TABLE 9: EXISTING AND RECOMMENDED SOLID STATE TRIP (SST) SETTINGS TABLE:

LOAD DATA CIRCUIT BREAKER RATING SOLID STATE TRIP (SST)


SIZE / AMP. SENSOR / TRIP P/U SHORT TIME GROUND OVERCURRENT
RATING V FLA MANUF MODEL NO FRAME PLUG TYPE MODEL CURRENT (SET) LT BAND INST
CIRCUIT BREKER TAG NO. DESCRIPTION PU BAND PU AMP BAND REMARKS
SET
Substation - 7:

MC71A Feeder
S71-2 406 KVA 480 488 A Mitsubishi DS-416 800 AF 800 A SST OCT 0.80 640 10 s 8 0.33s --- 0.20 160 A 0.33s EXISTING SETTING
(Existing)
MC71A Feeder
S71-2 442 KVA 480 532 A Mitsubishi DS-416 800 AF 800 A SST OCT 0.80 640 10 s 8 0.33s --- 0.20 160 A 0.33s RECOMMENDED (NO CHANGE)
(After adding New loads)

V21-MC71A Cub. B3G V25-007-PP-005 New Feeder 406 KVA 480 488 A Mitsubishi DS-416 800 AF 800 A SST OCT 0.80 640 10 s 8 0.33s --- 0.20 160 A 0.33s NEW FEEDER RECOMENDED SETTING

V21-MC71A Cub. B3G V25-007-PP-005 New Feeder 442 KVA 480 532 A Mitsubishi DS-416 800 AF 800 A SST OCT 0.80 640 10 s 8 0.33s --- 0.20 160 A 0.33s NEW FEEDER RECOMENDED SETTING

Substation - 10:

S101-1 MC81B Feeder 131 KVA 480 158 A Mitsubishi DS-416 800 AF 800 A SST OCT 1.00 800 10 s 8 0.33s --- 0.20 160 A 0.33s EXISTING SETTING

MC81B Feeder
S101-1 150 KVA 480 180 A Mitsubishi DS-416 800 AF 800 A SST OCT 1.00 800 10 s 8 0.33s --- 0.20 160 A 0.33s RECOMMENDED (NO CHANGE)
(After adding New loads)

S101-7 V21-010-PP-001 131 KVA 480 158 A Mitsubishi DS-416 800 AF 800 A SST OCT 1.00 800 10 s 8 0.33s --- 0.20 160 A 0.33s EXISTING SETTING

V21-010-PP-001
S101-7 150 KVA 480 180 A Mitsubishi DS-416 800 AF 800 A SST OCT 1.00 800 10 s 8 0.33s --- 0.20 160 A 0.33s RECOMMENDED (NO CHANGE)
(After adding New loads)

S101-2 MC101A (V21-EDP101) Feeder 131 KVA 480 158 A Mitsubishi DS-416 800 AF 800 A SST OCT 1.00 800 10 s 8 0.33s --- 0.20 160 A 0.33s EXISTING SETTING

MC101A (V21-EDP101) Feeder


S101-2 150 KVA 480 180 A Mitsubishi DS-416 800 AF 800 A SST OCT 1.00 800 10 s 8 0.33s --- 0.20 160 A 0.33s RECOMMENDED (NO CHANGE)
(After adding New loads)