Stiffness of slab can not be considered in analysis. It is not part of Lateral
load resisting system. It is used for diaphragm. Standard stiffness should be
considered as per code.
Manual mesh should be performed on Shear Wall. Otherwise it will not
perform as shear wall.
Cracked section should be considered for Seismic Design
Dynamic analysis should be performed
Stability index should be checked
Wind load should be calculated as Per BNBC-2006
Building is separated by two part. Finite element analysis should be performed
independently
‘Must be check soft story in ground floor and if exist, should be mitigated
All BNBC load combination must be used for Design
10. Beam size can be reduced
11 Secondary beam arrangement should be changed as per stiffness