nv Sy wow, gs 8. 9. Stiffness of slab can not be considered in analysis. It is not part of Lateral load resisting system. It is used for diaphragm. Standard stiffness should be considered as per code. Manual mesh should be performed on Shear Wall. Otherwise it will not perform as shear wall. Cracked section should be considered for Seismic Design Dynamic analysis should be performed Stability index should be checked Wind load should be calculated as Per BNBC-2006 Building is separated by two part. Finite element analysis should be performed independently ‘Must be check soft story in ground floor and if exist, should be mitigated All BNBC load combination must be used for Design 10. Beam size can be reduced 11 Secondary beam arrangement should be changed as per stiffness