Professional Documents
Culture Documents
Wiring Electrical Circuits PDF
Wiring Electrical Circuits PDF
Preview
All electrical systems have one thing in common—they must be properly connected. Schematic diagrams
and wiring plans are needed to properly connect and maintain electrical systems. As an electrician,
you should be able to identify and understand the common wiring terms and symbols used in these
diagrams and plans. Although most of the branch circuits discussed in this study unit are based on
residential use, they may also apply to many commercial and industrial applications.
· Identify the correct type of general or special-purpose circuit when given a list of circuit
descriptions
· Describe how wiring is installed for branch circuits in a residence under particular situations
· Differentiate between portable, fixed, and stationary appliances and describe how each
type is wired
Contents
SELF-CHECK ANSWERS . . . . . . . . . . . . . . . . . . . . . . . . . . 83
EXAMINATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
1
FIGURE 1A—This drawing shows a typical electrical system with the service entrance highlighted.
To understand how power is fed into the home, let’s look at the right
side of the diagram in Figure 1A.
The electric range uses a separate circuit breaker within the equipment
panel board. In this example, the range circuit is a 240-V circuit that’s
protected by a two-pole circuit breaker. In this study unit, you’ll learn
about the many types of branch circuits found in a modern residence,
and how to identify and install the required circuit components.
Electrical Circuits
Definition of a Circuit
According to the NEC, the term electrical equipment means any material,
fitting, device, appliance, or apparatus used as part of, or in connection
with, an electrical installation. The words equipment and component are
used interchangeably because each piece of equipment is a component
of the electrical installation. If electrical components are connected together
properly, they form an electrical circuit. Simply put, an electrical circuit
is the complete path followed by electric current.
A branch circuit consists of the conductors and devices installed between
the branch-circuit protection device (breaker or fuse) and the receptacle
or connection point of the load. Once an appliance or load is either
plugged into or connected to the receptacle or connection point, those
components used to plug in or connect to the branch circuit become part
of the circuit. These components are sometimes referred to as the “load
circuit,” although the electrical trade doesn’t recognize this phrase in
defining circuits.
Circuit Components
Figure 2 shows the five basic types of components in a simple electrical
circuit. All electrical circuits include, at the very least, the following three
components—the power source, load, and conductors that join them.
In Figure 2, a transformer is used as a power source and conductors join
the transformer to a lamp. This is the electrical load or destination.
Even without the fuse and switch, a complete circuit would still exist. The
power source may originate from a panel board, transformer, battery, or
generator. Most circuits contain at least one or more electrical devices
such as switches, which are control devices, or fuses, which are protective
devices. Many circuits also have circuit breakers, devices that both protect
and control the circuit. A receptacle is a convenience device, used with a
mating plug. A plug makes it easy to connect a conductor between the
power source and load.
6 Wiring Electrical Circuits
120V
SWITCH
CONDUCTORS
FUSE
LOAD
Types of Circuits
Electric circuits have names such as series circuits, branch circuits, 120-V
circuits, high-voltage circuits, and remote-control circuits. The different
names can be very confusing, especially when the same circuit is called
by more than one name. Often, two or more names are combined to give
a complete and accurate description of the circuit.
The following list shows how circuits are described in terms of their
characteristics.
Often there’s no clear-cut category for a circuit. The name of the circuit
used at any one time depends on the circuit characteristics being
discussed at that time.
FIGURE 3—When a series circuit is opened, no current flows. In a parallel circuit, one branch can
be opened, and current will still flow through the others.
Combination Circuits
Parts of a wiring system may be connected in a combination of series
and parallel circuits. Figure 4 shows two diagrams of a heater circuit. In
the schematic view, the heater and switch are connected in series with
each other. The fan motor is connected in parallel with them. The circuit
has two parallel branches. One branch has only one part, the fan motor;
the other branch contains two parts in series, the heater and the switch.
In this heater diagram, the switch controls only the heating element, not
the fan. This is a series-parallel combination, or compound circuit.
SOURCE
TERMINALS
LINE CORD
FIGURE 4—This shows schematic and pictorial diagrams of the same heater/fan circuit.
Wiring Electrical Circuits 9
The pictorial diagram in Figure 4 labels the colors of the wires. Note
that one side of each branch has a white wire. These white wires are
connected to the common white wire, which leads to a source terminal.
The red wire from the switch and the red wire from the fan motor are
connected to the black wire. The black wire then leads to the other
source terminal. Remember that in Figure 4, the common wire is white
and all white wires are connected together.
Remember that the same voltage exists across each branch of a parallel
circuit. For that reason, electrical loads are designed to operate at certain
standard voltages. All loads in a typical residence that require alternating
current operate at either 120 or 240 V. Industrial and some commercial
equipment are designed to operate at these or higher standard voltages.
No matter what the voltage is, all loads will be connected in parallel
with the voltage source.
Circuit Variables
Most circuits you’ll be dealing with are parallel circuits. These circuits
have the same voltage for all the parallel loads. Suppose you’re going
to connect a new electrical load in a parallel circuit. You’ll need to
know the circuit’s operating voltage and the branch circuit conductor’s
current-carrying capacity, or ampacity. Suppose the existing circuit is
rated at 120 V and 20 amperes; the new load will be connected to the
existing circuit to put it in parallel with the circuit. It’s critical that the
sum of the currents of all the parallel loads, including the newly added
load, doesn’t exceed 20 amperes.
Since the neutral conductors are connected together at the panel board,
they’re one-wire. Why use two wires when one will do? It’s important to
note that a three-wire 120/240-V circuit will do the work of two, two-wire
120-V circuits. However, opposite phase conductors sometimes share
the same neutral as in the three-wire (multi-wire) circuit shown in
Figure 5. If the neutral is disconnected or interrupted, the circuit would
become a series circuit with a nominal voltage of 240 V! The load, if not
rated for the higher voltage, would most likely be damaged or destroyed
by the higher voltage. For this reason, it’s very important to be cautious
in disconnecting neutral conductors in a panel.
Assume that equal loads of 20 A each are present on the multi-wire
circuit (which in this case is a three-wire circuit) in Figure 5. Then 20 A
flows in lines a and b, but the two arrows on the neutral n are in opposite
directions. Thus, the currents cancel and no current flows in the neutral.
The result is no voltage drop in the neutral and less voltage drop in each
circuit.
When the currents are unequal there’s less current in the neutral than in
either hot conductor. As an example, if line a is carrying 20 A and line b
is carrying 15 A, then the neutral n is carrying 5 A (20 – 15 = 5 A).
Although the neutral current now is no longer zero, it’s still much less
than either line current. This example remains there even when the sin-
gle loads in Figure 5 are replaced by several smaller loads located where
needed. However, this is true only if their current is drawn equally from
each of the two sides of the circuit.
Wiring Electrical Circuits 11
Grounded Circuits
You’ll remember that the neutral wire in a two-wire system is grounded
or connected to the earth. When the neutral wire is connected to the earth,
it’s a grounded conductor because it carries current during normal circuit
operation. Don’t confuse the grounded conductor with the grounding
conductor. The grounded conductor is part of the current-carrying electrical
circuit whose function is to provide a circuit path and stability to the level
of voltage. A grounding conductor, on the other hand, isn’t a current-
carrying conductor. Its function is to provide safety and protection to
both personnel and equipment with a low impedance path to ground in
case of a short in the electrical system.
The grounded conductor or neutral wire must be kept continuous. In
residential wiring, the neutral wire is never interrupted by a fuse, circuit
breaker, switch, or other device. In industrial wiring, the neutral wire
may be interrupted, but only if the ungrounded wires and the neutral
wire are interrupted at the same time.
Another type of circuit is the hazardous-area circuit. It’s unique in that the
circuit requires special explosion-proof devices and fittings. The
electrical loads on these circuits, such as motors and lamps, must be of
special construction.
T FRONT BACK
S-1
FRONT-
DOOR
SWITCH
S-2
BACK-
DOOR
SWITCH
Control Circuits
Control circuits are the next most common circuits an electrician has to
work on beside branch and feeder circuits. That’s why you, the electrician,
must have a thorough understanding of basic electricity and be able to
read and understand control drawings. Control circuits are commonly
used to regulate or control the supply of electrical power to a load. They
may either switch the power on or off or may adjust the power to a
desired level. Some control circuits are very simple while others are
quite complex.
In the control drawing for the air conditioner, the heavy black dots in the
mode switch indicate which connections are energized for the various
modes of operation. In the HI FAN position, notice that line terminal L is
connected only to terminal 1, which goes to the fan motor.
Review
Circuits may be referred to by different names but all circuits are basically
common to one another in that each circuit or group of circuits has three
components—a source of power, conductors, and an electrical load.
Most circuits will also likely contain protective and control devices.
✔ Self-Check 1
At the end of each section of Wiring Electrical Circuits, you’ll be asked to check your under-
standing of what you’ve just read by completing a “Self-Check.” Writing the answers to these
questions will help you review what you’ve learned so far. Please complete Self-Check 1 now.
1. The conductors that run in the air from a utility pole to the first point of attachment on a
building are called the ________ ________.
2. The two components in Figure 2 that provide the necessary circuit protection and control
are the fuse and the _______.
3. Protective and control devices are connected in _______ with the load.
4. Electricity is distributed by most electric utilities as _______ current.
5. In a three-wire 120/240-V circuit, if the current in line a is 17 A and the current in line b is
8 A, the current in the neutral is _______ A.
6. A _______ conductor is connected to the earth and doesn’t carry current during normal
operation.
7. When you call a circuit an electric heater circuit, or a motor circuit, you’re referring to it by
the type of _______ it supplies.
8. Name two types of special or auxiliary circuits.
_______________________________________________________________________________
9. If you’re installing an electrical system in a hazardous area, you must be sure to use
_______ devices and fittings.
Check your answers with those on page 83.
16 Wiring Electrical Circuits
However, the local code may dictate that the service load be calculated
using established methods. One such method is the optional calculations
for dwelling units described in Article 220-30 of the NEC. The following
steps show how to compute the estimated load on the hot and neutral
service-entrance conductors using this method. A sample calculation will
follow.
Follow Steps 1 through 6 to calculate the service conductor load.
Step 1: Calculate the volt-ampere (VA) load for the general lighting
and receptacles. Find this by multiplying the total square footage
of the building by 3 VA as stated in Article 220-30(b)(2) of the
NEC. (Note that to convert VA to kVA you divide by 1000.)
Save this number for a later calculation.
Wiring Electrical Circuits 17
Step 4: Calculate the total volt-ampere demand load from the last three
steps by applying the demand factors listed in Table 220-30 in
the NEC to the calculated total.
Step 6: Divide the total found in Step 5 by the system voltage, usually
240 volts. The result is the amperage rating for the service
conductors as covered in the NEC Article 310-16.
Follow Steps 7 through 8 to calculate the neutral conductor
load.
Step 7: Add the general load found in the first step with the kitchen
and laundry loads in the second step. Begin the neutral con-
ductor calculation by counting the first 3000 VA at 100%, or
3000VA. Combine this with 35% of the remaining VA from
steps 1 and 2. Now add 100% of the dishwasher VA, and 70%
of the range and the dryer VA.
Step 8: Divide this total by the system voltage (240 volts) and the
answer is the amperage. According to Article 310-16 of the NEC,
you’ll use this number to determine the required neutral
conductor type and size for this residence.
Example: Find the total estimated load on the hot and neutral
load service-entrance conductors for a dwelling with a total of
2500 square feet. The dwelling contains a 3 kVA or 3000 VA
water heater, 1.5 kVA or a 1500 VA dishwasher, and a 5 kVA or
5000 VA air conditioner. It also contains four or more combined
space heaters of 15 kVA or 15000 VA, a 5.5 kVA or 5500 VA
dryer, and a 12 kVA or 12000 VA range.
Electricians must follow the NEC and local codes closely when placing
the service-entrance cable. The minimum height of the power line above
pedestrians or vehicle traffic, the size of the conduit required (when
conduit is used), and the space between cable clamps (when service-
entrance cable is used) are all closely specified by the NEC (Figure 9).
Local codes sometimes expand on the requirements of the NEC but never
reduce the requirements. Always check local codes and ordinances before
installation to assure compliance. When calculating clearance heights
and conductor lengths, remember to account for the amount of conductor
the power company will require for a drip loop and splicing. It’s typically
acceptable to leave a minimum of two feet of excess cable beyond the
weatherhead. The local power company sometimes specifies the length
of excess cable to be extended beyond the weatherhead.
20 Wiring Electrical Circuits
FIGURE 8—(A) shows a typical service-drop installation while (B) shows how the power company uses splices
to connect the service drop to the service-entrance cable the electrician has installed.
Wiring Electrical Circuits 21
CLAMPS
NO MORE
THAN 30"
BETWEEN
CLAMPS
(DEPENDING ON
LOCAL CODES)
NO MORE
THAN 12"
METER BASE
Sometimes the meter base will be located on the opposite side of the
wall from the service panel, as illustrated in Figure 8A. When these two
pieces of equipment are located back-to-back, the job of completing the
service-entrance circuit is much easier and less expensive. However, the
electrician usually doesn’t decide on the location of the service.
22 Wiring Electrical Circuits
If the meter base and service panel aren’t located back-to-back, a longer
run of service-entrance conductor will be needed from the meter base to
the panel. This means that a service disconnecting means will be needed
to control the power within that additional run of service cable in case of
a short circuit. If the meter base and service panel are mounted back-to-
back, routing the wires from the base to the panel is simple. First, to mount
the meter base on the outside of the house, remove the knockouts from
the back of the base (designed to allow conductors to run from the base
to the panel box). Hold the meter base level against the building with the
correct side facing up. Trace the shape of the box opening onto the wall,
remove the box, and cut a hole slightly larger than the one traced.
Obviously, don’t cut through any wall studs because they’re designed
to support the structure.
Now attach any required conduit fittings to the meter base. Conduit
fittings attached may be those that accept the service-entrance cable from
the drip loop or ones that route the cable onto the panel box. Remember
that for an overhead service the connector on the top of the meter base
must be watertight and matched to the size conduit or service-entrance
cable being installed. The service-entrance cable from an underground
service will always be installed in conduit and fed into the bottom of the
meter base. In this case, the conduit will be joined to the meter base with
a standard conduit fitting.
Next, coat the wall around the outside of the hole with a heavy bead of
sealant. Make sure the meter base is level and fasten the meter base to
the wall using screws or appropriate anchors. To provide additional
sealing against moisture, place an additional bead of sealant where the
top and two sides of the meter base meet the wall. Don’t seal where the
bottom of the meter base meets the wall because moisture that seeps in
from the top or sides needs to exit the space behind the meter base.
When hooking up the meter base, remember that the incoming power
line is attached to the top (line side) terminals, while the conductors that
exit the meter base and feed the service panel will connect to the bottom
Wiring Electrical Circuits 23
NEUTRAL
CONDUCTOR
TWO HOT
CONDUCTORS
NEUTRAL
CONDUCTOR
TWO HOT
CONDUCTORS
24 Wiring Electrical Circuits
It’s more likely that the service panel won’t be located directly on the
other side of the wall from the meter base. If not, the service-entrance
cable will exit the bottom of the meter base, and may enter the dwelling
as shown in Figure 11.
FIGURE 11—In this example,
a service-entrance cable
exits the bottom of the
meter base, enters the
basement, is routed through
a main disconnect mounted INSIDE WALL
nearest the point of
basement entrance, and
enters the panel.
SE
CABLE
PANEL
BOX
SERVICE
OUTSIDE DISCONNECT
WALL
BASEMENT
Wiring Electrical Circuits 25
Before finishing your final systems design and certainly before purchasing
materials or submitting a material list or bid, the electrician should lay
out the complete service entrance on paper. One erroneous dimension
could result in several improperly placed systems components. Both
NEC requirements and local code requirements must be reviewed
prior to installing any components to assure compliance. Consider easily
forgotten components such as grounding rods, grounding conductors,
clamps, connectors, anchors, fittings, anti-oxidant (for aluminum
conductors) and other miscellaneous hardware when preparing a
material list or bid.
Panels are also rated based on the number of breakers they hold. The
largest-capacity 200-amp panels may hold up to forty-two circuit breakers.
In most cases, you should select the panel within the target amperage
range that’s capable of holding the most breakers.
Finally, remember that the electrician is ultimately the person who must
hook up the panel. When working with different panel designs, try to
pre-evaluate them for ease of assembly and growth. The location of
neutral buses, the arrangement of breaker installation, and several other
features contribute to making the panel either easier or more difficult to
wire.
panel, as shown in Figure 12. The switched conductors are always the
two hot conductors. When the main breaker in the service panel serves
as the main disconnecting device, it must be labeled “Service Discon-
nect.” The other two conductors entering the panel (neutral and ground)
are connected to the neutral bus and grounding bar (not shown) respec-
tively. The neutral bar must be bonded to the panel enclosure using a
bonding screw that’s normally supplied with the panel enclosure. You’ll
learn more about bonding in a later section.
now know, each of these branch circuits requires its own breaker and
in many cases, these breakers will be quite different from one another.
In this section of the study unit, we’ll discuss the various types of breakers
you’ll encounter and explain how they’re used in a modern residential
service panel.
Dual or piggyback breakers can usually be inserted only into panels that
provide slots for their installation. They’re designed to protect two indi-
vidually separate branch circuits. The dual breaker is normally the same
width as a standard breaker but contains two half-thickness breakers,
each with its own handle (Figure 13). A half breaker is simply one-half of a
dual breaker and can only be connected to one branch circuit. It’s some-
times referred to in the trade as a “thin” breaker. As more dual and half
breakers are used, the number of branch circuits connected in a panel
increases, as does the ambient temperature in the panel enclosure.
Therefore, the allowable number of dual and half breakers is limited. Half
and dual breakers can only be installed in slots indicated by the panel
box manufacturer. These panels incorporate a special groove designed
to accept a tab that’s formed into the bottom of the breaker. Only panels
that are equipped with the groove can accept these special breakers.
FIGURE 13—Dual and half
breakers are designed to
fit only grooved slots in a
panel enclosure.
28 Wiring Electrical Circuits
Double-pole breakers connect to both legs of the hot bus. These breakers
normally protect and control branch circuits that supply 240 volts.
Double-pole breakers protecting residential branch circuits usually range
from 15 to 70 amps, with 30-amp breakers protecting most clothes dryer
and water heater circuits. The 40- or 50-amp breakers are normally used
to protect the electric kitchen range and/or oven circuits.
To better balance a circuit, distribute the loads equally between the two
hot buses as much as possible. One method you may use is splitting the
two small-appliance circuits to the kitchen between the two hot buses.
The NEC and local codes specify many of the procedures associated
with the installation of the grounding system. The NEC also specifies
that the conductor used to connect the grounding rod to the service
panel be free from interruptions or splices.
Table 1
GROUNDING ELECTRODE CONDUCTOR FOR ALTERNATING-CURRENT SYSTEMS
Aluminum or Aluminum or
Copper Copper
Copper-Clad Aluminum Copper-Clad Aluminum2
2 or smaller 1/0 or smaller 8 6
Notes:
(a) Where multiple sets of service-entrance conductors are used as permitted in Section 230-40, Exception
No. 2, the equivalent size of the largest service-entrance conductor shall be determined by the largest
sum of the areas of the corresponding conductors of each set.
(b) Where there are no service-entrance conductors, the grounding electrode conductor size shall be
determined by the equivalent size of the largest service-entrance conductor required for the load
to be served.
1This table also applies to the derived conductors of separately derived AC systems.
2See installation restrictions in Section 250-64(a) of the NEC
(Reprinted with permission from NFPA 70-1999, the National Electrical Code®, Copyright© 1998, National Fire Protection Association, on the
referenced subject which is represented only by the standard in its entirety. National Electrical Code® and NEC® are registered trademarks
of the National Fire Protection Association, Inc., Quincy, MA 02269)
All raceways for the service entrance shall be bonded together. Again,
Table 1 indicates the size of the bonding jumper needed. If the conductors
within the conduit or the conduits themselves are larger than 1100 kcmil
copper or 1750 kcmil aluminum, the bonding jumper shall have an area
not less than 12 1 2 percent of the area of the largest phase conductor. In
the case of parallel conductors, the largest area of a phase conductor is
considered to be the sum of the areas of the conductors paralleled in one
phase.
Wiring Electrical Circuits 31
Problem 1:
What size of copper-bonding jumper is required to bond a metal conduit
with three 500-kcmil THWN Cu conductors and one neutral conductor?
Solution:
Figure 14 shows that we have only one 500 kcmil per phase. Refer to
Table 1 under service-entrance conductors in the Copper column. A
500 kcmil conductor falls under the “Over 350 kcmil through 600 kcmil”
category. Therefore, 1/0-size copper wire is needed to bond the metal
conduit properly.
FIGURE 14—This shows
the bonding of a raceway
with three conductors.
32 Wiring Electrical Circuits
Problem 2:
What size copper-bonding jumper is required to bond three raceways
using one bonding jumper, where each metal conduit contains three
600-kcmil Cu conductors that are parallel per phase? Figure 15 illustrates
this example.
FIGURE 15—This shows the
bonding of three raceways
in a series with three
parallel-phase conductors.
Solution:
The first step is to add up the conductors to find the total kcmil per
phase (600 ´ 3 = 1800 kcmil). Now that we know we have an area of
1800 kcmil per phase, we can check Table 1 for the size of the bonding
jumper needed.
Since Table 1 only goes up to 1100 kcmil Cu, we’re now required to take
12 1 2 % of the largest phase conductor. (The largest phase conductor is
considered to be the total area of the parallel conductors, or 1800 kcmil.)
Using Table 1, locate the largest phase conductor in the conduit (as
explained in note [a]). This would be 600 kcmil Cu. Then refer to the
“Over 350 kcmil through 600 kcmil” column in Table 1. A 1/0-size
conductor is the minimum size that would be required to bond each
conduit properly.
34 Wiring Electrical Circuits
This example shows that if the situations permits, it’s more cost-effective
(material and labor) to bond each conduit individually in a paralleled
system.
The interior metal piping through a building must also be bonded. Table 1
also sizes the bonding conductor for the metal piping. Refer to Figure 17
that shows the proper bonding of the interior metal water pipe. Keep in
mind that it serves no purpose to bond non-metallic water piping such
as PVC.
Subpanels
There may be instances in a residential wiring plan that call for a subpanel
installation. One may be that when a large number of major appliances
and similar heavy loads are located a long distance from the service
panel, a subpanel may be needed to supply these appliances or loads.
Subpanels are also used when an addition is added onto a house.
An addition usually requires several branch circuits and is generally
located quite far from the original service panel. Subpanels are sometimes
installed when adding equipment such as room air conditioners,
dishwashers, etc. because the existing service panel has no more room
for additional breakers.
In new installations, installing subpanels may reduce the amount of
conductor-routing work by permitting the electrician to install only one
large feeder cable from the service panel to the subpanel. The subpanel
can then be located much closer to the locations of the loads. A subpanel
resembles and functions much like a regular panel, with some exceptions.
First, because the subpanel is fed through the main panel, there’s no
need for a main breaker in the subpanel (although you may still install
one if you wish). Secondly, the neutral and ground buses in the subpanel
must be completely isolated from one another. This means that they
can’t be directly connected to one another and that the neutral bus must
be isolated from contacting the subpanel enclosure by mounting it in
the enclosure using some type of insulating material. This is usually
accomplished with plastic separators between the neutral bus and the
enclosure. As just learned, components such as panels, subpanels, and
other enclosures must be connected to equipment ground. Because of
the required separation between the neutral and ground buses, the
equipment-bonding device may only be connected to the ground bus
and not the neutral bus.
Power is supplied to the subpanel directly from the service panel,
normally using a four-conductor service-entrance cable.
Now take a few moments to review what you’ve learned by completing
Self-Check 2.
Wiring Electrical Circuits 39
✔ Self-Check 2
1. True or False? If possible, it’s best to ground each conductor individually.
2. Bonding screws are used to bond the _______ bar.
3. The main breaker can be used as the service _______.
4. The drip loop of the SEC attached to the building must be at least _______ feet above the
ground where only pedestrian traffic is a concern.
5. True or False? Residential wiring must always have a subpanel installed.
6. The neutral bus and subpanel are normally isolated by _______.
7. Heating and burning of conductors caused by short circuits can be reduced by bonding and
_______.
Check your answers with those on page 83.
40 Wiring Electrical Circuits
The arrowheads on the circuits indicate the home runs, which are the cable
runs to the distribution panel where the branch-circuit protective devices
are located. The number of 2- and 3-wire circuits can be found by counting
the arrowheads. The home runs for each circuit normally begin at the
outlet nearest the panel. The ideal location for the panel is where the load
is concentrated, which is in the kitchen and laundry. The location of the
home runs in Figure 21 isn’t typical of a house because the home runs
shown here are scattered without regard to the possible panel location.
Branch circuits normally end at lighting outlets or receptacle outlets. The
light gray lines connecting the outlets in Figure 21 represent runs of
cable. Broken lines are also used sometimes to indicate exposed wiring
in the basement, but the basement isn’t shown in this wiring layout.
In the kitchen, receptacles have been provided for the refrigerator, clock,
iron, can opener, toaster, and other small appliances. A special outlet S
is provided for an ironing station. It’s equipped with a switch and pilot
lamp so that the homeowner will know whether the iron is on or not. A
special receptacle (R) is provided for the range. Several special outlets
are represented in the wiring plan, including one for a clock (C),
dishwasher (DW), garbage disposal (GD), and range hood (RH). Each
special outlet is identified on the drawing to indicate its use. Many range
hoods contain both a fan and a lamp so separate fan and lamp holder
outlets aren’t shown. Note that the kitchen and dining room share two
small-appliance circuits and these circuits don’t enter other rooms. The
NEC doesn’t permit these circuits to supply power to any other rooms
except breakfast nooks.
A sufficient number of receptacles are installed in the other rooms. They’re
spaced approximately equal distances apart. The distance between
adjacent receptacles in the same room (excluding kitchen and bathroom)
should always be less than 12 feet according to the NEC. Each bedroom is
equipped with a combination switch and a receptacle outlet as well as a
ceiling light for general lighting. Each closet has an enclosed lamp
fixture controlled by a pull-chain switch. The receptacle at the entrance
door is conveniently located for connecting a vacuum cleaner or other
small appliances.
The bathroom has a ceiling light for general lighting and special lights at
the mirror. Electric heating is often used in the bathroom to supplement
the regular heating. All receptacles in a bathroom shall be ground-fault
protected. The bathroom circuit may not supply any other room other
than another bathroom.
A split-wired duplex receptacle is shown near the front door in the corner
of the living room. The top half of the receptacle is wired so that it’s con-
trolled by two three-way switches. The bottom half is always energized.
This permits a lamp to be plugged into the top half and controlled
from the front door and the hall, while an appliance such as a clock may
be plugged into the bottom half. The terrace is equipped with two
ground-fault-type weatherproof (WP) receptacles for portable lamps,
decorative lighting, or tools. Because two receptacles are installed, there’s no
need to pass cords over the doorway, thus reducing the chance of
42 Wiring Electrical Circuits
Location of Receptacles
There isn’t a required height for mounting receptacles but a convenient
recommended height for duplex receptacles is 16 inches (in.) above the
floor. At that height, the outlet is more accessible and more adaptable
to appliance cords. In the kitchen, bathroom, laundry, and garage, a
recommended height for receptacles is 48 inches above the floor. In
the kitchen, that height equates to approximately 12 inches above the
countertops.
Present practice is to provide enough receptacles so that no point in a
room (except kitchen and bathroom) is more than 6 feet from a receptacle.
Thus, the distance between receptacles is always less than 12 feet. Any
wall space greater than two feet in length shall require a receptacle.
Sliding panels, such as sliding glass doors, aren’t counted as wall space
according to the NEC Article 210-52(a)(2)(d). The receptacles should be
approximately equally spaced. However, the spacing may be changed
somewhat to address anticipated placement of furniture. In the kitchen,
receptacles installed on a countertop shall be installed so that no point
along the counter (measured horizontally) is more than 24 inches from
a receptacle outlet. A receptacle outlet should also be installed to serve
each counter space 12 inches wide or wider. The receptacle for the refrig-
erator should be hidden from view when the refrigerator is in place.
Weatherproof GFCI (ground-fault circuit interrupter) receptacles should
be installed at convenient outdoor locations, front and back, for supplying
decorative lighting and power tools. These receptacles should be kept at
least 18 inches above ground level for protection of the receptacle and
ease of accessibility. Special receptacles with key locks are available for
use where vandalism is a problem. For extra convenience, wall-mounted
switches may control these outdoor receptacles.
Location of Switches
A convenient height for light switches is approximately 48 inches above
the finished floor, on the lock side of a door, and within 6 inches of the
door frame. Switch locations should be carefully planned to accommodate
the residents by following the normal course of passage from room to
room that a resident may normally take. For example, upon entering the
house a person should be able to turn on a light without taking many
Wiring Electrical Circuits 43
steps. Upon leaving that room, they should also be able to enter the hall
or another room, turn on lights conveniently and turn off the preceding
light. This accommodation can be accomplished by installing three- and
four-way switches. A combination switch and pilot may be installed in
a situation where a light, such as a basement light, can’t be seen from the
switch location. Of course, the combination switch and pilot light
should be installed in a convenient place where it can be seen. When
the branch-circuit wires are run from the panel to the switch and then to
the light, it’s possible to install a combination switch and receptacle at the
switch location because both the hot wire and the neutral wire are present.
With a combination switch and receptacle the receptacle is always
energized regardless of the position of the light switch.
Note: A convenience outlet shall be at least of the duplex type (two or more plug-in positions) except as otherwise specified.
All spaces for which wall-switch controls are required, and which have no more than one principal entrance, shall be equipped with multiple-switch control at the lock side of doors or the
traffic side of arches. If this requirement would result in the placing of switches controlling the same light within 10 ft of each other, one of the switch locations may be eliminated.
45
46 Wiring Electrical Circuits
Not all the outlets listed are likely to be used in any one installation.
However, Table 2 is a good checklist to consult when deciding whether
the planned electrical wiring has enough outlets for safety and
convenience.
Area Requirements
Figure 22 shows a wiring plan for a three-level house. Starting with the
living room, we’ll examine some of the electrical circuits and outlets that
should be considered when wiring a new home or adding circuits to an
older home.
S3 S3 TO SECOND
LEVEL
FLUORESCENT LIGHT S3
S FRONT
DOOR
LIVING ROOM WIRING PLAN
Because there’s no central ceiling light outlet in the living room, a wall
switch at the living room entrance controls at least one of the convenience
outlets placed around the room. This arrangement permits a portable
light like an end table lamp to be switched on from the doorway. In some
designs, the top receptacles of a duplex receptacle are switch controlled
while the bottom receptacles stay hot at all times.
The switch-controlled outlets are called split receptacles. In such outlets,
the common hot metal tab is broken off, making the two receptacles
separate. The common neutral metal tab remains intact, supplying a
common neutral to both parts of the receptacle.
The location standards for these receptacles are the same as those
mentioned earlier in this lesson. The outlets should be installed 12 inches
above the floor line and installed approximately 12 feet apart around the
wall space so that no point along the floor line is more than 6 feet from
an outlet.
Convenience outlets are installed around the dining room walls and
may be supplied by the 20-ampere small-appliance circuits supplying
the kitchen countertop receptacles. However, it’s highly recommended
that separate 20-ampere branch circuits supply these receptacles due to a
high load potential caused by small appliances such as hot plates, toaster
ovens and the like. When a dining table or breakfast table is placed next
to a wall, an outlet located approximately 4 inches above the proposed
table height is often useful for appliances such as toasters.
Some dining rooms may be equipped with serving counters or serving
bars. An extra outlet just above the end of the counter is handy for
appliances such as blenders and ice crushers. This outlet is a NEC
requirement if the bar is a minimum of two feet by one foot in measure-
ment. If the bar is considered a “wet bar” with a water-supplied sink, the
receptacle must be GFCI protected.
50 Wiring Electrical Circuits
Rooms like the residential floor plan in Figure 22 and the one shown in
Figure 25 are defined as bathrooms and must meet or exceed the electri-
cal requirements for bathrooms.
S S
SHOWER GFCI
STALL
SINK
TOILET
FIGURE 25—Some bathrooms may also have special-purpose outlets for space heaters and exhaust fans. The
switch-controlled fan can be part of a light fixture or an individual fixture. Another option is a light fixture in the
shower stall.
Wiring Electrical Circuits 51
Shower stalls may have a vapor-proof light fixture installed, with the
wall switch installed outside of the stall. Steam bath and whirlpool
appliances are supplied separately or may be plugged into convenience
outlets if the load isn’t extremely high. Infrared and ultraviolet light
fixtures may be installed as ceiling fixtures. Receptacles should be
provided in proximity to each mirror to accommodate electric razors,
hair dryers, and other small, personal appliances. All receptacles in a
bathroom must be of the GFCI type.
Special-purpose outlets may also be installed in bathrooms to supply
space heaters and ventilating fans. Usually the vent fan is switch controlled.
It may be directly attached to a ceiling light or installed as an individual
fixture. Switch-controlled nightlights are also recommended as a
convenience feature in bathrooms.
Kitchen Requirements
The electric requirements of a kitchen are more numerous than other
rooms in a house and call for additional planning (Figure 26).
Wall switches usually control most general lighting in a kitchen. The
kitchen should be illuminated so that light is directed on the countertops,
sink, range, dishwasher, work area, and kitchen table. The interiors of
cabinets and other storage areas may have their own fixtures installed to
satisfy special designs.
As a rule, kitchen countertop receptacles should be supplied by at
least two small-appliance circuits. Receptacles on countertops shall be
installed so that no point along the counter space is more than 24 inches
(horizontally) from a receptacle outlet. Countertop receptacles should be
installed approximately 12 inches from the countertop to the bottom of
the receptacle. If a kitchen desk or cookbook shelf is planned, one outlet
should be installed to supply that specialized area. Tables placed against
walls should also have one outlet just above table level to accommodate
food preparation and warming appliances.
The refrigerator should have its own circuit and outlet. All other
convenience outlets may be split-receptacle types connected to two or
more 20-A small-appliance circuits.
Special-purpose circuits and outlets are used for the electric range,
ventilating fan, dishwasher, garbage disposal, food freezer, and other
major appliances located in the kitchen.
52 Wiring Electrical Circuits
Bedroom Requirements
The standard bedroom generally requires ceiling or cornice-type general
illumination. The sample-bedroom layouts shown in Figures 22 and 27
indicate ceiling light outlets. Light fixtures over full-length mirrors and
vanities are also convenient.
FIGURE 27—Install a sufficient number of receptacles in the bedroom. Usually, the night tables next to a bed will
hold such items as lamps, clocks, and radios.
54 Wiring Electrical Circuits
Basement Requirements
The lighting for an unfinished basement, like the one shown in Figure 28,
is more functional than decorative. Typical basement wiring can be almost
commercial appearing in nature. General illumination requirements are
usually one luminescent light for each 150 square feet of open space.
Although there should be no dark areas in a basement, it’s not a require-
ment to light individual areas in an unfinished basement.
FIGURE 28—Most modern,
finished basements require
numerous circuits, since
they contain work areas,
laundry areas, and family
rooms.
Wiring Electrical Circuits 55
A wall switch at the head of the stairs should control the light at the foot
of the stairs. If the number of stairs is six or more, two three-way switches
should be installed, with one at the top of the stairs and the other at the
bottom of the stairs. The switch at the top of the stairs should be equipped
with a pilot light and be located so that no reaching is required to operate
the switch. Fixtures with pull chains may be used in the remaining
sections of the basement. If the basement is equipped with a workbench,
one 20-ampere circuit and receptacle should be installed to supply
power to the workbench.
Outlets are also required if laundry appliances are located in the basement,
but these circuits should follow the same rules that apply to those
previously covered for laundry areas. Any other areas set aside in the
basement for special usage should be supplied with the necessary circuits
and receptacles required. Appliances such as emergency water (sump)
pumps, dehumidifiers, and space heaters should have special-purpose
circuits installed that are rated according to the load demand of the
appliance or equipment.
All general-purpose receptacles in an unfinished basement must be
GFCI. Receptacles that are of the single type and dedicated to supply
power to equipment such as freezers and pumps aren’t required to be
of the GFCI type. Receptacles located in a finished basement aren’t
required to be of the GFCI type.
Fixtures in Closets
The NEC defines storage space as “a volume bounded by the sides and
back closet walls and planes extending from the closet door vertically to
the height of 6 feet, or the highest clothing-hanging rod and parallel to
the walls at a horizontal distance of 24 inches from the sides and back of
the closet walls respectively, and continuing vertically to the closet ceiling
parallel to the walls at a horizontal distance of 12 inches or the width of
the shelf, whichever is greater.”
In the past, people could install all types of surface-mounted and recessed
incandescent fixtures directly over the shelves in closets. When clothes,
boxes, etc., were stored on the shelves, some of this material would
come in contact with the fixture creating a fire hazard within the closet.
Wiring Electrical Circuits 57
Because of those potential fire hazards, the NEC now only allows two
types of lighting fixtures in closets:
1. Surface-mount or recessed incandescent fixtures with the lamp
completely enclosed.
2. Surface-mount or recessed fluorescent fixtures with the lamp
exposed or enclosed.
A surface-mounted incandescent fixture mounted over a door on the
wall or ceiling must be a minimum of 12 inches from the shelf or, if
there’s no shelf, 24 inches from the wall (Figure 30).
✔ Self-Check 3
1. The maximum distance from any point along the floor line to a receptacle in the living
room is ______ feet.
2. True or False? The dining room usually has an outlet for a ceiling-mounted light.
3. Which room in a new house other than the kitchen must have receptacles protected by a
GFCI device?
______________________________________________________________________________
4. In which room of a house would you probably find the master control unit for a remotely
controlled lighting system?
______________________________________________________________________________
5. When should a switch be equipped with a pilot light?
______________________________________________________________________________
Check your answers with those on page 83.
60 Wiring Electrical Circuits
General-Purpose Circuits
General-purpose circuits are two-conductor circuits that provide 120 V to
the lighting outlets and general-purpose convenience outlets, not
including the kitchen countertops, laundry room, or bathroom. Two
rules of thumb apply for the number of circuits to be installed in a
residence.
· Install one 20-A circuit for no more than 750 square feetof floor
space.
· Install one 15-A circuit for no more than 500 square feetof floor
space.
In residential wiring applications, there aren’t a limited number of recep-
tacles that can be installed on a general-purpose circuit. Electricians
usually install six to ten outlets per circuit and divide the circuits as evenly
as possible between the general-purpose receptacles. One consideration
in deciding which receptacles should connect to which circuit might
be economics. A good rule of economics is to connect the outlets in a
configuration that uses the least amount of wire or cable. Another
alternative the electrician should consider in the configuration of the
circuitry of the outlets in any one room is connecting the outlets so that
they’re on more than just one circuit. Wiring in this manner permits
some of the receptacles in the room to remain energized, providing
lighting and power when the current serving the rest of the room fails.
This is done in case one of the circuits should fail or require turning off
for repair or other reasons. Outlets with split-wired receptacles may be
installed in the living room, kitchen, family room, dining areas, and
laundry room.
Small-Appliance Circuits
As you know, at least two small-appliance circuits are required in a
kitchen. These same two circuits can be extended into an adjoining
dining area. However, it’s recommended that you install additional
circuits for dining areas and other adjoining rooms. Only one appli-
ance circuit is required in a separate laundry area.
Wiring Electrical Circuits 61
Special-Purpose Circuits
Certain types of appliances require their own branch circuit. This means
that each appliance has its own conductors, outlet, and circuit breaker or
fuse.
These circuits can have ampacities of 15, 20, 30, 40, 50, 60, or even 70A.
These special-purpose or individual equipment circuits are considered to have
a relatively high load demand but their ampacities aren’t necessarily
extremely high. One of the reasons an individual circuit may be needed
is that the electrical load is heavy enough that no other load can share
the circuit without overloading it. For example, an electric range may be
rated at 20 kW (kilowatts). It would require a 240-volt, 50-A, three-wire
circuit. A household electric-clothes dryer may require a 240-volt, 30-A,
three-wire circuit. With an insulated neutral conductor should be insu-
lated. A standard residential washing machine normally requires a 120-
volt, 20-A, two-wire circuit. A combination washer-dryer usually re-
quires a 240-volt, 40-A, three-wire circuit. A water heater also requires a
special-purpose circuit, usually a 240-volt, 30 A, two-wire circuit.
Special-purpose circuits are also used for appliances that are either
automatically controlled or will be running for long periods without
supervision. For example, the circuit that supplies power to fuel-fired
heating equipment such as a furnace is normally controlled by a thermo-
stat. An individual circuit is required so that if a fault develops in the
equipment, the circuit’s protective device will open, removing power
from only the one outlet. This avoids the likelihood of other nonrelated
circuits being opened as a result of the equipment problem. Should a
group of outlets share the same circuit as other major appliances and
one of the connected loads causes the breaker to trip, power could be
interrupted to equipment such as food freezers, refrigerators and the
like, resulting in expensive food spoilage.
Dishwashers and garbage disposals are sometimes connected to the same
circuit since they’re seldom in operation at the same time. The preferred
way, however, is to have each one on its own circuit. Table 3 lists the
electrical and wiring requirements for several special-purpose circuits.
Always check the nameplate on the equipment to verify the equipment’s
load demand, as it may differ from those listed in Table 3.
62 Wiring Electrical Circuits
Table 3
Clothes Dryers
The receptacle shown in Figure 32A is a 30-ampere-rated, 4-wire receptacle
generally used to connect clothes dryers. Prior to the 1996 revision of
the NEC, the 30-A receptacle was only required to have three slots for
connection. All new clothes dryers now come equipped with the standard
4-prong pigtail and will require a 4-slot receptacle.
FIGURE 32—30-ampere
and 50-ampere 4-wire
receptacles
30-AMPERE
4-WIRE RECEPTACLE
(A)
50-AMPERE
4-WIRE RECEPTACLE
(B)
ranges. Any appliance or equipment that has the voltage and amperage
requirements to match may be connected using these receptacles. You
may find welding machines and other equipment connected in this
manner. However, never use the 30-ampere receptacle in a 50-ampere
requirement. In addition, freestanding electric ranges may be connected
directly into the junction box provided on the range. The basic rule the
electrician generally follows is that if the equipment comes equipped
with a 50-ampere rated pigtail, use the 50-ampere receptacle. If the
range comes equipped with a junction box and no pigtail, either use the
50-ampere receptacle by adding a 50-ampere pigtail, or connect the range
directly into a wall-mounted junction box with proper connectors. Always
make sure that any conductor used in the connection of these appliances
is in accordance with Table 310-16 in the NEC and never use the pigtail
as the disconnecting means for the circuit.
If none of the factors are present that require two individual branch
circuits for the sectional range, one branch circuit may be installed and
“tapped” in a junction box to provide power to each piece of sectional
range. Figure 33 shows such a configuration. Before installing any branch
conductors or devices, always check the nameplate load rating on the
specific equipment to make sure that all circuit components meet or
exceed the requirements of the NEC. When connecting a sectional range
using the single-branch circuit method, the electrician will normally run
a 50-ampere-rated conductor from a double-pole circuit breaker in the
panel, to a centrally located junction box, convenient to both the cooktop
and the oven. An example of this is shown in Figure 33. The electrician
will then tap or connect from this junction box with two separate load-rated
cables to both the cooktop and the oven. Always check the nameplate on
each piece of equipment. This determines what size conductor you should
install to each piece of equipment from the main branch-circuit junction
box. Normally the conductors to each separate cooking unit will be
smaller in size than the conductor used to feed the main circuit, since this
main circuit is based on the total of the loads of both pieces of equipment.
Connecting the equipment to the tapped circuits may be accomplished
by using the proper receptacle and pigtail or by direct connection into
the manufacturer-supplied junction box. Labeling the cables in the
junction box with what appliance they supply is also a good practice.
Water Heaters
In connecting residential water heaters, it’s common practice in the elec-
trical trade to use a two-wire, No. 12 cable, with a grounding conductor.
Be certain the nameplate load rating on the water heater doesn’t exceed
the ampacity of the No. 12 cable. However, when wiring in this man-
ner remember that the conductor colors in a No. 12 cable are usually
black and white, which requires the electrician to re-mark the white
conductor with black tape or paint it at any point where the white con-
ductor is accessible or visible. This is to prevent someone from mistaking
it for a grounded conductor. The grounding conductor, usually a bare
copper conductor, must be connected to the frame of the water heater.
The equipment manufacturer usually provides a green terminal screw
Wiring Electrical Circuits 65
FIGURE 33—This shows the connections for a sectional range using one branch circuit.
located inside the junction box for this purpose. Figure 34 shows a dia-
gram for a standard two-element water heater. Notice that the water
heater doesn’t require a grounded conductor, or neutral, to operate prop-
erly. Also noted is that the disconnect isn’t required as long as the circuit
breaker that supplies the branch circuit to the water heater is “readily
accessible”. The water heater normally is connected by using a pigtail
from the water heater to either a wall-mounted junction box or a single
240-volt, 30-ampere rated receptacle. As is the case with any larger ap-
pliance, never use the plug/receptacle as a disconnecting means for the
appliance. The reason for not using the plug/receptacle for a disconnect-
ing means on any large-load appliance is that larger appliances (ranges,
dryers, dishwashers, and water heaters) have working amperage levels
that are relatively high compared to smaller appliances, such as blenders
and radios. Should someone use the plug as a disconnecting means and
unplug a larger appliance while the load is applied, electrical arcing and
serious injury due to burn or shock can result. The electrical current
has a natural tendency to try and “stay connected” and will arc to itself.
This effort causes the arcing to be exposed to the person holding the
pigtail and most likely damaging the plug and/or receptacle.
The low-voltage control system in Figure 35B uses a thermal relay to control
the power to the heater. The thermal relay includes a transformer T, which
steps 240 volts down to 24 volts. The low-voltage thermostat controls the
flow of current through a resistance heater R. When the thermostat closes,
it calls for heat and current flows through the resistance heater R. The
heater is wound on the bimetallic strip constructed of two different met-
als. The resistance heater heats a bimetallic strip and causes it to bend
and close the switch contacts of the thermal relay. When the room tem-
perature rises, the thermostat opens. This action stops the flow of current
68 Wiring Electrical Circuits
through the resistance heater, which allows the bimetallic strip to cool.
After the bimetallic strip cools, the switch contacts of the thermal relay
open. Thus, the thermal relay silently controls the current flowing to the
heater.
In this system, the thermal relay directly controls the power to the heater.
The thermal relay could also be used to control a remotely located
switch such as a relay or contactor. This flexibility permits placing the
low-voltage thermostat and thermal relay in the most convenient places.
It also permits the installation of short cables to the heater.
Circuit Protection
The NEC devotes two parts of Article 422 to the electrical installation
and protection of appliances. Basically, the nameplate load rating
determines the branch circuit rating. If the nameplate rating isn’t available,
then Article 422 dictates how the branch circuit should be sized. For
small appliances whose rating is 13.3 amperes or less, the branch circuit
rating may not exceed 20 amperes. If an appliance is rated over 13.3 and
the branch-circuit maximum rating isn’t marked on the appliance, the
branch circuit rating may not exceed 150 percent of the estimated demand
load. For household-type appliances with surface heating elements
having a maximum demand of more than 60 amperes, the branch circuit
must be split into two circuits, with overcurrent protection rated less
than 50 amperes on either circuit. Electric heating appliances that use
resistance-type heating elements that have a demand of more than
48 amperes must have the heating elements subdivided so that no one
load is more than 48 amperes. The overcurrent protection device can’t
exceed 60 amperes on either circuit. An individual branch circuit must
supply central heating equipment. Branch circuits that supply water
heaters less than 120 gallons (household water heaters) must be rated at
no less than 125 percent of the nameplate load demand on the water
heater.
Circuit Grounding
Let’s review the two types of conductors used in a grounded circuit.
First is the grounded conductor. This current-carrying circuit conductor
is grounded at the service entrance and is called the neutral wire. Since
it’s grounded, there’s no voltage between the neutral wire and ground
unless the wire is disconnected from the ground connection. Then any
conducting material, including the human body, that completes the
path from the grounded conductor or neutral to earth ground while the
circuit’s energized will become part of the current-carrying conductor!
The other conductor associated with grounding is the equipment-grounding
conductor, usually called the ground or grounding wires. These conductors
connect the non-circuit metal parts of electrical equipment to ground.
These conductors don’t conduct any electrical current unless a fault
(short circuit) occurs in the circuit. This type of fault is called a ground fault.
When a ground fault occurs, current flows from one of the non-grounded
circuit conductors through the grounding wire to ground. The grounding
wires place the metal parts of equipment at ground potential (the
same as ground itself), thus making it reasonably safe to touch electrical
equipment even when a ground fault exists.
Ground Faults
When a short circuit occurs in a circuit, it will usually cause a very high
circuit current to flow. This high current normally causes the circuit
protection device, whether a fuse or circuit breaker, to open. What
happens if the current isn’t high enough to blow a fuse or open the
circuit breaker?
For example, suppose the insulation between a hot wire and ground
wire doesn’t break down fully and develops only a leakage of current
with a resistance of 240W.
Thus,
120V
240W
I = 0.5 A
Should this happen, 0.5 A of current flows from the ungrounded con-
ductor through the parallel circuit created by the short circuit, to earth
70 Wiring Electrical Circuits
ground. The 15- or 20-A circuit breaker or fuse won’t open because it
hasn’t been exposed to an excess of 15 or 20 amperes of current flow.
It allows the 0.5 A to flow. It doesn’t recognize that it’s a ground-fault
current. If a person like the one in Figure 36 should touch the hot wire
while also touching ground, that person’s body would provide the same
type of leakage path to ground. The leakage current wouldn’t be high
enough to trip the breaker, but it could be high enough to injure or kill
the person. For that reason, a ground fault circuit interrupter (GFCI) is
required in some areas for protection against ground faults. A GFCI is
designed to trip when it senses a ground-fault current of only 0.005 A.
This amount of current isn’t enough to kill or even injure a person.
FIGURE 36—The ground-fault
circuit interrupter responds
to the leakage current
returning to a voltage source
by a route other than the
normal return wire. In this
illustration, that route is
through the worker’s body.
GFCI-Protected Circuits
As you know, the NEC requires that GFCIs be used in locations where a
fault current would most likely occur. For a residence, GFCIs are re-
quired to protect the receptacles in the bathroom, kitchen countertops,
wet bars, garages, and on the outside of the house, including swimming
pool areas. To protect workers on construction jobs, GFCIs are required
in most of the general-purpose circuits, especially in those circuits used
to furnish power to hand-held power tools. The worker in Figure 36
would most likely be protected from electrical shock if the circuit that
the electric saw connects to was protected by a GFCI device.
There are three basic types of GFCI protection devices—GFCI receptacles,
GFCI circuit breakers, and portable GFCIs. Figure 37 shows three styles
of GFCI receptacles. The flush-mounted and surface-mounted styles are
available in terminated or feed-through models. Terminated models are
designed only to protect the one receptacle load from ground fault.
Wiring Electrical Circuits 71
Feed-through models are designed to protect the one receptacle load and
all other receptacles that are installed downstream from that receptacle.
However, the other receptacles must be connected to load side of the
GFCI unit. The plug-in unit shown in Figure 38 is available only in a
terminated model.
FIGURE 37—The
flush-mounted and
surface-mounted models
of circuit interrupters fit into
the outlet boxes normally
used to support and protect
power receptacles. The
receptacle into which it’s
plugged supports the
small plug-in model.
(Bottom photo courtesy of Leviton
Manufacturing Co., Inc.)
The second type of GFCI is the GFCI circuit breaker. In this type, a circuit
breaker and a GFCI are combined, providing both overcurrent and
fault-current protection. The circuit-breaker switch may also be used as
an on/off switch for the circuit.
72 Wiring Electrical Circuits
Circuit breakers with GFCI capability are available in models that can be
installed to replace most standard circuit breakers now in use. Examples
of circuit breakers with GFCI protection are shown in Figure 38. Note
that the devices shown also contain test buttons.
FIGURE 38—GFCI Circuit Breakers
The third type of GFCI device is the portable unit. These devices incorpo-
rate both receptacles and circuit breakers. You’ll most likely find these
devices in use on construction sites, where the NEC requires their use.
The ground-fault circuit in a device of this type may or may not be part
of the circuit-breaker assembly.
Other Circuits
Signal Circuits
A chime controlled by push-button switches is one of the most common
signal circuits that’s installed in residential wiring. Figure 39 shows a
circuit that’s supplied by a small step-down control transformer. This
transformer steps the 120 V down to between 12 and 20 V. Because the
transformer power demand is very limited, the normal door chime
transformer primary wires can be connected directly to a 15-A or 20-A
lighting or general-purpose circuit without a special circuit protection.
Small wiring referred to as bell wire, having very thin insulation, is
generally used as conductors in these circuits. This wiring should be
kept at least 2 inches from other wires to prevent currents from being
induced into the bell wire by electromagnetic force, which may cause
Wiring Electrical Circuits 73
FIGURE 39—The transformer secondary connections for a door chime circuit are shown in both block diagram
and schematic form. The transformer, shown as the low-voltage AC power source, could be replaced with DC
battery packs for emergency systems.
Communication Wiring
Computer/Internet connections, cable television, telephone, and audio
speakers are all examples of communications systems now installed in
modern homes. Communications circuits are often installed in a newly
constructed residence in the same way as electrical branch circuits.
Modern residential as well as commercial wiring jobs often demand
that electricians install data cable for computers, cable for television,
telephone wires, and speaker wire throughout a building.
Wiring for communication systems is often specified on the wiring
diagram to be installed and hooked up by the electrician. When faced
with the job of installing communications wiring, it’s important to select
the correct wire for each communication application and to have the
skills necessary for installing and terminating the cables and connectors.
As the world adapts to the interface of communications systems, the
demand for residential installations is increasing rapidly. The electrician
must now know how to identify cables and devices used to connect data
communications such as computers, DVD, and satellite systems, along
with coax cables for television, telephone cables, and all associated equip-
ment and devices.
Telephone Wiring
Modern residences are often wired with built-in telephone connections
throughout the dwelling. Computer Internet access, fax machines, and
the demand for more than one voice line have all contributed to the
increasing complexity of the typical residential telephone system.
When a telephone company installs a telephone line at a residence, it’s
connected to an enclosure called a demarcation box, shown in Figure 40.
This box may be placed either inside or outside the building. Terminal
blocks are usually located in the demarcation box. Terminal blocks
(Figure 41) are devices that allow multiple lines to be connected from the
demarcation box to multiple locations within the house or building. Think
of the demarcation box/terminal block combination as a distribution
point not unlike the service panel or branch-circuit distribution panel
of the electrical system.
FIGURE 41—A terminal block allows multiple jacks to be installed. This style of block is mounted
separately from the demarcation box.
Do the same with the green wire. If only one line is being installed,
you’ll need only to install the red and green conductors. The black and
yellow conductors are for a second line if one is to be installed. An
example is shown in Figure 42. After the telephone company has
connected the demarcation box to the telephone service line, test the
telephones for proper operation, and then install the cover on each
telephone jack.
As mentioned previously, a new residential wiring diagram may include
wiring instructions for the communication system conductors as well as
the conventional electrical wiring.
Wiring Electrical Circuits 77
BK=BLACK YL=YELLOW
RD=RED GR=GREEN
FIGURE 42—Conductors are simply attached with the screws according to the color code.
one another and don’t have enough space separating them. To avoid cross
talk, modern telephone cables contain only twisted pairs of conductors.
“Twisted pair” means that the wires in each conductor-pair are evenly
twisted around each other.
BLACK
120V WHITE
RED
(INTERCONNECT WIRE)
FIGURE 44—When smoke detectors are wired in this manner, it causes all of them to sound if smoke is detected
in an area.
✔ Self-Check 4
1. General-purpose circuits are usually _______ -conductor circuits that distribute 120 V.
2. An electric dryer, 4-wire receptacle is normally rated at _______ amperes.
3. The minimum number of small-appliance circuits required in a kitchen is _______.
4. List the three groups into which the NEC classifies appliances.
5. True or False? Pigtail cords can be used as a disconnecting means for fixed appliances.
6. The neutral wire is a _______ conductor.
7. A standard circuit breaker will trip when a _______ _______ occurs.
8. _______ _______ is used to deliver traditional cable television service.
Check your answers with those on page 83.
83
Self-Check Answers
1 3
1. service drop 1. 6
2. switch 2. True
3. series 3. The bathroom
4. alternating 4. The master bedroom
5. 9 (17 – 8 = 9) 5. A switch should be equipped with a
pilot light when the switch is out of
6. grounding sight of the light it controls.
7. load or equipment
8. Any two of the following are correct:
Emergency power, Hazardous area, 4
Alarm, Communication, Control
9. explosion-proof 1. two
2. 30
3. two
2
4. Fixed, Portable, Stationary
1. True 5. False
2. neutral 6. grounded
3. disconnect 7. short circuit
4. 10 8. Coaxial cable
5. False
6. plastic separators
7. grounding
Examination
ONLINE EXAMINATION
For the online exam, you must use this
EXAMINATION NUMBER:
00603701
When you’re confident that you’ve mastered the material in your studies, you can
complete your examination online. Follow these instructions:
1. Write down the eight-digit examination number shown in the box above.
2. Click the Back button on your browser.
3. Click the Take an Exam button near the top of the screen.
4. Type in the eight-digit examination number.