
15 Connecting pipe clamp 2611216401 2611216401 1
16 Rubber Plug (Water Tray) 76712012 76712012 1
17 Stepping Motor 1521212901 1521212901 1
18 Crank 73012005 73012005 1
19 Electric Box Assy 20402660 20402679 1
20 Axile Bush 10542036 10542036 1
21 Terminal Board 42010276 42010268 1
22 Jumper 4202300113 4202300113 1
23 Main Board 30135964 30135968 1
24 Electric Box Cover Sub-Assy 01402065 01402065 1
25 Shield Cover of Electric Box Cover 01592150 01592150 1
26 Electric Box Cover 20112207 20112207 1
27 Power Cord 400203495 400203495 1
28 Connecting Cable / 40020536 0
29 Connecting Cable 40020540 40020540 0
30 Remote Controller 30510474 30510474 1

Above data is subject to change without notice.

74 Installation and Maintenance


Service Manual

Part Code
Description
No. GWC12QC-K3NNA1G/I GWH12QC-K3NNA1D/I Qty
Product Code CA419N15300 CA419N15200
1 Front Case Assy 20022489 20022489 1
2 Display Board 30565231 30565231 1
3 Front Case Assy 20022489 20022489 1
4 Helicoid Tongue 26112507 26112507 1
5 Left Axile Bush 10512037 10512037 1
6 Rear Case assy 22202375 22202375 1
7 Drainage Hose 05230014 05230014 1
8 Ring of Bearing 26152022 26152022 1
9 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
10 Evaporator Support 24212179 24212179 1
11 Evaporator Assy 01002976 01002976 1
12 Wall Mounting Frame 01252484 01252484 1
13 Cross Flow Fan 10352056 10352056 1
14 Fan Motor 15012146 15012146 1
15 Connecting pipe clamp 2611216401 2611216401 1
16 Rubber Plug (Water Tray) 76712012 76712012 1
17 Stepping Motor 1521210701 1521210701 1
18 Crank 73012005 73012005 1
19 Electric Box Assy 20102000471 10000202018 1
20 Axile Bush 10542036 10542036 1
21 Terminal Board 42010276 42010268 1
22 Jumper 4202300107 4202300107 1
23 Main Board 30145022 30145024 1
24 Electric Box Cover Sub-Assy 01402065 01402065 1
25 Shield Cover of Electric Box Cover 01592150 01592150 1
26 Electric Box Cover 20112207 20112207 1
27 Power Cord 400203495 400203495 1
28 Connecting Cable 40020540 40020540 0
29 Connecting Cable / 40020536 0
30 Remote Controller 30510516 30510516 1

Above data is subject to change without notice.

Installation and Maintenance 75


Service Manual

Part Code
Description
No. GWH09QB-K3NNB6B/I GWH12QC-K3NNB6B/I Qty
Product Code CA435N01400 CA435N01300
1 Front Case Assy 00000200040 00000200045 1
2 Display Board 30565281 30565281 1
3 Front Case Assy 00000200040 00000200045 1
4 Helicoid Tongue 26112508 26112436 1
5 Left Axile Bush 10512037 10512037 1
6 Rear Case assy 20162010 00000100093 1
7 Drainage Hose 0523001408 05230014 1
8 Ring of Bearing 26152022 26152022 1
9 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
10 Evaporator Support 24212180 24212179 1
11 Evaporator Assy 0100200004402 01002976 1
12 Wall Mounting Frame 01252043 01252484 1
13 Cross Flow Fan 10352059 10352056 1
14 Fan Motor 150120874 1501214603 1
15 Connecting pipe clamp 2611216401 2611216401 1
16 Rubber Plug (Water Tray) 76712012 76712012 1
17 Stepping Motor 1521212901 1521210701 1
18 Crank 73012005 73012005 1
19 Electric Box Assy 10000202553 10000202538 1
20 Axile Bush 10542036 10542036 1
21 Terminal Board 42010268 42010268 1
22 Jumper 4202300117 4202300120 1
23 Main Board 30135968 30145024 1
24 Electric Box Cover Sub-Assy 01402065 01402065 1
25 Shield Cover of Electric Box Cover 01592150 01592150 1
26 Electric Box Cover 20112207 20112207 1
27 Power Cord 400203495 400203495 1
28 Connecting Cable 40020536 40020536 0
29 Connecting Cable 40020540 40020540 0
30 Remote Controller 30510474 30510474 1

Above data is subject to change without notice.

76 Installation and Maintenance


Service Manual

Part Code
Description
No. GWH09QB-K3NNC6B/I GWH12QC-K3NNC6B/I Qty
Product Code CA443N01000 CA443N01300
1 Front Case Assy 20000300101 20000300102 1
2 Display Board 30565260 30565260 1
3 Front Case Assy 00000200040 00000200045 1
4 Helicoid Tongue 26112508 26112436 1
5 Left Axile Bush 10512037 10512037 1
6 Rear Case assy 20162010 00000100093 1
7 Drainage Hose 0523001408 05230014 1
8 Ring of Bearing 26152022 26152022 1
9 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
10 Evaporator Support 24212180 24212179 1
11 Evaporator Assy 0100200004402 01002976 1
12 Wall Mounting Frame 01252043 01252484 1
13 Cross Flow Fan 10352059 10352056 1
14 Fan Motor 150120874 1501214603 1
15 Connecting pipe clamp 2611216401 2611216401 1
16 Rubber Plug (Water Tray) 76712012 76712012 1
17 Stepping Motor 1521212901 1521210701 1
18 Crank 73012005 73012005 1
19 Electric Box Assy 10000202554 10000204722 1
20 Axile Bush 10542036 10542036 1
21 Terminal Board 42010268 42010268 1
22 Jumper 4202300117 4202300120 1
23 Main Board 30135968 30145024 1
24 Electric Box Cover Sub-Assy 0140206501 0140206501 1
25 Shield Cover of Electric Box Cover 01592150 01592150 1
26 Electric Box Cover 20112207 20112207 1
27 Power Cord 400203495 400203495 1
28 Connecting Cable 40020536 40020536 0
29 Connecting Cable 40020540 40020540 0
30 Remote Controller 30510474 30510474 1

Above data is subject to change without notice.

Installation and Maintenance 77


Service Manual

Part Code
Description
No. GWC12QC-K3NNA1B/I GWH12QC-K3NNA1B/I Qty
Product Code CA419N06400 CA419N06500
1 Front Case Assy 20022489 20022489 1
2 Display Board 30565231 30565231 1
3 Front Case Assy 20022489 20022489 1
4 Helicoid Tongue 26112507 26112507 1
5 Left Axile Bush 10512037 10512037 1
6 Rear Case assy 22202557 22202557 1
7 Drainage Hose 05230014 05230014 1
8 Ring of Bearing 26152022 26152022 1
9 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
10 Evaporator Support 24212179 24212179 1
11 Evaporator Assy 01002976 01002976 1
12 Wall Mounting Frame 01252484 01252484 1
13 Cross Flow Fan 10352056 10352056 1
14 Fan Motor 15012146 15012146 1
15 Connecting pipe clamp 2611216401 2611216401 1
16 Rubber Plug (Water Tray) 76712012 76712012 1
17 Stepping Motor 1521210701 1521210701 1
18 Crank 73012005 73012005 1
19 Electric Box Assy 20102000471 20102000409 1
20 Axile Bush 10542036 10542036 1
21 Terminal Board 42010276 42010268 1
22 Jumper 4202300107 4202300107 1
23 Main Board 30145022 30145024 1
24 Electric Box Cover Sub-Assy 02601070 02601070 1
25 Shield Cover of Electric Box Cover 01592135 01592135 1
26 Electric Box Cover 20112207 20112207 1
27 Power Cord 400203495 400203495 1
28 Connecting Cable / 40020536 0
29 Connecting Cable 40020540 40020540 0
30 Remote Controller 30510474 30510474 1

Above data is subject to change without notice.

78 Installation and Maintenance


Service Manual

Part Code
Description
No. GWC12QC-K3NNA6B/I GWC12QC-K3NNC2B/I Qty
Product Code CA427N05600 CA439N03000
1 Front Case Assy 2002273101 00000200045 1
2 Display Board 30565265 30565281 1
3 Front Case Assy 2002273101 00000200045 1
4 Helicoid Tongue 26112507 26112436 1
5 Left Axile Bush 10512037 10512037 1
6 Rear Case assy 22202375 00000100093 1
7 Drainage Hose 05230014 05230014 1
8 Ring of Bearing 26152022 26152022 1
9 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
10 Evaporator Support 24212179 24212179 1
11 Evaporator Assy 01002976 01002976 1
12 Wall Mounting Frame 01252484 01252484 1
13 Cross Flow Fan 10352056 10352056 1
14 Fan Motor 15012146 1501214603 1
15 Connecting pipe clamp 2611216401 2611216401 1
16 Rubber Plug (Water Tray) 76712012 76712012 1
17 Stepping Motor 1521210701 1521210701 1
18 Crank 73012005 73012005 1
19 Electric Box Assy 10000202264 10000203363 1
20 Axile Bush 10542036 10542036 1
21 Terminal Board 42010276 42010276 1
22 Jumper 4202300120 4202300120 1
23 Main Board 30145022 30145022 1
24 Electric Box Cover Sub-Assy 01402065 01402065 1
25 Shield Cover of Electric Box Cover 01592150 01592150 1
26 Electric Box Cover 20112207 20112207 1
27 Power Cord 400203495 400203495 1
28 Connecting Cable / / 0
29 Connecting Cable 40020540 40020540 0
30 Remote Controller 30510474 30510474 1

Above data is subject to change without notice.

Installation and Maintenance 79


Service Manual

18K

The component picture is only for reference; please refer to the actual product.

80 Installation and Maintenance


Service Manual

Part Code
Description
No. GWC18QD-K3NNA1B/I GWH18QD-K3NNA1B/I Qty
Product Code CA419N06600 CA419N06700
1 Decorative Strip 20192613 20192613 1
2 Front Panel 20022481S 20022481S 1
3 Display Board 30565233 30565233 1
4 Filter Sub-Assy 11122089 11122089 2
5 Decorative Board (Left) 20192612 20192612 1
6 Front Case 20022484 20022484 1
7 Guide Louver 10512734 10512734 1
8 Axile Bush 10542036 10542036 2
9 Air Louver 10512732 10512732 3
10 Helicoid Tongue 26112512 26112512 1
11 Left Axile Bush 10512037 10512037 1
12 Rear Case assy 22202556 22202571 1
13 Rubber Plug (Water Tray) 76712012 76712012 1
14 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
15 Ring of Bearing 26152025 26152025 1
16 Evaporator Support 24212177 24212177 1
17 Evaporator Assy 01002686 01002686 1
18 Cross Flow Fan 10352060 10352060 1
19 Fan Motor 15012145 15012145 1
20 Motor Press Plate 26112511 26112511 1
21 Wall Mounting Frame 01362026 01362026 1
22 Connecting pipe clamp 2611218801 2611218801 1
23 Crank 73012005 73012005 1
24 Stepping Motor 1521240212 1521240212 1
25 Drainage Hose 05230014 05230014 1
26 Electric Box Assy 20102000390 10000200091 1
27 Lower Shield of Electric Box 01592139 01592139 1
28 Electric Box 20112211 20112211 1
29 Jumper 4202300116 4202300115 1
30 Main Board 30135987 30135991 1
31 Shield Cover of Electric Box 01592140 01592140 1
32 Electric Box Cover 20112209 20112209 1
33 Terminal Board 42010276 42010268 1
34 Decorative Board (Right) 20192611 20192611 1
35 Screw Cover 242520179 242520179 3
36 Electric Box Cover2 20112210 20112210 1
37 Power Cord 400203485 400203485 1
38 Connecting Cable / 4002053603 0
39 Connecting Cable 400205401 400205401 0
40 Remote Controller 30510474 30510474 1

Above data is subject to change without notice.

Installation and Maintenance 81


Service Manual

Part Code
Description
No. GWC18QD-K3NNA1F/I GWH18QD-K3NNA1D/I Qty
Product Code CA419N14000 CA419N13900
1 Decorative Strip 20192613 20192613 1
2 Front Panel 20022481S 20022481S 1
3 Display Board 30565233 30565233 1
4 Filter Sub-Assy 11122089 11122089 2
5 Decorative Board (Left) 20192612 20192612 1
6 Front Case 20022484 20022484 1
7 Guide Louver 10512734 10512734 1
8 Axile Bush 10542036 10542036 2
9 Air Louver 10512732 10512732 3
10 Helicoid Tongue 26112512 26112512 1
11 Left Axile Bush 10512037 10512037 1
12 Rear Case assy 22202571 22202571 1
13 Rubber Plug (Water Tray) 76712012 76712012 1
14 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
15 Ring of Bearing 26152025 26152025 1
16 Evaporator Support 24212177 24212177 1
17 Evaporator Assy 01002686 01002686 1
18 Cross Flow Fan 10352060 10352060 1
19 Fan Motor 1501214502 1501214502 1
20 Motor Press Plate 26112511 26112511 1
21 Wall Mounting Frame 01362026 01362026 1
22 Connecting pipe clamp 2611218801 2611218801 1
23 Crank 73012005 73012005 1
24 Stepping Motor 1521240212 1521240212 1
25 Drainage Hose 05230014 05230014 1
26 Electric Box Assy 20102000390 10000200091 1
27 Lower Shield of Electric Box 01592139 01592139 1
28 Electric Box 20112211 20112211 1
29 Jumper 4202300116 4202300115 1
30 Main Board 30135987 30135991 1
31 Shield Cover of Electric Box 01592140 01592140 1
32 Electric Box Cover 20112209 20112209 1
33 Terminal Board 42010276 42010268 1
34 Decorative Board (Right) 20192611 20192611 1
35 Screw Cover 242520179 242520179 3
36 Electric Box Cover2 20112210 20112210 1
37 Power Cord 400203485 400203485 1
38 Connecting Cable 400205401 400205401 0
39 Connecting Cable / 4002053603 0
40 Remote Controller 30510474 30510474 1

Above data is subject to change without notice.

82 Installation and Maintenance


Service Manual

Part Code
Description
No. GWH18QD-K3NNB6B/I GWH18QD-K3NNC6B/I Qty
Product Code CA435N01200 CA443N01200
1 Decorative Strip / / /
2 Front Panel 20000300040 20000300103 1
3 Display Board 30565278 30565260 1
4 Filter Sub-Assy 11122089 11122089 2
5 Decorative Board (Left) 20192662 20192662 1
6 Front Case 2002248401 2002248401 1
7 Guide Louver 1051276501 1051276501 1
8 Axile Bush 10542036 10542036 2
9 Air Louver 10512732 10512732 3
10 Helicoid Tongue 26112512 26112512 1
11 Left Axile Bush 10512037 10512037 1
12 Rear Case assy 22202571 22202571 1
13 Rubber Plug (Water Tray) 76712012 76712012 1
14 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
15 Ring of Bearing 26152025 26152025 1
16 Evaporator Support 24212177 24212177 1
17 Evaporator Assy 01002686 01002686 1
18 Cross Flow Fan 10352060 10352060 1
19 Fan Motor 1501214502 1501214502 1
20 Motor Press Plate 26112511 26112511 1
21 Wall Mounting Frame 01362026 01252033 1
22 Connecting pipe clamp 2611218801 2611218801 1
23 Crank 73012005 73012005 1
24 Stepping Motor 1521240212 1521240212 1
25 Drainage Hose 05230014 05230014 1
26 Electric Box Assy 10000202519 10000203937 1
27 Lower Shield of Electric Box 01592139 01592139 1
28 Electric Box 20112211 20112211 1
29 Jumper 4202300103 4202300103 1
30 Main Board 30135991 30135991 1
31 Shield Cover of Electric Box 01592140 01592139 1
32 Electric Box Cover 20112209 20112209 1
33 Terminal Board 42010268 42010268 1
34 Decorative Board (Right) 20192662 20192662 1
35 Screw Cover 2425201726 2425201726 3
36 Electric Box Cover2 20112210 20112210 1
37 Power Cord 400203485 400203485 1
38 Connecting Cable 4002053603 4002053603 0
39 Connecting Cable 400205401 400205401 0
40 Remote Controller 30510474 30510474 1

Above data is subject to change without notice.

Installation and Maintenance 83


Service Manual

24K

14 15
42
37 38 39 40 41
13
12
11 16

10
9
17
7 8
5 6 18
4 19
2 3
1
20

21
23 22
24
25
26
B4
pan
el 27
A1
/B6
/C2
28
pan
el
A6
pan
el
29 36
35
30 34
33
31 32
The component picture is only for reference; please refer to the actual product.

84 Installation and Maintenance


Service Manual

Part Code
Description
No. GWC24QE-K3NNA1B/I GWH24QE-K3NNA1B/I Qty
Product Code CA419N05600 CA419N05500
1 Front Panel Assy 20022491 20022491 1
2 Filter Sub-Assy 11012007 11012007 1
3 Screw Cover 24252453 24252453 1
4 Front Case Assy 20022487 20022487 2
5 Swing Lever 10512743 10512743 1
6 Air Louver 1 10512741 10512741 1
7 Helicoid Tongue 26112513 26112513 1
8 Left Axile Bush 10512037 10512037 2
9 Rear Case assy 22202558 22202558 3
10 Rubber Plug (Water Tray) 76712012 76712012 1
11 Ring of Bearing 26152025 26152025 1
12 O-Gasket sub-assy of Bearing 76512051 76512051 1
13 Cross Flow Fan 10352057 10352057 1
14 Evaporator Support 24212178 24212178 1
15 Evaporator Assy 01002687 01002687 1
16 Wall Mounting Frame 01252229 01252229 1
17 Motor Press Plate 26112515 26112515 1
18 Fan Motor 15012145 15012145 1
19 Connecting pipe clamp 26112514 26112514 1
20 Drainage Hose 0523001405 0523001405 1
21 Stepping Motor 1521240212 1521240212 1
22 Crank 73012005 73012005 1
23 Air Louver 1 10512742 10512742 1
24 Air Louver 10512744 10512744 1
25 Guide Louver 10512738 10512738 1
26 Axile Bush 10542036 10542036 1
27 Electric Box 20112211 20112211 1
28 Terminal Board 42011233 4201026201 1
29 Electric Box Cover2 20112210 20112210 1
30 Main Board 30135996 30145001 1
31 Display Board 30565233 30565233 1
32 Shield cover of Electric Box 01592140 01592140 1
33 Electric Box Cover 20112209 20112209 1
34 Jumper 4202300106 4202300106 3
35 Lower Shield of Electric Box 01592139 01592139 1
36 Electric Box Assy 20102000374 20102000373 1
37 Power Cord 400203463 400203463 1
38 Connecting Cable 400205382 400205382 0
39 Connecting Cable / 40020536 0
40 Temperature Sensor 3900031302 3900031302 1
41 Remote Controller 30510474 30510474 1
42 Cold Plasma Generator / / /

Above data is subject to change without notice.

Installation and Maintenance 85


Service Manual

Part Code
Description GWC24QE-K3NNA1B/I
No. GWC24QE-K3NNA6B/I Qty
(Cold Plasma)
Product Code CA419N05601 CA427N06100
1 Front Panel Assy 20022491 2002248602 1
2 Filter Sub-Assy 11012007 11012007 1
3 Screw Cover 24252453 2425245301 1
4 Front Case Assy 20022487 00000200024 2
5 Swing Lever / / /
6 Air Louver 1 10512737 10512737 1
7 Helicoid Tongue 26112513 26112513 1
8 Left Axile Bush 10512037 10512037 2
9 Rear Case assy 22202570 22202570 3
10 Rubber Plug (Water Tray) 76712012 76712012 1
11 Ring of Bearing 26152025 26152025 1
12 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
13 Cross Flow Fan 10352057 10352057 1
14 Evaporator Support 24212178 24212178 1
15 Evaporator Assy 01002988 01002988 1
16 Wall Mounting Frame 01252229 01252229 1
17 Motor Press Plate 26112515 26112515 1
18 Fan Motor 15012145 15012145 1
19 Connecting pipe clamp 26112514 26112514 1
20 Drainage Hose 0523001405 0523001405 1
21 Stepping Motor 1521240212 1521240212 1
22 Crank 73012005 73012005 1
23 Air Louver 1 10512737 10512737 1
24 Air Louver 10512738 10512738 1
25 Guide Louver 10512738 1051232001 1
26 Axile Bush 10542036 10542036 1
27 Electric Box 20112211 20112211 1
28 Terminal Board 42011233 42011233 1
29 Electric Box Cover2 20112210 20112210 1
30 Main Board 30135997 30135996 1
31 Display Board 30565233 30565264 1
32 Shield cover of Electric Box 01592140 01592140 1
33 Electric Box Cover 20112209 20112209 1
34 Jumper 4202300106 4202300127 3
35 Lower Shield of Electric Box 01592139 01592139 1
36 Electric Box Assy 10000202319 10000201340 1
37 Power Cord 400203463 400203463 1
38 Connecting Cable 400205382 400205382 0
39 Connecting Cable / / /
40 Temperature Sensor 3900031302 3900031302 1
41 Remote Controller 30510474 30510474 1
42 Cold Plasma Generator 1114001602 / 1

Above data is subject to change without notice.

86 Installation and Maintenance


Service Manual

Part Code
Description
No. GWH24QE-K3NNA1E/I GWH24QE-K3NNB6B/I Qty
Product Code CA419N15400 CA435N01500
1 Front Panel Assy 20022491 20000300048S 1
2 Filter Sub-Assy 11012007 11012007 1
3 Screw Cover 24252453 2425245301 1
4 Front Case Assy 20022487 00000200043 2
5 Swing Lever / 10512743 1
6 Air Louver 1 10512737 10512737 1
7 Helicoid Tongue 26112513 26112513 1
8 Left Axile Bush 10512037 10512037 2
9 Rear Case assy 22202570 22202570 3
10 Rubber Plug (Water Tray) 76712012 76712012 1
11 Ring of Bearing 26152025 26152025 1
12 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
13 Cross Flow Fan 10352057 10352057 1
14 Evaporator Support 24212178 24212178 1
15 Evaporator Assy 01100100052 01002988 1
16 Wall Mounting Frame 01252229 01252229 1
17 Motor Press Plate 26112515 26112515 1
18 Fan Motor 15012145 15012145 1
19 Connecting pipe clamp 26112514 26112514 1
20 Drainage Hose 0523001405 0523001405 1
21 Stepping Motor 1521240212 1521240212 1
22 Crank 73012005 73012005 1
23 Air Louver 1 / / /
24 Air Louver 10512737 10512737 3
25 Guide Louver 10512738 1051232001 1
26 Axile Bush 10542036 10542036 1
27 Electric Box 20112211 20112211 1
28 Terminal Board 4201026201 4201026201 1
29 Electric Box Cover2 20112210 20112210 1
30 Main Board 30145001 30145001 1
31 Display Board 30565233 30565278 1
32 Shield cover of Electric Box 01592140 01592140 1
33 Electric Box Cover 20112209 20112209 1
34 Jumper 4202300119 4202300128 3
35 Lower Shield of Electric Box 01592139 01592139 1
36 Electric Box Assy 10000202034 10000202527 1
37 Power Cord 400203485 400203463 1
38 Connecting Cable 40020538 40020538 0
39 Connecting Cable 40020536 40020536 0
40 Temperature Sensor 3900031302 3900031302 1
41 Remote Controller 30510474 30510474 1
42 Cold Plasma Generator / / /

Above data is subject to change without notice.

Installation and Maintenance 87


Service Manual

Part Code
Description
No. GWC24QE-K3NNB4B/I GWC24QE-K3NNC2B/I Qty
Product Code CA434N07000 CA439N02500
1 Front Panel Assy 20000300029T 20000300071S 1
2 Filter Sub-Assy 11012007 11012007 1
3 Screw Cover 2425245301 2425245301 1
4 Front Case Assy 00000200043 00000200043 2
5 Swing Lever / / /
6 Air Louver 1 10512737 10512737 1
7 Helicoid Tongue 26112513 26112513 1
8 Left Axile Bush 10512037 10512037 2
9 Rear Case assy 22202570 22202570 3
10 Rubber Plug (Water Tray) 76712012 76712012 1
11 Ring of Bearing 26152025 26152025 1
12 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
13 Cross Flow Fan 10352057 10352057 1
14 Evaporator Support 24212178 24212178 1
15 Evaporator Assy 01002988 01002988 1
16 Wall Mounting Frame 01252229 01252229 1
17 Motor Press Plate 26112515 26112515 1
18 Fan Motor 15012145 15012145 1
19 Connecting pipe clamp 26112514 26112514 1
20 Drainage Hose 0523001405 0523001405 1
21 Stepping Motor 1521240212 1521240212 1
22 Crank 73012005 73012005 1
23 Air Louver 1 10512737 10512737 1
24 Air Louver 60311226 60311226 1
25 Guide Louver 1051232001 1051232001 1
26 Axile Bush 10542036 10542036 1
27 Electric Box 20112211 20112211 1
28 Terminal Board 42011233 42011233 1
29 Electric Box Cover2 20112210 20112210 1
30 Main Board 30135997 30135996 1
31 Display Board 30565260 30565278 1
32 Shield cover of Electric Box 01592140 01592140 1
33 Electric Box Cover 20112209 20112209 1
34 Jumper 4202300127 4202300127 3
35 Lower Shield of Electric Box 01592139 01592139 1
36 Electric Box Assy 10000203313 10000203236 1
37 Power Cord 400203463 400203463 1
38 Connecting Cable 400205382 400205382 0
39 Connecting Cable / / /
40 Temperature Sensor 3900031302 3900031302 1
41 Remote Controller 30510474 30510474 1
42 Cold Plasma Generator 1114001602 / 1

Above data is subject to change without notice.

88 Installation and Maintenance


Service Manual

Part Code
Description
No. GWC24QE-K3NNA1E/I GWH24QE-K3NNC6C/I Qty
Product Code CA419N15600 CA443N01100
1 Front Panel Assy 20022491 20000300104 1
2 Filter Sub-Assy 11012007 11012007 1
3 Screw Cover 24252453 2425245301 1
4 Front Case Assy 20022487 00000200043 2
5 Swing Lever / / 1
6 Air Louver 1 10512738 10512737 1
7 Helicoid Tongue 26112513 26112513 1
8 Left Axile Bush 10512037 10512037 2
9 Rear Case assy 22202570 22202570 3
10 Rubber Plug (Water Tray) 76712012 76712012 1
11 Ring of Bearing 26152025 26152025 1
12 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
13 Cross Flow Fan 10352057 10352057 1
14 Evaporator Support 24212178 24212178 1
15 Evaporator Assy 01100100052 01002988 1
16 Wall Mounting Frame 01252229 01252229 1
17 Motor Press Plate 26112515 26112515 1
18 Fan Motor 15012145 15012145 1
19 Connecting pipe clamp 26112514 26112514 1
20 Drainage Hose 0523001405 0523001405 1
21 Stepping Motor 1521240212 1521240212 1
22 Crank 73012005 73012005 1
23 Air Louver 1 10512738 10512737 1
24 Air Louver 60311226 60311226 1
25 Guide Louver 10512738 1051232001 1
26 Axile Bush 10542036 10542036 1
27 Electric Box 20112211 20112211 1
28 Terminal Board 42011233 4201026201 1
29 Electric Box Cover2 20112210 20112210 1
30 Main Board 30135996 30145001 1
31 Display Board 30565233 30565260 1
32 Shield cover of Electric Box 01592140 01592139 1
33 Electric Box Cover 20112209 20112209 1
34 Jumper 4202300106 4202300128 3
35 Lower Shield of Electric Box 01592139 01592139 1
36 Electric Box Assy 10000202878 10000204679 1
37 Power Cord 400203485 400203463 1
38 Connecting Cable / 400205382 0
39 Connecting Cable 40020538 40020536 0
40 Temperature Sensor 3900031302 3900031302 1
41 Remote Controller 30510516 30510474 1
42 Cold Plasma Generator / / /

Above data is subject to change without notice.

Installation and Maintenance 89


Service Manual

10.2 Outdoor Unit


GWC09QB-K3NNA1B/O GWC09QB-K3NNA1J/O

21 20 19 18

22

17
23

16
24

15
25

14

13

12

1 2 3 4 5 6 26 7 8 9 10 11

The component picture is only for reference; please refer to the actual product.

90 Installation and Maintenance


Service Manual

Part Code
Description
No. GWC09QB-K3NNA1B/O GWC09QB-K3NNA1J/O Qty
Product Code CA419W06000 CA419W15100
1 Front Grill 22263002 22263002 1
2 Front Panel 01533255P 01533255P 1
3 Chassis Sub-assy 0280312301P 01700000121P 1
4 Clapboard Sub-Assy 01233179 01233384 1
5 Compressor and Fittings 00103841 00103337 1
6 Inhalation Tube Sub-assy 03833392 03001000316 1
7 Capillary Sub-assy 03163534 / 1
8 Valve Support 01713041 01713041 1
9 Valve 07100003 07100003 1
10 Valve 07100005 07100005 1
11 Big Handle 26233042 2623304202 1
12 Right Side Plate Assy 01303243 01303243 1
13 Electric Box Assy 02613682 01403000201 1
14 Terminal Board 42011154 42011154 1
15 Capacitor Clamp 02143014 02143401 1
16 Capacitor CBB61 33010020 3301074701 1
17 Capacitor CBB65 33000081 33000081 1
18 Discharge Tube 03543414 03500800666 1
19 Rear Grill 11123204 11123204 1
20 Top Cover Sub-Assy 01253045P 01253045P 1
21 Condenser Assy 01103000236 01100200429 1
22 Motor Support 01703204 01703204 1
23 Fan Motor 1501315604 1501315604 1
24 Axial Flow Fan 10333002 10333002 1
25 Small Handle 26233100 26233100 1
26 Throttle Valve Sub-assy / 03005500014 1

Above data is subject to change without notice.

Installation and Maintenance 91


Service Manual

GWH09QB-K3NNA1B/O GWH09QB-K3NNA1J/O GWH12QC-K3NNA1B/O GWH12QC-K3NNA1D/O

The component picture is only for reference; please refer to the actual product.

92 Installation and Maintenance


Service Manual

Part Code
Description
No. GWH09QB-K3NNA1B/O GWH09QB-K3NNA1J/O Qty
Product Code CA419W06100 CA419W15000
1 Front grill 22413433 22413008 1
2 Front Panel 01533034P 01533034P 1
3 Chassis Sub-assy 0120374801P 01700000048P 1
4 Drainage Connecter 06123401 06123401 1
5 Compressor and fittings 00103804 00103978 1
6 Magnet Coil 4300040047 4300040047 1
7 4-way Valve Assy 03073300 03073384 1
8 4-way Valve 430004022 430004022 1
9 Strainer A 07210022 / 1
10 Capillary Sub-Assy 03163527 / 1
11 Valve 07100003 07100003 1
12 Valve 07100005 07100005 1
13 Big Handle 26233433 262334332 1
14 Valve Support 0170308901P 0170308901P 1
15 Right Side Plate Sub-Assy 01303183 01303183 1
16 Electric Box Assy 01403000150 10000202088 1
17 Terminal Board 42010265 42010265 1
18 Terminal Board 42011147 42011147 1
19 Capacitor CBB65 33000081 33000081 1
20 Capacitor CBB61 33010026 3301074710 1
21 Rear grill 1112320501 1112320501 1
22 Condenser Assy 01103000226 01100200419 1
23 Top Cover Sub-Assy 01253087 01253087 1
24 Clapboard Sub-Assy 01233066 01233059 1
25 Motor Support 01703103 01703103 1
26 Fan Motor 150130676 150130676 1
27 Small Handle 26233100 26233100 1
28 Axial Flow Fan 10333427 10333427 1
29 Throttle Valve Sub-assy / 03005500013 1

Above data is subject to change without notice.

Installation and Maintenance 93


Service Manual

Part Code
Description
No. GWH12QC-K3NNA1B/O GWH12QC-K3NNA1D/O Qty
Product Code CA419W06500 CA419W15200
1 Front grill 22413008 22413008 1
2 Front Panel 01533034P 01533034P 1
3 Chassis Sub-assy 0280325701P 01700000116P 1
4 Drainage Connecter 06123401 06123401 1
5 Compressor and fittings 00103937 00103344 1
6 Magnet Coil 4300040022 4300040022 1
7 4-way Valve Assy 03073310 03073389 1
8 4-way Valve 430004022 430004022 1
9 Strainer A 07210022 07210022 1
10 Capillary Sub-Assy 03163541 03163541 1
11 Valve 07100003 07100003 1
12 Valve 07100006 07100006 1
13 Big Handle 26233433 262334332 1
14 Valve Support 0170308901P 0170308901P 1
15 Right Side Plate Sub-Assy 01303183 01303183 1
16 Electric Box Assy 02613706 10000201973 1
17 Terminal Board 42010265 42010265 1
18 Terminal Board 42011147 42011147 1
19 Capacitor CBB65 3300008102 3300008101 1
20 Capacitor CBB61 33010026 3301074710 1
21 Rear grill 1112320501 1112320501 1
22 Condenser Assy 01103000244 00010000002 1
23 Top Cover Sub-Assy 01253087 0125308701 1
24 Clapboard Sub-Assy 01233066 01233066 1
25 Motor Support 01703104 01703104 1
26 Fan Motor 150130676 150130676 1
27 Small Handle 26233100 26233100 1
28 Axial Flow Fan 10333427 10333427 1
29 Throttle Valve Sub-assy / 03005500015 1

Above data is subject to change without notice.

94 Installation and Maintenance


Service Manual

GWC12QC-K3NNA1B/O GWC12QC-K3NNA1G/O

The component picture is only for reference; please refer to the actual product.

Installation and Maintenance 95


Service Manual

Part Code
Description
No. GWC12QC-K3NNA1B/O GWC12QC-K3NNA1G/O Qty
Product Code CA419W06400 CA419W15300
1 Front Grill 22413008 22413008 1
2 Front Panel 01533034P 01533034P 1
3 Chassis Sub-assy 02803257P 0170000011601P 1
4 Compressor and Fittings 00103937 00103344 1
5 Inhalation Tube 03753872 03001000201 1
6 Discharge Tube 03543437 03500800671 1
7 Capillary Sub-assy 03163543 03163543 1
8 Valve 07100003 07100003 1
9 Valve 07100006 07100006 1
10 Big Handle 26233433 262334332 1
11 Valve Support 0170308901P 0170308901P 1
12 Right Side Plate Sub-Assy 01303183 01303183 1
13 Electric Box Assy 02613663 10000202033 1
14 Terminal Board 42011154 42011154 1
15 Capacitor CBB61 33010026 3301074710 1
16 Capacitor CBB65 3300008102 3300008101 1
17 Rear Grill 1112320501 1112320501 1
18 Condenser Assy 01103000248 00010000003 1
19 Top Cover Sub-Assy 0125308701 01253087 1
20 Clapboard Sub-Assy 01233066 01233066 1
21 Motor Support 01703103 01703103 1
22 Fan Motor 150130676 150130676 1
23 Small Handle 26233100 26233100 1
24 Axial Flow Fan 10333427 10333427 1
25 Throttle Valve Sub-assy / 03005500016 1

Above data is subject to change without notice.

96 Installation and Maintenance


Service Manual

GWC18QD-K3NNA1B/O GWC18QD-K3NNA1F/O

24

The component picture is only for reference; please refer to the actual product.

Installation and Maintenance 97


Service Manual

Part Code
Description
No. GWC18QD-K3NNA1B/O GWC18QD-K3NNA1F/O Qty
Product Code CA419W06600 CA419W14000
1 Front Grill 22413433 22413433 1
2 Front Panel 0153303204P 0153303204P 1
3 Chassis Sub-assy 02803254P 01700000073P 1
4 Compressor and Fittings 00105054 00103989 1
5 Inhalation Tube Sub-assy 03833922 03001000334 1
6 Discharge Tube 03543438 03001300220 1
7 Capillary Sub-assy 03163544 03700200445 1
8 Valve 07100003 07100003 1
9 Valve 07100006 07100006 1
10 Big Handle 26233433 262334332 1
11 Valve Support 01713041 01713041 1
12 Right Side Plate Assy 0130200404 0130200404 1
13 Terminal Board 42011154 42011154 1
14 Capacitor CBB65 3300008104 3300008113 1
15 Capacitor CBB61 33010026 3301074710 1
16 Electric Box Assy 01403000167 10000201455 1
17 Rear Grill 11123205 11123205 1
18 Condenser Assy 01103000249 01100200417 1
19 Top Cover Plate 01253443 01253443 1
20 Clapboard Sub-Assy 01233417 012334172 1
21 Motor Support 0170310401 0170310302 1
22 Fan Motor 1501307103 1501307103 1
23 Axial Flow Fan 10333427 10333427 1
24 Throttle Valve Sub-assy / 03005500008 1

Above data is subject to change without notice.

98 Installation and Maintenance


Service Manual

GWH18QD-K3NNA1B/O

5 6 7 8 9 10 11

2
12
1
13

14
15
16
17
18

23 22 21 20 19
The component picture is only for reference; please refer to the actual product.

Installation and Maintenance 99


Service Manual

Part Code
Description
No. GWH18QD-K3NNA1B/O Qty
Product Code CA419W06700
1 Rear Grill 014730371 1
2 Left Handle 26235401 1
3 Front Panel 01305015 1
4 Axial Flow Fan 10335261 1
5 Fan Motor 15015057 1
6 Motor Support Sub-Assy 01703098 1
7 Top Cover 01255001 1
8 Clapboard Sub-Assy 01233035 1
9 Electric Box Assy 02613633 1
10 Condenser Assy 01103000303 1
11 Rear Grill 014730371 1
12 Capacitor CBB61 33010026 1
13 Capacitor CBB65 33000046 1
14 Terminal Board 42010265 1
15 Right Side Plate 01305095P 1
16 Handle 26235254 1
17 Valve Support Sub-Assy 01713075 1
18 Cut off Valve Sub-Assy 07133491 1
19 Cut off Valve 07130213 1
20 Capillary Sub-assy 03163591 1
21 4-Way Valve Assy 03073327 1
22 Compressor and Fittings 00105054 1
23 Chassis Sub-assy 01203826P 1

Above data is subject to change without notice.

100 Installation and Maintenance


Service Manual

GWC24QE-K3NNA1B/O

24 23 22 21 20 19 18

25 17

16

15
26
14

13

12

11

1 2 3 4 5 6 7 8 9 10

The component picture is only for reference; please refer to the actual product.

Installation and Maintenance 101


Service Manual

Part Code
Description
No. GWC24QE-K3NNA1B/O Qty
Product Code CA419W05600
1 Front Grill 26235254 1
2 Front Panel 01305015 1
3 Axial Flow Fan 10335261 1
4 Chassis Sub-assy 0120382601P 1
5 Clapboard Sub-Assy 01233035 1
6 Compressor Gasket 76711043 3
7 Compressor and Fittings 00103872 1
8 Gas Valve Sub-Assy 07103030 1
9 Cut off Valve 07130239 1
10 Cut off Valve Sub-Assy 07133019 1
11 Discharge Tube 03543175 1
12 Handle 26235254 1
13 Right Side Plate 01305095P 1
14 Capillary Sub-assy 03163517 1
15 Inhalation Tube 03833933 1
16 Condenser Assy 01103000217 1
17 Motor Support Sub-Assy 0170309801 1
18 Rear Grill 014730371 1
19 Coping 01255002 1
20 Fan Motor 15015057 1
21 Electric Box Assy 01403000139 1
22 AC Contactor 44010245 1
23 Terminal Board 42011113 1
24 Capacitor CBB61 33010027 1
25 Capacitor CBB65 3300008105 1
26 Left Handle 26235401 1

Above data is subject to change without notice.

102 Installation and Maintenance


Service Manual

GWH24QE-D1NTA1A/O

25 24 23 22 21 20 19
26
27 18

17

28 16

15
14

13

12

1 2 3 4 5 6 7 8 9 10 11

The component picture is only for reference; please refer to the actual product.

Installation and Maintenance 103


Service Manual

Part Code
Description
No. GWH24QE-D1NTA1A/O Qty
Product Code CA419W05500
1 Front Grill 22415001 1
2 Front Panel 01435001P 1
3 Axial Flow Fan 10335261 1
4 Drainage Plug 0681340101 3
5 Drainage Connecter 06123401 1
6 Chassis Sub-assy 02803202P 1
7 Clapboard Sub-Assy 01233035 1
8 Compressor and Fittings 00103872 1
9 Valve Support Sub-Assy 01715001 1
10 Cut off Valve Sub-Assy 07133798 1
11 Gas Valve Sub-Assy 07103030 1
12 Handle 26235254 1
13 Right Side Plate 01305095P 1
14 Magnet Coil 4300040047 1
15 4-Way Valve Assy 03073297 1
16 4-Way Valve 4300008201 1
17 Condenser Assy 01103000218 1
18 Motor Support Assy 01703222 1
19 Rear Grill 01473069 1
20 Coping 01255002 1
21 Fan Motor 15015057 1
22 Electric Box Assy 02613594 1
23 AC Contactor 44010245 1
24 Terminal Board 42010194 1
25 Capacitor CBB61 33010027 1
26 Capacitor Clamp 02141375 1
27 Capacitor CBB65 3300008105 1
28 Left Handle 26235401 1

Above data is subject to change without notice.

104 Installation and Maintenance


Service Manual

GWH18QD-K3NNA1D/O

5 6 7 8 9 10 11

2
12
1
13

14

15

16

17
18

24

23 22 25 21 20 19

The component picture is only for reference; please refer to the actual product.

Installation and Maintenance 105


Service Manual

Part Code
Description
No. GWH18QD-K3NNA1D/O Qty
Product Code CA419W13900
1 Front grill 22415001 1
2 left handle 26235401 1
3 Cabinet 01305015 1
4 Axial Flow Fan 10335261 1
5 Fan Motor 15015057 1
6 Motor Support Sub-Assy 01703098 1
7 Top Cover 01255001 1
8 Clapboard Sub-Assy 01233035 1
9 Electric Box Assy 10000201882 1
10 Condenser Assy 01100200396 1
11 Rear grill 014730371 1
12 Capacitor CBB61 3301074704 1
13 Capacitor CBB65 3300008113 1
14 Terminal Board 42010265 1
15 Right Side Plate 01305095P 1
16 Handle 2623525404 1
17 Valve Support Sub-Assy 01713075 1
18 Cut-off valve Sub-Assy 07133491 1
19 Cut-off Valve 07130213 1
20 Capillary Sub-assy / /
21 4-Way Valve Assy 03073361 1
22 Compressor and Fittings 00103989 1
23 Chassis Sub-assy 01203826P 1
24 Valve Cover 22243003 1
25 Throttle Valve Sub-assy 03005500007 1

Above data is subject to change without notice.

106 Installation and Maintenance


Service Manual

GWC24QE-K3NNA1E/O

24 23 22 21 20
26 25

27

28

29

19
30
18
17
16
15
14

1 2 3 4 5 6 7 8 9 10 11 12 13

The component picture is only for reference; please refer to the actual product.

Installation and Maintenance 107


Service Manual

Part Code
Description
No. GWC24QE-K3NNA1E/O Qty
Product Code CA419W15600
1 Front grill 22415002 1
2 Front Panel 01535013P 1
3 Chassis Sub-assy 01700000144P 1
4 Compressor and fittings 00103872 1
5 Overload Protector 00180299 1
6 Compressor Gasket 76711065 1
7 Discharge tube 2 03500800665 1
8 Inhalation Tube 03500600609 1
9 Right Side Plate 0130509402P 1
10 Valve Support Sub-Assy 01713098P 1
11 Cut-off valve Sub-Assy 07133170 1
12 Cut-off Valve 07130239 1
13 Handle 26233053 1
14 Terminal Board 42011113 1
15 AC Contactor 44010245 1
16 Capacitor CBB61 3301074705 1
17 Capacitor CBB65 3300008105 1
18 Electric Box Assy 10000202030 1
19 Capillary Sub-Assy / /
20 Rear Grill 01473061 1
21 Condenser Assy 01100200542 1
22 Supporting board(condenser) 01173127 1
23 Top Cover 01255005P 1
24 Clapboard Sub-Assy 01235027 1
25 Motor Support Sub-Assy 01703154 1
26 left handle 26233053 1
27 Fan Motor 1501506102 1
28 Left Side Plate 01305093P 1
29 Axial Flow Fan 10335008 1
30 Throttle Valve Sub-assy 03005500009 1

Above data is subject to change without notice.

108 Installation and Maintenance


Service Manual

GWH24QE-K3NNA1E/O

26 25 24 23
28 27

29

30

31 22

21

32 20

19

18
17
16

15

1 2 3 4 5 6 7 8 9 33 10 11 12 13 14

The component picture is only for reference; please refer to the actual product.

Installation and Maintenance 109


Service Manual

Part Code
Description
No. GWH24QE-K3NNA1E/O Qty
Product Code CA419W15400
1 Front grill 22415002 1
2 Front Panel 01535013P 1
3 Drainage Plug 06813401 3
4 Drainage Connecter 06123401 1
5 Chassis Sub-assy 01700000020P 1
6 Compressor and fittings 00103872 1
7 Overload Protector / /
8 Compressor Gasket 76711065 3
9 4-way Valve Assy 03073385 1
10 Right Side Plate 01305094P 1
11 Valve Support Sub-Assy 01713098P 1
12 Cut-off valve Sub-Assy 07133170 1
13 Cut-off Valve 07133157 1
14 Handle 26233053 1
15 Terminal Board 42010194 1
16 AC Contactor 44010245 1
17 Terminal Board 42010194 1
18 Capacitor CBB61 3301074705 1
19 Capacitor CBB65 3300008105 1
20 Electric Box Assy 10000202032 1
21 Magnet Coil 4300040047 1
22 Capillary tube 81020167 1
23 Rear Grill 01473061 1
24 Condenser Assy 01100200422 1
25 Top Cover 01255005P 1
26 Supporting board(condenser) 01795010 1
27 Clapboard Sub-Assy 01235027 1
28 Motor Support Sub-Assy 01705036 1
29 left handle 26233053 1
30 Fan Motor 1501506102 1
31 Left Side Plate 01305093P 1
32 Axial Flow Fan 10335008 1
33 Throttle Valve Sub-assy 03005500011 1

Above data is subject to change without notice.

110 Installation and Maintenance


Service Manual

11. Removal Procedure


Caution: discharge the refrigerant
11.1 Removal Procedure of Indoor Unit
completely before removal.
09/12K

Step Procedure

1.Remove filter assy


Front panel
Open the front panel. Push the left and
right filters to make them break away
from the groove on the front case. Then
remove the left and right filters one by Front
one. Left filter case

Groove Right filter

2. Remove horizontal louver

Push out the axile bush on horizontal


louver. Bend the horizontal louver with
hand and then separate the horizontal
louver from the crankshaft of step motor
to remove it.
Location of step motor
Horizontal louver
Axile bush

3. Remove panel A1/B6/C2 display


A6 display

A1/B6/C2 panel:Screw off the 2 screws


a that are locking the display board.
Separate the display board from the front
panel.

A6 panel:Screw off the 2 screws that are Panel


Screws
locking the display board. B4/C6 display Screws
B4/C6 panel:Screw off the 2 screws that
Front panel Screws
are locking the display board.

b Separate the panel rotation shaft from


the groove fixing the front panel and then
removes the front panel.
Panel rotation

Groove

Installation and Maintenance 111


Service Manual

Step Procedure

4. Remove electric box cover 2


Screw
Electric box cover 2

Remove the screws on the electric box


cover 2 to remove the electric box cover 2.

5. Remove front case sub-assy


Screws

a Remove the screws fixing front case.

Note:
1.Open the screw caps before removing
the screws around the air outlet.
2.The quantity of screws fixing the front
Front case
case sub-assy is different for different
sub-assy Screw caps
models.
Screw
Clasp
Bottom
b Loosen the connection clasps between
front case sub-assy and bottom case. Lift Front case
up the front case sub-assy and take it out. sub-assy

6. Remove vertical louver

Loosen the connection clasps between


vertical louver and bottom case to remove
vertical louver. Bottom
case

Vertical
louver

Clasps Vertical
louver

112 Installation and Maintenance


Service Manual

Step Procedure

7. Remove electric box assy


Screw

a Loosen the connection clasps between


shield cover of electric box sub-assy and Clasps
electric box, and then remove the shield
cover of electric box sub-assy.
Remove the screw fixing electric box assy .

Electric box
Shield cover of electric
box sub-assy
Indoor tube
temperature
① Remove the cold plasma generator by Cold plasma Screw sensor Electric box assy
b
generator
screwing off one locking screw on the
generator.
② Take off the indoor tube temperature
sensor.
③ Screw off one grounding screw.
④ Remove the wiring terminals of motor and Wiring
stepping motor. terminal
⑤ Remove the electric box assy. of motor
Grounding
screw Wiring
terminal
of stepping
motor
Screw
Main board
c Twist off the screws that are locking lead Power cord
wire and rotate the electric box assy.
Screw
Twist off the screws that are locking wire
clip.
Loosen the power cord and remove its wiring
terminal. Lift up the main board and take it
off. Wire clip

Screw
Wiring terminal of
temperature sensor

d Remove the display board by taking out its


wiring terminal.
Remove temperature sensor by taking out
its wiring terminal.
Main board Wiring terminal
of display board

Installation and Maintenance 113


Service Manual

Step Procedure

Instruction: Some wiring terminal of this


product is with lock catch and other devices. circlip
The pulling method is as below:
holder
1.Remove the soft sheath for some terminals
at first, hold the circlip and then pull out the
terminals.
soft sheath connector
2.Pull out the holder for some terminals at
first (holder is not available for some wiring
terminal), hold the connector and then pull the
terminal.

8. Remove evaporator assy Screws Evaporator assy

a Remove 3 screws fixing evaporator assy.

Connection pipe clamp


b At the back of the unit, remove the Screw
screw fixing connection pipe clamp
and then remove the connection pipe
clamp.

Groove
Bottom shell
c First remove the left side of evaporator from
the groove of bottom shell and then remove
the right side from the clasp on the bottom
shell. Clasp
Evaporator assy

Connection pipe

d Adjust the position of connection pipe


on evaporator slightly and then lift the
evaporator upwards to remove it.

114 Installation and Maintenance


Service Manual

Step Procedure

9. Remove motor and cross flow blade

a Remove the screws fixing motor clamp


Screws
and then remove the motor clamp.

Motor clamp

Cross flow
b Remove the screws at the connection Screw
place of cross flow blade and motor; lift Holder Motor
the motor and cross flow blade upwards sub-assy
to remove them.
Remove the bearing holder sub-assy.
Remove the screw fixing step motor and
then remove the step motor.

Screws
Step motor

Installation and Maintenance 115


Service Manual

18/24K
NOTE: Take A1 panel for example.

1. Remove filter as s y
Front panel

Open the front panel. Push the left and right


filters to make them break away from the
groove on the front case. Then remove the left
and right filters one by one. Front
Left filter case

Groove Right filter

A1/B6 A6 Display

Screw off the 2 screws that are locking the


display board. Separate the display board from
the front panel.
screws

116 Installation and Maintenance


Service Manual

2 2

Loosen the connection clasps between front


case sub-assy and bottom case. Lift up the
front case sub-assy and take it out.

S wing motor
Screw off the screws that are locking the
swing motor and take the motor off.

Installation and Maintenance 117


Service Manual

Indoor tube
Cut off the wire binder and pull out the temperature s ensor
indoor tube temperature sensor.
Screw off one grounding screw.
Main
Remove the wiring terminals of motor and
stepping motor. board
Remove the electric box assy. G rounding
Screw off the screws that are locking each s c rew Wi ring
lead wire. terminal
of motor
Wire binder

Wiring
terminal
of stepping
S crew motor

Rotate the electric box assy. Twist off the screws


that are locking the wire clip and loosen the S crew
power cord. Remove the wiring terminal of
power cord. Lift up the main board and take it off. P ower cord

Wire clip

118 Installation and Maintenance


Service Manual

G roove
R ear case ass y

First remove the left side of evaporator from


the groove on the rear case assy. Then
remove the right side from the clasp on the
rear case assy. C lasp

Installation and Maintenance 119


Service Manual

120 Installation and Maintenance


Service Manual

11.2 Removal Procedure of Outdoor Unit


GWC09QB-K3NNA1B/O GWC09QB-K3NNA1J/O

1.Remove big handle

a Before disassembly.

b Remove the screw fixing the big handle.


Remove the big handle.
big handle

2.Remove top cover


top panel

Remove the screws connecting the top panel with the


front panel and right side panel.
Remove the top cover.

Installation and Maintenance 121


Service Manual

3.Remove front grille

Remove screws fixing the front grille and the front


panel. Remove the grille.

front grille

4.Remove front panel

Remove screws connecting the front panel with


the chassis and the motor support. Remove the
front panel.

front panel

5.Remove right side plate

right side plate

Remove screws connecting the right side plate with


the chassis, the valve support and the electric box.
Remove the right side plate.

6.Remove axial flow blade

axial flow blade


Remove the nut on the blade. Remove the axial
flow blade.

122 Installation and Maintenance


Service Manual

7.Remove motor and motor support

Remove the tapping screws fixing the motor;


disconnect the leading wire insert of the motor.
Remove the motor.
Remove the tapping screws fixing the motor support.
Lift the motor support to remove it.
motor support
motor

8.Remove electric box

electric box

Remove screws fixing the electric box subassembly.


Loosen the wire bundle; unplug the wiring terminals
and lift the electric box to remove it.

9.Remove isolation sheet

isolation sheet
Remove the 3 screws fixing the isolation sheet.
Remove the isolation sheet.

10.Remove sound proof sponge

Remove the soundproof sponge wrapping the


compressor.

sound proof sponge

Installation and Maintenance 123


Service Manual

11.Remove gas valve and liquid valve

Unsolder the capillary, valves and the outlet pipe of


condenser. Do not block the capillary with welding
slag during unsoldering. Remove the 2 screws
fixing the gas valve. Unsolder the gas valve and
the air-return pipe .
(NOTE: Discharge the refrigerant completely before
unsoldering; when unsoldering, wrap the gas valve
with wet cloth to avoid damage to the valve caused
by high temperature). Remove the 2 screws fixing liquid valve
the liquid valve and unsolder the liquid valve and
the Y-type pipe to remove the liquid valve.

gas valve

12.Remove compressor

discharge pipe
suction pipe

a Unsolder the pipes connecting with the compressor.

capillary

b Remove the foot nuts on the compressor.


Remove the compressor. foot nuts

compressor

124 Installation and Maintenance


Service Manual

GWH09QB-K3NNA1B/O GWH09QB-K3NNA1J/O GWC12QC-K3NNA1B/O GWC12QC-K3NNA1G/O GWH12QC-K3NNA1B/O


GWH12QC-K3NNA1D/O GWC18QD-K3NNA1B/O GWC18QD-K3NNA1F/O
NOTE: Take GWH09QB-K3NNA1B/O for example.

1. Before disassembly

2. Remove big handle

Remove the connection screw fixing the big handle big handle
and then remove the handle.

3. Remove top panel


top panel

Remove connection screws connecting the top


panel with the front panel and the right side plate,
and then remove the top panel.

Installation and Maintenance 125


Service Manual

4. Remove front grille

Remove connection screws between the front


grille and the front panel. Then remove the front
grille.

front grille

5. Remove front panel

Remove connection screws connecting the front


panel with the chassis and the motor support,
and then remove the front panel.

front panel

6. Remove right side plate


right side plate

Remove connection screws connecting the


right side plate with the chassis, the valve
support and the electric box. Then remove
the right side plate.

7. Remove axial flow blade

Remove the nut on the blade and then remove


the axial flow blade.

axial flow blade

126 Installation and Maintenance


Service Manual

8. Remove motor and motor support


motor support

Remove the 4 tapping screws fixing the motor and


disconnect the leading wire insert of the motor. Then
remove the motor.
Remove the 2 tapping screws fixing the motor
support and lift the motor support to remove it.

motor

9. Remove electric box

electric box

Remove screws fixing the electric box subassembly;


loosen the wire bundle and unplug the wiring
terminals. Then lift the electric box to remove it.

10. Remove isolation sheet

Remove the 3 screws fixing the isolation sheet and


then remove the isolation sheet.

isolation sheet

11. Remove soundproof sponge

Remove the soundproof sponge wrapping the


compressor.

soundproof sponge

Installation and Maintenance 127


Service Manual

12. Remove magnet coil magnet coil

Remove the screw fixing the magnet coil and then


remove the coil.

13. Remove valves and 4-way valve subassembly


4-way valve

Unsolder welding joint connecting the capillary,


the valve and the outlet pipe of condenser to
remove the capillary. Do not block the capillary
with welding slag during unsoldering.
Remove the 2 screws fixing the gas valve and
unsolder the welding point between the gas valve
and the air-return pipe to remove the gas valve.
(NOTE: Discharge the refrigerant completely
before unsoldering; when unsoldering, wrap the
gas valve with a wet cloth completely to avoid
damage to the valve caused by high temperature).
Remove the 2 screws fixing the liquid valve and
unsolder the welding joint connecting the liquid liquid valve
valve to the Y-type pipe to remove the liquid valve.
Unsolder the welding joint connecting the 4-way
valve, the compressor and the condenser to
gas valve
remove the 4-way valve.

14. Remove compressor foot nuts

compressor

Remove the foot nuts on the compressor and then


remove the compressor.

128 Installation and Maintenance


Service Manual

GWH18QD-K3NNA1B/O GWC24QE-K3NNA1B/O GWH24QE-K3NNA1B/O GWH18QD-K3NNA1D/O


NOTE: Take GWH18QD-K3NNA1D/O for example.

Steps Procedure

1. Before disassembly

2. Remove handle and valve cover

handle

Remove the screw fixing the handle and


then remove the handle.
Remove the screw fixing the valve cover and
then remove the valve cover.

valve cover

3. Remove top panel and grille

top panel
Remove screws fixing the top panel and
the grille respectively, and then remove the
top panel and the grille.

grille

Installation and Maintenance 129


Service Manual

Step Procedure

4. Remove front panel and rear guard grille


rear guard grille
screw
panel

Remove screws fixing the front panel and


the rear guard grille respectively, and then
remove the front panel and the rear guard
grille. screw

screw

5. Remove right side plate


right side plate

Remove screws connecting the front panel


with the chassis and the motor support,
and then remove the right side plate.

screw

6. Remove axial flow blade

axial flow blade

Remove nut fixing the blade and then


remove the blade.

nut

130 Installation and Maintenance


Service Manual

Step Procedure

7. Remove motor and motor support


motor support

Remove screws on the motor and the motor


motor support, and then remove the motor
and the motor support. screw

8. Remove electric box

electric box assy

Remove the 2 screws fixing the electric


box; loosen the wire bundle; pull out the
wiring terminals and then pull electric box
upwards to remove it.

9. Remove soundproof sponge

Remove the soundproof sponge wrapping


the compressor.

soundproof sponge

Installation and Maintenance 131


Service Manual

Step Procedure

10. Remove solenoid coil

Remove the screw on the solenoid coil,


and then remove the solenoid coil.

solenoid coil

screw

11. Remove compressor


4-way valve assy

compressor
Unsolder the pipes (including the soldering
a joint among the 4-way valve,the compressor
the condenser,the gas valve and the liquid
valve)connected to the compressor at rirst.
(NOTE:Berore unsoldering the joints,
discharge the refrigerant completely)
gas valve

liquid valve

nut

b Remove the 3 foot nuts fixing the compressor


with wrench,and then remove the compressor.

132 Installation and Maintenance


Service Manual

Step Procedure

12. Remove isolation sheet

Remove the 3 screws fixing the isolation


sheet and then remove the isolation sheet.

isolation sheet
screw

13. Remove valve support and condenser

Remove screws fixing the valve support condenser


and then remove the valve support;
Remove the screw fixing the condenser
and then pull the condenser upwards to
remove it.

valve support screw

Installation and Maintenance 133


Service Manual

GWC24QE-K3NNA1E/O GWH24QE-K3NNA1E/O
NOTE: Take GWH24QE-K3NNA1E/O for example.

Steps Procedure

1. Remove top panel

a Before disassembly.

top panel
b Remove the screws connecting the top panel with
the front panel and the right side plate, and then
remove the top panel.

2.Remove grille and panel

a Remove the screws connecting the grille and the


panel, and then remove the grille.

grille

134 Installation and Maintenance


Service Manual

Steps Procedure

b Remove the screws connecting the panel with the


chassis and the motor support, and then remove the
panel.

panel

3.Remove left side plate and right side plate

a Remove the screws connecting the right side plate


with the chassis, the valve support and the electric
box, and then remove the right side plate assy.

left side plate right side plate

b Remove the screws connecting the left side plate


and the chassis, and then remove the left side plate
assy.

Installation and Maintenance 135


Service Manual

Steps Procedure

4. Remove fan motor

a Remove the nut fixing the blade and then remove the
axial flow blade. axial flow blade

nut

motor support

b Remove the 4 tapping screws fixing the motor;


disconnect the leading wire insert of the motor and
then remove the motor.
Remove the 2 tapping screws fixing the motor
support and then pull the motor support upwards to r
emove it.

motor

5. Remove electric box electric box

Remove the screws fixing the electric box sub-assy;


loosen the wire bundle; pull out the wiring terminals
and then pull the electric box upwards to remove it.

136 Installation and Maintenance


Service Manual

Steps Procedure

6.Remove 4-way valve assy

4-way valve assy

Discharge the refrigerant completely; unsolder the


pipelines connecting the compressor and the
condenser assy, and then remove the 4-way valve
assy.(Recover the refrigerant before unsoldering)

7.Remove compressor

compressor

Discharge the refrigerant completely; unsolder the


pipelines connecting the compressor and the
condenser assy, and then remove the 4-way valve
assy.

8.Remove chassis sub-assy and condenser sub-assy

a Remove the screws fixing the isolation sheet and


then remove the isolation sheet.

isolation sheet

Installation and Maintenance 137


Service Manual

Steps Procedure

support

b Remove the screws connecting the support


(condenser) and condenser assy,and then remove
the support (condenser).

condenser sub-assy

c Dissemble the chassis sub-assy and condenser


sub-assy.

chassis sub-assy

138 Installation and Maintenance


Service Manual

Appendix:
Appendix 1: Reference Sheet of Celsius and Fahrenheit
Conversion formula for Fahrenheit degree and Celsius degree: Tf=Tcx1.8+32
Set temperature
Fahrenheit Fahrenheit Fahrenheit
display Fahrenheit display Fahrenheit display Fahrenheit
Celsius(℃) Celsius(℃) Celsius(℃)
temperature (℉) temperature (℉) temperature (℉)
(℉) (℉) (℉)
61 60.8 16 69/70 69.8 21 78/79 78.8 26
62/63 62.6 17 71/72 71.6 22 80/81 80.6 27
64/65 64.4 18 73/74 73.4 23 82/83 82.4 28
66/67 66.2 19 75/76 75.2 24 84/85 84.2 29
68 68 20 77 77 25 86 86 30
Ambient temperature
Fahrenheit Fahrenheit Fahrenheit
display Fahrenheit display Fahrenheit display Fahrenheit
Celsius(℃) Celsius(℃) Celsius(℃)
temperature (℉) temperature (℉) temperature (℉)
(℉) (℉) (℉)
32/33 32 0 55/56 55.4 13 79/80 78.8 26
34/35 33.8 1 57/58 57.2 14 81 80.6 27
36 35.6 2 59/60 59 15 82/83 82.4 28
37/38 37.4 3 61/62 60.8 16 84/85 84.2 29
39/40 39.2 4 63 62.6 17 86/87 86 30
41/42 41 5 64/65 64.4 18 88/89 87.8 31
43/44 42.8 6 66/67 66.2 19 90 89.6 32
45 44.6 7 68/69 68 20 91/92 91.4 33
46/47 46.4 8 70/71 69.8 21 93/94 93.2 34
48/49 48.2 9 72 71.6 22 95/96 95 35
50/51 50 10 73/74 73.4 23 97/98 96.8 36
52/53 51.8 11 75/76 75.2 24 99 98.6 37
54 53.6 12 77/78 77 25

Appendix 2: Configuration of Connection Pipe


1.Standard length of connection pipe Max length of Max height
Cooling capacity
connection pipe difference
● 5m, 7.5m, 8m.
5000 Btu/h(1465 W) 15 m 5m
2.Min. length of connection pipe is 3m.
7000 Btu/h(2051 W) 15 m 5m
3.Max. length of connection pipe and max. high difference.
9000 Btu/h(2637 W) 15 m 10 m
4.The additional refrigerant oil and refrigerant charging required after 12000 Btu/h(3516 W) 20 m 10 m
prolonging connection pipe 18000 Btu/h(5274 W) 25 m 10 m
● After the length of connection pipe is prolonged for 10m at the basis 24000 Btu/h(7032 W) 25 m 10 m
of standard length, you should add 5ml of refrigerant oil for each 28000 Btu/h(8204 W) 30 m 10 m
additional 5m of connection pipe. 36000 Btu/h(10548 W) 30 m 20 m
● The calculation method of additional refrigerant charging amount (on 42000 Btu/h(12306 W) 30 m 20 m
the basis of liquid pipe): 48000 Btu/h(14064 W) 30 m 20 m
● When the length of connection pipe is above 5m, add refrigerant according to the prolonged length of liquid pipe. The additional
refrigerant charging amount per meter is different according to the diameter of liquid pipe. See the following sheet.
● Additional refrigerant charging amount = prolonged length of liquid pipe X additional refrigerant charging amount per meter
Additional refrigerant charging amount for R22, R407C, R410A and R134a
Diameter of connection pipe Outdoor unit throttle
Liquid pipe(mm) Gas pipe(mm) Cooling only(g/m) Cooling and heating(g/m)
Ф6 Ф9.5 or Ф12 15 20
Ф6 or Ф9.5 Ф16 or Ф19 15 20
Ф12 Ф19 or Ф22.2 30 120
Ф16 Ф25.4 or Ф31.8 60 120
Ф19 / 250 250
Ф22.2 / 350 350

Installation and Maintenance 139


Service Manual

Appendix 3: Pipe Expanding Method


Pipe
Note:

Improper pipe expanding is the main cause of refrigerant leakage.Please Pipe cutter
expand the pipe according to the following steps:
Leaning Uneven Burr
A:Cut the pip
● Confirm the pipe length according to the distance of indoor unit and outdoor unit.
● Cut the required pipe with pipe cutter.

B:Remove the burrs Pipe

● Remove the burrs with shaper and prevent the burrs from getting into the pipe. Shaper

Downwards
C:Put on suitable insulating pipe

D:Put on the union nut Union pipe


● Remove the union nut on the indoor connection pipe and outdoor valve; install
the union nut on the pipe. Pipe

E:Expand the port


● Expand the port with expander.
Hard
Note: mold
Expander
● "A" is different according to the diameter, please refer to the sheet below:
A(mm) Pipe
Outer diameter(mm)
Max Min
Ф6 - 6.35 (1/4") 1.3 0.7
Ф9.52 (3/8”) 1.6 1.0
Ф12 - 12.70 (1/2”) 1.8 1.0
Ф16 - 15.88 (5/8”) 2.4 2.2

Smooth surface
F:Inspection
● Check the quality of expanding port. If there is any blemish, expand the
Improper expanding
port again according to the steps above.

leaning damaged crack uneven


surface thickness
The length is equal

140 Installation and Maintenance


Service Manual

Appendix 4: List of Resistance for Temperature Sensor


Resistance Table of Ambient Temperature Sensor for Indoor and Outdoor Units (15K)

Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ)


-19 138.1 20 18.75 59 3.848 98 1.071
-18 128.6 21 17.93 60 3.711 99 1.039
-17 121.6 22 17.14 61 3.579 100 1.009
-16 115 23 16.39 62 3.454 101 0.98
-15 108.7 24 15.68 63 3.333 102 0.952
-14 102.9 25 15 64 3.217 103 0.925
-13 97.4 26 14.36 65 3.105 104 0.898
-12 92.22 27 13.74 66 2.998 105 0.873
-11 87.35 28 13.16 67 2.896 106 0.848
-10 82.75 29 12.6 68 2.797 107 0.825
-9 78.43 30 12.07 69 2.702 108 0.802
-8 74.35 31 11.57 70 2.611 109 0.779
-7 70.5 32 11.09 71 2.523 110 0.758
-6 66.88 33 10.63 72 2.439 111 0.737
-5 63.46 34 10.2 73 2.358 112 0.717
-4 60.23 35 9.779 74 2.28 113 0.697
-3 57.18 36 9.382 75 2.206 114 0.678
-2 54.31 37 9.003 76 2.133 115 0.66
-1 51.59 38 8.642 77 2.064 116 0.642
0 49.02 39 8.297 78 1.997 117 0.625
1 46.6 40 7.967 79 1.933 118 0.608
2 44.31 41 7.653 80 1.871 119 0.592
3 42.14 42 7.352 81 1.811 120 0.577
4 40.09 43 7.065 82 1.754 121 0.561
5 38.15 44 6.791 83 1.699 122 0.547
6 36.32 45 6.529 84 1.645 123 0.532
7 34.58 46 6.278 85 1.594 124 0.519
8 32.94 47 6.038 86 1.544 125 0.505
9 31.38 48 5.809 87 1.497 126 0.492
10 29.9 49 5.589 88 1.451 127 0.48
11 28.51 50 5.379 89 1.408 128 0.467
12 27.18 51 5.197 90 1.363 129 0.456
13 25.92 52 4.986 91 1.322 130 0.444
14 24.73 53 4.802 92 1.282 131 0.433
15 23.6 54 4.625 93 1.244 132 0.422
16 22.53 55 4.456 94 1.207 133 0.412
17 21.51 56 4.294 95 1.171 134 0.401
18 20.54 57 4.139 96 1.136 135 0.391
19 19.63 58 3.99 97 1.103 136 0.382

Installation and Maintenance 141


Service Manual

Resistance Table of Tube Temperature Sensors for Outdoor and Indoor (20K)

Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ)


-19 181.4 20 25.01 59 5.13 98 1.427
-18 171.4 21 23.9 60 4.948 99 1.386
-17 162.1 22 22.85 61 4.773 100 1.346
-16 153.3 23 21.85 62 4.605 101 1.307
-15 145 24 20.9 63 4.443 102 1.269
-14 137.2 25 20 64 4.289 103 1.233
-13 129.9 26 19.14 65 4.14 104 1.198
-12 123 27 18.13 66 3.998 105 1.164
-11 116.5 28 17.55 67 3.861 106 1.131
-10 110.3 29 16.8 68 3.729 107 1.099
-9 104.6 30 16.1 69 3.603 108 1.069
-8 99.13 31 15.43 70 3.481 109 1.039
-7 94 32 14.79 71 3.364 110 1.01
-6 89.17 33 14.18 72 3.252 111 0.983
-5 84.61 34 13.59 73 3.144 112 0.956
-4 80.31 35 13.04 74 3.04 113 0.93
-3 76.24 36 12.51 75 2.94 114 0.904
-2 72.41 37 12 76 2.844 115 0.88
-1 68.79 38 11.52 77 2.752 116 0.856
0 65.37 39 11.06 78 2.663 117 0.833
1 62.13 40 10.62 79 2.577 118 0.811
2 59.08 41 10.2 80 2.495 119 0.77
3 56.19 42 9.803 81 2.415 120 0.769
4 53.46 43 9.42 82 2.339 121 0.746
5 50.87 44 9.054 83 2.265 122 0.729
6 48.42 45 8.705 84 2.194 123 0.71
7 46.11 46 8.37 85 2.125 124 0.692
8 43.92 47 8.051 86 2.059 125 0.674
9 41.84 48 7.745 87 1.996 126 0.658
10 39.87 49 7.453 88 1.934 127 0.64
11 38.01 50 7.173 89 1.875 128 0.623
12 36.24 51 6.905 90 1.818 129 0.607
13 34.57 52 6.648 91 1.736 130 0.592
14 32.98 53 6.403 92 1.71 131 0.577
15 31.47 54 6.167 93 1.658 132 0.563
16 30.04 55 5.942 94 1.609 133 0.549
17 28.68 56 5.726 95 1.561 134 0.535
18 27.39 57 5.519 96 1.515 135 0.521
19 26.17 58 5.32 97 1.47 136 0.509

142 Installation and Maintenance


Service Manual

Resistance Table of Discharge Temperature Sensor for Outdoor (50K)

Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ)


-29 853.5 10 98 49 18.34 88 4.75
-28 799.8 11 93.42 50 17.65 89 4.61
-27 750 12 89.07 51 16.99 90 4.47
-26 703.8 13 84.95 52 16.36 91 4.33
-25 660.8 14 81.05 53 15.75 92 4.20
-24 620.8 15 77.35 54 15.17 93 4.08
-23 580.6 16 73.83 55 14.62 94 3.96
-22 548.9 17 70.5 56 14.09 95 3.84
-21 516.6 18 67.34 57 13.58 96 3.73
-20 486.5 19 64.33 58 13.09 97 3.62
-19 458.3 20 61.48 59 12.62 98 3.51
-18 432 21 58.77 60 12.17 99 3.41
-17 407.4 22 56.19 61 11.74 100 3.32
-16 384.5 23 53.74 62 11.32 101 3.22
-15 362.9 24 51.41 63 10.93 102 3.13
-14 342.8 25 49.19 64 10.54 103 3.04
-13 323.9 26 47.08 65 10.18 104 2.96
-12 306.2 27 45.07 66 9.83 105 2.87
-11 289.6 28 43.16 67 9.49 106 2.79
-10 274 29 41.34 68 9.17 107 2.72
-9 259.3 30 39.61 69 8.85 108 2.64
-8 245.6 31 37.96 70 8.56 109 2.57
-7 232.6 32 36.38 71 8.27 110 2.50
-6 220.5 33 34.88 72 7.99 111 2.43
-5 209 34 33.45 73 7.73 112 2.37
-4 198.3 35 32.09 74 7.47 113 2.30
-3 199.1 36 30.79 75 7.22 114 2.24
-2 178.5 37 29.54 76 7.00 115 2.18
-1 169.5 38 28.36 77 6.76 116 2.12
0 161 39 27.23 78 6.54 117 2.07
1 153 40 26.15 79 6.33 118 2.02
2 145.4 41 25.11 80 6.13 119 1.96
3 138.3 42 24.13 81 5.93 120 1.91
4 131.5 43 23.19 82 5.75 121 1.86
5 125.1 44 22.29 83 5.57 122 1.82
6 119.1 45 21.43 84 5.39 123 1.77
7 113.4 46 20.6 85 5.22 124 1.73
8 108 47 19.81 86 5.06 125 1.68
9 102.8 48 19.06 87 4.90 126 1.64

Installation and Maintenance 143


JF00301976

GREE ELECTRIC APPLIANCES,INC.OF ZHUHAI


Add: West Jinji Rd, Qianshan, Zhuhai, Guangdong, China 519070
Tel: (+86-756) 8522218 Fax: (+86-756) 8669426
Email: gree@gree.com.cn Http://www.gree.com